neptronic SKVF Series Evaporative Cooler
Introduction
The SKVF Modbus Communication Module User Guide provides information for using
Neptronic® communication feature. The controller uses Modbus communication
protocol over serial line in the RTU mode and provides a Modbus network
interface between client devices and Neptronic SKVF devices.
The SKVF Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus:
- Data Model. The Evaporative Cooler Modbus server data model uses only the Modbus Registers table.
- Register Address:
- As per protocol base (base 0); for PLC add 1 to protocol base.
- As per holding register (base 400001).
Note: Ensure that the Modbus communication software used does not have a limit on the range of the register addresses that can be viewed and supports 6-digit holding registers.
- Function Codes. The Evaporative Cooler Modbus server supports a limited function codes subset comprising:
- Read Holding Registers (0x03)
- Write Single Register (0x06)
- Write Multiple Registers (0x10)
- Exception Responses. The Evaporative Cooler Modbus server supports the following exception codes:
- Illegal data address
- Illegal data value
- Slave device busy
- Serial Line. The Evaporative Cooler Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
- The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
- The supported baud rates are 9600, 19200, 38400, and 57600.
- The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2.
- In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
- Addressing. The Evaporative Cooler device only answers at the following address:
- The device’s unique address (1 to 246) that can be set through the device menu or through holding register index 0.
Modbus Registers
Table Glossary
Name | Description | Name | Description |
---|---|---|---|
W | Writable Register | ASCII | For registers containing ASCII (8-bit) characters |
RO | Read Only Register | MSB | Most Significant Byte |
Unsigned | For range of values from 0 to 65,535, unless otherwise specified | ||
LSB | Least Significant Byte | ||
Signed | For range of values from -32,768 to 32,767, unless otherwise | ||
specified | MSW | Most Significant Word | |
Bit String | For registers with multiple values using bit mask (example, | ||
flags) | LSW | Least Significant Word |
Modbus Registers Table
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
0
| ****
40000 1
| ****
Modbus Address and Product Type
| ****
Unsigned
| MSB = Product type, not writable
LSB = Modbus Address (1 to 247), writable
| ****
W
|
1| 40000 2| Device Baud Rate| Unsigned
Scale 100
| 0, 9600, 19200, 38400, and 57600, 0 = Auto Baud Rate
Detection Value/100 (e.g. 38400 baud = 384)
| W| 19200
2
| ****
40000 3
| ****
Modbus Slave Communication Port Configuration
| ****
Unsigned
| 0 = No parity, 2 Stop bits 1 = Even parity, 1 Stop bit 2 = Odd parity, 1 Stop bit| ****
W
| ****
No parity, 2 Stops bits
3| 40000 4| Product Name (characters 8 & 7)| ASCII| MSB = char 6, LSB =
char 7| W|
4| 40000 5| Product Name (characters 6 & 5)| ASCII| MSB = char 4, LSB =
char 5| W|
5| 40000 6| Product Name (characters 4 & 3)| ASCII| MSB = char 2, LSB =
char 3| W|
6| 40000 7| Product Name (characters 2 & 1)| ASCII| MSB = char 0, LSB =
char 1| W|
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
7| 40000 8| Product Actual Firmware Version (in Integer x100)| Unsigned
Scale 100
| 1 to 65535 (e.g. 100)| RO|
8| 40000 9| Product Actual EEPROM Version (in Integer x100)| Unsigned
Scale 100
| 1 to 65535 (e.g. 100)| RO|
2000
| ****
40 2001
| ****
Control Signal
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
2001
| ****
40 2002
| ****
Room RH Signal
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
2002
| ****
40 2003
| ****
Supply RH Signal
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
2003
| ****
40 2004
| ****
ECM Fan Feedback
| Unsigned
Scale 1
| Units: Hz, Range: 0 to 30000Hz
Value x 1 (e.g. 10Hz = 10)
| ****
RO
| ****
0Hz
2004
| ****
40 2005
| ****
Float Switch Signal
| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
2005
| ****
40 2006
| ****
Board Temperature Signal
| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
2006
| ****
40 2007
| ****
Main Power Supply
| Unsigned
Scale 10
| Unit: Volt (V), Range: 0V to 40V
Value x 10 (e.g. 2V = 20)
| ****
RO
| ****
0V
2007
| ****
40 2008
| ****
ECM Fan Feedback 2
| Unsigned
Scale 1
| Units: Hz, Range: 0 to 30000Hz
Value x 1 (e.g. 10Hz = 10)
| ****
RO
| ****
0Hz
2008
| ****
40 2009
| ****
Room Temperature Signal
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
2009
| ****
40 2010
| ****
Supply Temperature Signal
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
2010
| ****
40 2011
| ****
Control Signal
| Unsigned
Scale 1000
| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
4000
| ****
40 4001
| ****
Power Output Feedback Signal
| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)
| ****
RO
| ****
0V
4001| 40 4002| ECM Fan Signal| Unsigned
Scale 100
| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)
| RO| 0V
6000
| ****
40 6001
| ****
Demand
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6001
| ****
40 6002
| ****
Power Output
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6002
| ****
40 6003
| ****
Control Input
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6003
| ****
40 6004
| ****
Control Min
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6004
| ****
40 6005
| ****
Control Max
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6005
| ****
40 6006
| ****
Control Bias
| Signed
Scale 100
| Unit: %, Range: -10% to 10%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6006
| ****
40 6007
| ****
Room RH
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
6007
| ****
40 6008
| ****
Room RH Min
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6008
| ****
40 6009
| ****
Room RH Max
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6009
| ****
40 6010
| ****
Room RH Bias
| Unsigned
Scale 100
| Unit: % RH, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6010
| ****
40 6011
| ****
Supply High Limit RH
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6011
| ****
40 6012
| ****
Supply High Limit RH Min
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6012
| ****
40 6013
| ****
Supply High Limit RH Max
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6013
| ****
40 6014
| ****
Supply High Limit RH Bias
| Signed
Scale 100
| Unit: %, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6014
| ****
40 6015
| ****
Run Time (0)
| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)
| ****
RO
| ****
0h
6015| 40 6016| Run Time (1)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6016| 40 6017| Run Time (2)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6017| 40 6018| Run Time (3)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6018
| ****
40 6019
| ****
On Time (0)
| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)
| ****
RO
| ****
0h
6019| 40 6020| On Time (1)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6020| 40 6021| On Time (2)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6021| 40 6022| On Time (3)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6022
| ****
40 6023
| ****
Water Treated Volume (0)
| Unsigned
Scale 100
| Units: Litres (l), Range: 0 to 9999999 l
Value x 100 (e.g. 10 h = 1000)
| ****
RO
| ****
0l
6023| 40 6024| Water Treated Volume (1)| | Units: Litres (l), Range: 0
to 9999999 l| |
6024| 40 6025| Water Treated Volume (2)| | Units: Litres (l), Range: 0
to 9999999 l| |
6025| 40 6026| Water Treated Volume (3)| | Units: Litres (l), Range: 0
to 9999999 l| |
6026
| ****
40 6027
| ****
Service On Time (0)
| Unsigned
Scale 100
| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)
| ****
RO
| ****
0h
6027| 40 6028| Service On Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6028| 40 6029| Service On Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6029| 40 6030| Service On Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6030
| ****
40 6031
| ****
Dead Band
| Unsigned
Scale 1
| Unit: %, Range: 1% to 100%
Value x 1 (e.g. 10% = 10)
| ****
W
| ****
5%
6031
| ****
40 6032
| ****
Minimum Production Output
| Unsigned
Scale 1
| Unit: %, Range: 0% to 100%
Value x 1 (e.g. 10% = 10)
| ****
W
| ****
10%
6032
| ****
40 6033
| ****
Maximum Production Output
| Unsigned
Scale 1
| Unit: %, Range: 0% to 100%
Value x 1 (e.g. 10% = 10)
| ****
W
| ****
100%
6033
| ****
40 6034
| ****
Idle Fan Speed
| Unsigned
Scale 1
| Unit: %, Range: 0% to 100%
Value x 1 (e.g. 10% = 10)
| ****
W
| ****
0%
6034
| ****
40 6035
| ****
Service Interval
| Unsigned
Scale 1
| Units: Hours (h), Range: 1000 to 3000 h
Value x 1 (e.g. 10 h = 10)
| ****
W
| ****
1000h
6035
| ****
40 6036
| ****
Board Temperature
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F
Value x 100 (e.g. 5°C = 500 or 32ºF = 3200)
| ****
W
| ****
0°C or 32°F
6036
| ****
40 6037
| ****
Power Output Feedback Bias
| Unsigned
Scale 1000
| Unit: V, Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
0V
6037
| ****
40 6038
| ****
Power Output Feedback Min
| Unsigned
Scale 1000
| Unit: V, Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
0V
6038
| ****
40 6039
| ****
Power Output Feedback Max
| Unsigned
Scale 1000
| Unit: V, Range: 0V to 10V
Value x 1000 (e.g. 1V = 1000)
| ****
W
| ****
10V
6039
| ****
40 6040
| ****
Power Output Feedback
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6040
| ****
40 6041
| ****
Dilution Ratio
| Unsigned
Scale 1
| Unit: %, Range: 0% to 300%
Value x 1 (e.g. 10% = 10)
| ****
W
| ****
100%
6041
| ****
40 6042
| ****
Drain Interval
| Unsigned
Scale 1
| Unit: Hours (h), Range: 0 to 24 h
Value x 1 (e.g. 10h = 10)
| ****
W
| ****
4h
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6042
| ****
40 6043
| ****
Fixed Drain Time
| Unsigned
Scale 1
| Unit: Hours (h), Range: 4 to 72 h
Value x 1 (e.g. 10h = 10)
| ****
W
| ****
6h
6043
| ****
40 6044
| ****
Line Rinse Time
| Unsigned
Scale 1
| Unit: Seconds (sec), Range: 0sec to 2000sec
Value x 1 (e.g. 10sec = 10)
| ****
W
| ****
180 sec
6044
| ****
40 6045
| ****
Water Treatment Service Volume
| Unsigned
Scale 1
| Unit: Litres (l), Range: 2500 to 10000 l
Value x 1 (e.g. 10h = 10)
| ****
W
| ****
7500 l
6045
| ****
40 6046
| ****
Water Supply Duty Cycle
| Unsigned
Scale 1
| Unit: %, Range: 8% to 70%
Value x 1 (e.g. 10% = 10)
| ****
W
| ****
10%
6046
| ****
40 6047
| ****
Water Supply Period
| Unsigned
Scale 1
| Unit: Seconds (sec), Range: 0sec to 180sec
Value x 1 (e.g. 10sec = 10)
| ****
W
| ****
60 sec
6047
| ****
40 6048
| ****
Room RH Network Reading
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6048
| ****
40 6049
| ****
Room RH Setpoint
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
40% RH
6049
| ****
40 6050
| ****
Room RH Unoccupied Setpoint
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
30% RH
6050
| ****
40 6051
| ****
Room RH Vacant Setpoint
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
20% RH
6051
| ****
40 6052
| ****
Room RH Demand Proportional Gain
| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)
| ****
W
| ****
28.5
6052
| ****
40 6053
| ****
Room RH Demand Integral Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
6053
| ****
40 6054
| ****
Room RH Demand Derivative Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
6054
| ****
40 6055
| ****
Room RH Demand
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6055
| ****
40 6056
| ****
RH Supply High Limit Network Reading
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
0% RH
6056
| ****
40 6057
| ****
RH Supply High Limit Setpoint
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
80% RH
6057
| ****
40 6058
| ****
RH Supply High Limit Unoccupied Setpoint
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
80% RH
6058
| ****
40 6059
| ****
RH Supply High Limit Vacant Setpoint
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
W
| ****
80% RH
6059
| ****
40 6060
| ****
RH Supply High Limit Proportional Gain
| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)
| ****
W
| ****
28.5
6060
| ****
40 6061
| ****
RH Supply High Limit Integral Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
6061
| ****
40 6062
| ****
RH Supply High Limit Derivative Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
6062
| ****
40 6063
| ****
RH Supply High Limit Demand
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
6063
| ****
40 6064
| ****
Control Network Demand
| Unsigned Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6064
| ****
40 6065
| ****
Control Network High Limit
| Unsigned Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0%
6065
| ****
40 6066
| ****
User Demand
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6066
| ****
40 6067
| ****
System Steam Capacity
| ****
Unsigned
Scale 10
| Unit: kg/hr or lb/hr, Range: 0 to 3000 kg/hr or 0 to 6614 lb/hr
Value x 10 (e.g. 10kg/hr = 100 or 10lb/hr = 100)
| ****
RO
| ****
0 kg/hr or
0 lb/hr
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6067
| ****
40 6068
| ****
Room Temperature
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
20.0°C or
68.0°F
6068
| ****
40 6069
| ****
Room Temperature Min
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
0.0°C or
32.0°F
6069
| ****
40 6070
| ****
Room Temperature Max
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
40.0°C or
104.0°F
6070
| ****
40 6071
| ****
Room Temperature Bias
| ****
Signed
Scale 100
| Unit: C or F, Range : -18.0°F, max: 18.0°F or
-10.0°C, max: 10.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
0.0°C or 0.0°F
6071
| ****
40 6072
| ****
Room Temperature Network Reading
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to 500°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| ****
0°C or 32°F
6072
| ****
40 6073
| ****
Room Temperature Setpoint
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| 22°C or 71.6°F
6073
| ****
40 6074
| ****
Room Temperature Unoccupied Setpoint
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| 24°C or 75.2°F
6074
| ****
40 6075
| ****
Room Temperature Vacant Setpoint
| Unsigned
Scale 100
| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| 26°C or 78.8°F
6075
| ****
40 6076
| Room Temperature Demand Proportional Gain| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)
| ****
W
| ****
28.5
6076
| ****
40 6077
| ****
Room Temperature Demand Integral Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
6077
| ****
40 6078
| Room Temperature Demand Derivative Time| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6078
| ****
40 6079
| ****
Room Temperature Demand
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
6079
| ****
4 06080
| ****
HRL Temperature
| Signed
Scale 100
| Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to 500°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
RO
| ****
0°C or 32°F
6080
| ****
40 6081
| ****
HRL Humidity
| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
6081
| ****
40 6082
| ****
Room Temp Demand Proportional Band
| Unsigned
Scale 10
| Unit: %, Range: 1% to 100%
Value x 10 (e.g. 10% = 100)
| ****
W
| ****
5%
6082
| ****
40 61083
| ****
Temp Supply High Limit Network Reading
| Signed Scale 100| Unit: ºC/ºF, Range: -40°C to 100°C or -40°F to 212°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| ****
0°C or 32°F
6083
| ****
40 6084
| ****
Temp Supply High Limit Setpoint
| Unsigned Scale 100| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| ****
15°C or 59°F
6084
| ****
40 6085
| Temp Supply High Limit Unoccupied Setpoint| Unsigned Scale 100| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| 17°C or 62.6°F
6085
| ****
40 6086
| ****
Temp Supply High Limit Vacant Setpoint
| Unsigned Scale 100| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
| ****
W
| 16°C or 60.8°F
6086
| ****
40 6087
| ****
Temp Supply High Limit Proportional Gain
| Unsigned
Scale 10
| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)
| ****
W
| ****
28.0
6087
| ****
40 6088
| ****
Temp Supply High Limit Integral Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
6088
| ****
40 6089
| ****
Modbus TCP IP Keep Alive Time Out
| Unsigned
Scale 1
| Unit: Minutes (min), Range: 1 to 1440 mins
Value x 1 (e.g. 5 mins = 5)
| ****
W
| ****
5 min
6089
| ****
40 6090
| ****
Temp Supply High Limit Derivative Time
| Unsigned
Scale 10
| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10 sec = 100)
| ****
W
| ****
0 sec
6090
| ****
40 6091
| ****
Temp Supply High Limit Demand
| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
RO
| ****
0%
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6091
| ****
40 6092
| ****
Temp Supply High Limit Proportional Band
| Unsigned
Scale 10
| Unit: %, Range: 1% to 100%
Value x 100 (e.g. 10% = 100)
| ****
RO
| ****
10%
6092
| ****
40 6093
| ****
Supply High Limit Temperature
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
20.0°C or
68.0°F
6093
| ****
40 6094
| ****
Supply High Limit Temperature Min
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
0.0°C or
32.0°F
6094
| ****
40 6095
| ****
Supply High Limit Temperature Max
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
40.0°C or
104.0°F
6095
| ****
40 6096
| ****
Supply High Limit Temperature Bias
| ****
Signed
Scale 100
| Unit: C or F, Range : -18.0°F, max: 18.0°F or
-10.0°C, max: 10.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
20.0°C or
68.0°F
6096
| ****
40 6097
| ****
Control Input
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
20.0°C or
68.0°F
6097
| ****
40 6098
| ****
Control Min
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
0.0°C or
32.0°F
6098
| ****
40 6099
| ****
Control Max
| ****
Signed
Scale 100
| Unit: C or F, Range : -40.0°F, max: 212.0°F or
-40.0°C, max: 100.0°C
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
40.0°C or
104.0°F
6099
| ****
40 6100
| ****
Control Bias
| ****
Signed
Scale 100
| Unit: C or F, Range : -18.0°F, max: 18.0°F or
-10.0°C, max: 10.0°C
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
20.0°C or
68.0°F
6100
| ****
40 6101
| ****
Demand Low Dead Band
| Unsigned Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| ****
W
| ****
1%
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
6101
| ****
40 6102
| ****
Network Timeout
| Unsigned Scale 1| Unit: Seconds (sec), Range: 1 to 900 sec
Value x 1 (e.g. 10sec = 10)
| ****
W
| ****
900 sec
6102
| ****
40 6103
| ****
Room RH Demand Proportional Band
| Unsigned
Scale 10
| Unit: %, Range: 1% to 100%
Value x 10 (e.g. 10% = 100)
| ****
W
| ****
5%
6103
| ****
40 6104
| ****
RH Supply High Limit Proportional Band
| Unsigned
Scale 10
| Unit: %, Range: 1% to 100%
Value x 100 (e.g. 10% = 100)
| ****
RO
| ****
10%
6104
| ****
40 6105
| ****
Completely Dry Delay
| Unsigned
Scale 1
| Unit: Hours (h), Range: 0 to 24 h Value x 1 (e.g. 10h = 10)| ****
W
| ****
2h
6105
| ****
40 6106
| ****
Hour of Day Drying Cycle
| Unsigned
Scale 1
| Unit: Hours (h), Range: 0 to 24 h Value x 1 (e.g. 10h = 10)| ****
W
| ****
0h
6106
| ****
40 6107
| ****
Drying Fan Speed
| Unsigned
Scale 1
| Unit: %, Range: 0% to 100%
Value x 1 (e.g. 10% = 10)
| ****
W
| ****
100%
6107
| ****
40 6108
| ****
HRL Temperature Bias
| ****
Signed
Scale 100
| Unit: C or F, Range : -18.0°F, max: 18.0°F or
-10.0°C, max: 10.0°C
Value x 100 (e.g. 10°C = 1000)
| ****
W
| ****
0.0°C or 0.0°F
6108
| ****
40 6109
| ****
HRL Humidity Bias
| Unsigned
Scale 100
| Unit: % RH, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)
| ****
RO
| ****
0% RH
10000
| ****
4 10001
| ****
Air Flow
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10001
| ****
4 10002
| ****
Supply High Limit
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10002
| ****
4 10003
| ****
Interlock
| Unsigned
Scale 1
| 0 = Closed
1 = Open
| ****
RO
| ****
Closed
10003
| ****
4 10004
| ****
Binary External Demand
| Unsigned
Scale 1
| 0 = 0%
1 = 100%
| ****
RO
| ****
0%
10004
| ****
4 10005
| ****
Water Leak Detection
| Unsigned
Scale 1
| 0 = Ok
1 = Leak
| ****
RO
| ****
Ok
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
10005
| ****
4 10006
| ****
RS485 Interface
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
RO
| ****
No
10006
| ****
4 10007
| ****
Ethernet Interface
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
RO
| ****
No
10007
| ****
4 10008
| ****
Relay Fuse
| Unsigned
Scale 1
| 0 = Normal
1 = Blown Fuse
| ****
RO
| ****
Normal
10008
| ****
4 10009
| ****
Control PCB Fuse
| Unsigned
Scale 1
| 0 = Normal
1 = Open Fuse
| ****
RO
| ****
Normal
11000| 4 11001| Alarm Warning Relay| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11001| 4 11002| Service Warning Relay| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11002| 4 11003| Water Supply Valve| Unsigned
Scale 1
| 0 = Off
1 = On
| RO| Off
11003
| ****
4 11004
| ****
Drain Valve
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11004
| ****
4 11005
| ****
Circulation Pump
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11005
| ****
4 11004
| ****
Alarm LED
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11006
| ****
4 11005
| ****
Power LED
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
11007
| ****
4 11008
| ****
Buzzer
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
12000
| ****
4 12001
| ****
Float Switch
| Unsigned
Scale 1
| 0 = Inactive
1 = Active
| ****
RO
| ****
Inactive
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
12001
| ****
4 12002
| ****
Water Treatment Service Due
| Unsigned
Scale 1
| 0 = No
1 = Yes
| ****
RO
| ****
No
12002
| ****
4 12003
| ****
Service Due
| Unsigned
Scale 1
| 0 = Not Allowed 1 = Allowed| ****
W
| ****
Not Allowed
12003
| ****
4 12004
| ****
Run While Water Service Alarm
| Unsigned
Scale 1
| 0 = Not Allowed 1 = Allowed| ****
W
| ****
Not Allowed
12004| 4 12005| Startup Line Rinse| Unsigned
Scale 1
| 0 = Off
1 = On
| W| Off
12005| 4 12006| Run While Service Alarm| Unsigned
Scale 1
| 0 = Not Allowed 1 = Allowed| W| Allowed
12006
| ****
4 12007
| ****
HRL Lock Setpoint
| Unsigned
Scale 1
| 0 = Unlock
1 = Lock
| ****
W
| ****
Unlock
12007
| ****
4 12008
| ****
Network Control State
| Unsigned
Scale 1
| 0 = Normal
1 = Fault
| ****
W
| ****
Normal
12008
| ****
4 12009
| ****
Notify Alarm
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
Off
12009
| ****
4 12010
| ****
Notify Warning
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
Off
12010
| ****
4 12011
| ****
Notify App Msg
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
W
| ****
Off
15000
| ****
4 15001
| ****
Modbus Server Units
| Unsigned
Scale 1
| 0 = Metric
1 = Imperial
| ****
W
| ****
Metric
15001
| ****
4 15002
| ****
Control Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15002
| ****
4 15003
| ****
Room RH Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
15003
| ****
4 15004
| ****
Supply RH Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15004
| ****
4 15005
| ****
Control Profile
| ****
Unsigned
Scale 1
| 0 = ExternAnalog
1 = ExternNetwork
2 = InternHumAnalog
3 = InternHumNetwork
| 4 = InternCoolAnalog
5 = InternCoolNetwork
6 = HRLHum
7 = HRLCool
8 = Custom
| ****
W
| ****
ExternAnalog
15005
| ****
4 15006
| ****
Modulating High Limit Profile
| ****
Unsigned
Scale 1
| 0 = Disabled
1 = ExternAnalog
2 = ExternNetwork
3 = InternHumAnalog
| 4 = InternHumNetwork
5 = InternCoolAnalog
6 = InternCoolNetwork
7 = Custom
| ****
W
| ****
Disabled
15006
| ****
4 15007
| ****
Occupancy State
| Unsigned
Scale 1
| 0 = Occupied
1 = Unoccupied
| 2 = Vacant
3 = Off
| ****
RO
| ****
Occupied
15007
| ****
4 15008
| ****
Room RH Source
| Unsigned
Scale 1
| 0 = None
1 = RoomRH
| 2 = Network
3 = HRL
| ****
W
| ****
None
15008
| ****
4 15009
| ****
Room RH Setpoint Source
| Unsigned
Scale 1
| 0 = None
1 = Internal
| ****
2 = ControlInput
| ****
W
| ****
None
15009
| ****
4 15010
| ****
RH Supply High Limit Reading Source
| Unsigned
Scale 1
| 0 = None
1 = SuppyHLRH
| ****
2 = Network
| ****
W
| ****
None
15010
| ****
4 15011
| ****
RH Supply High Limit Setpoint Source
| Unsigned
Scale 1
| 0 = None
1 = Internal
| ****
2 = ControlInput
| ****
W
| ****
None
15011
| ****
4 15012
| ****
Control Demand Source
| Unsigned
Scale 1
| 0 = None
1 = ControlInput
| 2 = RoomDemand
3 = Network
| ****
W
| ****
ControlInput
15012
| ****
4 15013
| ****
Control High Limit Source
| Unsigned
Scale 1
| 0 = None
1 = ControlInput
| 2 = RHSupplyHLDemand
3 = Network 4=TempSupplyHLDemand
| ****
W
| ****
None
15013
| ****
4 15014
| ****
Control Cutout State
| Unsigned
Scale 1
| 0 = Off
1 = Normal
2 = LowLimit
| 3 = HighLimit
4 = NoAirFlow
5 = Interlock
| ****
RO
| ****
Off
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
15014
| ****
4 15015
| ****
State
| ****
Unsigned
Scale 1
| 0 = Off
1 = Idle
2 = LineRinse
3 = Filling
| 4 = Draining
5 = Running
6 = Alarm
7 = Drying
| ****
RO
| ****
Off
15015
| ****
4 15016
| ****
System Alarm
| Unsigned
Scale 1
| 0 = Normal
1 = DrainTimeout
2 = FillTimeout
| 3 = WaterLeak
4 = FanDefect
| ****
RO
| ****
Normal
15016
| ****
4 15017
| ****
Fan Request
| Unsigned
Scale 1
| 0 = Off
1 = Default
2 = On
| ****
W
| ****
Default
15017
| ****
4 15018
| ****
Pump Request
| Unsigned
Scale 1
| 0 = Off
1 = Default
2 = On
| ****
W
| ****
Default
15018
| ****
4 15019
| ****
Water Supply Request
| Unsigned
Scale 1
| 0 = Off
1 = Default
2 = On
| ****
W
| ****
Default
15019
| ****
4 15020
| ****
Room Temperature Setpoint Source
| Unsigned
Scale 1
| 0 = None
1 = Internal
| ****
2 = ControlInput
| ****
W
| ****
None
15020
| ****
4 15021
| ****
Temp Supply High Limit Reading Source
| Unsigned
Scale 1
| 0 = None
1 = SuppyHLTemp
| ****
2 = Network
| ****
W
| ****
None
15021
| ****
4 15022
| ****
Temp Supply High Limit Setpoint Source
| Unsigned
Scale 1
| 0 = None
1 = Internal
| ****
2 = ControlInput
| ****
W
| ****
None
15022
| ****
4 15023
| ****
Room Temperature Source
| Unsigned
Scale 1
| 0 = None
1 = RoomTemp
| 2 = Network
3 = HRL
| ****
W
| ****
None
15023
| ****
4 15024
| ****
Room Temperature Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15024
| ****
4 15025
| ****
Supply Temperature Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
Protocol Base| Holding Register| ****
Description
| ****
Data Type
| ****
Units, Limits, State Texts
| Writa ble| ****
Default Value
---|---|---|---|---|---|---
15025
| ****
4 15026
| ****
Control Signal Type
| Unsigned
Scale 1
| 0 = 0-10Vdc
1 = 2-10Vdc
| 2 = 4-20mA
3 = 0-20mA
| ****
W
| ****
0-10Vdc
15026
| ****
4 15027
| ****
System Power State
| Unsigned
Scale 1
| 0 = Off
1 = On
| ****
RO
| ****
Off
15027
| ****
4 15028
| ****
Recirculation Request
| Unsigned
Scale 1
| 0 = None
1 = ResetAlarms
2 = Drain
| 3 = ResetServCnt
4 = ResetWtrServCnt
5 = Filling
| ****
W
| ****
None
15028
| ****
4 15029
| ****
DirectFeed Request
| Unsigned
Scale 1
| 0 = None
1 = ResetAlarms
| 3 = ResetServCnt
4 = ResetWtrServCnt
| ****
W
| ****
None
400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com
Toll free in North America:
1-800-361-2308 Tel.:
514-333-1433 Fax:
514-333-3163 Customer service fax:
514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)