neptronic SKVF Series Evaporative Cooler User Guide

June 3, 2024
neptronic

neptronic SKVF Series Evaporative Cooler

Introduction

The SKVF Modbus Communication Module User Guide provides information for using Neptronic® communication feature. The controller uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic SKVF devices.
The SKVF Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus:

  • Data Model. The Evaporative Cooler Modbus server data model uses only the Modbus Registers table.
  • Register Address:
    • As per protocol base (base 0); for PLC add 1 to protocol base.
    • As per holding register (base 400001).

Note: Ensure that the Modbus communication software used does not have a limit on the range of the register addresses that can be viewed and supports 6-digit holding registers.

  • Function Codes. The Evaporative Cooler Modbus server supports a limited function codes subset comprising:
    • Read Holding Registers (0x03)
    • Write Single Register (0x06)
    • Write Multiple Registers (0x10)
  • Exception Responses. The Evaporative Cooler Modbus server supports the following exception codes:
    • Illegal data address
    • Illegal data value
    • Slave device busy
  • Serial Line. The Evaporative Cooler Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
    • The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
    • The supported baud rates are 9600, 19200, 38400, and 57600.
    • The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2.
    • In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
  • Addressing. The Evaporative Cooler device only answers at the following address:
    • The device’s unique address (1 to 246) that can be set through the device menu or through holding register index 0.

Modbus Registers

Table Glossary

Name Description Name Description
W Writable Register ASCII For registers containing ASCII (8-bit) characters
RO Read Only Register MSB Most Significant Byte
Unsigned For range of values from 0 to 65,535, unless otherwise specified
LSB Least Significant Byte
Signed For range of values from -32,768 to 32,767, unless otherwise
specified MSW Most Significant Word
Bit String For registers with multiple values using bit mask (example,
flags) LSW Least Significant Word

Modbus Registers Table

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


0

| ****

40000 1

| ****

Modbus Address and Product Type

| ****

Unsigned

| MSB = Product type, not writable

LSB = Modbus Address (1 to 247), writable

| ****

W

|
1| 40000 2| Device Baud Rate| Unsigned

Scale 100

| 0, 9600, 19200, 38400, and 57600, 0 = Auto Baud Rate

Detection Value/100 (e.g. 38400 baud = 384)

| W| 19200


2

| ****

40000 3

| ****

Modbus Slave Communication Port Configuration

| ****

Unsigned

| 0 = No parity, 2 Stop bits 1 = Even parity, 1 Stop bit 2 = Odd parity, 1 Stop bit| ****

W

| ****

No parity, 2 Stops bits

3| 40000 4| Product Name (characters 8 & 7)| ASCII| MSB = char 6, LSB = char 7| W|
4| 40000 5| Product Name (characters 6 & 5)| ASCII| MSB = char 4, LSB = char 5| W|
5| 40000 6| Product Name (characters 4 & 3)| ASCII| MSB = char 2, LSB = char 3| W|
6| 40000 7| Product Name (characters 2 & 1)| ASCII| MSB = char 0, LSB = char 1| W|
Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---
7| 40000 8| Product Actual Firmware Version (in Integer x100)| Unsigned

Scale 100

| 1 to 65535 (e.g. 100)| RO|
8| 40000 9| Product Actual EEPROM Version (in Integer x100)| Unsigned

Scale 100

| 1 to 65535 (e.g. 100)| RO|


2000

| ****

40 2001

| ****

Control Signal

| Unsigned

Scale 1000

| Units: Volt (V), Range: 0V to 15V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V


2001

| ****

40 2002

| ****

Room RH Signal

| Unsigned

Scale 1000

| Units: Volt (V), Range: 0V to 15V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V


2002

| ****

40 2003

| ****

Supply RH Signal

| Unsigned

Scale 1000

| Units: Volt (V), Range: 0V to 15V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V


2003

| ****

40 2004

| ****

ECM Fan Feedback

| Unsigned

Scale 1

| Units: Hz, Range: 0 to 30000Hz

Value x 1 (e.g. 10Hz = 10)

| ****

RO

| ****

0Hz


2004

| ****

40 2005

| ****

Float Switch Signal

| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V


2005

| ****

40 2006

| ****

Board Temperature Signal

| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V


2006

| ****

40 2007

| ****

Main Power Supply

| Unsigned

Scale 10

| Unit: Volt (V), Range: 0V to 40V

Value x 10 (e.g. 2V = 20)

| ****

RO

| ****

0V


2007

| ****

40 2008

| ****

ECM Fan Feedback 2

| Unsigned

Scale 1

| Units: Hz, Range: 0 to 30000Hz

Value x 1 (e.g. 10Hz = 10)

| ****

RO

| ****

0Hz


2008

| ****

40 2009

| ****

Room Temperature Signal

| Unsigned

Scale 1000

| Units: Volt (V), Range: 0V to 15V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V


2009

| ****

40 2010

| ****

Supply Temperature Signal

| Unsigned

Scale 1000

| Units: Volt (V), Range: 0V to 15V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V


2010

| ****

40 2011

| ****

Control Signal

| Unsigned

Scale 1000

| Units: Volt (V), Range: 0V to 15V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


4000

| ****

40 4001

| ****

Power Output Feedback Signal

| Unsigned

Scale 1000

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 2V = 2000)

| ****

RO

| ****

0V

4001| 40 4002| ECM Fan Signal| Unsigned

Scale 100

| Unit: Volt (V), Range: 0V to 10V

Value x 1000 (e.g. 2V = 2000)

| RO| 0V


6000

| ****

40 6001

| ****

Demand

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%


6001

| ****

40 6002

| ****

Power Output

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%


6002

| ****

40 6003

| ****

Control Input

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0%


6003

| ****

40 6004

| ****

Control Min

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0%


6004

| ****

40 6005

| ****

Control Max

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0%


6005

| ****

40 6006

| ****

Control Bias

| Signed

Scale 100

| Unit: %, Range: -10% to 10%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0%


6006

| ****

40 6007

| ****

Room RH

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

RO

| ****

0% RH


6007

| ****

40 6008

| ****

Room RH Min

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6008

| ****

40 6009

| ****

Room RH Max

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6009

| ****

40 6010

| ****

Room RH Bias

| Unsigned

Scale 100

| Unit: % RH, Range: -10% RH to 10% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6010

| ****

40 6011

| ****

Supply High Limit RH

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

RO

| ****

0% RH

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


6011

| ****

40 6012

| ****

Supply High Limit RH Min

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6012

| ****

40 6013

| ****

Supply High Limit RH Max

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6013

| ****

40 6014

| ****

Supply High Limit RH Bias

| Signed

Scale 100

| Unit: %, Range: -10% RH to 10% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6014

| ****

40 6015

| ****

Run Time (0)

| Unsigned

Scale 100

| Units: Hours (h), Range: 0 to 2147483647 h

Value x 100 (e.g. 10 h = 1000)

| ****

RO

| ****

0h

6015| 40 6016| Run Time (1)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |
6016| 40 6017| Run Time (2)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |
6017| 40 6018| Run Time (3)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |


6018

| ****

40 6019

| ****

On Time (0)

| Unsigned

Scale 100

| Units: Hours (h), Range: 0 to 2147483647 h

Value x 100 (e.g. 10 h = 1000)

| ****

RO

| ****

0h

6019| 40 6020| On Time (1)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |
6020| 40 6021| On Time (2)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |
6021| 40 6022| On Time (3)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |


6022

| ****

40 6023

| ****

Water Treated Volume (0)

| Unsigned

Scale 100

| Units: Litres (l), Range: 0 to 9999999 l

Value x 100 (e.g. 10 h = 1000)

| ****

RO

| ****

0l

6023| 40 6024| Water Treated Volume (1)|  | Units: Litres (l), Range: 0 to 9999999 l|  |
6024| 40 6025| Water Treated Volume (2)|  | Units: Litres (l), Range: 0 to 9999999 l|  |
6025| 40 6026| Water Treated Volume (3)|  | Units: Litres (l), Range: 0 to 9999999 l|  |


6026

| ****

40 6027

| ****

Service On Time (0)

| Unsigned

Scale 100

| Units: Hours (h), Range: 0 to 2147483647 h

Value x 100 (e.g. 10 h = 1000)

| ****

RO

| ****

0h

6027| 40 6028| Service On Time (1)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |
6028| 40 6029| Service On Time (2)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |
Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---
6029| 40 6030| Service On Time (3)|  | Units: Hours (h), Range: 0 to 2147483647 h|  |


6030

| ****

40 6031

| ****

Dead Band

| Unsigned

Scale 1

| Unit: %, Range: 1% to 100%

Value x 1 (e.g. 10% = 10)

| ****

W

| ****

5%


6031

| ****

40 6032

| ****

Minimum Production Output

| Unsigned

Scale 1

| Unit: %, Range: 0% to 100%

Value x 1 (e.g. 10% = 10)

| ****

W

| ****

10%


6032

| ****

40 6033

| ****

Maximum Production Output

| Unsigned

Scale 1

| Unit: %, Range: 0% to 100%

Value x 1 (e.g. 10% = 10)

| ****

W

| ****

100%


6033

| ****

40 6034

| ****

Idle Fan Speed

| Unsigned

Scale 1

| Unit: %, Range: 0% to 100%

Value x 1 (e.g. 10% = 10)

| ****

W

| ****

0%


6034

| ****

40 6035

| ****

Service Interval

| Unsigned

Scale 1

| Units: Hours (h), Range: 1000 to 3000 h

Value x 1 (e.g. 10 h = 10)

| ****

W

| ****

1000h


6035

| ****

40 6036

| ****

Board Temperature

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F

Value x 100 (e.g. 5°C = 500 or 32ºF = 3200)

| ****

W

| ****

0°C or 32°F


6036

| ****

40 6037

| ****

Power Output Feedback Bias

| Unsigned

Scale 1000

| Unit: V, Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| ****

W

| ****

0V


6037

| ****

40 6038

| ****

Power Output Feedback Min

| Unsigned

Scale 1000

| Unit: V, Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| ****

W

| ****

0V


6038

| ****

40 6039

| ****

Power Output Feedback Max

| Unsigned

Scale 1000

| Unit: V, Range: 0V to 10V

Value x 1000 (e.g. 1V = 1000)

| ****

W

| ****

10V


6039

| ****

40 6040

| ****

Power Output Feedback

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%


6040

| ****

40 6041

| ****

Dilution Ratio

| Unsigned

Scale 1

| Unit: %, Range: 0% to 300%

Value x 1 (e.g. 10% = 10)

| ****

W

| ****

100%


6041

| ****

40 6042

| ****

Drain Interval

| Unsigned

Scale 1

| Unit: Hours (h), Range: 0 to 24 h

Value x 1 (e.g. 10h = 10)

| ****

W

| ****

4h

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


6042

| ****

40 6043

| ****

Fixed Drain Time

| Unsigned

Scale 1

| Unit: Hours (h), Range: 4 to 72 h

Value x 1 (e.g. 10h = 10)

| ****

W

| ****

6h


6043

| ****

40 6044

| ****

Line Rinse Time

| Unsigned

Scale 1

| Unit: Seconds (sec), Range: 0sec to 2000sec

Value x 1 (e.g. 10sec = 10)

| ****

W

| ****

180 sec


6044

| ****

40 6045

| ****

Water Treatment Service Volume

| Unsigned

Scale 1

| Unit: Litres (l), Range: 2500 to 10000 l

Value x 1 (e.g. 10h = 10)

| ****

W

| ****

7500 l


6045

| ****

40 6046

| ****

Water Supply Duty Cycle

| Unsigned

Scale 1

| Unit: %, Range: 8% to 70%

Value x 1 (e.g. 10% = 10)

| ****

W

| ****

10%


6046

| ****

40 6047

| ****

Water Supply Period

| Unsigned

Scale 1

| Unit: Seconds (sec), Range: 0sec to 180sec

Value x 1 (e.g. 10sec = 10)

| ****

W

| ****

60 sec


6047

| ****

40 6048

| ****

Room RH Network Reading

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6048

| ****

40 6049

| ****

Room RH Setpoint

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

40% RH


6049

| ****

40 6050

| ****

Room RH Unoccupied Setpoint

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

30% RH


6050

| ****

40 6051

| ****

Room RH Vacant Setpoint

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

20% RH


6051

| ****

40 6052

| ****

Room RH Demand Proportional Gain

| Unsigned

Scale 10

| No Unit, Range: 1 to 200

Value x 10 (e.g. 10 = 100)

| ****

W

| ****

28.5


6052

| ****

40 6053

| ****

Room RH Demand Integral Time

| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 900 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec


6053

| ****

40 6054

| ****

Room RH Demand Derivative Time

| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 60 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec


6054

| ****

40 6055

| ****

Room RH Demand

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

RO

| ****

0% RH

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


6055

| ****

40 6056

| ****

RH Supply High Limit Network Reading

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

0% RH


6056

| ****

40 6057

| ****

RH Supply High Limit Setpoint

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

80% RH


6057

| ****

40 6058

| ****

RH Supply High Limit Unoccupied Setpoint

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

80% RH


6058

| ****

40 6059

| ****

RH Supply High Limit Vacant Setpoint

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

W

| ****

80% RH


6059

| ****

40 6060

| ****

RH Supply High Limit Proportional Gain

| Unsigned

Scale 10

| No Unit, Range: 1 to 200

Value x 10 (e.g. 10 = 100)

| ****

W

| ****

28.5


6060

| ****

40 6061

| ****

RH Supply High Limit Integral Time

| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 900 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec


6061

| ****

40 6062

| ****

RH Supply High Limit Derivative Time

| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 60 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec


6062

| ****

40 6063

| ****

RH Supply High Limit Demand

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

RO

| ****

0% RH


6063

| ****

40 6064

| ****

Control Network Demand

| Unsigned Scale 100| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0%


6064

| ****

40 6065

| ****

Control Network High Limit

| Unsigned Scale 100| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0%


6065

| ****

40 6066

| ****

User Demand

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%


6066

| ****

40 6067

| ****

System Steam Capacity

| ****

Unsigned

Scale 10

| Unit: kg/hr or lb/hr, Range: 0 to 3000 kg/hr or 0 to 6614 lb/hr

Value x 10 (e.g. 10kg/hr = 100 or 10lb/hr = 100)

| ****

RO

| ****

0 kg/hr or

0 lb/hr

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


6067

| ****

40 6068

| ****

Room Temperature

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

20.0°C or

68.0°F


6068

| ****

40 6069

| ****

Room Temperature Min

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

0.0°C or

32.0°F


6069

| ****

40 6070

| ****

Room Temperature Max

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

40.0°C or

104.0°F


6070

| ****

40 6071

| ****

Room Temperature Bias

| ****

Signed

Scale 100

| Unit: C or F, Range : -18.0°F, max: 18.0°F or

-10.0°C, max: 10.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

0.0°C or 0.0°F


6071

| ****

40 6072

| ****

Room Temperature Network Reading

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to 500°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| ****

0°C or 32°F


6072

| ****

40 6073

| ****

Room Temperature Setpoint

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| 22°C or 71.6°F


6073

| ****

40 6074

| ****

Room Temperature Unoccupied Setpoint

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| 24°C or 75.2°F


6074

| ****

40 6075

| ****

Room Temperature Vacant Setpoint

| Unsigned

Scale 100

| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| 26°C or 78.8°F


6075

| ****

40 6076

| Room Temperature Demand Proportional Gain| Unsigned

Scale 10

| No Unit, Range: 1 to 200

Value x 10 (e.g. 10 = 100)

| ****

W

| ****

28.5


6076

| ****

40 6077

| ****

Room Temperature Demand Integral Time

| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 900 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec


6077

| ****

40 6078

| Room Temperature Demand Derivative Time| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 60 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


6078

| ****

40 6079

| ****

Room Temperature Demand

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%


6079

| ****

4 06080

| ****

HRL Temperature

| Signed

Scale 100

| Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to 500°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

RO

| ****

0°C or 32°F


6080

| ****

40 6081

| ****

HRL Humidity

| Unsigned

Scale 100

| Unit: % RH, Range: 0% RH to 100% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

RO

| ****

0% RH


6081

| ****

40 6082

| ****

Room Temp Demand Proportional Band

| Unsigned

Scale 10

| Unit: %, Range: 1% to 100%

Value x 10 (e.g. 10% = 100)

| ****

W

| ****

5%


6082

| ****

40 61083

| ****

Temp Supply High Limit Network Reading

| Signed Scale 100| Unit: ºC/ºF, Range: -40°C to 100°C or -40°F to 212°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| ****

0°C or 32°F


6083

| ****

40 6084

| ****

Temp Supply High Limit Setpoint

| Unsigned Scale 100| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| ****

15°C or 59°F


6084

| ****

40 6085

| Temp Supply High Limit Unoccupied Setpoint| Unsigned Scale 100| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| 17°C or 62.6°F


6085

| ****

40 6086

| ****

Temp Supply High Limit Vacant Setpoint

| Unsigned Scale 100| Unit: ºC/ºF, Range: 0°C to 40°C or 32°F to 104°F,

Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

| ****

W

| 16°C or 60.8°F


6086

| ****

40 6087

| ****

Temp Supply High Limit Proportional Gain

| Unsigned

Scale 10

| No Unit, Range: 1 to 200

Value x 10 (e.g. 10 = 100)

| ****

W

| ****

28.0


6087

| ****

40 6088

| ****

Temp Supply High Limit Integral Time

| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 900 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec


6088

| ****

40 6089

| ****

Modbus TCP IP Keep Alive Time Out

| Unsigned

Scale 1

| Unit: Minutes (min), Range: 1 to 1440 mins

Value x 1 (e.g. 5 mins = 5)

| ****

W

| ****

5 min


6089

| ****

40 6090

| ****

Temp Supply High Limit Derivative Time

| Unsigned

Scale 10

| Unit: Seconds (sec), Range: 0 to 60 sec

Value x 10 (e.g. 10 sec = 100)

| ****

W

| ****

0 sec


6090

| ****

40 6091

| ****

Temp Supply High Limit Demand

| Unsigned

Scale 100

| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

RO

| ****

0%

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


6091

| ****

40 6092

| ****

Temp Supply High Limit Proportional Band

| Unsigned

Scale 10

| Unit: %, Range: 1% to 100%

Value x 100 (e.g. 10% = 100)

| ****

RO

| ****

10%


6092

| ****

40 6093

| ****

Supply High Limit Temperature

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

20.0°C or

68.0°F


6093

| ****

40 6094

| ****

Supply High Limit Temperature Min

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

0.0°C or

32.0°F


6094

| ****

40 6095

| ****

Supply High Limit Temperature Max

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

40.0°C or

104.0°F


6095

| ****

40 6096

| ****

Supply High Limit Temperature Bias

| ****

Signed

Scale 100

| Unit: C or F, Range : -18.0°F, max: 18.0°F or

-10.0°C, max: 10.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

20.0°C or

68.0°F


6096

| ****

40 6097

| ****

Control Input

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

20.0°C or

68.0°F


6097

| ****

40 6098

| ****

Control Min

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

0.0°C or

32.0°F


6098

| ****

40 6099

| ****

Control Max

| ****

Signed

Scale 100

| Unit: C or F, Range : -40.0°F, max: 212.0°F or

-40.0°C, max: 100.0°C

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

40.0°C or

104.0°F


6099

| ****

40 6100

| ****

Control Bias

| ****

Signed

Scale 100

| Unit: C or F, Range : -18.0°F, max: 18.0°F or

-10.0°C, max: 10.0°C

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

20.0°C or

68.0°F


6100

| ****

40 6101

| ****

Demand Low Dead Band

| Unsigned Scale 100| Unit: %, Range: 0% to 100%

Value x 100 (e.g. 10% = 1000)

| ****

W

| ****

1%

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


6101

| ****

40 6102

| ****

Network Timeout

| Unsigned Scale 1| Unit: Seconds (sec), Range: 1 to 900 sec

Value x 1 (e.g. 10sec = 10)

| ****

W

| ****

900 sec


6102

| ****

40 6103

| ****

Room RH Demand Proportional Band

| Unsigned

Scale 10

| Unit: %, Range: 1% to 100%

Value x 10 (e.g. 10% = 100)

| ****

W

| ****

5%


6103

| ****

40 6104

| ****

RH Supply High Limit Proportional Band

| Unsigned

Scale 10

| Unit: %, Range: 1% to 100%

Value x 100 (e.g. 10% = 100)

| ****

RO

| ****

10%


6104

| ****

40 6105

| ****

Completely Dry Delay

| Unsigned

Scale 1

| Unit: Hours (h), Range: 0 to 24 h Value x 1 (e.g. 10h = 10)| ****

W

| ****

2h


6105

| ****

40 6106

| ****

Hour of Day Drying Cycle

| Unsigned

Scale 1

| Unit: Hours (h), Range: 0 to 24 h Value x 1 (e.g. 10h = 10)| ****

W

| ****

0h


6106

| ****

40 6107

| ****

Drying Fan Speed

| Unsigned

Scale 1

| Unit: %, Range: 0% to 100%

Value x 1 (e.g. 10% = 10)

| ****

W

| ****

100%


6107

| ****

40 6108

| ****

HRL Temperature Bias

| ****

Signed

Scale 100

| Unit: C or F, Range : -18.0°F, max: 18.0°F or

-10.0°C, max: 10.0°C

Value x 100 (e.g. 10°C = 1000)

| ****

W

| ****

0.0°C or 0.0°F


6108

| ****

40 6109

| ****

HRL Humidity Bias

| Unsigned

Scale 100

| Unit: % RH, Range: -10% RH to 10% RH

Value x 100 (e.g. 10% RH = 1000)

| ****

RO

| ****

0% RH


10000

| ****

4 10001

| ****

Air Flow

| Unsigned

Scale 1

| 0 = Closed

1 = Open

| ****

RO

| ****

Closed


10001

| ****

4 10002

| ****

Supply High Limit

| Unsigned

Scale 1

| 0 = Closed

1 = Open

| ****

RO

| ****

Closed


10002

| ****

4 10003

| ****

Interlock

| Unsigned

Scale 1

| 0 = Closed

1 = Open

| ****

RO

| ****

Closed


10003

| ****

4 10004

| ****

Binary External Demand

| Unsigned

Scale 1

| 0 = 0%

1 = 100%

| ****

RO

| ****

0%


10004

| ****

4 10005

| ****

Water Leak Detection

| Unsigned

Scale 1

| 0 = Ok

1 = Leak

| ****

RO

| ****

Ok

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


10005

| ****

4 10006

| ****

RS485 Interface

| Unsigned

Scale 1

| 0 = No

1 = Yes

| ****

RO

| ****

No


10006

| ****

4 10007

| ****

Ethernet Interface

| Unsigned

Scale 1

| 0 = No

1 = Yes

| ****

RO

| ****

No


10007

| ****

4 10008

| ****

Relay Fuse

| Unsigned

Scale 1

| 0 = Normal

1 = Blown Fuse

| ****

RO

| ****

Normal


10008

| ****

4 10009

| ****

Control PCB Fuse

| Unsigned

Scale 1

| 0 = Normal

1 = Open Fuse

| ****

RO

| ****

Normal

11000| 4 11001| Alarm Warning Relay| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off
11001| 4 11002| Service Warning Relay| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off
11002| 4 11003| Water Supply Valve| Unsigned

Scale 1

| 0 = Off

1 = On

| RO| Off


11003

| ****

4 11004

| ****

Drain Valve

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11004

| ****

4 11005

| ****

Circulation Pump

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11005

| ****

4 11004

| ****

Alarm LED

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11006

| ****

4 11005

| ****

Power LED

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


11007

| ****

4 11008

| ****

Buzzer

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


12000

| ****

4 12001

| ****

Float Switch

| Unsigned

Scale 1

| 0 = Inactive

1 = Active

| ****

RO

| ****

Inactive

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


12001

| ****

4 12002

| ****

Water Treatment Service Due

| Unsigned

Scale 1

| 0 = No

1 = Yes

| ****

RO

| ****

No


12002

| ****

4 12003

| ****

Service Due

| Unsigned

Scale 1

| 0 = Not Allowed 1 = Allowed| ****

W

| ****

Not Allowed


12003

| ****

4 12004

| ****

Run While Water Service Alarm

| Unsigned

Scale 1

| 0 = Not Allowed 1 = Allowed| ****

W

| ****

Not Allowed

12004| 4 12005| Startup Line Rinse| Unsigned

Scale 1

| 0 = Off

1 = On

| W| Off
12005| 4 12006| Run While Service Alarm| Unsigned

Scale 1

| 0 = Not Allowed 1 = Allowed| W| Allowed


12006

| ****

4 12007

| ****

HRL Lock Setpoint

| Unsigned

Scale 1

| 0 = Unlock

1 = Lock

| ****

W

| ****

Unlock


12007

| ****

4 12008

| ****

Network Control State

| Unsigned

Scale 1

| 0 = Normal

1 = Fault

| ****

W

| ****

Normal


12008

| ****

4 12009

| ****

Notify Alarm

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

W

| ****

Off


12009

| ****

4 12010

| ****

Notify Warning

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

W

| ****

Off


12010

| ****

4 12011

| ****

Notify App Msg

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

W

| ****

Off


15000

| ****

4 15001

| ****

Modbus Server Units

| Unsigned

Scale 1

| 0 = Metric

1 = Imperial

| ****

W

| ****

Metric


15001

| ****

4 15002

| ****

Control Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc


15002

| ****

4 15003

| ****

Room RH Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


15003

| ****

4 15004

| ****

Supply RH Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc



15004

| ****


4 15005

| ****


Control Profile

| ****

Unsigned

Scale 1

| 0 = ExternAnalog

1 = ExternNetwork

2 = InternHumAnalog

3 = InternHumNetwork

| 4 = InternCoolAnalog

5 = InternCoolNetwork

6 = HRLHum

7 = HRLCool

8 = Custom

| ****


W

| ****


ExternAnalog


15005

| ****

4 15006

| ****

Modulating High Limit Profile

| ****

Unsigned

Scale 1

| 0 = Disabled

1 = ExternAnalog

2 = ExternNetwork

3 = InternHumAnalog

| 4 = InternHumNetwork

5 = InternCoolAnalog

6 = InternCoolNetwork

7 = Custom

| ****

W

| ****

Disabled


15006

| ****

4 15007

| ****

Occupancy State

| Unsigned

Scale 1

| 0 = Occupied

1 = Unoccupied

| 2 = Vacant

3 = Off

| ****

RO

| ****

Occupied


15007

| ****

4 15008

| ****

Room RH Source

| Unsigned

Scale 1

| 0 = None

1 = RoomRH

| 2 = Network

3 = HRL

| ****

W

| ****

None


15008

| ****

4 15009

| ****

Room RH Setpoint Source

| Unsigned

Scale 1

| 0 = None

1 = Internal

| ****

2 = ControlInput

| ****

W

| ****

None


15009

| ****

4 15010

| ****

RH Supply High Limit Reading Source

| Unsigned

Scale 1

| 0 = None

1 = SuppyHLRH

| ****

2 = Network

| ****

W

| ****

None


15010

| ****

4 15011

| ****

RH Supply High Limit Setpoint Source

| Unsigned

Scale 1

| 0 = None

1 = Internal

| ****

2 = ControlInput

| ****

W

| ****

None


15011

| ****

4 15012

| ****

Control Demand Source

| Unsigned

Scale 1

| 0 = None

1 = ControlInput

| 2 = RoomDemand

3 = Network

| ****

W

| ****

ControlInput


15012

| ****

4 15013

| ****

Control High Limit Source

| Unsigned

Scale 1

| 0 = None

1 = ControlInput

| 2 = RHSupplyHLDemand

3 = Network 4=TempSupplyHLDemand

| ****

W

| ****

None


15013

| ****

4 15014

| ****

Control Cutout State

| Unsigned

Scale 1

| 0 = Off

1 = Normal

2 = LowLimit

| 3 = HighLimit

4 = NoAirFlow

5 = Interlock

| ****

RO

| ****

Off

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


15014

| ****

4 15015

| ****

State

| ****

Unsigned

Scale 1

| 0 = Off

1 = Idle

2 = LineRinse

3 = Filling

| 4 = Draining

5 = Running

6 = Alarm

7 = Drying

| ****

RO

| ****

Off


15015

| ****

4 15016

| ****

System Alarm

| Unsigned

Scale 1

| 0 = Normal

1 = DrainTimeout

2 = FillTimeout

| 3 = WaterLeak

4 = FanDefect

| ****

RO

| ****

Normal


15016

| ****

4 15017

| ****

Fan Request

| Unsigned

Scale 1

| 0 = Off

1 = Default

2 = On

| ****

W

| ****

Default


15017

| ****

4 15018

| ****

Pump Request

| Unsigned

Scale 1

| 0 = Off

1 = Default

2 = On

| ****

W

| ****

Default


15018

| ****

4 15019

| ****

Water Supply Request

| Unsigned

Scale 1

| 0 = Off

1 = Default

2 = On

| ****

W

| ****

Default


15019

| ****

4 15020

| ****

Room Temperature Setpoint Source

| Unsigned

Scale 1

| 0 = None

1 = Internal

| ****

2 = ControlInput

| ****

W

| ****

None


15020

| ****

4 15021

| ****

Temp Supply High Limit Reading Source

| Unsigned

Scale 1

| 0 = None

1 = SuppyHLTemp

| ****

2 = Network

| ****

W

| ****

None


15021

| ****

4 15022

| ****

Temp Supply High Limit Setpoint Source

| Unsigned

Scale 1

| 0 = None

1 = Internal

| ****

2 = ControlInput

| ****

W

| ****

None


15022

| ****

4 15023

| ****

Room Temperature Source

| Unsigned

Scale 1

| 0 = None

1 = RoomTemp

| 2 = Network

3 = HRL

| ****

W

| ****

None


15023

| ****

4 15024

| ****

Room Temperature Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc


15024

| ****

4 15025

| ****

Supply Temperature Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc

Protocol Base| Holding Register| ****

Description

| ****

Data Type

| ****

Units, Limits, State Texts

| Writa ble| ****

Default Value

---|---|---|---|---|---|---


15025

| ****

4 15026

| ****

Control Signal Type

| Unsigned

Scale 1

| 0 = 0-10Vdc

1 = 2-10Vdc

| 2 = 4-20mA

3 = 0-20mA

| ****

W

| ****

0-10Vdc


15026

| ****

4 15027

| ****

System Power State

| Unsigned

Scale 1

| 0 = Off

1 = On

| ****

RO

| ****

Off


15027

| ****

4 15028

| ****

Recirculation Request

| Unsigned

Scale 1

| 0 = None

1 = ResetAlarms

2 = Drain

| 3 = ResetServCnt

4 = ResetWtrServCnt

5 = Filling

| ****

W

| ****

None


15028

| ****

4 15029

| ****

DirectFeed Request

| Unsigned

Scale 1

| 0 = None

1 = ResetAlarms

| 3 = ResetServCnt

4 = ResetWtrServCnt

| ****

W

| ****

None

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com
Toll free in North America: 1-800-361-2308 Tel.: 514-333-1433 Fax: 514-333-3163 Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

neptronic User Manuals

Related Manuals