EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual

June 3, 2024
EATON

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction
Manual

⚠ WARNING

  1. ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT.
  2. ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION.
  3. DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO THE DISCONNECT POSITION.
  4. ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION AND MECHANISM SPRINGS DISCHARGED.

FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR PROPERTY DAMAGE.

⚠ WARNING

THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES:
– DISCONNECTING
– ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED
– VERIFY ISOLATION FROM THE SUPPLY
– EARTHING AND SHORT-CIRCUITING
– COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS

DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED
MAINTENANCE INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR AND EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT INJURY TO PERSONNEL AND DAMAGE TO THE EQUIPMENT.

General information

This Series NRX 65 kA bus extension kit is for a fixed front connect configuration (Figure 1). The arc hood on a Series NRX fixed circuit breaker is positioned over the breaker’s arc chambers to primarily direct arc gas discharge. An arc hood is used on all fixed circuit breakers whether they are configured for rear or front connection. This front connect configuration also contains a shroud mounted on the load side of the breaker. Mounting feet are used to attach breakers to a vertical surface. Refer to IL01301020E for mounting instructions.

⚠ CAUTION
IT IS IMPORTANT NOT TO EXCEED THE RECOMMENDED TORQUE VALUES WHEN MAKING BOLTED CONNECTIONS TO THE EQUIPMENT OR TO THE ADAPTERS THEMSELVES, ALL WHICH HAVE PRE-TAPPED HOLES. FAILURE TO FOLLOW THESE REQUIREMENTS COULD RESULT IN EQUIPMENT DAMAGE AND/OR FAILURE.

The front connect breaker configuration has bus adapters that are internal to the breaker and are intended to accommodate cable terminals and/or bus extension connections. These cannot be replaced in the field.

The arc hood on the line side and the shroud on the load side serve to insulate the bus adapters from their surroundings (Figure 2). Refer to Table 1 for a list of available front connectors.

Note: For applications of 65 kA, the bus extension kits below must be utilized for the line side only.

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Table
1

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Table
2

Instructions to assemble

Bus extension kit installation
In order to attach cable terminals or bus conductor extensions to the line and load bus adapters, proceed with the following steps.

Step 1
Remove the four screws (or five screws for a four-pole breaker) while holding the front of the arc hood (Figure 3).

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
3

Step 2
With the screws removed, pull out the front of the arc hood and set it aside (Figure 4).EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction
Manual - Figure 4

Step 3
Slide each of the baffles forward and out to provide proper access to the bus adapters (Figure 5).

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
5

Step 4
Remove four screws and lift up front cover. On the line side, remove the three screws on the secondary contact block assembly. Slide out secondary contact block shield. With the screws removed, pull out the secondary contact block assembly (Figure 6).

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
6

Step 5
Access is now available to make the required bus conductor extension or cable terminal connections (Figure 7).

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
7

Step 6
Bolt the bus conductor extensions to the breaker bus adapters using the provided hardware. Torque the bolted connections to 30 ft-lb (40.7 NM). Make sure that the hardware used to make the connections does not extend out past the adapter surface. Check that the bolt goes all the way through the bus adapters.

  1. Attach back plate on extender support to join all 3 extenders as shown in Figure 8.
  2. Once the bolted connections are made, replace the baffles removed in Step 3 by sliding them back into position, making sure that the baffle notches are oriented toward the breaker. The bus extensions will fit through the space available between the baffles and the arc hood. Replace secondary block assembly shield.
  3. Replace the secondary contact block assembly previously removed in Step 4.
  4. Replace front of the arc hood and the front of the shroud previously removed in Step 1 and Step 2. Replace front cover.
  5. Phase barriers made from flexible rubber material are supplied with the bus extension kit, along with the cable terminals. The phase barriers should be installed to the right and left of the center bus connector extension on both the line and the load sides. These phase barriers provide proper insulation integrity.
  6. Remove and replace side sheets with side sheets included in this kit with hardware.

⚠ CAUTION
MAKE SURE THE PHASE BARRIERS FROM STEP 6.5 ARE PROPERLY INSTALLED BEFORE PLACING THE CIRCUIT BREAKER INTO SERVICE. FAILURE TO FOLLOW THESE REQUIREMENTS COULD RESULT IN EQUIPMENT DAMAGE AND/OR FAILURE.

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
8 EATON IL0131123EN NRX
Type NF Bus Extension Kit Instruction Manual - Figure 9

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
10

If only using bus conductor extension kit, skip Step 7.
Cable terminal kit installation
Note: Step 1 through Step 4 need to be completed before proceeding with Step 7.

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
11,12

Step 7
Cable terminal now can be installed to the bus conductor extensions that extend out of the line side of the breaker. Cable terminals are described in Table 2. To complete the connections, proceed with the following steps.

  1. Bolt the cable terminals directly to the extenders using the hardware provided. Cable terminals can also be bolted to the bus connector extensions (Figure 13). Torque the bolted connections to 30 ft-lb (27 N∙m).
    Note: Terminals are not included in kit, but hardware to attach them is included.![EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual
  • Figure 13](https://manuals.plus/wp-content/uploads/2022/12/EATON- IL0131123EN-NRX-Type-NF-Bus-Extension-Kit-Instruction-Manual-Figure-13.jpg)

    1. When making the cable terminal connections, properly torque the cable retaining screws and periodically check all mounting hardware for proper torque loading. Refer to Figure 15 for rope lacing support instructions. To remove the cable terminals, reverse the procedure described above.EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure 14
    2. When making the cable terminal connections, properly torque the cable retaining screws and periodically check all mounting hardware for proper torque loading. Refer to Figure 15 for rope lacing support instructions.
      To remove the cable terminals, reverse the procedure described above.

EATON IL0131123EN NRX Type NF Bus Extension Kit Instruction Manual - Figure
15

Disclaimer of warranties and limitation of liability

The information, recommendations, descriptions, and safety notations in this document are based on Eaton’s experience and judgment, and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted.

Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.

THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein.

The information contained in this manual is subject to change without notice.

Eaton
1000 Eaton Boulevard Cleveland, OH 44122
United States
Eaton.com

© 2016 Eaton
All Rights Reserved Printed in USA
Publication No. IL0131123EN / Z17828
Part Number: IL0131123ENH01
February 2016

Eaton is a registered trademark.
All other trademarks are property of their respective owners.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EATON User Manuals

Related Manuals