Midea DUCMI70IB Middle Static Pressure Duct Type Air Conditioner User Manual
- September 28, 2024
- Midea
Table of Contents
- DUCMI70IB Middle Static Pressure Duct Type Air Conditioner
- Specifications
- Product Overview
- Product Installation
- Install Your Indoor Unit
- Install Your Outdoor Unit
- Refrigerant Piping Connection
- Wiring Precautions
- Air Evacuation
- Note On Adding Refrigerant
- Test Run
- Q: What age group is this product suitable for?
- Q: What type of fuse is required for the circuit board?
- Q: How often should maintenance be performed on the air
DUCMI70IB Middle Static Pressure Duct Type Air Conditioner
“`html
Specifications
- Product: Middle Static Pressure Duct Type Air Conditioner
- Model Numbers: DUCMI70IB, DUCMI90IB
Product Overview
The Middle Static Pressure Duct Type Air Conditioner by Midea
offers efficient cooling for your space. It is designed to provide
a comfortable environment while being energy-efficient.
Product Installation
Install Your Indoor Unit
Follow the step-by-step instructions provided in the manual to
properly install the indoor unit of the air conditioner. Ensure
that it is securely mounted and connected to the necessary
ductwork.
Install Your Outdoor Unit
Similarly, follow the detailed instructions for installing the
outdoor unit. Place it in a suitable location with proper
ventilation and secure the connections as per the guidelines.
Refrigerant Piping Connection
Connect the refrigerant piping according to the specified
guidelines to ensure optimal performance and efficiency of the air
conditioner.
Wiring Precautions
Take necessary precautions when handling wiring during
installation to avoid electrical hazards. Follow the wiring
diagrams and instructions carefully.
Air Evacuation
Prior to operation, ensure proper air evacuation to remove any
air bubbles from the system. This step is crucial for the air
conditioner to function effectively.
Note On Adding Refrigerant
If additional refrigerant needs to be added in the future, refer
to the guidelines provided in the manual for the correct procedure
and type of refrigerant to use.
Test Run
After installation, perform a test run of the air conditioner to
ensure that it is working correctly. Monitor its performance and
make any necessary adjustments.
FAQ
Q: What age group is this product suitable for?
A: The air conditioner can be used by children
aged 8 years and above under supervision. It is not recommended for
individuals with reduced capabilities without proper
instruction.
Q: What type of fuse is required for the circuit board?
A: The specifications for the fuse are printed
on the circuit board. For units with R32 or R290 refrigerant, use
only blast-proof ceramic fuses.
Q: How often should maintenance be performed on the air
conditioner?
A: Regular maintenance is essential for optimal
performance. Refer to the Care and Maintenance section in the
manual for detailed instructions on upkeep.
“`
MIDDLE STATIC PRESSURE DUCT TYPE AIR CONDITIONER
USER MANUAL
MODEL NUMBER: DUCMI70IB DUCMI90IB
Warning notices: Before using this product, please read this manual carefully
and keep it for future reference. The design and specifications are subject to
change without prior notice for product improvement. Consult with your dealer
or manufacturer for details. The diagram above is just for reference. Please
take the appearance of the actual product as the standard.
THANK YOU LETTER
Thank you for choosing Midea! Before using your new Midea product, please read
this manual thoroughly to ensure that you know how to operate the features and
functions that your new appliance offers in a safe way.
CONTENTS
THANK YOU LETTER
01
SAFETY PRECAUTIONS
02
SPECIFICATIONS
06
PRODUCT OVERVIEW
07
PRODUCT INSTALLATION
08
Install Your Indoor Unit
10
Install Your Outdoor Unit
18
Refrigerant Piping Connection
21
Wiring Precautions
24
Air Evacuation
30
Note On Adding Refrigerant
31
Test Run
32
SPECIFICATIONS AND FEATURES
33
WIRE REMOTE CONTROLLER
36
CARE AND MAINTENANCE
64
TROUBLESHOOTING
65
PACKING AND UNPACKING THE UNIT
69
TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT 71
DISPOSAL AND RECYCLING
71
DATA PROTECTION NOTICE
72
01
SAFETY PRECAUTIONS
It’s really important you read Safety Precautions Before Operation and
Installation Incorrect installation due to ignoring instructions can cause
serious damage or injury. The seriousness of potential damage or injuries is
classified as either a WARNING or CAUTION.
Explanation of Symbols
Warning of electrical voltage This symbol indicates that there is a danger to
life and health of persons due to voltage. Warning The signal word indicates a
hazard with a medium level of risk which, if not avoided, may result in death
or serious injury. Caution The signal word indicates a hazard with a low
degree of risk which, if not avoided, may result in minor or moderate injury.
Attention The signal word indicates important information (e.g. damage to
property), but not danger. Observe instructions This symbol indicates that a
service technician should only operate and maintain this appliance in
accordance with the operating instructions.
Read these operating instructions carefully and attentively before
using/commissioning the unit and keep them in the immediate vicinity of the
installation site or unit for later use!
WARNING
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision(European Union countries).
This appliance is not intended for use by persons(including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
02
WARNING FOR PRODUCT USE
° If an abnormal situation arises (like a burning smell), immediately turn off
the unit and disconnect the power. Call your dealer for instructions to avoid
electric shock, fire or injury.
° Do not insert fingers, rods or other objects into the air inlet or outlet.
This may cause injury, since the fan may be rotating at high speeds.
° Do not use flammable sprays such as hair spray, lacquer or paint near the
unit. This may cause fire or combustion.
° Do not operate the air conditioner in places near or around combustible
gases. Emitted gas may collect around the unit and cause explosion.
° Do not operate your air conditioner in a wet room such as a bathroom or
laundry room. Too much exposure to water can cause electrical components to
short circuit.
° Do not expose your body directly to cool air for a prolonged period of time.
° Do not allow children to play with the air conditioner. Children must be
supervised
around the unit at all times. ° If the air conditioner is used together with
burners or other heating devices,
thoroughly ventilate the room to avoid oxygen deficiency. ° In certain
functional environments, such as kitchens, server rooms, etc., the use of
specially designed air-conditioning units is highly recommended.
ELECTRICAL WARNINGS
° Only use the specified power cord. If the power cord is damaged, it must be
replaced by the manufacturer, its service agent or similarly qualified persons
in order to avoid a hazard.
° The product must be properly grounded at the time of installation, or
electrical shock may occur.
° For all electrical work, follow all local and national wiring standards,
regulations, and the Installation Manual. Connect cables tightly, and clamp
them securely to prevent external forces from damaging the terminal. Improper
electrical connections can overheat and cause fire, and may also cause shock.
All electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units.
° All wiring must be properly arranged to ensure that the control board cover
can close properly. If the control board cover is not closed properly, it can
lead to corrosion and cause the connection points on the terminal to heat up,
catch fire, or cause electrical shock.
° Disconnection must be incorporated in the fixed wiring in accordance with
the wiring rules.
° Do not pull power cord to unplug unit. Hold the plug firmly and pull it from
the outlet. Pulling directly on the cord can damage it, which can lead to fire
or electric shock.
° Do not modify the length of the power supply cord or use an extension cord
to power the unit.
° Do not share the electrical outlet with other appliances. Improper or
insufficient power supply can cause fire or electrical shock.
° Keep power plug clean. Remove any dust or grime that accumulates on or
around the plug. Dirty plugs can cause fire or electric shock.
° If connecting power to fixed wiring, an all-pole disconnection device which
has at least 3mm clearances in all poles, and have a leakage current that may
exceed 10mA, the residual current device(RCD) having a rated residual
operating current not exceeding 30mA, and disconnection must be incorporated
in the fixed wiring ` in accordance with the wiring rules.
03
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide
overcurrent protection. The specifications of the fuse are printed on the
circuit board ,such as : T5A/250VAC, T10A/250VAC, etc.
T20A/250VAC(<=24000Btu/h units), T30A/250VAC(>24000Btu/h units) NOTE: For the
units with R32 or R290 refrigerant , only the blast-proof ceramic fuse can be
used.
WARNINGS FOR PRODUCT INSTALLATION
° Installation must be performed by an authorized dealer or specialist.
Defective installation can cause water leakage, electrical shock, or fire.
° Installation must be performed according to the installation instructions.
(In North America, installation must be performed in accordance with the
requirement of NEC and CEC by authorized personnel only). Improper
installation can cause water leakage, electrical shock, or fire.
° Contact an authorized service technician for repair or maintenance of this
unit. This appliance shall be installed in accordance with national wiring
regulations.
° Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage, electrical
shock, fire, and can cause the unit to fail.
° Install the unit in a firm location that can support the unit’s weight. If
the chosen location cannot support the unit’s weight, or the installation is
not done properly, the unit may drop and cause serious injury and damage.
° Install drainage piping according to the instructions in this manual.
Improper drainage may cause water damage to your home and property.
° For units that have an auxiliary electric heater, do not install the unit
within 1 meter (3 feet) of any combustible materials.
° Do not install the unit in a location that may be exposed to combustible gas
leaks. If combustible gas accumulates around the unit, it may cause fire.
° Do not turn on the power until all work has been completed. ° When moving or
relocating the air conditioner, consult experienced service
technicians for disconnection and reinstallation of the unit. ° How to install
the appliance to its support, please read the information for details
in “indoor unit installation” and “outdoor unit installation” sections .
CAUTION
° Turn off the air conditioner and disconnect the power if you are not going
to use it for a long time.
° Turn off and unplug the unit during storms. ° Make sure that water
condensation can drain unhindered from the unit. ° Do not operate the air
conditioner with wet hands. This may cause electric shock. ° Do not use device
for any other purpose than its intended use. ° Do not climb onto or place
objects on top of the outdoor unit. ° Do not allow the air conditioner to
operate for long periods of time with doors or
windows open, or if the humidity is very high.
04
CLEANING AND MAINTENANCE WARNINGS
° Turn off the device and disconnect the power before cleaning. Failure to do
so can cause electrical shock.
° Do not clean the air conditioner with excessive amounts of water. ° Do not
clean the air conditioner with combustible cleaning agents. Combustible
cleaning agents can cause fire or deformation.
Note about Fluorinated Gasses(Not applicable to the unit using R290
Refrigerant)
° This air-conditioning unit contains fluorinated greenhouse gasses. For
specific information on the type of gas and the amount, please refer to the
relevant label on the unit itself or the “Owner’s Manual – Product Fiche ” in
the packaging of the outdoor unit. (European Union products only).
° Installation, service, maintenance and repair of this unit must be performed
by a certified technician.
° Product uninstallation and recycling must be performed by a certified
technician. ° For equipment that contains fluorinated greenhouse gases in
quantities of 5 tonnes
of CO2 equivalent or more, but of less than 50 tonnes of CO2 equivalent, If
the system has a leak-detection system installed, it must be checked for leaks
at least every 24 months. ° When the unit is checked for leaks, proper record-
keeping of all checks is strongly recommended.
WARNING FOR USING R32/R290 REFRIGERANT
° When flammable refrigerant are employed, appliance shall be stored in a well
ventilated area where the room size corresponds to the room area as specifiec
for operation.
° For R32 frigerant models: Appliance shall be installed, operated and stored
in a room with a floor area larger than X m . Appliance shall not be installed
in an unvertilated space, if that space is smaller than X m (Please see the
following form).
Model (Btu/h)
12000 18000 24000 30000 36000 42000-48000 55000-60000
Amount of refrigerant to be charged (kg)
1.11 1.65 2.58 3.08
3.84 4.24 4.39
Minimum room area (m )
1 2 5 7
10 12 13
° Reusable mechanical connectors and flared joints are not allowed indoors.
(EN Standard Requirements).
° Mechanical connectors used indoors shall have a rate of not more than
3g/year at 25% of the maximum allowable pressure. When mechanical connectors
are reused indoors, sealing parts shall be renewed. When flared joints are
reused indoors, the flare part shall be re-fabricated. (UL Standard
Requirements)
° When mechanical connectors are reused indoors, sealing parts shall be
renewed. When flared joints are reused indoors, the flare part shall be re-
fabricated. (IEC Standard Requirements)
05
SPECIFICATIONS
Product Model Power source Cooling capacity Heating capacity Rated current Rated power input Outdoor unit resistance class
DUCMI70IB UCMI70OB
7.3kW 7.4kW 16.0A 3400W
220-240V~ 50Hz, 1Ph
IP24
DUCMI90IB UCMI90OB
10.5kW 11.0kW 21.0A 4600W
IPX4
06
PRODUCT OVERVIEW
NOTE ON ILLUSTRATIONS:
Illustrations in this manual are for explanatory purposes. The actual shape of
your indoor unit may be slightly different. The actual shape shall prevail.
The installation must be performed in accordance with the requirement of local
and national standards. The installation may be slightly different in
different areas.
1 2
7
or
3
4
1 2
7 3
4 5
6
1 Air inlet 2 Air outlet 3 Drain pipe
4 Connecting pipe 5 Outdoor Unit (A) 6 Outdoor Unit (B)
7 Electric control cabinet
07
PRODUCT INSTALLATION
ACCESSORIES
The air conditioning system comes with the following accessories. Use all of
the installation parts and accessories to install the air conditioner.
Improper installation may result in water leakage, electrical shock and fire,
or cause the equipment to fail. The items are not included with the air
conditioner must be purchased separately.
Name of Accessories
Q`ty(pc)
Shape
Name of Accessories
Q`ty(pc)
Shape
Manual
2~4
Drain joint (some models)
1
Soundproof/insulation sheath
2
Copper nut
2
Outlet pipe sheath (some models)
Outlet pipe clasp (some models)
Orifice (some models)
Transfer connector ( 12.7- 15.9) (some models)
Transfer connector ( 9.52- 12.7) (some models)
1
1~2 (depending on models)
1
Transfer connector
1
NOTE: When the connecting pipes of
indoor and outdoor
units do not match,
this part needs to be
added.(See the Fig.a
or Fig.b)
1
Transfer connector
( 6.35- 9.52)
1
(some models)
(Fig.a) (Fig.b)
Seal ring (some models)
Connecting wire for display (2m) (some models)
Magnetic ring (wrap the electric wires S1 & S2 ( P & Q & E ) around the
magnetic ring twice) (some models)
Magnetic ring (Hitch it on the connective cable between indoor unit and
outdoor unit after installation.) (some models)
Cord protection rubber ring (some models)
Display panel *Just for testing purposes only ( some modelsKJR-120G,KJR-120H)
1 1
1 S1&S2(P&Q&E)
Varies by model
1 1
Optional accessories There are two types of remote controls: wired and wireless. Select a remote controller based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote controller.
Name
Connecting pipe assembly
Liquid side Gas side
Shape 6.35( 1/4in) 9.52( 3/8in) 12.7( 1/2in) 9.52( 3/8in) 12.7( 1/2in) 16( 5/8in) 19( 3/4in) 22( 7/8in)
Quantity(PC)
Parts you must purc hase separately. Consult the dealer about the proper pipe
size of the unit you purchased.
08
INSTALLATION SUMMARY – INDOOR UNIT
1
2
3
Install the indoor unit
Install the drainpipe
Install the outdoor unit
6
5
4
MC
MC
L(L1) N(L2)
Evacuate the refrigeration system
7
Connect the wires
Connect the refrigerant pipes
Perform a test run 09
Install Your Indoor Unit
1 Select installation location NOTE
Before installing the indoor unit, you must choose an appropriate location.
The following are standards that will help you choose an appropriate location
for the unit.
Proper installation locations meet the following standards:
Enough room exists for
Enough room exists for the
There is no direct radiation
installation and maintenance. connecting the pipe and drainpipe.
from heaters.
The air inlet and outlet The airflow can fill
are not blocked.
the entire room.
The ceiling is horizontal and its structure can
sustain the weight of the indoor unit.
Models with a cooling capacity of 9000Btu to 18000Btu only apply to one room.
DO NOT install unit in the following locations:
Areas with oil drilling or fracking
Coastal areas with high salt content in the air
Areas with caustic gases in the air, such as hot springs Areas that experience
power fluctuations, such as factories
Enclosed spaces, such as cabinets Kitchens that use natural gas Areas with strong electromagnetic waves Areas that store flammable materials or gas Rooms with high humidity, such as bathrooms or laundry rooms
10
90.6in(230cm) (When no ceiling)
2 Confirm installation sizes
Installation place
The distance between the mounted indoor unit should meet the specifications illlustrated in the following diagram.
11.8in(30cm)
Left side
Strong and durable ceiling Indoor unit
0.8in(2cm)
Right side
B >0.8in(2cm)
7.9in(20cm) Maintenance space
11.8in(30cm)
Service access
Ceiling
Floor
Air outlet 7.9in(20cm)
11.8in(30cm)
Air inlet
23.6inx23.6in (60cmx60cm) checkingorifice
11
3 Hang indoor unit
1. Please refer to the following diagrams to locate the four positioning
screw bolt holes on the ceiling. Be sure to mark the paces where you will
drill ceiling hook holes.
Air outlet dimensions
Air inlet dimensions
Air filter
Descending ventilation opening and mounted hook
Air filter Electric control box
(unit: mm/inch)
MODEL (Btu/h) 9K/12K
A 700/27.6
Outline dimension
air outlet opening size air return opening size Size of mounted lug
B
C
D
E
F
G
H
I
J
200/7.9 506/19.9 450/17.7 152/6 537/21.1 186/7.3 599/23.6 741/29.2 360/14.2
18K
880/34.6 210/8.3 674/26.5 600/23.6 136/5.4 706/27.8 190/7.5 782/30.8 920/36.2 508/20
24K~36K 1100/43.3 249/9.8 774/30.5 700/27.6 175/6.9 926/36.5 228/8.9 1001/39.4 1140/44.9 598/23.5
30K~36K 1360/53.5 249/9.8 774/30.5 700/27.6 175/6.9 1186/46.7 228/8.9 1261/49.6 1400/55.1 598/23.5
36K~60K 1200/47.2 300/11.8 874/34.4 800/31.5 227/8.9 1044/41.1 280/11 1101/43.3 1240/48.8 697/27.4
12
Wood
The mounting holes for upper foam are used for auxiliary positioning bolts (if
the foam is damaged or damaged, the spacing between the actual lifting lugs
shall be the standard).
Upper foam
Installation locating hole
Place the wood mounting across the roof beam, then install the hanging screw
bolts.
Wood mounting
Roof beam Ceiling
Hanging screw bolts
New concrete bricks
Inlay or embed the screw bolts.
(Blade shape insertion)
(Slide insertion)
Original concrete bricks
Use an embedding screw bolt, crock, and stick harness.
Steel bar Embedding screw bolt (Pipe hanging and embedding screw bolt)
Steel roof beam structure
Install and use the supporting steel angle.
Hanging screw bolt
Hanging bolts
Supporting angle steel
CAUTION
The unit body must be completely aligned with the hole. Ensure that the unit
and the hole are the same size before moving on.
2. Install and fit pipes and wires after you have finished installing the
main body.When choosing where to start, determine the direction of the pipes
to be drawn out. Especially in cases where there is a ceiling involved, align
the refrigerant pipes, drain pipes, and indoor and outdoor lines with their
connection points before mounting the unit.
3. Install hanging screw bolts. Cut off the roof beam. Strengthen the point
at which the cut was made. Consolidate the roof beam.
4. After you select an installation location,align the refrigerant pipes,
drain pipes, as well as indoor and outdoor wires with their connection points
before mounting the unit.
5. Drill 4 holes 10cm (4″) deep at the ceiling hook positions in the internal
ceiling. Be sure to hold the drill at a 90° angle to the ceiling.
6. Secure the bolt using the washers and nuts provided.
7. Install the four suspension bolts.
8. Mount the indoor unit with at least two people to lift and secure it.
Insert suspension bolts into the unit’s hanging holes. Fasten them using the
washers and nuts provided.
9. Mount the indoor unit onto the hanging screw bolts with a block. Position the indoor unit flat using a level indicator to prevent leaks.
Shockproof cushion
Screw nut
Washer Hanging screw bolt
Overhang part
NOTE: Confirm the minimum drain tilt is
1/100 or more.
13
Step 3: Duct and accessories installation
1. Install the filter (optional) according to the size of the air inlet.
2. Install the canvas tie-in between the body and duct.
3. The air inlet and air outlet duct should be far enough apart enough to a
avoid air passage short-circuit.
4. Connect the duct according to the following diagram:
Canvas tie-in Canvas tie-in
Isolation booth
Air outlet
Isolation booth
checking orifice
Air inlet Air dust filter
NOTE: The min. length of the duct should be more than 1m, and fix on the air inlet by screws (applicable to the unit that the air inlet filter is not fasten by screws).
5. Refer to the following static pressure guidelines when installing the indoor unit.
MODEL (Btu/h)
9K 12K 18K
24K 30K~36K 42K~60K
Static Pressure (Pa/in.wg)
0~50/0~0.2 0~50/0~0.2 0~100/0~0.4 0~160/0~0.64 0~160/0~0.64 0~160/0~0.64
Change the fan motor static pressure according to external duct static pressure.
Step 4: Adjust the air inlet direction (From rear side to under-side)
1. Take off the ventilation panel and flange. Air return flange
Ventilation panel Bend the rear ventilation panel 90 degrees along the dotted
line into a descending ventilation panel.(some models)
2. Change the mounting positions of the ventilation panel and air return
flange.
3. When installing the filter mesh, fit it into the flange as illustrated in
the following figure.
Ventilation panel
Air return flange Or
Ventilation panel
NOTE:
1. Do not place the connecting duct weight on the indoor unit.
2.When connecting the duct, use an nonflammable canvas tie-in to prevent
vibrating.
3.Insulation foam must be wrapped outside the duct to avoid condensate. An
internal duct underlayer can be added to reduce noise, if the end-user
requires.
Air return flange
NOTE: All the figures in this manual are for
demonstration purposes only. The air conditioner you have purchased may be
slightly different in design, though similar in shape.
14
Step 5: Fresh air duct installation
Dimension : Duct joint for fresh air
Pump maintainance:
1. Remove four screws from the drain pump. 2. Unplug the pump power supply
and water
level switch cable. 3. Detach the pump.
Ø92mm(3.62″)
MODLE 9-12 Ø113mm(4.45″)
Ø125mm(4.92″)
MODLE 18-60
Ø160mm(6.3″)
Pump
Step 7: Drill wall hole for connective piping
1. Determine the location of the wall hole based on the location of the
outdoor unit.
2. Using a 65mm (2.5in) or 90mm(3.54in) (depending on models )core drill,
drill a hole in the wall. Make sure that the hole is drilled at a slight
downward angle, so that the outdoor end of the hole is lower than the indoor
end by about 12mm (0.5in). This will ensure proper water drainage.
Step 6: Motor and drain pump maintenance
(the rear ventilated panel is used as an example)
Motor maintenance:
1. Take off the ventilated panel. 2. Take off the blower housing. 3. Take off
the motor.
3. Place the protective wall cuff in the hole. This protects the edges of the
hole and will help seal it when you finish the installation process.
CAUTION
When drilling the wall hole, make sure to avoid wires, plumbing, and other
sensitive components.
Wall
Outdoor
Indoor
Motor
Blower housing Ventilated panel
12mm / 0.5 inch
15
Step 8: Connect drain hose
The drainpipe is used to drain water away from the unit. Improper installation
may cause unit and property damage.
CAUTION
· Insulate all piping to prevent condensation, which could lead to water
damage.
· If the drainpipe is bent or installed incorrectly, water may leak and cause
a water-level switch malfunction.
· In HEAT mode, the outdoor unit will discharge water. Ensure that the drain
hose is placed in an appropriate area to avoid water damage and slippage.
· DO NOT pull the drainpipe forcefully. This could disconnect it.
NOTE ON PURCHASING PIPES
Installation requires a polyethylene tube (exterior diameter = 3.7-3.9cm,
interior diameter = 3.2cm), which can be obtained at your localhardware store
or dealer.
Indoor Drainpipe Installation
Install the drainpipe as illustrated in the following Figure.
1. Cover the drainpipe with heat insulation to prevent condensation and
leakage.
2. Attach the mouth of the drain hose to the unit’s outlet pipe. Sheath the
mouth of the hose and clip it firmly with a pipe clasp.
Drain hose
NOTE ON DRAINPIPE INSTALLATION
· When using an extended drainpipe, tightenthe indoor connection with an
additionalprotection tube. This prevents it from pulling loose.
· The drainpipe should slope downward at a gradient of at least 1/100 to
prevent water from flowing back into the air conditioner.
· To prevent the pipe from sagging, space hanging wires every 1-1.5m (39-59″).
· If the outlet of the drainpipe is higher than the body’s pump joint, use a
lift pipe for the indoor unit’s exhaust outlet. The lift pipe must be
installed no higher than 55cm (21.7″) from the ceiling board. The distance
between the unit and the lift pipe must be less than 20cm (7.9″). Incorrect
installation could cause water to flow back into the unit and flood.
· To prevent air bubbles, keep the drain hose level or slightly tiled up
(<75mm / 3″).
Drainpipe installation for units with a pump
Ceiling
<20cm (7.9″)
1-1.5m Lean over (39-59″) 1/50
NOTE: When connecting multiple drainpipes, install the pipes as illustrated.
Units with a pump
0-55cm (21.7″)
Drainpipe Pipe clasp connecting port
Ceiling
Insulation
Units without a pump
10cm (4″)
1-1.5m (39-59″)
Lean over 1/50
<55cm (21.7″)
16
3. Pass the drain hose through the wall hole. Make sure the water drains to a
safe location where it will not cause water damage or a slipping hazard.
NOTE: The drainpipe outlet should be at least 5cm (1.9″) above the ground. If
it touches the ground, the unit may become blocked and malfunction. If you
discharge the water directly into a sewer, make sure that the drain has a U or
S pipe to catch odors that might otherwise come back into the house.
Units with a pump.
1. Remove the test cover. Fill the water pan with 2 liters of water.
Drainage test
Check whether the drainpipe is unhindered. This test should be performed on
newly built houses before the ceiling is paved.
Units without a pump.
CLOSED
OPEN
CLOSED
OPEN
Stow tube
Fill the water pan with 2 liters of water. Check that the drainpipe is
unhindered.
Test cap
Stow tube
2. Turn on the unit in COOLING mode. You will hear the drain pump.Check
whether the water is discharged properly (a 1-minute lag is possible,
depending on the length of the drain pipe), Check whether water leaks from the
joints.
3. Turn off the air conditioner and put the cap back on.
17
Install Your Outdoor Unit
1
Select installation location
NOTE : PRIOR TO INSTALLATION
Before installing the outdoor unit, you must choose an appropriate location.
The following are standards that will help you choose an appropriate location
for the unit.
Proper installation locations meet the following standards:
60cmc24″ above
30cmc12″ on left
10cmc4″ from back wall
Good air circulation Firm and solid–the
Noise from the unit
and ventilation.
location can support the will not disturb other
unit and will not vibrate. people.
65cmc26″ in front
60cmc24″ on right
Long-term
Meets all spatial requirements shown in Installation Protected from prolonged periods Where snowfall is anticipated, take
Space Requirements above.
of direct sunlight or rain.
appropriate measures to prevent
ice buildup and coil damage.
NOTE
Install the unit by following local codes and regulations , there may be differ slightly between different regions.
CAUTION:
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:
Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier
in front of the unit to protect it from extremely heavy winds. See Figures below.
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow
around the unit.
If the unit is frequently exposed to salty air(seaside):
Use outdoor unit that is specially designed to resist corrosion.
Strong wind
Wind Baffle
Shelter
Strong wind
90° angle to the direction of the wind
Strong wind
Build a wind Baffle to protect the unit
Build a shelter to protect the unit
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets
Near a public street, crowded areas, or where noise from the unit will disturb
others.
Near animals or plants that will be harmed by hot air discharge.
Near any source of combustible gas.
In a location that is exposed to large amounts of dust
In a location exposed to a excessive amounts of salty air.
18
2 Install drain joint(Heat pump unit only)
Step 1 Find out the base pan hole of outdoor unit.
Seal
Base pan hole of outdoor unit
Step 2 ° Fit the rubber seal on the end of the drain joint that will connect
to the
outdoor unit. ° Insert the drain joint into the hole in the base pan of the
unit. The drain joint
will click in place. ° Connect a drain hose extension (not included) to the
drain joint to redirect
water from the unit during heating mode.
IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
19
3 Anchor Outdoor Unit
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIME.
° The outdoor unit can be anchored to the ground or to a wall-mounted bracket
with bolt(M10). Prepare the installation base of the unit according to the
dimensions below.
° The following is a list of different outdoor unit sizes and the distance
between their mounting feet. Prepare the installation base of the unit
according to the dimensions below.
Outdoor Unit Types and Specifications (Split Type Outdoor Unit)
D B
H
A H
W
W
Front view
(unit: mm/inch)
Outdoor Unit Dimensions W x H x D
Mounting Dimensions Distance A Distance B
760x590x285 (29.9×23.2×11.2)
530 (20.85) 290 (11.4)
810x558x310 (31.9x22x12.2)
549 (21.6) 325 (12.8)
845x700x320 (33.27×27.5×12.6)
560 (22)
335 (13.2)
900x860x315 (35.4×33.85×12.4) 590 (23.2) 333 (13.1)
945x810x395 (37.2×31.9×15.55)
640 (25.2) 405 (15.95)
990x965x345 (38.98x38x13.58)
624 (24.58) 366 (14.4)
938x1369x392 (36.93×53.9×15.43) 634 (24.96) 404 (15.9)
900x1170x350 (35.4x46x13.8)
590 (23.2) 378 (14.88)
800x554x333 (31.5×21.8×13.1) 845x702x363 (33.27×27.6×14.3) 946x810x420 (37.24×31.9×16.53)
514 (20.24) 540 (21.26) 673 (26.5)
340 (13.39) 350 (13.8) 403 (15.87)
946x810x410 (37.24×31.9×16.14) 952x1333x410 (37.5×52.5×16.14)
673 (26.5) 403 (15.87) 634 (24.96) 404 (15.9)
952x1333x415 (37.5×52.5×16.34)
634 (24.96) 404 (15.9)
890x673x342 (35×26.5×13.46) 765x555x303 (30.1×21.8×11.9)
663 (26.1) 452 (17.8)
354 (13.94) 286(11.3)
805x554x330 (31.7×21.8×12.9) 770x555x300 (30.3×21.8×11.8)
511 (20.1) 487 (19.2)
317 (12.5) 298 (11.7)
980X975X410 (38.58X38.39X16.14) 616(24.25) 397(15.63)
980X975X415 (38.58X38.39X16.34) 616(24.25) 397(15.63)
Top view Rows of series installation The relations between H, A and L are as follows.
L
L 1/2H L H
1/2H < L H
A 25 cm / 9.8″ or more 30 cm / 11.8″ or more
L > H
Can not be installed
o2r5mcomre/ 9.8″
25 or
mcmore/ 9.8″
H
L A
300 cm / 118″ or more
150 ocmr m/o5r9e”
60
cm or
/m2o3r.e6″
20
Refrigerant Piping Connection
When connecting refrigerant piping, DO NOT let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.
Notes on pipe length and elevation
The maximum length and drop height based on models.(Unit:m/ft.)
Type of model
North America, Australia and The
EU frequency conversion split
type
Other Split Type
Capacity (Btu/h)
<15K 15K-<24K 24K-<36K 36K-<60K
12K 18K-24K 30K-36K 42K-60K
Length of piping
25/82 30/98.4 50/164 65/213
15/49 25/82 30/98.4 50/164
Maximum drop height
10/32.8 20/65.6 25/82 30/98.4
8/26 15/49 20/65.6 30/98.4
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in the table next to it
CAUTION
Gas piping Oil trap
Indoor unit/ Outdoor unit
Oil traps
If oil flows back into the outdoor unit’s compressor, this might cause liquid
compression or deterioration of oil return. Oil traps in the rising gas piping
can prevent this. An oil trap should be installed every 6m(20ft) of vertical
suction line riser (36000Btu/h unit). An oil trap should be installed every
10m(32.8ft) of vertical suction line riser (36000Btu/h unit).
Indoor unit/ Outdoor unit
6m/20ft (<36000Btu/h unit) 10m/32.8ft Liquid piping(36000Btu/h unit)
6m/20ft (<36000Btu/h unit) 10m/32.8ft (36000Btu/h unit)
21
Connection Instructions–Refrigerant Piping
CAUTION
· The branching pipe must be installed horizontally. An angle of more than 10°
may cause malfunction. · DO NOT install the connecting pipe until both indoor
and outdoor units have been installed. · Insulate both the gas and liquid
piping to prevent condensation.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them
properly. This will ensure efficient operation and minimize the need for
future maintenance.
Measure the distance between the · indoor and outdoor units.
Using a pipe cutter, cut the pipe a · little longer than the measured
distance. Make sure that the pipe is cut at a · perfect 90° angle.
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They
must be completely removed.
· Hold the pipe at a downward angle to prevent burrs from falling into the
pipe.
· Using a reamer or deburring tool, remove all burrs from the cut section of
the pipe.
Pipe Reamer
Point down
90°
Oblique Rough Warped
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This
will drastically reduce the heating
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
· After removing burrs from cut pipe, seal the ends with PVC tape to prevent
foreign materials from entering the pipe.
· Sheath the pipe with insulating material. · Place flare nuts on both ends of
pipe. Make sure
they are facing in the right direction, because you can’t put them on or
change their direction after flaring.
Flare nut
Copper pipe
· Remove PVC tape from ends of pipe when ready to perform flaring work.
22
· Clamp flare from on the end of the pipe. The end of the pipe must extend
beyond the flare form.
Flare form
Outdoor unit
Liquid side piping (Smaller diameter)
(Bigger
Pipe
· Place flaring tool onto the form. · Turn the handle of the flaring tool
clockwise
until the pipe is fully flared.
PIPING EXTENSION BEYOND FLARE FORM
Pipe gauge
Tightening torque
Flare dimension(A) (Unit:mm/lnch)
Min.
Max.
Flare shape
(180-200kgf.cm)
32-39 N.m (320-390kgf.cm)
49-59 N.m (490-590kgf.cm)
57-71 N.m (570-710kgf.cm)
67-101 N.m (670-1010kgf.cm)
85-110 N.m (850-1100kgf.cm)
· Remove the flaring tool and flare form, then inspect the end of the pipe for
cracks and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the
outdoor unit. You should first connect the low-pressure pipe, then the
highpressure pipe.
· When connecting the flare nuts, apply a thin coat of refrigeration oil to
the flared ends of the pipes.
· Align the center of the two pipes that you will connect.
· Tighten the flare nut snugly by hand. · Using a wrench, grip the nut on the
unit tubing. · While firmly gripping the nut, use a torque
wrench to tighten the flare nut according to the torque values in above table.
NOTICE
Use both a spanner and a torque wrench when connecting or disconnecting pipes
to/from the unit.
Torque wrench
CAUTION
Ensure to wrap insulation around the piping. Direct contact with the bare
piping may result in burns or frostbite. · Make sure the pipe is properly
connected.
Over tightening may damage the bell mouth and under tightening may lead to
leakage.
NOTICE MINIMUM BEND RADIUS
Carefully bend the tubing in the middle according to the diagram below. DO NOT
bend the tubing more than 90° or more than 3 times.
Use appropriate tool
min-radius 10cm(3.9 )
· After connecting the copper pipes to the indoor unit, wrap the power cable,
signal cable and the piping together with binding tape.
NOTICE
DO NOT intertwine signal cable with other wires. While bundling these items
together. DO NOT intertwine or cross the signal cable with any other wiring.
23
Wiring Precautions
WARNING
BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE WARNINGS.
° All wiring must comply with local and national electrical codes, regulations
and must be installed by a licensed electrician.
° All electrical connections must be made according to the Electrical
Connection Diagramlocated on the panels of the indoor and outdoor units.
° If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
° Power voltage should be within 90-110% of rated voltage. Insufficient power
supply can cause malfunction, electrical shock, or fire.
° Installation of an external surge suppressor at the outdoor disconnect is
recommended.
° If connecting power to fixed wiring, a switch or circult breaker that
disconnects all poles and has a contact separation of at least 1/8in (3mm)
must be incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
° Only connect the unit to an individual branch circuit. Do not connect
another appliance to that outlet.
° Make sure to properly ground the air conditioner. ° Every wire must be
firmly connected. Loose
wiring can cause the terminal to overheat, resulting in product malfunction
and possible fire.
° Do not let wires touch or rest against refrigerant tubing, the compressor,
or any moving parts within the unit.
° If the unit has an auxiliary electric heater, it must be installed at least
1 meter (40in) away from any combustible materials.
° To avoid getting an electric shock, never touch the electrical components
soon after the power supply has been turned off. After turning off the power,
always wait 10 minutes or more before you touch the electrical components.
° Make sure that you do not cross your electrical wiring with your signal
wiring. This may cause distortion, interference or
° possibly damage to circuit boards. ° No other equipment should be connected
to the same power circuit. ° Connect the outdoor wires before
connecting the indoor wires.
WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO
THE SYSTEM.
24
NOTE ON AIR SWITCH
When the maximum current of the air conditioner is more than 16A, an air
switch or leakage protection switch with protective device shall be
used(purchased seperately). When the maximum current of the air conditioner is
less than 16A, the power cord of air conditioner shall be equipped with plug
(purchased seperately). In North Americathe applicance should be wired
according to NEC and CEC requirements.
(A)
Air switch (purchased seperately)
Outdoor unit power wires Indoor & Outdoor connective wires
(purchased seperately)
Outdoor unit
Indoor unit
(B)
Indoor unit power wires
Outdoor unit
Air switch (purchased seperately)
Indoor unit
(C) Air switch
(purchased seperately) Indoor unit power wires
Outdoor unit power wires
Outdoor unit
Indoor & Outdoor connective wires (purchased seperately)
Indoor & Outdoor connective wires (purchased seperately)
(D) Only for the North American
Air switch (purchased seperately)
Air switch (purchased seperately)
Outdoor unit power wires
Indoor & Outdoor connective wires (purchased seperately)
Indoor unit
Outdoor unit
Air switch (purchased seperately)
Indoor unit
NOTE: The cographs are for explanation purpose only. Your machine may be slightly different. The actual shape shall prevail.
OUTDOOR UNIT WIRING
WARNING
Before performing any electrical or wiring work, turn off the main power to
the system.
1. Prepare the cable for connection a. You must first choose the right cable
size. Be sure to use H07RN-F cables.
NOTE: In North America, choose the cable type according to the local electrical codes and regulations.
25
Minimum Cross-Sectional Area of Power and Signal Cables (For reference)
Rated Current of Appliance (A)
3 and 6 > 6 and 10 > 10 and 16 > 16 and 25 > 25 and 32 > 32 and 40
Nominal Cross-Sectional Area (mm )
0.75 1 1.5
2.5 4 6
CHOOSE THE RIGHT CABLE SIZE
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit. Refer to
this nameplate to choose the right cable, fuse, or switch. NOTE: In North
America, please choose the right cable size according to the Minimum Circuit
Ampacity indicated on the nameplate of the unit. b. Using wire strippers,
strip the rubber
jacketfrom both ends of the signal cable to reveal approximately 15cm (5.9″)
of wire. c. Strip the insulation from the ends. d. Using a wire crimper, crimp
u-lugs on the ends.
NOTE: When connecting the wires, strictly follow the wiring diagram found
inside the electrical box cover.
2. Remove the 2 screws fixed on the front panel and side panel, then take it
down to perform wire connection(see the figure of outdoor unit A). Unscrew the
electrical wiring cover and remove it.(see the figure of outdoor unit B)
4. Clamp down the cable with the cable clamp. 5. Insulate unused wires with
electrical tape.
Keep them away from any electrical or metal parts. 6. Reinstall the cover of
the electric control box. Australia models Please prepare spanner and flat-
blade screwdriver before your installation work . 1. Remove two fixing screws,
then remove the front panel.
2 Screws
2. Use spanner and flat-blade screwdriver to knock down two metal seals, then
pick the metal flakes out.
3. Connect the power cable and indoor & outdoor connection cable. Clamp down
the cable with the cable clamp.
4. The wire groups shall be bound with cable ties and fixed on the right side
plate after they are connected. The strong electric wire group and weak
electric wire group shall be led out separately through the two knock down
holes on the bottom of the right side plate and fastened with a locking
connector as shown in the figure below.
Cover Screw
2 Screws
Outdoor Unit A
Outdoor Unit B
3. Connect the u-lugs to the terminals
Match the wire colors/labels with the labels on the terminal block. Firmly
screw the u-lug of each wire to its corresponding terminal.
26
INDOOR UNIT WIRING
1. Prepare the cable for connection. a. Using wire strippers, strip the
rubber jacket from both ends of the signal cable to reveal about 15cm (5.9″)
of the wire. b. Strip the insulation from the ends of the wires. c. Using a
wire crimper, crimp the u-lugs to the ends of the wires.
2. Remove the cover of the electric control box on your indoor unit.
3. Connect the u-lugs to the terminals. Match the wire colors/labels with the
labels on the terminal block. Firmly screw the u-lug of each wire to its
corresponding terminal. Refer to the Serial Number and Wiring Diagram located
on the cover of the electric control box.
Control box
CAUTION
· While connecting the wires, please strictly follow the wiring diagram.
· The refrigerant circuit can become very hot. Keep the interconnection cable
away from the copper tube.
4. Clamp down the cable with the cable clamp. The cable must not be loose or
pull on the u-lugs.
5. The display box needs to be installed in the electric control box, the
display box needs to be installed inside the electric control, stuck on the
electric control box sheet metal clips.
Display box
Wiring diagram
Connective wiring diagram
Magnetic ring (if supplied and packed with the accessories)
1 2 3
Electric control box
Electric control box cover
Display box
Pass the belt through the hole of the Magnetic ring to fix it on the cable
Electric control box
Electric control box cover
6. Reattach the electric box cover.
27
Power Specifications(Not applicable for North America)
NOTE
Electric auxiliary heating type circuit breaker/fuse need to add more than 10
A. The circuit breaker/fuse specification shall be subject to the unit
nameplate. (applicable for Australian model)
Indoor Power Supply Specifications
MODEL(Btu/h)
POWER
PHASE VOLT
CIRCUIT BREAKER/ FUSE(A)
18K 1 Phase 208-240V
19K~24K 1 Phase 208-240V
25K~36K 1 Phase 208-240V
37K~48K 1 Phase 208-240V
25/20
32/25
50/40
70/55
49K~60K 1 Phase 208-240V
70/60
POWER
MODEL(Btu/h) PHASE VOLT
CIRCUIT BREAKER/FUSE(A)
36K 3 Phase 380-420V 25/20
37K~60K 3 Phase 380-420V 32/25
36K 3 Phase 208-240V 32/25
Outdoor Power Supply Specifications
MODEL(Btu/h)
POWER
PHASE VOLT
CIRCUIT BREAKER/ FUSE(A)
18K 1 Phase 208-240V
19K~24K 1 Phase 208-240V
25K~36K 1 Phase 208-240V
37K~48K 1 Phase 208-240V
25/20
32/25
50/40
70/55
37K~60K 3 Phase 208-240V 45/35
49K~60K 1 Phase 208-240V 70/60
MODEL(Btu/h)
POWER
PHASE VOLT
CIRCUIT BREAKER/FUSE(A)
36K 3 Phase 380-420V 25/20
37K~60K 3 Phase 380-420V 32/25
36K 3 Phase 208-240V 32/25
37K~60K 3 Phase 208-240V 45/35
28
Independent Power Supply Specifications
MODEL(Btu/h)
POWER (indoor)
PHASE VOLT
CIRCUIT BREAKER/ FUSE(A)
POWER (outdoor)
PHASE VOLT
18K 1 Phase 208-240V
19K~24K 1 Phase
208-240V
25K~36K 1 Phase 208-240V
37K~48K 1 Phase
208-240V
15/10 1 Phase 208-240V
15/10 1 Phase 208-240V
15/10 1 Phase 208-240V
15/10 1 Phase 208-240V
CIRCUIT BREAKER/ FUSE(A)
25/20
32/25
50/40
70/55
MODEL(Btu/h)
POWER (indoor)
PHASE VOLT
CIRCUIT BREAKER/FUSE(A)
POWER (outdoor)
PHASE VOLT
CIRCUIT BREAKER/FUSE(A)
36K 1 Phase 208-240V 15/10 3 Phase 380-420V 25/20
37K~60K 1 Phase 208-240V 15/10 3 Phase 380-420V 32/25
36K 1 Phase 208-240V 15/10 3 Phase 208-240V 32/25
Inverter Type A/C Power Specifications
MODEL(Btu/h)
POWER (indoor)
PHASE VOLT
CIRCUIT BREAKER/ FUSE(A)
POWER (outdoor)
PHASE VOLT
18K 1 Phase 220-240V
19K~24K 1 Phase
220-240V
25K~36K 1 Phase 220-240V
37K~48K 1 Phase
220-240V
15/10 1 Phase 208-240V
15/10 1 Phase 208-240V
15/10 1 Phase 208-240V
15/10 1 Phase 208-240V
CIRCUIT BREAKER/ FUSE(A)
25/20
25/20
40/30
50/40
MODEL(Btu/h)
POWER (indoor)
PHASE VOLT
CIRCUIT BREAKER/FUSE(A)
POWER (outdoor)
PHASE VOLT
CIRCUIT BREAKER/FUSE(A)
36K 1 Phase 220-240V 15/10 3 Phase 380-420V 25/20
37K~60K 1 Phase 220-240V 15/10 3 Phase 380-420V 32/25
36K 1 Phase 220-240V 15/10 3 Phase 208-240V 32/25
49K~60K 1 Phase 208-240V
15/10 1 Phase 208-240V
70/60
37K~60K 1 Phase 208-240V
15/10 3 Phase 208-240V 45/35
49K~60K 1 Phase 220-240V
15/10 1 Phase 208-240V
50/40
37K~60K 1 Phase 220-240V
15/10 3 Phase 208-240V 40/30
29
Air evacuation
NOTE
When opening valve stems, turn the hexagonal wrench until it hits against the
stopper. Do not try to force the valve to open further.
Preparations and precautions
Air and foreign matter in the refrigerant circuit can cause abnormal rises in
pressure, which can damage the air conditioner, reduce its efficiency, and
cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is
relocated.
6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum
pump.
7. Wait for 5 minutes, then check that there has been no change in system
pressure.
8. If there is a change in system pressure, refer to Gas Leak Check section
for information on how to check for leaks. If there is no change in system
pressure, unscrew the cap from the packed valve (high pressure valve).
9. Insert hexagonal wrench into the packed valve (high pressure valve) and
open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen
for gas to exit the system, then close the valve after 5 seconds.
10.Watch the Pressure Gauge for one minute to make sure that there is no
change in pressure. The Pressure Gauge should read slightly higher than
atmospheric pressure.
11. Remove the charge hose from the service port.
Evacuation Instructions
Flare nut
1. Connect the charge hose of the manifold gauge
to service port on the outdoor unit’s low
pressure valve.
2. Connect another charge hose from the manifold
gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed.
Cap
4. Turn on the vacuum pump to evacuate the system.
5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG(-105Pa).
valve body
valve stem
Outdoor unit
Manifold Gauge
-76cmHg
12. Using hexagonal wrench, fully open both the high pressure and low
pressure valves.
13. Tighten valve caps on all three valves (service port, high pressure, low
pressure) by hand. You may tighten it further using a torque wrench if needed.
Compound gauge
Pressure gauge
Low pressure
valve Pressure hose
or Charge hose
Low pressure valve
High pressure valve
Charge hose
Vacuum pump
30
Note On Adding Refrigerant
CAUTION
DO NOT mix refrigerant types.
Some systems require additional charging depending on pipe lengths. The
standard pipe length varies according to local regulations. For example, in
North America, the standard pipe length is 7.5m (25′). In other areas, the
standard pipe length is 5m (16`). The refrigerant should be charged from the
service port on the outdoor unit’s low pressure valve. The additional
refrigerant to be charged can be calculated using the following formula:
R22 (orifice tube in the indoor unit):
(Total pipe length standard pipe length)x 30g (0.32oZ)/m(ft)
(Total pipe length standard pipe length)x 65g(0.69oZ)/m(ft)
(Total pipe length standard pipe length)x 115g(1.23oZ)/m(ft)
R22 (orifice tube in the outdoor unit):
(Total pipe length standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length standard pipe length) x30(0.32oZ)/m(ft)
(Total pipe length standard pipe length) x60g(0.64oZ)/m(ft)
R410A: (orifice tube in the indoor unit):
(Total pipe length standard pipe length) x30g(0.32oZ)/m(ft)
(Total pipe length standard pipe length) x65g(0.69oZ)/m(ft)
(Total pipe length standard pipe length) x115g(1.23oZ)/m(ft)
R410A: (orifice tube in the outdoor unit):
(Total pipe length standard pipe length) x15g(0.16oZ)/m(ft)
(Total pipe length standard pipe length) x30g(0.32oZ)/m(ft)
(Total pipe length standard pipe length) x65g(0.69oZ)/m(ft)
R32 :
(Total pipe length standard pipe length)x 12g(0.13oZ)/m(ft)
(Total pipe length standard pipe length)x 24g(0.26oZ)/m(ft)
(Total pipe length standard pipe length)x 40g(0.42oZ)/m(ft)
CAUTION DO NOT mix refrigerant types.
Only for Australia models :
· This unit contains factory charged refrigerant covering 20m of refrigerant
piping and additional refrigerant charge on the installation site is not
required for an installation with up to 20m refrigerant piping. When
refrigerant piping exceeds 20m, additionally charge an amount calculated from
the pipe length and the above table for the portion in excess of 20m.
· If an existing pipe system is used, a required refrigerant charge volume
will vary depending on the liquid pipe size. Formula to calculate the volume
of additional refrigerant required Additional charge volume (kg) = { Main
length (m) Factory charged volume 20(m) } × 0.03(kg/m)
· Make sure to remove the additional refrigerant amount according to the
nameplate rated charge (under 5m refrigerant piping ) under market or
government verification testing.
31
Test Run
CAUTION
Failure to perform the test run may result in unit damage, property damage, or
personal injury.
Before test run
A test run must be performed after the entire system has been completely
installed. Confirm the following points before performing the test: a) Indoor
and outdoor units are properly installed. b) Piping and wiring are properly
connected. c) No obstacles near the inlet and outlet of the unit that might
cause poor performance or product malfunction. d) Refrigeration system does
not leak. e) Drainage system is unimpeded and draining to a safe location. f)
Heating insulation is properly installed. g) Grounding wires are properly
connected. h) Length of the piping and additional refrigerant capacity have
been recorded. i) Power voltage is the correct voltage for the air conditioner
Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the Indoor Unit
a. Ensure the remote control and its buttons work properly.
b. Ensure the louvers move properly and can be changed using the remote
control.
c. Double check to see if the room temperature is being registered correctly.
d. Ensure the indicators on the remote control and the display panel on the
indoor unit work properly.
e. Ensure the manual buttons on the indoor unit works properly.
f. Check to see that the drainage system is unimpeded and draining smoothly.
g. Ensure there is no vibration or abnormal noise during operation.
5. For the Outdoor Unit
a. Check to see if the refrigeration system is leaking.
b. Make sure there is no vibration or abnormal noise during operation.
c. Ensure the wind, noise, and water generated by the unit do not disturb your
neighbors or pose a safety hazard.
6. Drainage Test
a. Ensure the drainpipe flows smoothly. New buildings should perform this test
before finishing the ceiling.
b. Remove the test cover. Add 2,000ml of water to the tank through the
attached tube.
c. Turn on the main power switch and run the air conditioner in COOL mode.
d. Listen to the sound of the drain pump to see if it makes any unusual
noises.
e. Check to see that the water is discharged. It may take up to one minute
before the unit begins to drain depending on the drainpipe.
f. Make sure that there are no leaks in any of the piping.
g. Stop the air conditioner. Turn off the main power switch and reinstall the
test cover.
NOTE: If the unit malfunctions or does not operate according to your
expectations, please refer to the Troubleshooting section of the Owner’s
Manual before calling customer service.
32
SPECIFICATIONS AND FEATURES
Indoor unit
NOTE: Different models have different display panel. Not all the indicators
describing below are available for the air conditioner you purchased. Please
check the indoor display panel of the unit you purchased. Illustrations in
this manual are for explanatory purposes. The actual shape of your indoor unit
may be slightly different. The actual shape shall prevail.
(A) For the unit which the filter is removed for left or right side
Air inlet Electric control cabinet
Air filter(on some models)
Air outlet
Drain hose Refrigerant connecting pipe
(B) For the unit which the filter is removed from the bottom side
Air inlet
Air outlet
Air filter (on some models)
Drain hose
screw
Air filter
Refrigerant connecting pipe 1.Put the filter into the flange subassembly
through the bottom side; 2.Lock the screw.
(C) For the unit which the filter is removed from the back
Air filter(on some models)
1. Remove two flange coaming; 2. Put the filter into the flange subassembly; 3. Rotate the air filter; 4. Put back to the flange coaming.
screw
Flange coaming
33
Display panel
Timer Infrared indicator receiver
Manual button
LED display
Operation Alarm indicator indicator
PRE-DEF (pre-heating/defrost) indicator
· MANUAL button : This button selects the mode in the following order: AUTO,
FORCED COOL, OFF.
FORCED COOL mode : In FORCED COOL mode, the Operation light flashes. The
system will then turn to AUTO after it has cooled with a high wind speed for
30 minutes. The remote control will be disabled during this operation. OFF
mode : When the display panel is turned OFF, the unit turns off and the remote
control is re-enabled.
Operating temperature
When your air conditioner is used outside of the following temperature ranges,
certain safety protection features may activate and cause the unit to disable.
Inverter Split Type
Room Temperature
COOL mode
17°C – 32°C (62°F – 90°F)
0°C – 50°C (32°F – 122°F)
Outdoor Temperature
-15°C – 50°C (5°F – 122°F) (For models with low temp. cooling systems.)
0°C – 52°C (32°F – 126°F) (For special tropical models)
HEAT mode
0°C – 30°C (32°F – 86°F)
DRY mode
10°C – 32°C (50°F – 90°F)
-15°C – 24°C (5°F – 75°F)
0°C – 50°C (32°F – 122°F)
0°C – 52°C (32°F – 126°F)
(For special tropical models)
FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER
When outside temperature is below 0°C (32°F ), we strongly recommend keeping
the unit plugged in at all time to ensure smooth ongoing performance.
34
Fixed-speed Type
Room Temperature
Outdoor Temperature
COOL mode
17°C-32°C (62°F-90°F)
18°C-43°C (64°F-109°F) -7°C-43°C (19°F-109°F) (For models with low-temp
cooling systems) 18°C-52°C (64°F-126°F) (For special tropical models)
HEAT mode 0°C-30°C (32°F-86°F)
-7°C-24°C (19°F-75°F)
DRY mode
10°C-32°C (50°F-90°F) 11°C-43°C (52°F-109°F) 18°C-43°C (64°F-109°F) 18°C-52°C
(64°F-126°F) (For special tropical models)
NOTE: Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
To further optimize the performance of your unit, do the following: · Keep doors and windows closed. · Limit energy usage by using TIMER ON and TIMER OFF functions. · Do not block air inlets or outlets. · Regularly inspect and clean air filters.
Other features
Default Setting
When the air conditioner restarts after a power failure, it will default to
the factory settings (AUTO mode, AUTO fan, 24°C (76°F)). This may cause
inconsistencies on the remote control and unit panel. Use your remote control
to update the status.
Three-minute protection feature (some models)
A protection feature prevents the air conditioner from being activated for
approximately 3 minutes when it restarts immediately after operation.
Auto-Restart (some models)
In case of power failure, the system will immediately stop. When power
returns, the Operation light on the indoor unit will flash. To restart the
unit, press the ON/OFF button on the remote control. If the system has an auto
restart function, the unit will restart using the same settings.
Refrigerant Leak Detection System (some models)
The indoor unit will automatically display “EC” or “EL0C”or flash LEDS (model
dependent ) when it detects refrigerant leakage.
35
WIRE REMOTE CONTROLLER
NOTE
the wired remote controller you purchased (depend on model). The actual shape
shall prevail. Read this description carefully before installing or operating
your wired remote controller.
Model
KJR-120M(X4)/BGEF, KJR-120M(X4W)/BGEF, KJR-120M(X5)/BGEF, KJR-120M(X5W)/BGEF, KJR-120M(X6)/BGEF, KJR-120M(X6W)/BGEF, KJR-120M1(X4)/BGEF
1. Safety precaution
WARNING
· Please entrust the distributor or professionals to install the unit. ·
Installation by other persons may lead to imperfect installation, electric
shock or fire. · Adhere to this installation manual. · Imporper installation
may lead to electric shock or fire. · Reinstallation must be performed by
professionals. Do not uninstall the unit randomly.
Random uninstalling may lead to abnormal operation, heating or fre of the air
condition.
NOTE: · Do not install the unit in a place vulnerable to leakage of flammable
gases.Once flammable gases are
leaked and left around the wire controller, fire may occure. · Do not operate
with wet hands or let water enter the wire controller. Otherwise, electric
shock may occur. · The wiring should adapt to the wire controller current.
Otherwise, electric leakage or heating may occur and result in fire. · The
specified cables shall be applied in the wiring. No external force may be
applied to the terminal.
Otherwise, wire cut and heating may occur and result in fire.
(For North America area)
BATTERY WARNING
WARNING: Contains coin battery.
WARNING INGESTION HAZARD: This product contains a button cell or coin battery.
BATTERY WARNING: KEEP OUT OF REACH OF CHILDREN; If the battery compartment (if
applicable) does not close securely, stop using the product and keep it away
from children; If you think batteries might have been swallowed or placed
inside any part of the body, seek immediate medical attention.
36
BATTERY WARNING
KEEP OUT OF REACH OF CHILDREN. Swallowing can lead to chemical burns,
perforation of soft tissue, and death. Severe burns can occur within 2 hours
of ingestion. Seek medical attention immediately.
WARNING
INGESTION HAZARD: This product contains a button cell or coin battery. DEATH
or serious injury can occur if ingested. A swallowed button cell or coin
battery can cause Internal Chemical Burns in as little as 2 hours. KEEP new
and used batteries OUT OF REACH of CHILDREN. Seek immediate medical attention
if a battery is suspected to be swallowed or inserted inside any part of the
body.
WARNING
· Remove and immediately recycle or dispose of used batteries according to
local regulations and keep away from children. Do NOT dispose of batteries in
household trash or incinerate.
· Even used batteries may cause severe injury or death. · Call a local poison
control center for treatment information. · Non-rechargeable batteries are not
to be recharged. · Do not force discharge, recharge, disassemble, heat above
(-20-70°C) or incinerate. Doing so may
result in injury due to venting, leakage or explosion resulting in chemical
burs. · Ensure the batteries are installed correctly according to polarity (+
and -). · Do not mix old and new batteries, different brands or types of
batteries, such as alkaline, carbon-zinc,
or rechargeable batteries. · Remove and immediately recycle or dispose of
batteries from equipment not used for an extended period
of time according to local regulations. · Always completely secure the battery
compartment. If the battery compartment does not close securely,
stop using the product, remove the batteries, and keep them away from
children. · Battery type: CR2032 · Battery nominal voltage: 3.0 V
(For other regions)
BATTERY WARNING
WARNING: Contains button or coin cell battery.
WARNING: The battery is hazards and KEEP OUT OF REACH OF CHILDREN (Whether the
battery is new or used). If the battery compartment(if applicable) does not
close securely, stop using the product and keep it away from children.
37
For appliances which contain coin or lithium batteries: BATTERY WARNING
KEEP OUT OF REACH OF CHILDREN. Swallowing can lead to chemical burns,
perforation of soft tissue, and death. Severe burns can occur within 2 hours
of ingestion. Seek medical attention immediately.
For appliances which contain button or non-lithium batteries. – The battery
can cause serious injuries if it is swallowed or placed inside
any part of the body. – If you think batteries might have swallowed or placed
inside any part of
the body, seek immediate medical attention.
Battery Performance
For more durable batteries, it is recommended to turn off the power when not
in use for a period of time.
Battery Disposal
Do not dispose of batteries as unsorted municipal waste. Refer to local laws
for proper disposal of batteries. Batteries may have a chemical symbol at the
bottom of the disposal icon. This chemical symbol means that the battery
contains a heavy metal that exceeds a certain concentration. An example is Pb:
Lead (>0.004%). Appliances and used batteries must be treated in a specialized
facility for reuse, recycling and recovery. By ensuring correct disposal, you
will help avoid possible negative consequences for the environment and human
health.
Pb
38
2. Installation accessory
Select the installation location Don’t install at the place where cover with
heavy oil, vapor or sulfureted gas, otherwise, this product would be deformed
that would lead to system malfunction.
Preparation before installation 1. Please confirm that all the following parts
you have been supply.
No.
Name
1 Wire controller
2 Installation and owner’s manual 3 Screws 4 Wall plugs 5 Screws 6 Plastic
screw bars 7 Battery
8 The connective wires group 9 Screw
Qty.
Remarks
1 1 3 M3.9*25 (For Mounting on the Wall) 3 For Mounting on the Wall 2 M4X25 (For Mounting on switch box) 2 For fixing on switch box 1 1 Optional 1 M4X8(For Mounting the connective wire group)
2. Prepare the following assemblies on the site.
No.
Name
1
Switch box
2
Wiring Tube(Insulating Sleeve and Tightening Screw)
Qty.(embeded into wall)
1 1
Specification (only for reference)
Remarks
1. This manual provides the installation method of wired controller. Please
refer to the wiring diagram of this installation manual to connect the wire
controller with indoor unit.
2. The wired controller works in low voltage loop circuit. Forbid to directly
contact the cable of high voltage above, like 115V,220V,380V, and don’t wire
this kind of wire in the said loop; wiring clearance between configured tubes
should be at the range of 300~500mm or above.
3. The Shielded wire of the wired controller must be grounded frmly. 4. Upon
finish the wire controller connection, do not employed tramegger to detect the
insulation.
3. Installation method
1.Wired remote controller structural dimensions
120mm
20mm
120mm 84mm 19mm
44mm
Fig 3-1 39
46mm 60mm
2.Remove the upper part of wired controller
Insert a slot screwdriver into the slots in the lower part of the wired controller (2 places), and remove the upper part of the wire controller. (Fig.3-2)
Buckling position
NOTE: Do not pry up and down, you can only rotate the screwdriver.
Back cover
NOTE: The PCB is mounted in the upper part of the wired controller. Be careful
not to damage the board with the slot screwdriver.
3. Fasten the back plate of the wired controller
For exposed mounting, fasten the back plate on the wall with the 3 screws
(ST3.9*25) and plugs. (Fig.3-3)
Back plate
Screws (ST3.9*25)
Fig 3-3 Use two M4X25 screws to install the back cover on the 86 switch box,
and use one ST3.925 screw to fix to the wall.
Screw hole fixed on the wall,useone ST3.925mm
Screw hole installed on 86 switch box, use two M4X25mm Fig 3-4
NOTE: Put on a flat surface. Be careful not to distort the back plate of the
wire controller by overtightening the mounting screws.
40
4. Battery installation
Fig 3-5 · Please contact professional technical after-sales service if the
battery needs to be replaced. · Put the battery into the installationsite and
make sure the positive side of the battery is in accordance
with the positive side of installationsite. (See Fig.3-5) · Please set the
time corrected on the first time operation. Batteries in the wire controller
can time under
power failure which ensure the time keep right. When the power restores, if
the time displayed is not correct, it means the battery is dead and replace
the battery.
5. Wire with the indoor unit
B A
switch box
44mm
Model A
60mm
Wiring hole
A
B
switch box
44mm
1
HA HB
Model B Fig 3-6
41
60mm
Wiring hole
Model A
Connect the wire from the display panel of the indoor unit to a connecting
cable. Then connect the other side of the connecting cable to the remote
control.
4-core wire
The connective wires group
Mainboard
Applicable to Light Commercial air conditioner
shielded wire(some units)
Fig 3-7
4-core wire
Adaptor board The connection cable D
Display board
The connection cable A
X Y E 5V/12V
Applicable to split-type air conditioner
White
Red
YellowBrown
Fig 3-8
Model B
1 indoor unit Notch the part for the wiring to pass through with nippers, etc.
Connect the terminals on the wired controller (HA ,HB), and the terminals of
the indoor unit (HA ,HB). (HA and HB do not have polarity.)
NOTE: · DO NOT allow water to enter the wired control.
Use the trap and putty to seal the wires. · Connecting wires must be fixed
reliably and cannot be pulled.
For some units, the wired controller connects to the unit HA and HB ports
through the HA and HB ports. There is no polarity between HA and HB. SeeFig.
3-9
Indoor Unit
HA HB
Wired Controller 42
Fig.3-9
The main/secondary wired controller can be used to enable two wired
controllers to control one unit, and the wired controllers connect to the unit
HA and HB ports through the HA and HB port on the controller. There is no
polarity between HA and HB. SeeFig. 3-10
Indoor Unit
HA HB
HB HA HB HA
0
Wired Controller 1
1
Wired Controller 2
Fig.3-10
NOTE: Wire controller with WiFi function does not have this function.
For some units, one wired controller can support multiple units (a maximum of
16 units). In this case, the wired controller and unit need to be connected to
the HA and HB ports at the same time. In group control, there will be no error
displayed on the wired controller . SeeFig. 3-11
Indoor Unit 1
0 HA HB
Indoor Unit 2
1
HA HB
Indoor Unit n (n<=16)
2 …..
HA HB
HB HA
Wired Controller 1 Putty
Fig.3-11
Trap
Putty
Trap Fig 3-12
43
Putty Trap
6. Reattach the upper part of the wired controller
After adjusting the upper case and then buckle the upper case; avoid clamping
the wiring during installation. (Fig 3-13)
All the pictures in this manual are for explanation purpose only. Your wire
controller may be slightly different .The actual shape shall prevail.
Fig 3-13
4. Specification
Input voltage Ambient temperature Ambient humidity
Wiring specifications
12V 0~43°C(32~110°F) Ambient humidity
NOTE: Suggested to use the connective wire of 6 meters length.
5. Feature and function of the wired controller
Feature:
LCD display. Malfunction code display: it can display the error code, helpful
for service. 4-way wire layout design, no raised part at backside, more
convenient to place the wires and install the device. Room temperature
display. Weekly Timer.
Function:
Mode: Choose AutoCool-Dry- Heat -Fan Fan speed: Auto/Low/ Med/High speed Swing(on some models) Timer ON/OFF Temp setting Weekly timer Follow me Turbo 24-hour System 12-hour System
Auto-restart Individual louver control (on some models) Automatic airflow test Rotation&Back-up Dual Control Group Control Child Lock LCD display Clock
44
6. Name on the LCD of the wired controller
MODE display Displays the current mode,including:
Temperature display Lock display
°C / °F display Room temperature display
Relative humidity display Wireless control feature display Follow me feature
display Breeze away display
Delay off display
Weekly Timer/ ON/Off Timer display
Clock display
FAN SPEED display Displays selected fan speed: LOW MED
HIGH AUTO
HORIZONTAL SWING display
VERTICAL SWING display Secondary unit display
Turbo feature display ECO feature display Purify feature display Filter
reminder display SLEEP feature display GEAR feature display Breezeless display
Rotation display
Active clean display Intelligent eye display
Electric heating display Main unit and secondary unit display
7. Name of button on the wired controller
1 FAN SPEED button 2 MODE button 3 FUNC. button 4 SWING botton 5 ADJUST button 6 TIMER button 7 COPY button 8 POWER button 9 CONFIRM button 10 BACK botton 11 DAY OFF/DELAY button 12 CHILD LOCK button
45
8. Preparatory operation
Set the current day and time
1
Press the Timer button for 2 seconds or more.
The timer display will flash.
Press the button ” ” or ” ” to set the date.
2
The selected date will flash.
3
The date setting is finished and the time setting is prepared after pressing
Timer button or CONFIRM button or there is no pressing button in 10 seconds.
Press the button ” ” or ” ” to set the current time.
Press repeatedly to adjust the current time in 1-minute increments.
4
Press and hold to adjust the current time continuous.
ex.Monday 11:20
5
The setting is done after pressing CONFIRM button or there is no pressing
button in 10 seconds.
6
Time scale selection Press the buttons ” ” and ”
” for 2 seconds will alternate the clock time
display between the 12h & 24h scale.
9. Operation
To start/stop operation
Press the Power button.
8 degree heating function (on some models)
When the heating mode is 10°C(50°F )/16°C(60°F)/17°C (62°F )/20°C( 68°F ),
press the down button twice within 1 second to turn on the 8 ° heating
function, and press the Power, Mode, adjust , Fan speed, Timer, and Swing
button to cancel the 8° heating function.
NOTE: For some models, the 8° heating function can only be set by remote control, you can not choose this function by wired controller.
46
9. Operation
To set the operation mode
Operation mode setting(Heat mode is invalid for cool only type unit) Press
this button to select the operation mode:
If the indoor unit has Electric heating(Emergent heating) feature, press this
button to select the operation mode:
When the mode is selected as emergency heating (or electric heating) mode, is displayed, the fan speed is Auto. The Sleep, 8-degree heating, Turbo, and Rotation functions are not available in emergency heating mode.
When the mode is selected as heating & electric heating mode, Rotation functions are disable.
is displayed, and the Turbo and
Room temperature setting
Lower Raise
Press the button” “or ” ” to set the room temperature. Indoor Setting Temperature Range : 10/16/17~30°C(50/60/62~86°F ) or 20~28°C(68~82°F ). (Model dependent)
°C & °F scale selection (on some models) Press the buttons ” ” and ” ” for 3
seconds will alternate the temperature display between the °C & °F scale.
Fan speed setting
Press the Fan speed button to set the fan speed. (This button is unavailable
under Auto or Dry mode)
Auto LOW MED HIGH
When stepless speed regulation is supported, press the fan speed key to cycle through:
20%
40% 60%
80% 100% Auto
Press the buttons and keypad tone.
together for 3 seconds to turn on or turn off the
Child lock function
Press the buttons ” ” and ” ” for 3 seconds to activate the child lock
function and lock all buttons on the wire controller. You can’t press the
button to operate and receive the remote control signal after the child lock
is activate. Press these two buttons again for 3 seconds to deactivate the
child lock function. When the child lock function is activated, the” “mark
appears.
47
Swing function(For the units with horizontal & vertical swing features only)
1 Up-Down swing
Press the SWING button to start up-down swing function. The ” ” mark appears.
Press it again to stop.
2 Left-Right swing
Press the Swing button for 2 seconds to start Left-Right swing function. The ”
” mark appears. Press it for 2 seconds again to stop.
Swing function(For the units without vertical swing function)
Use Swing button to adjust the Up-down airflow direction and start the auto swing function.
1.Each time you press this button, the louver swings an angle of 6 degrees.
Press this button until the desired direction reaches.
2.If press and hold the button for 2 seconds, the auto swing is activated. The
” ” mark appears. Press it again to stop. (some units)
For the units with four Up-Down louvers, it can be operated individually.
1.Press the Swing button to activate the Up-Down adjusting louver function.
The mark will flash.(Not applicable to all the models)
2.Pressing the button ” ” or ” ” can select the movement of four louvers.Each
time you push the button, the louver will be selected in a sequence as:
( -0 means the four louvers move at the same time.)
-0 -1
-2 -3
-4
3. And then use Swing button to adjust the Up-Down airflow direction of the selected louver.
**
Press the FUNC. button to scroll through operation functions as followings:
[*]: Model dependent. If the indoor unit has no this function, it will not display. The select function icon will flash, then press the Confrm button to confrm the setting.
Turbo function (on some models)
Under COOL/HEAT mode, press the FUNC. button to activate the turbo function.
Press the button again to deactivate the turbo function. When the turbo
function is activated,the ” ” mark appears.
PTC function (on some models)
In heating operation, for the units with electric heating feature, press this
button to activate electric heating mode. When the PTC function is
activated,the ” “mark appears.
NOTE: The electric auxiliary heating function of the AHU model is switched by
the MODE button , and the FUNC. button is a turbo function.
PTC function (on some models)
Press the FUNC. button to select whether the room temperature is detected at
the indoor unit or the wire controller.
48
Intelligent eye display
1.This function is valid in any mode of power-on state. 2.When the indoor unit
sending wire controller has the smart eye function, press the function key to
select
the smart eye icon, press the OK key to turn on the smart eye, and light up
the smart eye icon at the same time; when the smart eye is turned off, the
smart eye icon goes out. 3.Shutdown, switch mode, turn on self-cleaning, turn
on 8-degree heating function will automatically cancel the smart eye function.
Filter reset function
After the indoor unit sends the wire controller flter usage time, the filter
cleaning prompt icon lights up, press the function key to select the filter
cleaning prompt icon, and press the OK key to reset the flter screen time. The
filter cleaning reminder icon goes out.
Humidity setting function
1.When the indoor unit sending wire controller has dual control function of
temperature and humidity, in dehumidification mode, press the function key to
select the RH icon, press the confirm key to enter the humidity control mode,
the RH icon flashes, press the up and down keys to adjust the humidity, the
setting range is OFF->35%~85%, adjusted with 5% humidity. Exit humidity
adjustment state after 5 seconds of inactivity.
2.After entering the humidity control mode, press the up and down keys to
adjust the set temperature and display the set temperature for 5 seconds, and
then restore the set humidity display.
3.After switching the mode, exit the humidity control mode.
GEAR function
1.When the indoor unit sending wire controller has the GEAR function, in the
boot cooling mode, press the function key to select the GEAR icon, press the
confirm key to enter the GEAR control mode, and first display the current GEAR
status. 50%->75%->OFF can be switched by the up and down keys within 5
seconds. After 5 seconds, the set temperature will be displayed, press the up
and down keys to adjust the set temperature.
Turn off, switch to mode or turn on sleep, ECO, strong, self-cleaning
functions to cancel the GEAR function.
When the follow me function indicator appears,the room temperature is detected
by the wire controller.
Press the button again to cancel the follow me function.
Indoor Unit
Rotation & Back-up indication
When there are two units, press the button to select the rotating function,
and press “Confrm”to turn on or off the rotating function. 1. Press “Confrm”
to set the rotating time,then press the button ” “or ” ” to set time. Setting
time
Range :1~99h,the default time is 10 hours. 2. Step 2 set high temperature co-
open temperature — or 26~32 degrees — that is, this function is invalid.
When the ambient temperature is 26~32 degrees, when the ambient temperature is
greater than or equal to the set temperature, the two machines will run 24
degrees at the same time in the COOL mode. 3. Step 3 set the low-temperature
co-open temperature — or 5-15 degrees — that is, this function is invalid.
When the ambient temperature is 5-15 degrees, when the ambient temperature is
lower than the set temperature, the two units will run at the same time for 24
degrees to make the heating mode. 4. Step 4: set which machine will run first.
Select A or B. 5. After this function is turned on, as long as the air
conditioner is running at the setting hour, it will automatically turn on
another air conditioner and turn off the current air conditioner. Press the
POWER button to switch to another one immediately.A or B icons ficker to
indicate the corresponding air conditioning failure. Automatically switch to
another machine when running time is reached or machine failure occurs.
49
10. Timer functions
WEEKLY timer Use this timer function to set operating times for each day of
the week.
On timer Use this timer function to start air conditioner operation. The timer
operatesand air conditioner operation starts after the time has passed.
Off timer Use this timer function to stop air conditioner operation. The timer
operates and air conditioner operation stops after the time has passed.
On and Off timer Use this timer function to start and stop air conditioner
operation. The timer operates and air conditioner operation starts and stops
after the time has passed.
To set the On or Off TIMER
1
Press the Timer button to select the
or
.
No display
2
Press the Confirm button and the Timer display is flashing.
3
Press the button ” ” or ” ” to set the time. After the time is set, the timer will start or stop automatically.
4
Press the Confirm button again to finish the settings.
To set the On and Off TIMER
1
Press the Timer button to select the
.
2
Press the Confirm button and the Clock display is flashing.
3 Press the button ” ” or ” ” to set the time of On timer,
and then press the Confirm button to confirm the setting.
4 Press the button ” ” or ” ” to set the time of Off timer.
5
Press the Confirm button to finish the settings.
NOTE: The secondary wired controller cannot set the timer. 50
11. Weekly Timer 1
1. Weekly timer setting
Press the Timer button to select the button to confirm.
and then press the Confirm
2. Day of the week setting
Press the button ” ” or ” ” to select the day of the week and then press the
Confirm button to confirm the setting.
3. ON timer setting of timer setting 1
Press the button ” ” or ” ” to set the time of On timer and then press the
Confirm button to confirm the setting.
ex.Tuesday time scale 1 Up to 4 timer settings can be saved for each day of
the week. It is conventent if the WEEKLY TIMER is set according to the user’s
life style.
4. Off timer setting of timer setting 1
Press the button ” ” or ” ” to set the time of Off timer and then press the
Confirm button to confirm the setting.
ex.Tuesday time scale 1
5. Different timer settings can be setted by repeating step 3 to 4. 6. Other
days in one week can be setted by repeating step 2 to 5.
NOTE: The weekly timer setting can be returned to the previous step by
pressing Back button.The time of timer setting can be delete by pressing Day
off botton The current setting will be restored and withdrawn the weekly timer
setting automatically when there is no operation for 30 seconds.
51
WEEKLY timer operation
To activate WEEKLY TIMER operation
Press the Timer button while
is displayed on the LCD.
ex.
To deactivate WEEKLY TIMER operation Press the Timer button while
is disappear from the LCD.
To turn off the air conditioner during the weekly timer
1. If press the Power button once and quickly , the air conditioner will turn off temporarily. And the air conditioner will turn on automatically until the time of On timer.
ON
OFF
ON
OFF
8:00 10:00 12:00
14:00
17:00
ex. If press the POWER button once and quickly at 10:00, the air conditioner will turn on at 14:00. 2. When press the Power button for 2 seconds , the air conditioner will turn off completely,at the same time cancel the timing function.
To set the DAY OFF (for a holiday)
1
During the weekly timer, press the Confirm button.
2
Press the button ” ” or ” ” to select the day in this week.
3
Press the Day off button to set the DAY OFF.
The mark is hidden
ex.The DAY OFF is set for Wednesday
4
The DAY OFF can be setted for other days by repeating the steps 2 and 3.
5
Press the Back button to back to the weekly timer.
To cancelFollow the same procedures as those for setup. NOTE: The DAY OFF setting is cancelled automatically after the set day has passed.
52
DELAY function
During the weekly timer, press the FUNC. button , select the delay function
and press the Confirm button,display” ” ” “” ” and wait 3 seconds to confirm.
When the delay function is activated,the ” “mark appears. The delay function
can only be enabled in Weekly Timer 1 and Weekly Timer 2.
ex. If press select ” ” at 18:05, the air conditioner will delay to turn off
at 20:05.
Copy out the setting in one day into the other day.
A reservation made once can be copied to another day of the week. The whole
reservation of the selected day of the week will be copied. The effective use
of the copy mode ensures ease of making reservations.
1
During the weekly timer, press the Confirm button.
2
Press the button ” ” or ” ” to select the day to copy from.
3
Press the Copy button,the letter “CY” will be shown on the LCD.
4
Press the button ” ” or ” ” to select the day to copy to.
5
Press the Copy button to confirm .
ex. Copy the setting of Monday to Wednesday
6
Other days can be copied by repeating step 4 and 5.
7
Press the Confirm button to confirm the settings.
8
Press the Back button to back to the weekly timer.
12. Weekly Timer 2
1. Weekly timer setting
Press Timer to select the
and press Confirm.
53
2. Day of the week setting
Press ” ” or ” ” to select the day of the week and then press CONFIRM.
3. ON timer setting of timer setting 1
Press ” ” or ” ” to select the setting time. The setting time, mode,
temperature and fan speed appear on the LCD. Press CONFIRM to enter the
setting time process.
IMPORTANT: Up to 8 scheduled events can be set on one day. Various events can be scheduled in either MODE, TEMPERATURE and FAN speeds.
ex.Tuesday time scale 1
4. Time setting
Press ” ” or ” ” to set the time, then press CONFIRM.
5. Operation mode setting
Press ” ” o r ”
” to set the operation mode then press CONFIRM.
6. Room temperature setting
Press ” ” or ”
” to set the room temperature,then press CONFIRM.
NOTE: This setting is unavailable in the FAN or OFF modes.
7. Fan speed setting
Press ” ” or ” ” to set the fan speed then press CONFIRM.
NOTE: This setting is unavailable in the AUTO, DRY or OFF modes.
8. Different scheduled events can be set by repeating steps 3 through 7. 9.
Additional days, in a one week period, can be set by repeating steps 3 through
8.
NOTE: The weekly timer setting can be returned to the previous step by
pressing BACK. The current setting is restored. The controller will not save
the weekly timer settings if there is no operation within 30 seconds.
54
WEEKLY timer operation
To start
Press Timer to select the
, and then the timer starts automatically.
To cancel
ex.
Press the Power buttons for 2 seconds to cancel the timer mode.
The timer mode can also be canceled by changing the timer mode using Timer.
To set the DAY OFF (for a holiday)
1
After setting the weekly timer, press CONFIRM.
2
Press ” ” or ” ” to select the day of the week.
3
Press DAY OFF to create an off day.
The mark is hidden
ex.The DAY OFF is set for Wednesday
4
Set the DAY OFF for other days by repeating the steps 2 and 3.
5
Press BACK to revert to the weekly timer.
To cancel, follow the same procedures used for setup. NOTE: The DAY OFF setting is cancelled automatically after the set day has passed.
Copy out the setting in one day into the other day.
A scheduled event, made once, can be copied to another day of the week. The
scheduled events of the selected day of the week will be copied. The effective
use of the copy mode ensures the ease of reservation making.
1 In the weekly timer, press CONFIRM.
2
Press ” ” or ” ” to select the day to copy from.
3
Press COPY, the letters CY appear on the LCD.
4
Press ” ” or ” ” to select the day to copy to.
55
Press COPY to confirm. 5
ex. Copy the setting of Monday to Wednesday
6
Other days can be copied by repeating steps 4 and 5.
7
Press CONFIRM to confirm the settings.
8
Press BACK to revert to the weekly timer.
Delete the time scale in one day.
1
During the weekly timer setting, press CONFIRM.
2 Press ” ” or ” ” to select the day of the week and then press CONFIRM.
3
Press ” ” or ” ” to select the setting time want to delete. The setting time,
mode, temperature and fan speed appear on the LCD. The setting time, mode,
temperature and fan speed can be deleted by pressing the DEL (day of).
ex. Delet the time scale 1 in saturday
13. Fault alarm handing
If the system does not properly operate except the above mentioned cases or
the above mentioned malfunctions is evident, investigate the system according
to the following procedures.
NO. MALFU N C T ION & PROT EC T ION D EFIN E
1
Error of communication between wire controler and indoor unit
D ISPLAY D IGITAL TU BE
The error displayed on the wire controller are different from those on the
unit. If error code appears, please check the <<Owner’s And Installation
Manual>>and<
56
14.Technical indication and requirement
EMC and EMI comply with the CE certification requirements.
15.Queries and settings
When the air conditioning unit is switch machine, Long press “COPY” for 3
seconds , first display P:00, if connected to an indoor unit, display P:00, if
connected to multiple indoor units, press ” “or ” “to display P:01, P:02, and
then press “Confirm” to enter the query indoor unit Tn(T1~T4) temperature and
fan fault(CF), press” “or ” “to select.
Not operating keys 15 seconds or press “Back” or press “ON/OFF”drop out of
query temperature.
When the air conditioning unit is off, into the query function of temperature,
press” ” or ” “to select SP, press “Confrm” to adjust the static pressure
value.
When the air conditioning unit is off, into the query function of temperature, press ” “or ” “to select AF, press “Confirm” into test mode, press “Back” or press “ON/OFF” or press “Confirm”drop out of test mode.In AF mode, 3~6 minutes test completion automatically exits, if the test process, press “Back” or press “ON/OFF” or press “Confrm” , the test exits will be interrupted.
Follow me function temperature compensation
When the air conditioning unit is off, into the query function of temperature,
press ” “or ” “to select tF. The compensation temperature Range : -5~5°C.
Press “Confirm” into setting state, press” “or ” “to select the temperature,
then press “Confirm” to complete it.
: compensation temperature
When the air conditioning unit is off, into the query function of temperature, press ” “or ” “to select tyPE. Press “Confirm” into setting state, press” “or ” “to select the type, then press “Confirm” to complete it.
CH:
HH:
CC:
NA:
Set the highest and lowest temperature values
When the air conditioning unit is off, into the query function of temperature, press ” “or ” “to select tHI or tLo. Press “Confirm” into setting state, press” “or ” “to select the temperature, then press “Confirm” to complete it. The highest setting temperature range : 25~30°C The lowest setting temperature range: 17 ~24°C.
: Highest value setting function. : Minimum value setting function.
57
Remote control function selection of wire controller
When the air conditioning unit is off, into the query function of temperature,
press ” “or ” “to select rEC. ON or OF will be displayed in the temperature
area to indicate whether it is valid or invalid.
When the selection is invalid, the wire controller does not process any remote
control signals. Press “Confirm” into setting state, press” “or ” “to select ,
then press “Confirm” to complete it.
Two – line controller address selection
When the air conditioning unit is off, into the query function of temperature,
press ” “or ” “to select Adr, the temperature zone will display — or A, B.
Where -refers to the code setting of the wirecontroller. Press “Confirm” into
setting state, press” “or ” “to select , then press “Confirm” to complete it.
— : The code setting of the wire controller shall prevail.
: The wire controller address setting.
Restore factory Settings
When the air conditioning unit is off, into the query function of temperature,
press ” “or ” “to select INIt, the temperature zone displayed –. Press
“Confirm” into setting state, press” “or ” “to select to “ON” , then press
“Confirm” to complete it. : Restore factory Settings .
After the wire controller resumes the factory parameter setting, the rotating
parameter setting is restored to 10 hours (the highest and lowest temperature
are not set); The compensation of body temperature is uncompensated; COOL and
HEAT/single COOL mode is restored to COOL and HEAT model; Restore the
temperature range to the factory setting. Remote receiving function is
restored to be effective; The address of the two-control frst-line controller
is restored to the code switch.
16.Wireless control connection
SAFETY PRECAUTION
Read the safety precautions carefully before installing the unit. Stated below
are important safety issues that must be obeyed. Applicable system: IOS,
Android. (Suggest:IOS 9 and above, Android 6.0 and above)
NOTE: Due to special situation may be occured, we explicitly claim below: Not
all of the Andriod and IOS systems are compatible with APP. We will not be
responsible for any issues as a result of the incompatibility.
SAFETY PRECAUTION Smart kit only support WPA-PSK/WPA2-PSK encryption and none
encryption . WPA-PSK/WPA2-PSK encryption is recommended.
58
CAUTION
· Please Check The Service Website For More Information. · Smart Phone camera
needs to be 5 million pixels or above to make sure scan QR code well. · Due to
different network situation, sometimes, request time-out could happen, thus,
it is necessary to
do network confguration again. · Due to different network situation, control
process may return time-out sometimes. If this situation occurs,
the display between board and App may not be the same, please do not feel
confused.
NOTE: Company will not be liable for any issues and problems caused by
Internet, Wi-Fi Router and Smart Devices. Please contact the original provider
to get further help.
DOWNLOAD AND INSTALL APP
On an app market (Google Play Store, Apple App Store), search for “MSmartHome”
and find the MSmartHome app. Download and install it on your phone, You can
also download the app by scanning the QR code below.
MSmartHome
Download the app & activate product
· Please ensure your mobile device is connected to Wireless Network router.
Also, the Wireless Network router has already connected to Internet before
doing user registration and network configuration.
· Make sure your mobile device has already been connected to the Wireless
Network which you want to use. Also, you need to forget other irrelative
Wireless Network in case it influences your cofiguration process.
NETWORK CONFIGURATION
CAUTION
· It is necessary to forget any other around network and make sure the Android
or IOS device just connect to the Wireless Network you want to configure.
· Make sure the Android or IOS device Wireless Network function works well and
can be connected back to your original Wireless Network network automatically.
How to enter AP distribution network
Press the FUNC. button until the icon is selected and then press the CONFIRM
buttton. AP mode is activiated if the icon is blinked.
59
Register and log in
Open the MSmartHome app, and create a new account to start ( you can also
register through a third-party account). If you already had an existing
account, use the account to log in.
Login
Enter email XXXXXXXXX Enter password
Login
Login
Connect your devices to MSmartHome
1. Please make sure your mobile phone is connected to Wireless Network. If
not, go to Settings and turn on the wireless connection, select and connect to
a Wireless Network. Also please turn on the Bluetooth on your phone. If not,
go to Settings and turn it on.
2. Please power on your devices. 3. Open MSmartHome app on your phone. 4. If
a message of “Smart devices discovered nearby” appears, click to add.
… Washing machine
60
5. If no message appears, select “+” on the page and select your device in
the list of nearby devices available. If your device is not listed, please add
your device manually by the device category.
6. Connect your device to Wireless Network according to the instructions on
app. If the connection fails, please follow the instructions provided by the
app to continue with the operation.
Add device
61
NOTE: · Make sure your devices are powered on. · Keep your mobile phone close
enough to your device when you are connecting network to your device. ·
Connect your mobile phone to the wireless network at home, and make sure you
know the password of
the Wireless Network. · Check if your router supports 2.4 GHz Wireless Network
band and turn it on. If you are not sure whether
the router supports 2.4 GHz band, please contact the router manufacturer. ·
The device cannot connect to the Wireless Network that requires
authentication, and it usually appears
in public area such as hotels, restaurants, etc. Please connect to a Wi-Fi
that does not require authentication. · It is recommended to use a Wireless
Network name that only contains letters and numbers. If your Wireless Network
name contains special characters, please modify it in the router. · Turn off
the WLAN+ (Android) or WLAN Assistant (iOS) function of your mobile phone when
connecting network to your devices. · In the case that your device connected
to Wireless Network before but it needs to reconnect, please click “+” on app
Home page, and add your device again by the device category and model
according to the instructions on app.
APP DECLARATION
Hereby, we declare that this Smart kit is in compliance with the essential
requirements and other relevant provisions of Directive 2014/53/EU. A copy of
the full DoC is attached.(European Union products only)
CAUTIONS: WirelessNetwork module models: US-SK107EU-SK107:
FCC ID: 2ADQOMDNA21 IC: 12575A-MDNA21 This device complies with Part 15 of the
FCC Rules and it contains licence-exempt transmitter(s)/receiver(s) that
comply with Innovation, Science and Economic Development Canada’s licence-
exempt RSS(s). Operation is subject to the following two conditions: (1) This
device may not cause interference;and (2) This device must acceptany
interference,including interference
that may cause undesired operation of the device. Only operate the device in
accordance with the instructions supplied. Changes or modifications to this
unit not expressly approved by the party responsible for compliance could void
the user’s authority to operate the equipment. This device complies with FCC
radiation exposure limits set forth for an uncontrolled environment. In order
to avoid the possibility of exceeding the FCC radio frequency exposure limits,
human proximity to the antenna shall not be less than 20cm (8 inches) during
normal operation.
NOTE: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more
of the following measures: –Reorient or relocate the receiving antenna.
–Increase the separation between the equipment and receiver. –Connect the
equipment into an outlet on a circuit different from
that to which the receiver is connected. –Consult the dealer or an experienced
radio/TV technician for help.
62
Breezeless function of dip switch. NTOE: This feature is only available under
cool mode.
This feature is for some models.
INDOOR UNIT MAIN BOARD
SW2-1
SW2-2
SW2-2 dip switch to be “ON”,turn on the breezeless.
SW2-2 dip switch to be “OFF”,turn off the breezeless.
63
CARE AND MAINTENANCE
CAUTION
Cleaning Your Indoor Unit
· Always TURN OFF your AC system and disconnect its power supply before
cleaning or maintenance.
· Only use a soft, dry cloth to wipe the unit clean. You can use a cloth
soaked in warm water to wipe it clean if the unit is especially dirty.
· Do not use chemicals or chemically treated cloths to clean the unit · Do not
use benzene, paint thinner, polishing powder or other solvents to clean the
unit. They can
cause the plastic surface to crack or deform. · Do not use water hotter than
40°C (104°F) to clean the front panel. This can cause the panel to
deform or become discolored. · Before changing the filter or cleaning, turn
off the unit and disconnect its power supply. Removal
and maintenance must be performed by a certified technician. · When removing
filter, do not touch metal parts in the unit. The sharp metal edges can cut
you. · Do not use water to clean the inside of the indoor unit. This can
destroy insulation and cause
electrical shock. · Do not expose filter to direct sunlight when drying. This
can shrink the filter. · Any maintenance and cleaning of outdoor unit should
be performed by an authorized dealer or
a licensed service provider. · Any unit repairs should be performed by an
authorized dealer or a licensed service provider.
Maintenance your AC.
Maintenance Long Periods of Non-Use
If you plan not to use your air conditioner for an extended period of time, do
the following:
Maintenance Pre-Season Inspection
After long periods of non-use, or before periods of frequent use, do the
following:
Turn off the unit and disconnect the power
Turn on FAN function until unit dries out completely
Check for damaged wires
Check for leaks
Make sure nothing is blocking all air inlets and outlets
64
TROUBLESHOOTING
CAUTION
If any of the following conditions occurs, turn off your unit immediately! ·
The power cord is damaged or abnormally warm · You smell a burning odor · The
unit emits loud or abnormal sounds · A power fuse blows or the circuit breaker
frequently trips · Water or other objects fall into or out of the unit DO NOT
ATTEMPT TO FIX THESE YOURSELF! CONTACT AN AUTHORIZED SERVICE PROVIDER
IMMEDIATELY
Common Issues
The following problems are not a malfunction and in most situations will not require repairs.
Issue
Unit does not turn on when pressing ON/OFF button
The unit changes from COOL/HEAT mode to FAN mode
The indoor unit emits white mist Both the indoor and outdoor units emit white
mist
The indoor unit makes noises
Both the indoor unit and outdoor unit make noises
Possible Causes
The Unit has a 3-minute protection feature that prevents the unit from
overloading. The unit cannot be restarted within three minutes of being turned
off. Cooling and Heating Models: If the Operation light and PRE-DEF (Pre-
heating/ Defrost) indicators are lit up, the outdoor temperature is too cold
and the unit’s anti-cold wind is activated in order to defrost the unit. In
Cooling-only Models: If the “Fan Only” indicator is lit up, the outdoor
temperature is too cold and the unit’s anti-freeze protection is activated in
order to defrost the unit.
The unit may change its setting to prevent frost from forming on the unit.
Once the temperature increases, the unit will start operating in the
previously selected mode again. The set temperature has been reached, at which
point the unit turns off the compressor. The unit will continue operating when
the temperature uctuates again.
In humid regions, a large temperature difference between the room’s air and
the conditioned air can cause white mist.
When the unit restarts in HEAT mode after defrosting, white mist may be
emitted due to moisture generated from the defrosting process.
A rushing air sound may occur when the louver resets its position. A squeaking
sound is heard when the system is OFF or in COOL mode. The noise is also heard
when the drain pump (optional) is in operation. A squeaking sound may occur
after running the unit in HEAT mode due to expansion and contraction of the
unit’s plastic parts. Low hissing sound during operation: This is normal and
is caused by refrigerant gas owing through both indoor and outdoor units.
Low hissing sound when the system starts, has just stopped running, or is
defrosting: This noise is normal and is caused by the refrigerant gas stopping
or changing direction.
Squeaking sound: Normal expansion and contraction of plastic and metal parts
caused by temperature changes during operation can cause squeaking noises.
65
Issue
The outdoor unit makes noises
Dust is emitted from either the indoor or outdoor unit
Possible Causes
The unit will make different sounds based on its current operating mode.
The unit may accumulate dust during extended periods of non-use, which will be
emitted when the unit is turned on. This can be mitigated by covering the unit
during long periods of inactivity.
The unit emits a bad odor
The unit may absorb odors from the environment (such as furniture, cooking,
cigarettes, etc.) which will be emitted during operations.
The unit’s lters have become moldy and should be cleaned.
The fan of the outdoor unit does not operate
During operation, the fan speed is controlled to optimize product operation.
NOTE: If problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed description of the unit malfunction as well as your model number.
When troubles occur, please check the following points before contacting a repair company.
Problem
Possible Causes
Solution
Temperature setting may be higher than ambient room temperature
Lower the temperature setting
Poor Cooling Performance
The heat exchanger on the indoor Clean the affected heat exchanger or outdoor unit is dirty
The air filter is dirty
The air inlet or outlet of either unit is blocked Doors and windows are open
Excessive heat is generated by sunlight
Remove the lter and clean it according to instructions
Turn the unit off, remove the obstruction and turn it back on
Make sure that all doors and windows are closed while operating the unit
Close windows and curtains during periods of high heat or bright sunshine
Too many sources of heat in the room (people, computers, electronics, etc.)
Reduce amount of heat sources
Low refrigerant due to leak or long-term use
Check for leaks, re-seal if necessary and top off refrigerant
66
Problem
The unit is not working
The unit starts and stops frequently
Poor heating performance
Indicator lamps continue flashing Error code appears and begins with the
letters as the following in the window display of indoor unit: · E(x), P(x),
F(x) · EH(xx), EL(xx), EC(xx) · PH(xx), PL(xx), PC(xx)
Possible Causes Power failure
Solution Wait for the power to be restored
The power is turned off
Turn on the power
The fuse is burned out
Replace the fuse
Remote control batteries are dead Replace batteries
The Unit’s 3-minute protection has been activated
Timer is activated
Wait three minutes after restarting the unit
Turn timer off
There’s too much or too little refrigerant in the system
Check for leaks and recharge the system with refrigerant.
Incompressible gas or moisture Evacuate and recharge the system
has entered the system.
with refrigerant
System circuit is blocked
Determine which circuit is blocked and replace the malfunctioning piece of equipment
The compressor is broken
The voltage is too high or too low
The outdoor temperature is extremely low
Cold air is entering through doors and windows
Low refrigerant due to leak or long-term use
Replace the compressor Install a manostat to regulate the voltage Use
auxiliary heating device
Make sure that all doors and windows are closed during use Check for leaks,
re-seal if necessary and top off refrigerant
The unit may stop operation or continue to run safely. If the indicator lamps continue to ash or error codes appear, wait for about 10 minutes. The problem may resolve itself. If not, disconnect the power, then connect it again. Turn the unit on. If the problem persists, disconnect the power and contact your nearest customer service center.
67
Troubleshoot Your Wireless Remote Control
Problem
Possible Causes
The fan speed cannot be changed.
Check whether AUTO mode is selected.
Check whether DRY mode is selected.
Solution
In AUTO mode, the fan speed is set automatically and cannot be changed.
In DRY mode, the FAN SPEED button is ineffective. The fan speed can only be
changed in COOL, FAN and HEAT mode.
The temperature display is off
Check whether FAN mode is selected.
In FAN mode, the temperature cannot be adjusted.
The TIMER OFF disappears after a period of time
If the TIMER OFF function was activated, the operation may have nished.
The TIMER ON indicator disappears after a period of time
If the TIMER ON function was activated,the operation may have nished.
There is no sound when the ON/OFF button is pressed.
Check whether the signal transmitter of the remote control is properly directed towards the infrared signal receiver of the indoor unit.
The air conditioner will automatically stop at the set time and the indicator
light will turn off.
The air conditioner will automatically start at the set time and the indicator
light will turn off.
Point the remote control directly at the receiver and press the ON/OFF button
twice.
NOTE: If your problem persists after performing the checks and diagnostics above, turn off your unit immediately and contact an authorized service center.
68
PACKING AND UNPACKING THE UNIT
Instructions for packing unpacking the unit: Unpacking: Indoor unit: 1. Cut
the packing belt. 2. Unpack the package. 3. Take out the packing cushion and
packing support. 4. Remove the packing film. 5. Take out the accessories. 6.
Lift the machine out and lay it flat. Outdoor Unit 1. Cut the packing belt. 2.
Take the unit out of the package. 3. Remove the foam from the unit. 4. Remove
the packing film from the unit. Packing: Indoor unit: 1. Put the indoor unit
into the packing film. 2. Put the accessories in. 3. Place the packing cushion
and packing support. 4. Put the indoor unit into the package. 5. Close the
package and seal it. 6. Using the packing belt if necessary. Outdoor unit: 1.
Put the outdoor unit into the packing film. 2. Put the bottom foam into the
box. 3. Put the outdoor unit into the package, then put the upper packaging
foam on the unit. 4. Close the package and seal it. 5. Using the packing belt
if necessary.
NOTE: Please keep all packaging items if you may need in the future.
69
IMPEDANCE INFORMATION
(APPLICABLE TO SOME COUNTRIES OF MIDDLE EAST AREA ONLY)
To be in compliance with EN61000-3-11, the product MTI-48HWN1-R shall be
connected only to a supply of the system impedance: Zsys = 0.267802236 or
less. Before connecting the product to public power network, please consult
your local power supply authority to ensure the power network meet above
requirement. To be in compliance with EN61000-3-11, the product MTI-60HWN1-R
shall be connected only to a supply of the system impedance: Zsys = 0.214 or
less. Before connecting the product to public power network, please consult
your local power supply authority to ensure the power network meet above
requirement. To be in compliance with EN61000-3-11, the product
MTIT4-36CWN1-QC5 (Indoor Unit: MTIT4-36CWN1-QC5 , Outdoor Unit:MOT4DU-
36CN1-QC5)shall be connected only to a supply of the system impedance: Zsys =
0.021893 or less. Before connecting the product to public power network,
please consult your local power supply authority to ensure the power network
meet above requirement. To be in compliance with EN61000-3-11, the product
MTIT4-36CWN1-QC5 (Indoor Unit: MTIT4-36CWN1-QC5 , Outdoor Unit:MOT4V-36CN1-QC5
)shall be connected only to a supply of the system impedance: Zsys = 0.024 or
less. Before connecting the product to public power network, please consult
your local power supply authority to ensure the power network meet above
requirement. To be in compliance with EN61000-3-11, the product MTIT-
32CWN1-QC5 shall be connected only to a supply of the system impedance: Zsys =
0.083964 or less. Before connecting the product to public power network,
please consult your local power supply authority to ensure the power network
meet above requirement.
70
TRADEMARKS, COPYRIGHTS AND LEGAL STATEMENT
logo, word marks, trade name, trade dress and all versions thereof are
valuable assets of Midea Group and/or its affiliates (“Midea”), to which Midea
owns trademarks, copyrights and other intellectual property rights, and all
goodwill derived from using any part of an Midea trademark. Use of Midea
trademark for commercial purposes without the prior written consent of Midea
may constitute trademark infringement or unfair competition in violation of
relevant laws.
This manual is created by Midea and Midea reserves all copyrights thereof. No
entity or individual may use, duplicate, modify, distribute in whole or in
part this manual, or bundle or sell with other products without the prior
written consent of Midea.
All the described functions and instructions were up to date at the time of
printing this manual. However, the actual product may vary due to improved
functions and designs.
DISPOSAL AND RECYCLING
Important instructions for environment(European Disposal Guidelines)
Compliance with the WEEE Directive and Disposing of the Waster Product: This
product complies with EU WEEE Directive (2012/19/EU). This product bears a
classification symbol for waster electrical and electronic equipment (WEEE).
This symbol indicates that this product shall not be disposed with other
household wastes at the end of its service life. Used device must be returned
to official collection point for recycling of electrical electronic devices.
To find these collection systems please contact to your local authorities or
retailer where the product was purchased. Each household performs important
role in recovering and recycling of old appliance. Appropriate disposal of
used appliance helps prevent potential negative consequences for the
environment and human health.
71
DATA PROTECTION NOTICE
For the provision of the services agreed with the customer, we agree to comply
without restriction with all stipulations of applicable data protection law,
in line with agreed countries within which services to the customer will be
delivered, as well as, where applicable, the EU General Data Protection
Regulation (GDPR). Generally, our data processing is to fulfil our obligation
under contract with you and for product safety reasons, to safeguard your
rights in connection with warranty and product registration questions. In some
cases, but only if appropriate data protection is ensured, personal data might
be transferred to recipients located outside of the European Economic Area.
Further information are provided on request. You can contact our Data
Protection Officer via MideaDPO@midea.com. To exercise your rights such as
right to object your personal date being processed for direct marketing
purposes, please contact us via MideaDPO@midea.com. To find further
information, please follow the QR Code.
Importer: MIDEA APPLIANCE AUSTRALIA Manufacturer: GD Midea Air-Conditioning
Equipment Co,.Ltd. Lingang Road Beijiao Shunde Foshan Guangdong People’s
Republic of China 528311 The design and specifications are subject to change
without prior notice for product improvement. Consult with the sales agency or
manufacturer for details. Any updates to the manual will be uploaded to the
service website, please check for the latest version.
72
www.midea.net.au
QS001UI-T2(B) 16123000A32200
20230215
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>