SmartGen HMC6000RM Remote Monitoring Controller User Manual

June 3, 2024
SmartGen

SmartGen HMC6000RM Remote Monitoring Controller

OVERVIEW

HMC6000RM controller integrates digitization, intelligentization and network technology which is used for remote monitoring system of single unit to achieve automatic start/stop, data measurement, alarm protection and record checking. It fits with 132*64 LCD display, optional Chinese/English languages interface, and it is reliable and easy to use.

PERFORMANCE AND CHARACTERISTICS

  • 32-bit ARM microprocessor, 132*64 liquid display, optional Chinese/English interface, push-button operation;
  • Connect to HMC6000A/HMC6000A 2 module via CANBUS port to achieve remote start/stop control;
  • With monitor mode which can achieve check data only but not control the engine.
  • Modular design, self-extinguishing ABS plastic enclosure and embedded installation way; small size and compact structure with easy mounting.

TECHNICAL PARAMETERS

Parameter Details
Working Voltage DC8.0V to DC35.0V, uninterrupted power supply.
Power Consumption <3W (Standby mode: ≤2W)
Case Dimension 197mm x 152mm x 47mm
Panel Cutout 186mm x 141mm
Working Temperature (-25~70)ºC
Working Humidity (20~93)%RH
Storage Temperature (-25~70)ºC
Protection Level IP55 Gasket

Insulation Intensity

| Apply AC2.2kV voltage between high voltage terminal and low voltage terminal;

The leakage current is not more than 3mA within 1min.

Weight| 0.45kg

INTERFACE

MAIN INTERFACE
All data of HMC6000RM are read from local controller HMC6000A/HMC6000A 2 via CANBUS. Specific display content stays the same with local controller.

INFORMATION INTERFACE

After pressing Enter for 3s,    the    controller    will enter into select interface of parameter setting and

controller information.

| Return Parameter Setting Controller Information| After selected controller information, press Enter to enter into controller information interface.
---|---|---
First Panel| Controller Information Software Version       2.0

Release Date    2016-02-10

2015.05.15(5)09:30:10

| This panel will display software version, hardware version and controller time.


Press to enter into second panel.

Second Panel| O:S F S H A 1 2 3 4 5

6 7 8 9 10 11 12 At Rest

| This panel will display output port status, and genset status.


Press to enter into third panel.

Third Panel| I: E S S 1 2 0 F 3 4 5  6 At Rest| This  panel will display input  port  status, and genset status.


Press to enter into first panel.

OPERATION

KEY FUNCTION DESCRIPTION

Key Function Description
**** Stop Stop running generator in remote mode.
**** Start Start genset in remote mode.
**** Mute Alarm sound off.
**** Dimmer+ Adjust backlight brighter, 6 kinds of lamp brightness levels.
**** Dimmer- Adjust backlight darker, 6 kinds of lamp brightness levels.
**** Lamp Test Press it will test panel LED indicators and display screen.
**** Home Return to the main screen.
**** Event Log Shortcut Quickly turn to alarm record page.
**** Up/Increase 1.         Screen scroll;

2.         Up cursor and increase value in setting menu.

****| Down/Decrease| 1.       Screen scroll;

2.       Down cursor and decrease value in setting menu.

|

Set/Confirm

| 1.       Pressing and holding for more than 3s to enter the parameter configuration menu;

2.       In settings menu confirms the set value.

CONTROLLER PANEL

SmartGen-HMC6000RM-Remote-Monitoring-Controller-13

REMOTE START/STOP OPERATION

INSTRUCTION
Configure any auxiliary input port of HMC6000A/HMC6000A 2 as remote start input. Remote start/stop can be done via remote controller when remote mode is active.

REMOTE START SEQUENCE

  1. When “Remote Start” is active, “Start Delay” timer is initiated;
  2. “Start Delay” countdown will be displayed on LCD;
  3. When start delay is over, preheat relay energizes (if configured), “Preheat Delay XX s” information will be displayed on LCD;
  4. After the above delay, the Fuel Relay is energized, and then one second later, the Start Relay is engaged. The engine is cranked for a pre-set time. If the engine fails to fire during this cranking attempt then the fuel relay and start relay are disengaged for the pre-set rest period; “Crank Rest Time” begins and wait for the next crank attempt;
  5. Should this start sequence continue beyond the set number of attempts, the start sequence will be terminated, the first line of LCD display will be highlighted with black and ‘Fail to Start fault’ will be displayed;
  6. In case of successful crank attempt, the “Safety On” timer is activated. As soon as this delay is over, “Start Idle” delay is initiated (if configured);
  7. After the start idle, if the Rotate Speed, Temperature, Oil Pressure of controller are regular, the generator will enter into Normal Running status directly.

REMOTE STOP SEQUENCE

  1. When the “Remote Stop” or “Stop Input” signal is effective, the Stop Delay is initiated.
  2. Once this “Stop Delay” has expired, the “Stop Idle” is initiated. During “Stop Idle” Delay (if configured), idle relay is energized.
  3. Once this “Stop Idle” has expired, the “ETS Solenoid Hold” begins. ETS relay is energized while fuel relay is de-energized.
  4. Once this “ETS Solenoid Hold” has expired, the “Fail to Stop Delay” begins. Complete stop is detected automatically.
  5. Generator is placed into its standby mode after its complete stop. Otherwise, fail to stop alarm is initiated and the corresponding alarm information is displayed on LCD (If generator is stop successfully after “fail to stop” alarm has initiated, it will enter standby mode).

PARAMETER SETTING

Enter into operating mode setting while pressing **for 3s after controller starts.
2 Operating modes:**

  • 0: Monitoring mode: When HMC6000A/HMC6000A 2 is in remote mode, the controller can achieve either remote monitoring data and records or remote start/stop.
  • 1: Surveilling mode: When HMC6000A/HMC6000A 2 is in remote mode, the controller can achieve remote monitoring data and records but not remote start/stop.
    NOTE: HMC6000RM can auto-identify main controller type, language setting and CANBUS baud rate.

REAR PANEL

SmartGen-HMC6000RM-Remote-Monitoring-Controller-15

Icon No. Function Cable Size Description
**** 1. DC input B- 1.0mm2 DC power supply negative input. Connected

with negative of starter battery.

2.| DC input B+| 1.0mm2| DC power supply positive input. Connected

with positive of starter battery.

3.| NC|  | Not connected.
**** CANBUS (EXPANSION)| 4.| CANL| 0.5mm2| Used for connect to HMC6000A/HMC6000A

2 local monitor and control module. Using 120Ω shielding wire whose single end earthed is recommended.

5.| CANH| 0.5mm2
6.| SCR| 0.5mm2
LINK|  |  |  | Used for software update.

CANBUS (EXPANSION) BUS COMMUNICATION

HMC6000A/HMC6000A 2 can be connected to achieve remote monitoring via EXPANSION port, which can connect at most 16 HMC6000RMs via only 1 EXPANSION port to achieve monitoring and controlling simultaneously in several places.

SmartGen-HMC6000RM-Remote-Monitoring-Controller-17

INSTALLATION

FIXING CLIPS
Controller is panel built-in design; it is fixed by clips when installed.

  1. Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
  2. Pull the fixing clip backwards (towards the back of the module) ensuring four clips are inside their allotted slots.
  3. Turn the fixing clip screws clockwise until they are fixed on the panel.
    NOTE: Care should be taken not to over tighten the screws of fixing clips.

OVERALL DIMENSIONS AND CUTOUT

SmartGen-HMC6000RM-Remote-Monitoring-Controller-19

TROUBLESHOOTING

Problem Possible Solution
Controller no response with power. Check starting batteries;

Check controller connection wirings; Check DC fuse.

**** CANBUS communication failure| Check wiring;

Check if CANBUS CANH and CANL wires are connected in the opposite way; Check if CANBUS CANH and CANL wires at both ends are connected in the opposite way;

Putting a 120Ω resistor between CANBUS CANH and CANL is recommended.

SmartGen Technology Co., Ltd.
No.28 Jinsuo Road, Zhengzhou, Henan Province, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Web: www.smartgen.com.cn/
www.smartgen.cn/
Email: sales@smartgen.cn

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. SmartGen Technology reserves the right to change the contents of this document without prior notice.

Version History

Date Version Content
2015-11-16 1.0 Original release.
2016-07-05 1.1 Add HMC6000RMD type.
2017-02-18 1.2 Modify working voltage range in the table of technical

parameters.
2020-05-15| 1.3| Modify local module type connect to HMC6000RM.
2022-10-14| 1.4| Update company logo and manual format.

Sign Instruction

Sign Instruction
NOTE Highlights an essential element of a procedure to ensure correctness.
CAUTION Indicates wrong operation may lead to impair apparatus.