SmartGen ATA600 Dual Power Switch Adaptor User Manual

June 3, 2024
SmartGen

SmartGen ATA600 Dual Power Switch Adaptor

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Note
2019-12-30 1.0 Original Release
2021-02-25 1.1 Add illustration for optional terminals.
2022-04-19 1.2 Update the logo of SmartGen.

OVERVIEW

ATA600 Dual Power Switch Adapter is a kind of adapter which makes convenience for connection between HAT600/HAT600N/HAT600P/HAT700 dual power ATS controller and smart breaker, reducing a lot of field wiring work for users, not only labor saving, time saving but also reliable.

PERFORMANCE AND CHARACTERISTICS

  • Suitable for 3Ph 4W AC system;
  • Two integrated 400V/50Hz/10A circuits of air breaker, which are individually used to connect two circuits of AC power;
  • All-in-one integrated adaptor, which can simultaneously connect S1 breaker, and S2 breaker;
  • Suitable for HAT600/HAT600N/HAT600P/HAT700 dual power ATS controller;
  • Cold rolled plate closure;
  • With screw installation method, adapter is fixed by 4 screws.

SPECIFICATION

Table 2 Performance Parameters

Item

|

Description

---|---
Rated Working Voltage| AC 400V 50/60Hz
Max Working Current| 10A
Air Breaker| 400V~   50Hz   10A
Case Dimensions| 144.4mmx252mmx75.3mm
Working Temperature| (-25~+70)°C
Working Humidity| (20~93)%RH
Storage Temperature| (-30~+80)°C
Insulation Strength| Apply AC1.5kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1min.
Weight| 1.6kg

PANEL DESCRIPTION

PANEL ILLUSTRATION

Panel illustration is as Fig. 1.

  • Two circuits of air breaker, connect separately with S1/S2 AC power.
  • Connector M1, M2, M3 need to connect to the side of
  • HAT600/HAT600N/HAT600P/HAT700 controller.
  • Connector S1-A, S1-B need to connect to the side of S1 breaker.
  • Connector S2-A, S2-B need to connect to the side of S2 breaker.
    Fig. 1 Panel Instruction
    Panel illustration
CONNECTOR ILLUSTRATION

The pin numbers of connector terminals are as Fig. 2.

Fig. 2 Pin Numbers of Connector Terminals
Pin Numbers of Connector Terminals

Terminal Wirings of connector is as Table 3

Table 3 Connector Wiring Illustration

Connector No.| Pin No.| Wire No.| Wire Harness No.| Connector No.| Pin No.| Wire No.| Wire Harness No.
---|---|---|---|---|---|---|---
M1| 1| M-15| WH600-M-20-RM| S1-A| 1| Q1-28| WH600-Q1-30-RM
2| M-14| 2| Q1-2
3| M-13| 3| Q1-27
4| M-16| 4| Q1-33
5| NC| 5| Q1-30
6| M-12| 6| Q1-36
7| M-17| 7| Q1-24
8| M-18| 8| Q1-35
9| M-11| 9| Q1-29
M2| 1| M-4| 10| Q1-32
2| M-28| 11| Q1-1
3| M-5| 12| Q1-25
4| M-8| S1-B| 1| NC
5| M-1| 2| Q1-4
6| M-9| 3| Q1-23
7| M-6| 4| NC
8| M-27| 5| Q1-22
9| M-3| 6| Q1-5
10| M-10| | |
11| M-29| | |
| 12| NC| | | | |
---|---|---|---|---|---|---|---
13| M-7| | | |
14| M-2| | | |
15| M-30| | | |

M3

| 1| M-21| | | |
2| M-22| | | |
3| NC| | | |
4| M-24| | | |
5| M-19| | | |
6| NC| | | |

NOTE : Connector S2-A and S2-B connected wire number starts with Q2; Others are the same with S1-A, S1-B, connected  with WH600-Q2-30-RM. For example: P1 wire number of connector S2-A is Q2-28.

Wire number definition:

APPLICATION DIAGRAM

Fig. 3 Application Diagram
Application Diagram

ACCESSORY ILLUSTRATION

The connected wire harness and terminals matched with terminal block of this product are optional; Users can make clarification at ordering, note the harness requirements and breaker type. See Table 4 for details.

Table 4 Optional Accessory Description

Category

|

Note

---|---


Optional Wire Harness

| There are three in total, one of them will be connected to the controller side and the other two will be connected to the circuit breaker side. The length of the wire harness (unit: m) and the model of the circuit breaker should be indicated when choosing.
Optional Terminals| Include the matching terminals and connector terminals.

CASE DIMENSIONS

This adapter is designed by screw installation method, and is fixed by four screws at installation.  Unit: mm

Fig. 4 Case Dimensions and Panel Cutout
Case Dimensions and Panel Cutout

Customer Support

No.28 Jinsuo Road, Zhengzhou, Henan Province, China
Tel : +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax : +86-371-67992952
Email : sales@smartgen.cn
Web : www.smartgen.com.cn
www.smartgen.cn