SmartGen CMM366B-4G Cloud Monitoring Communication Module User Manual

June 3, 2024
SmartGen

SmartGen CMM366B-4G Cloud Monitoring Communication Module

SmartGen — make your generator smart SmartGen Technology Co., Ltd.
No.28 Jinsuo Road, Zhengzhou, Henan Province, China Tel: +86-371-67988888/67981888/67992951

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.

  • Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above.
  • Any reference to trademarked product names used within this publication is owned by their respective companies.
  • SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Note
2020-03-10 1.0 Original release.
2020-05-15 1.1 Fix Fig. 14 Unit from cm to mm.
2020-08-04 1.2 Fix Fig. 6 Link interface communication line according to the

real

Figure.



2021-06-07

| ****


1.3

| 1.       Apply the latest user manual format;

2.       Change font from Arial to Roboto;

3.       Modify APP installation steps;

4.       Change the app download QR code of CMM366B-4G mask.

2021-10-21| 1.4| 1.       Modify Fig.1 Panel Indicator;

2.       Add 2 notes in 4.4 SIM Card Installation.

2022-08-30| 1.5| Update company logo and manual format.

OVERVIEW

CMM366B-4G/CMM366CAN-4G

Cloud Monitoring Communication Module is 4G wireless network communication protocol conversion module of all-modes, which can achieve genset (with SCI) connection with Internet. After logging into cloud server, module will receive corresponding genset controller communication protocol from cloud server. Cloud monitoring module can obtain genset data information via RS485, USB, LINK, CAN, or RS232 port, and send the information to related could server via 4G wireless network. Users can monitor genset running status at real time and check genset running records by mobile APP (IOS or Android), or PC etc. terminal device.

  • It not only can realize genset monitoring, but also can be connected with some digital alarm inputs, to realize monitoring of genset entrance guard, prevention of burglary, fire control etc. ancillary facilities.
  • It has GPS positioning function, which can upload the obtained longitude and latitude, altitude information at real time to the corresponding cloud server.
  • CMM366CAN-4G cloud monitoring communication module has CAN port, but CMM366B-4G hasn’t.
  • Except for this, these two cloud monitoring communication modules has same functions.

PERFORMANCE AND CHARACTERISTICS

  • **** Connect to cloud server via 4G wireless network, one cloud monitoring module for one genset;
  • Multiple communicating ports with genset control module: RS485, RS232, LINK, CAN port, USB (Host), which can monitor most genset control modules of leading brands internationally;
  • Wide power supply: DC (8~35)V, which can directly use engine build-in starting battery;
  • With ARM-based 32-bit SCM, high integration of system and strong programming ability;
  • GPS positioning function for obtaining genset location information, to realize genset positioning;
  • Apply network data communication protocol of JSON format, upload the genset data changes at real time, meanwhile compression algorithm is applied, which extremely reduces network flow;
  • Immediately upload the data to cloud server when genset alarms occur;
  • Event log memory function, which can ensure data won’t get lost when network is not steady;
  • Cloud Modem can be upgraded by 4G network, convenient for module’ s maintenance;
  • 2 configurable digital input ports, which can be connected with external alarm signals;
  • Module panel has power and multiple communication status indicators; clear display module working status;
  • Lamp test function;
  • Parameter setting function: users can do parameter setting by module USB port;
  • Apply standard Π-type 35mm guide-rail installation or screw-fixed installation, and the module can be installed in the genset control box;
  • Modular structure design, flame retardant ABS enclosure, light weight, compact structure with easy installation.

SPECIFICATION

Table 2 Technical Data

Items Contents
Operating Voltage DC8.0V~35.0V, continuous power supply.
Power Consumption Standby: ≤2W

Working: ≤5W

Digital Input| Digital Input, connect (B-) is active.
USB Host| A-type USB female port
RS485 Port| Isolated type
RS232| General type
LINK| SmartGen exclusive port
USB Device| B-type USB female port
CAN Port| Isolated type
GPRS Port| Standard SMA port (female), SMA port (male) for antenna.
GPS Port| Standard SMA port (female), SMA port (male) for antenna, active antenna.
Wireless Network| LTE-TDD/LTE-FDD/HSPA+/TD-SCDMA/EVDO

GSM/GPRS/EDGE

Case Dimensions| 72.5mmx105mmx34mm
Working Temperature| (-25~+70)°C
Working Humidity| (20~93)%RH
Storage Temperature| (-30~+80)°C
Weight| 0.15kg

PANEL AND TERMINAL DESCRIPTION

**PANEL INDICATOR AND KEYS**

Icon Note
POWER/ALARM Green LED Light On: Power supply normal indicator;

Red LED Light On: Common alarm indicator.


RS485 (Red)

| Normally Light Off: RS485 disabled; Normally Light On: Communication failed;

Flash: Communication normal.


USB (Red)

| Normally Light Off: USB(Host) disabled; Normally Light On: Communication failed;

Flash: Communication normal.


GPS (Red)

| Normally Light Off: GPS disabled;

Normally Light On: GPS not gained satellite signal; Flash: GPS gained satellite signal.


RS232/LINK (Red)

| Normally Light Off: RS232/LINK Disabled; Normally Light On: Communication failed;

Flash: Communication normal.


CAN (Red)

| Normally Light Off: CAN disabled;

Normally Light On: Communication failed; Flash: Communication normal.


GPRS/4G (Red)

| Normally Light Off: 4G module logins with server unsuccessfully; Normally Light On: Login with server successfully;

Flash: Real-time communication normal.

Fig.1 – Panel Indicator Table 3 – Indicators Description

Internal Lamp Test/Reset Key:

Press and hold this key for 1s, all the LEDs are illuminated; press and hold for 10s, recover default configurations of CMM366B-4G/CMM366CAN-4G and all LEDs flash for 3 times.

NOTE: After reset the module, parameters need to be re-configured via PC software or mobile APP. Please operate cautiously.

GPRS/4G ANTENNA PORT

Connect GPRS antenna to GRRS/4G port. Antenna port: 50Ω/SMA female.

GPS ANTENNA PORT

GPS enabled, connect GPS antenna to CMM366B-4G/CMM366CAN-4G.
NOTE: GPS antenna needs to be placed to open outdoors, otherwise location information may not be accurate or cannot be gained. Antenna port: 50Ω/SMA female, active antenna

Fig.2 CMM366B-4G/CMM366CAN-4G Antenna Connection

NOTE: GPRS antenna and GPS antenna cannot be connected reversely.

SIM CARD INSTALLATION

  • Insert 4G SIM card. CMM366B-4G/CMM366CAN-4G will connect to server via wireless mobile network.
    NOTE: This module supports 4G wireless network of all modes. Standard SIM card is applied (size: 25mmx15mm);

  • GPS indicator and GPRS indicator flash at the same time means SIM card is not inserted or SIM card is in bad contact. After removing the head cover, the installation steps are as below:

Fig.3 SIM Card Installation Steps

NOTE: IMEI number can be viewed from the controller side.

NOTE: One card for one controller, the same card can’t be removed from a module and inserted into another module, which will affect the normal use.

RS485 PORT

  • **** Receive genset data information by connecting RS485 port with genset controller RS485 port.
  • 120Ω terminal resistor is recommonded, and short connect RS485 A(+) and TR terminal.

Fig.4 RS485 Connection Diagram

RS232 PORT

Receive genset data information by connecting RS232 port with genset controller RS232 port.

Fig.5 RS232 Connection Diagram

LINK PORT

Receive genset data information by connecting LINK port with genset controller LINK port.

Fig.6 – LINK Connection Diagram

USB HOST PORT

Receive genset data information by connecting A-type USB port (female) with genset controller USB port via USB cable.

Fig.7 – USB Host Connection Diagram

USB DEVICE PORT

All the parameters can be configured and view CMM366B-4G/CMM366CAN-4G module ID&Login password by connecting USB port with PC. ****

CAN PORT

CMM366CAN-4G model has this function. Obtain genset data information by connecting CAN port and genset CAN port. 120Ω terminal resistor is recommended and short connect CANH and TR terminal.

TERMINALS

Fig.10 – CAN Connection Diagram

Table 4 Terminals Description ****

No. Function Cable Size Note
1 B- 1.0mm2 Connected with negative of starter battery.
2 B+ 1.0mm2 Connected with positive of starter battery. 3A

fuse is recommended.

3| Digital Input 1| 1.0mm2| Active when connect to B-.
4| Digital Input 2| 1.0mm2| Active when connect to B-.
5| CANL| 0.5mm2| 120Ω terminal resistor is recommended, short connect CANH and TR terminal.
6| CANH| 0.5mm2
7| TR| 0.5mm2
8| RS485 B(-)| 0.5mm2| 120Ω terminal resistor is recommended, short connect RS485 A(+) and TR terminal.
9| RS485 A(+)| 0.5mm2
10| TR| 0.5mm2
11| RS232 RX| 0.5mm2| ****

RS232 port.

12| RS232 TX| 0.5mm2
13| RS232 GND| 0.5mm2

PROGRAMMABLE PARAMETERS

CONTENTS AND SCOPES OF PARAMETERS

No. Items Parameters Defaults Description

Gateway
1| Site Name| | 20 Chinese characters, letters or

numbers.

2| Server URL| | www.smartgencloudplus.com| 40 characters
3| Server Port| (0-65535)| 21318
4| Security Code| | 123456| 16 characters
GPS
1| GPS Enabled| (0-1)| 1| 0: Manual Input     1: GPS Location
2| Longitude| ((-180)-180)°| 113.554879| ****

GPS location, altitude information.

3| Latitude| ((-90)-90)°| 34.802335
4| Altitude| ((-9999.9)-9999.9)m| 100.0
Digital Inputs
Digital Input 1
1| Setting| (0-9)| 0| Default: Not used.



2

| ****


Type

| ****


(0-1)

| ****


0

| 0: Active when close; 1: Active when open.

See: Table 6 Digital Input Ports

Content.

3| Delay| (0-20.0)| 0.0| Action delay.
Digital Input 2
1| Setting| (0-9)| 1| Default: Lamp test.



2

| ****


Type

| ****


(0-1)

| ****


0

| 0: Active when close; 1: Active when open.

See: Table 6 – Digital Input Ports

Content.

3| Delay| (0-20.0)| 0.0| Action delay.
| | | | |

NOTE: Monitoring genset controller model, communication port, communication baud rate, and communication ID need to be set on the platform, and cloud monitoring module needs to re-power after all parameters being set.


No. Item Description
0 Not Used Not used.
1 Lamp Test All the indicators are illuminated when input is active.
2 Remote Control Inhibited Cloud start/stop control is prohibited when input

is active.
3| Access Alarm Input| Access alarm is uploaded to server when input is active.
4| Fire Alarm Input| Fire alarm is uploaded to server when input is active.
5| Alarm Input| External alarm is uploaded to server when input is active.
6| Reserved|
7| Reserved|
8| Reserved|
9| Factory Test Mode| It is only used for factory test.

PC CONFIGURATION INTERFACE

Connecting the USB port of CMM366B-4G/CMM366CAN-4G communication module with PC to configure the parameters.

Fig.11 Gateway Configuration

Fig.12 Module Monitoring Interface

SYSTEM APPLICATION DIAGRAM

One CMM366B-4G/CMM366CAN-4G module connects with one genset monitoring module. It can be connected via RS485 port, LINK port, CAN port, RS232 port or USB port.

CASE DIMENSION AND INSTALLATION

35mm guide rail cabinet installation or screw-fixed (M4) installation can be applied. Case dimensions are as below:

Unit : mm

APP INSTALLATION STEPS

  • Scan the QR code on the enclosure of CMM366B-4G/CMM366CAN-4G cloud monitoring communication module (QR code is as 17), download the APP and install it in the mobile;
  • Open the APP from the mobile, users have to register for the first using, then input account number and password to enter APP;
  • Other related settings please refer to “Me-Guidance” (as 18).
FAULT FINDING

Table 7 Fault Finding

Symptoms Possible Solutions

Module    No    Response    with

Power

| Check power voltage;

Check module connection wirings.

GPRS/4G Indicator Off| Check SIM card is inserted or not;

Check GPRS antenna is connected or not.

GPS Not Gain Location| Check GPS parameters are enabled or not;

Check GPS antenna is connected or not and placed outdoor or not.



RS485 Comm. Abnormal

| Check connections;

Check RS485 port is enabled or not on cloud server platform communication port;

Check settings of genset ID and baud rate are correct or not.

Check RS485’s connections of A and B is reversely connected or not.



RS232 Comm. Abnormal

| Check connections;

Check RS232 port is enabled or not on cloud server platform communication port;

Check settings of genset ID and baud rate are correct or not.



LINK Comm. Abnormal

| Check connections;

Check LINK port is enabled or not on cloud server platform communication port;

Check settings of genset ID and baud rate are correct or not.




CAN Comm. Abnormal

| Check connections;

Check CAN port is enabled or not on cloud server platform communication port;

Check communication baud rate is correct or not; Check CANL and CANH are reversely connected or not;

Check genset controller ID is correct or not.



USB(Host) Comm. Abnormal

| Check connections;

Check USB port is enabled or not on cloud server platform communication port;

Check genset controller ID is correct or not.

PACKING LIST

**Table 8 – Packing List**

No. Name Quantity Remark
1 Cloud Monitoring

Communication Module

| 1| CMM366CAN-4G (with CAN port)

CMM366B-4G (without CAN port)

2| 4G+GPS/BD Two-in-one Antenna| 1|
3| User Manual| 1|
4| SIM Card Tray| 1|
5| RS485 Communication Cable| 1| Length: 50cm

APPENDIX (ORDER MODEL)

**Table 9 – CMM366B-4G/CMM366CAN-4G Order Model**

Order Model Country/Area Frequency Band Remark


CMM366B-4G CMM366CAN-4G

| ****



Chinese Mainland

| FDD-LTE: B1/B3/B8

TDD-LTE: B38/B39/B40/B41 TD-SCDMA: B34/B39 WCDMA: B1/B8 EVDO/CDMA: BC0

GSM: 900/1800MHz

|
CMM366B-4G-S01

CMM366CAN-4G-S01

| ****


North America

| FDD-LTE: B2/B4/B12

WCDMA: B2/B5

|
CMM366B-4G-S04

CMM366CAN-4G-S04

| FDD-LTE: B2/B4/B5/B13|


CMM366B-4G-S02 CMM366CAN-4G-S02

| Europe/Africa/ South Korea/Thailand/

Middle East

| FDD-LTE: B1/B3/B5/B7/B8/B20 TDD-LTE: B38/B40/B41 WCDMA: B1/B5/B8

GSM: 900/1800MHz

|



CMM366B-4G-S03 CMM366CAN-4G-S03

| ****

South America/ Australia/

New Zealand

| FDD-LTE: B1/B2/B3/B4/B5/B7/B8/B28 TDD-LTE: B40

WCDMA: B1/B2/B5/B8

GSM: 850/900/1800/1900MHz

|
CMM366B-4G-S05

CMM366CAN-4G-S05

| Japan| FDD-LTE: B1/B3/B8/B18/B19/B26|