SmartGen HMP300 Power Integrated Protection Module User Manual

June 3, 2024
SmartGen

**SmartGen HMP300 Power Integrated Protection Module User Manual

**

SmartGen

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication  should be addressed to Smartgen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Note
2017-09-22 1.0 Original release.
2019-11-05 1.1 Added differential protection contents.
2021-03-05 1.2 Modify the figure 1 error and update the format.
2022-10-11 1.3 Update company logo and manual format.

OVERVIEW

HMP300 power integrated protection module integrates digital, intelligent and network technology, and is used for collecting generator-set data (voltage, current, power and frequency) and related action output for data errors to protect the device. It fits with LCD display, optional Chinese and English bilingual interface, and it is reliable and easy to use.
HMP300 power integrated protection module adopts micro-processor technology with precise  parameter measuring, fixed value adjustment, set value adjusting functions etc. All parameters can be configured from front panel or through LINK interface via PC. It can be widely used in all types of marine/land electrical device with compact structure, advanced circuits, simple connections and high reliability.

PERFORMANCE AND CHARACTERISTICS

Main features are as below:

  • 132×64 LCD display with backlight, selectable language interface (Chinese and English), push-button operation.

  • Equipped with LINK communication port; Through LINK interface on PC, data and parameters can be monitored and adjusted.

  •  Equipped with CANBUS port, which can connect with HMC9000/HMC6000 module to realize power and engine data collecting and display at the same time.

  • Differential protection function, and controller will issue related alarm information after differential protection is active.

  •  Protections for over/under voltage, over/under frequency, reverse power, over power and over current.
    ➢ Harmonic test function, and each phase voltage/current harmonic distortion rate can be tested.

  • Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with frequency 50/60Hz.

  •  Collects and shows 3-phase voltage, 3-phase current, frequency and power parameters.
    Generator
    Line voltage (Uab, Ubc, and Uca)
    Phase voltage (Ua, Ub, and Uc)
    Frequency Hz
    Load
    Current Ia, Ib, Ic A (unit)
    Each phase and total active power P       kW (unit)
    Each phase and total reactive power Q       kvar (unit)
    Each phase and average power factor P

  • Parameter setting function: users are allowed to set and change parameters and parameters shall be stored in internal FLASH memory and cannot be lost even in case of power outage; most of them can be adjusted using front panel of the controller.

  • Wide power supply range DC (8~35) V, suitable for different starting battery voltage environment.

  • All parameters apply digital adjustment, instead of conventional analog modulation with normal potentiometer, improving whole reliability and stability.

  • Module is mounted on the 35mm guide rail.

SPECIFICATION

Table 2 Technical Parameters

Item Content
Operating Voltage DC8.0V to DC35.0V, Continuous Power Supply
Power Consumption <3W (standby ≤2W)

Alternator Volt Input Range 3Phase 4Wire

3Phase 3Wire Single Phase 2Wire

2Phase 3Wire

| ****

30V AC ~ 360 V AC (ph-N)

30V AC ~ 620 V AC (ph-ph)

30V AC ~ 360 V AC (ph-N)

30V AC ~ 360 V AC (ph-N)

Alternator Frequency| 50Hz/60Hz
Programmable Relay Output 1| 5A     AC250V volt free output
Programmable Relay Output 2| 5A     AC250V volt free output
Programmable Relay Output 3| 10A    AC250V volt free output
Programmable Relay Output 4| 10A    AC250V volt free output
Overall Dimension| 107.6mm x 89.7mm x 60.7mm
CT Secondary Current| 5A rated
Working Temperature| (-25~+70)°C
Working Humidity| (20~93)%
Storage Temperature| (-25~+70)°C


Insulating Intensity

| Apply AC2.2kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1min
Weight| 0.30kg

OPERATION

Table 3 Key Description

Icons Function Description
**** ****

Set/Confirm

| Pressing this key will enter into password screen; In setting parameter status, pressing this key will shift cursor or confirm the set value.
| Up/Increase| Scrolls the screen up; Shift the cursor up or increase the set value in parameter setting menu.
| Down/Decrease| Scrolls the screen down; Shift the cursor down or decrease the set value in parameter setting menu.
Pressing both **and down icon**  simultaneously can reset alarms.


SCREENS DISPLAY

POWER DATA DISPLAY

Table 4 Power Data Displa y

1st Screen Description

UL-L 380V 380V 380 V UL-N   220V    220V   220 V I:          500A    500A 500 A

P:        276 kW   Q : 200 kvar

PF        0.80             50.0Hz

| Line voltage Uab, Ubc, Uca
Phase voltage Ua, Ub, Uc
Current Ia, Ib, Ic
Active power, reactive power
Average power factor, frequency
2nd Screen| Description
P(kW)        Q(kvar)                     S(kVA) A:    89.0 65.0           110.0

B:    89.0         65.0           110.0

C:    89.0         65.0           110.0

PF    0.80         0.80           0.80

| Active power display, reactive power display, apparent power display
A phase: active power, reactive power, apparent power
B Phase: active power, reactive power, apparent power
C Phase: active power, reactive power, apparent power
A phase, B phase and C phase power factors
3rd Screen| Description
THDu(%)      THDi(%)

A:    0.5                   0.3

B:    0.5                   0.3

C:    0.5                   0.3

Phase Seq: 0°    120°         240°

| Voltage harmonic distortion rate, current harmonic distortion rate
A phase: voltage/current harmonic distortion rate
B phase: voltage/current harmonic distortion rate
C phase: voltage/current harmonic distortion rate
Phase sequence
4th Screen| Description
Total kWh           276.3 kWh Total kvarh 200.0 kvarh kWh % 32%

kvarh %           32%

| Total active energy

Total reactive energy

Active power percentage

Reactive power percentage


ALARM DISPLAY

All alarm information (trip alarm and warning alarm) collected by the module is real time displayed on the alarm screen as bellow:
Table 5 Alarm Display

Display Content Description

Alarm

Warning Alarm Under Volt Warning

| Page title
Alarm type
Alarm content

MODULE INFORMATION DISPLAY

Module information including output port status, software version, hardware version and release time can be displayed on this screen as bellow:
Table 6 Module Information Display

Display Content Description

OUT: 1    2    3   4

Software Version: V1.3 Hardware Version: V2.1 Issue Date: 2017-09-20

| Output port number
Outputs status
Software version
Hardware version
Issue date

PROTECTION

WARNING

When controller detects the warning signals, alarm indicator flashes and LCD displays the warning information.
Table 7 Module Warning Types

No. Type Description

1

| ****

Over Voltage

| When the module detects that the genset voltage has exceeded the pre-set value, it will initiate a warning alarm and the corresponding alarm

information will be displayed on LCD.


2

| ****

Under Voltage

| When the module detects that the genset voltage has fallen below the pre-set value, it will initiate a warning alarm and the corresponding alarm

information will be displayed on LCD.


3

| ****

Over Frequency

| When the module detects that the genset frequency has exceeded the

pre-set value, it will initiate a warning alarm and the corresponding alarm information will be displayed on LCD.


4

| ****

Under Frequency

| When the module detects that the genset frequency has fallen below the

pre-set value, it will initiate a warning alarm and the corresponding alarm information will be displayed on LCD.


5

| ****

Over Power

| When the module detects that the genset power (power is positive) has exceeded the pre-set value, it will initiate a warning alarm and the

corresponding alarm information will be displayed on LCD.


6

| ****

Over Current

| When the module detects that the genset current has exceeded the pre-set value, it will initiate a warning alarm and the corresponding alarm

information will be displayed on LCD.


7

| ****

Current Pre-alarm

| When module detects genset current is above the current pre-alarm limit, it will initiate a warning alarm and the corresponding alarm information

will be displayed on LCD.


8

| ****

Reverse Power

| When the module detects that the genset reverse power value (power is negative) has exceeded the pre-set value, it will initiate a warning alarm

and the corresponding alarm information will be displayed on LCD.


9

| Differential Protection| When module detects differential current is above the pre-set current

pre-alarm limit, it will initiate a warning alarm and the corresponding alarm information will be displayed on LCD.


TRIP ALARM

When controller detects trip alarm, it will send signals to trip the generator and the corresponding alarm information will be displayed on LCD.
Table 8 Trip Alarms

No. Type Description

1

| ****

Over Voltage

| When the module detects that the genset voltage has exceeded the pre-set value, it will initiate a trip alarm and the corresponding alarm

information will be displayed on LCD.


2

| ****

Under Voltage

| When the module detects that the genset voltage has fallen below the pre-set value, it will initiate a trip alarm and the corresponding alarm

information will be displayed on LCD.


3

| ****

Over Frequency

| When the module detects that the genset frequency has exceeded the

pre-set value, it will initiate a trip alarm and the corresponding alarm information will be displayed on LCD.


4

| ****

Under Frequency

| When the module detects that the genset frequency has fallen below

the pre-set value, it will initiate a trip alarm and the corresponding alarm information will be displayed on LCD.


5

| ****

Over Power

| When the module detects that the genset power (power is positive) has exceeded the pre-set value, it will initiate a trip alarm and the

corresponding alarm information will be displayed on LCD.


6

| ****

Over Current

| When the module detects that the genset current has exceeded the pre-set value, it will initiate a warning alarm and the corresponding alarm information will be displayed on LCD.


7

| Differential Protection| When the module detects differential current is above the pre-set limit, it will initiate a warning alarm and the corresponding alarm information will be displayed on LCD.


8

| ****

Reverse Power

| When the module detects that the genset reverse power value (power is negative) has exceeded the pre-set value, it will initiate a warning alarm and the corresponding alarm information will be displayed on LCD.


9

| ****

Loss of Phase

| When the module detects that genset voltage phase loss, it will initiate trip alarm signals and the corresponding alarm information will be displayed on LCD.


10

| Reverse             Phase Sequence| When the module detects that genset voltage phase sequence wrong, it will initiate trip alarm signals and the corresponding alarm information will be displayed on LCD.

WIRING CONNECTION
HMP300 controller panel is as below:

Fig. 1 HMP300 Panel Diagram

Table 9 Terminal Wiring Connection

No. Function Cable Size Remarks
1 B- 1.5mm2 Connected with negative of starter battery, engine

starter battery can be used directly.

2| B+| 1.5mm2| Connected with positive of starter battery, engine

starter battery can be used directly.

3| 120Ω| 1.0mm2| After short connecting with CANL, it doesn’t need to

externally connect with 120Ω.

4| CANH| 1.0mm2| CANBUS Communication   port,   which   supports

J1939-81 power data communication protocol.

5| CANL| 1.0mm2
6| ****

Aux. Output 1

| 1.0mm2| Relay normally open volt free contact, rated 5A, and volt free

contact output.

| ****





Details see 8.2.

7| 1.0mm2
8| ****

Aux. Output 2

| 1.0mm2| Relay normally open volt free contact, rated 5A, and volt free contact output.
9| 1.0mm2
10| ****

Aux. Output 3

| 1.0mm2| Relay normally open volt free contact, rated 10A, and volt free contact output.
11| 1.0mm2
12| 1.0mm2
13| ****

Aux. Output 4

| 1.0mm2| Relay normally open volt free contact, rated 10A, and volt free contact output.
14| 1.0mm2
15| 1.0mm2
16| Gen      L1      Phase       Volt

Monitoring Input

| 1.0mm2| Connect with output U Phase of generator (2A fuse is recommended)
17| Gen      L2      Phase       Volt

Monitoring Input

| 1.0mm2| Connect with output V Phase of generator (2A fuse is recommended).
18| Gen      L3      Phase       Volt

Monitoring Input

| 1.0mm2| Connect with output W Phase of generator (2A fuse is recommended).
19| Gen N Wire Input| 1.0mm2| Connect with output N Wire of generator.
20| CT     A-Phase      Monitoring

Input

| 2.5mm2| External connected current transformer secondary coil (rated 5A).
21| 2.5mm2
22| CT     B-Phase      Monitoring

Input

| 2.5mm2| External connected current transformer secondary coil (rated 5A).
23| 2.5mm2
24| CT     C-Phase      Monitoring

Input

| 2.5mm2| External connected current transformer secondary coil (rated5A).
25| 2.5mm2
LINK| | Test software   interface. Connect with   PC test software via SG72 module.


SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

CONTENTS AND SCOPES OF PARAMETERS
Table 10 Parameter Setting Contents and Scopes

No. Items Range Default Description

Voltage Settings


1

| ****

AC System

| ****

(0-3)

| ****

0

| 0: 3P4W

1: 3P3W

2: 2P3W

3: 1P2W




2

| ****



Rated Voltage

| ****



(30-30000)V

| ****



230

| Provide standard for over/under voltage and voltage on load. If voltage transformer is used, this value is primary voltage of transformer.

When AC system is 3P3W, this setting value

is line voltage; for other supply AC systems, it is phase voltage.


3

| Voltage Transformer Enabled| (0-1)

0: Disabled

1: Enabled

| ****

0

| ****

Disabled

4| Primary Voltage| (30-30000)V| 100| Primary voltage of voltage transformer.
5| Secondary Voltage| (30-1000)V| 100| Secondary voltage of voltage transformer.


6

| Over    Volt    Warning Enabled| (0-1)

0: Disabled

1: Enabled

| ****

1

| When it is enabled, module starts to detect over voltage warning.


7

| ****

Over    Volt    Warning Value

| ****

(0-200)%

| ****

110%

| When generator voltage has exceeded the set value and warning delay is expired, module will initiate over voltage warning

alarm.

8| Over    Volt    Warning

Delay

| (0-3600)s| 3| Time duration from alarm is detected to it

initiates alarm.


9

| Over        Volt        Trip Enabled| (0-1)

0: Disabled

1: Enabled

| ****

1

| When it is enabled, module starts to detect over voltage trip.


10

| ****

Over Volt Trip Value

| ****

(0-200)%

| ****

120

| When generator voltage has exceeded the set value and trip delay is expired, module

will initiate over voltage trip alarm.

11| Over Volt Trip Delay| (0-3600)s| 2| Time duration from alarm is detected to it

initiates alarm.


12

| Under Volt Warning Enabled| (0-1)

0: Disabled

1: Enabled

| ****

1

| When it is enabled, module starts to detect under voltage warning.


13

| Under Volt Warning Value| ****

(0-200)%

| ****

84

| When generator voltage has fallen below the set value and warning delay is expired,

module will initiate under voltage warning


2 DEFINED CONTENTS OF PROGRAMMABLE OUTPUT PORTS 1~4

Table 11 Defined Contents of Programmable Output Ports 1-4

No. Items Description
0 Not Used Output port is deactivated when “Not Used” is selected.
1 Common Alarm Output when alarms occurred.
2 Common Warning Alarm Output when warning alarm is occurred.
3 Common Trip Alarm Output when trip alarm is occurred.
4 Over Volt Trip Alarm Output when over voltage trip alarm is occurred.
5 Under Volt Trip Alarm Output when under voltage trip alarm is occurred.
6 Loss     of    Phase      Trip

Alarm

| Output when loss of phase trip alarm is occurred.
7| Reverse Phase

Sequence Trip Alarm

| Output when reverse phase sequence trip alarm is occurred.
8| Over     Frequency      Trip

Alarm

| Output when over frequency trip alarm is occurred.
9| Under    Frequency     Trip

Alarm

| Output when under frequency trip alarm is occurred.
10| Over Current Trip Alarm| Output when over current trip alarm is occurred.
11| Over Current Pre-alarm| Output when over current pre-alarm is active.
12| Over Power Trip Alarm| Output when generator over power trip alarm is occurred.
13| Reserved| Reserved
14| Reverse       Power      Trip

Alarm

| Output when generator reverse power trip alarm is occurred.
15| Over Volt Warning| Output when generator over voltage warning alarm is occurred.
16| Under Volt Warning| Output when generator under voltage warning alarm is occurred.
17| Allow to Output On-load| Output when module meets the set on-load conditions.
18| Reserved| Reserved
19| Over Frequency Warning| Output when generator over frequency warning alarm is occurred.
20| Under              Frequency

Warning

| Output when generator under frequency warning alarm is occurred.
21| Reserved| Reserved
22| Over Current Warning| Output when generator over current warning alarm is occurred.
23| Differential      Protection

Warning

| Output when differential protection warning occurs.
24| Over Power Warning| Output when generator over power warning alarm is occurred.
25| Differential      Protection

Trip

| Output when differential protection trip occurs.
26| Reverse Power Warning| Output when generator reverse power warning alarm is occurred.


27

| ****

Custom Output

| Separately customized column A and column B output functions,

when one is active, module will start output. Detailed to see Table 12 as bellow.

28| Reserved| Reserved
29| Reserved| Reserved
30| Reserved| Reserved


Table 12 Custom Output Port List

No. Custom Output Column A Custom Output Column B
00 Over Volt Warning Alarm Over Volt Warning Alarm
01 Under Volt Warning Alarm Under Volt Warning Alarm
02 Over Frequency Warning Alarm Over Frequency Warning Alarm
03 Under Frequency Warning Alarm Under Frequency Warning Alarm
04 Over Power Warning Over Power Warning
05 Over Current Warning Over Current Warning
06 Reverse Power Warning Reverse Power Warning
07 Reverse Phase Sequence Trip Alarm Reverse Phase Sequence Trip Alarm
08 Over Volt Trip Alarm Over Volt Trip Alarm
09 Under Volt Trip Alarm Under Volt Trip Alarm
10 Over Frequency Trip Alarm Over Frequency Trip Alarm
11 Under Frequency Trip Alarm Under Frequency Trip Alarm
12 Over Power Trip Alarm Over Power Trip Alarm
13 Over Current Trip Alarm Over Current Trip Alarm
14 Reverse Power Trip Alarm Reverse Power Trip Alarm
15 Loss of Phase Trip Alarm Loss of Phase Trip Alarm
16 Over Current Warning + Over Current Trip Over Current Warning + Over

Current Trip
17| Differential Protection Warning| Differential Protection Warning
18| Differential Protection Trip| Differential Protection Trip


PARAMETERS SETTING

After module is powered up, press Setting Icon to enter into the password screen. Input correct password (default password is “0318”) to enter into the parameter setting menu and select parameter item via and down
iconbuttons. Then press Setting
Icon to start setting.   is to increase value, and down
icon is to decrease value. After the setting is finished, press Setting
Icon again to confirm it. Parameters also can be set through PC software via SG72 module. Password is not needed for parameter setting on PC software. If it needs to set more parameters (such as voltage/current calibration) or the password is forgotten, please contact the factory.
NOTES :

  • Over voltage set value must be higher than under voltage set value, otherwise over voltage and under voltage condition may occur simultaneously.
  • For alarms not needed, please select “Disabled” in the alarm enabled selection

TYPICAL APPLICATION

MODULE TYPICAL APPLICATION
HMP300 Typical Application Diagram
Fig.2 HMP300 Typical Application Diagram

DIFFERENTIAL CURRENT PROTECTION APPLICATION

Fig.3 Differential Current Protection Application Diagram

NOTE: CTs on the two sides must have same parameter characteristics, and cable load on the two sides also must be equal.

INSTALLATION

Fig.4 Overall and Cutout Dimensions

ATTENTION:

  • OUTPUT AND EXPAND RELAYS
    All outputs of controller are relay contact output type. If it needs to expand the relays, please add freewheel diode to both ends of expand relay’s coils (when coils of relay have DC current) or, increase resistance- capacitance return circuit (when coils of relay have AC current), inorder to prevent disturbanceB for controller or other equipments.

  • AC INPUT
    Current input of controller must be connected to outside current transformer. And the current transformer’s secondary current must be 5A. At the same time, the phases of current transformer and input voltage must be correct. Otherwise, the collected current and active power may be not correct.
    NOTE: When there is load current, transformer’s secondary side is prohibited to open circuit.

  • WITHSTAND VOLTAGE TEST
    When controller has been installed on control panel, if it needs the high voltage test, please disconnect controller’s all terminal connections, in order to prevent high voltage going into controller and damaging it.

SmartGen
SmartGen
— make your generator smart
SmartGenTechnology Co.,Ltd.
No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Web: www.smartgen.com.cn
www.smartgen.cn
Email: sales@smartgen.cn

All rights reserved. No part of this publicati

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals