condair 2594905 Humi Life Whole Home Steam Humidifier RH Instruction Manual
- September 27, 2024
- condair
Table of Contents
- 2594905 Humi Life Whole Home Steam Humidifier RH
- Specifications
- Product Overview
- Installation Overview (Furnace)
- Installation Overview (HRV)
- Location and Clearances
- Product Usage Instructions
- 1. Install the Humidifier
- 2. Location and Clearances
- 3. Mounting Instructions
- 4. Steam Line Setup
- 5. Electrical Setup
- Q: What tools are required for installation?
- Q: Where should I position the steam distributor?
- Q: What are the safety recommendations for installation?
2594905 Humi Life Whole Home Steam Humidifier RH
“`html
Specifications
- Net / Full Weight: 19 / 26 lb (8.6 / 11.8 kg)
- Dimensions: 18.4 x 10.4 x 6.9 in (467 x 265 x 175 mm)
Product Overview
- Steam hose
- Steam distributor
- Drain valve
- Power button & LED
- Steam cylinder
- Water inlet
- Drain outlet
- Control board
Installation Overview (Furnace)
Details on how to install the humidifier in conjunction with a
furnace.
Installation Overview (HRV)
Details on how to install the humidifier in conjunction with a
Heat Recovery Ventilator (HRV).
Location and Clearances
Guidelines on where and how to position the humidifier for
optimal performance and maintenance access.
Product Usage Instructions
1. Install the Humidifier
Follow the detailed installation overview provided in the manual
for either furnace or HRV installations.
2. Location and Clearances
Ensure proper clearance for servicing, maintenance, and
installation of steam line and distributor.
3. Mounting Instructions
If installing on a wall, mount on wall studs using the supplied
template. For duct installations, use the mounting template for
pilot holes.
4. Steam Line Setup
For remote installations, use a longer steam hose as needed.
Follow the recommendations provided for efficient
humidification.
5. Electrical Setup
Ensure all electrical connections are made according to local
regulations and safety standards.
FAQ
Q: What tools are required for installation?
A: The tools required for installation include…
Q: Where should I position the steam distributor?
A: It is recommended to install the distributor first, as its
location will define the placement of the humidifier.
Q: What are the safety recommendations for installation?
A: It is recommended to install high limit humidistat and air
proving switch for safety. The specific part numbers are…
“`
2594905_F_EN_2404_Condair_RH_SIOM
QUICK INSTALL GUIDE FOR PROFESSIONALS
Condair HumiLife Whole-home Steam Humidifier Condair RH
Humidification and Evaporative Cooling
Thank you for choosing Condair
Cautions and Warnings
CAUTION: Servicing
· The unit is mains powered. Disconnect main power before any servicing.
· Electrical compartment contains high voltage components. Access should be
limited to authorized personnel only.
· The unit is hot. Wait for the unit to drain and cool before servicing.
During and following operation of the humidifier, the steam and components in
contact with the steam such as the steam lines, steam distributors, and
condensate lines can become hot and can burn if touched.
· Condair does not accept any liability for installations of humidity
equipment installed by unqualified personnel, or the use of parts, components,
or equipment that are not authorized or approved by Condair.
CAUTION: Electrical
· All electrical work should be done according to all applicable local and
national codes.
· Electrical connection to be performed by a licensed electrician.
CAUTION: Plumbing
· (Recommended) Plumbing to be performed by a licensed plumber.
· Drain water from the humidifier can be very hot. Drain to an appropriate
floor drain.
· All plumbing work should be done according to local plumbing code.
CAUTION: Installation
· Do NOT mount in area where freezing can occur. · Do NOT mount on vibrating
surface. · Do NOT mount on the floor. · Do NOT block the steam outlet. ·
(Recommended) Install an air proving switch. · Do install steam lines to
prevent any restrictions that
may cause back-pressure in the humidifier. · Ensure furnace fan is operating
while the humidifier is
generating steam. · Keep out of reach of children.
2
What’s in the box?
· Condair HumiLife Steam Humidifier · Quick Start Guide · Steam Distributor &
Gasket · Humidity sensor (duct) · Water (fill) hose, 20 ft (6 m) · Steam hose,
5 ft (1.5 m) · Drain hose, 10 ft (3 m) · Fittings
Accessing the Condair RH manuals
To access all Condair RH manuals, including the French manuals, please scan
the QR Code below.
What you’ll need
Condair HumiLife app. Find the app in the App Store® (iPhone) or Google Play Store (Android). (required to finalize the installation)
Google Play (Android)
App Store (iOS)
Access to:
· Drain · Water supply · Forced air ventilation system · Wall studs (for wall
mounted installations)
Tools:
· · · · · · · ·
Phillips (+) screwdriver Flat-head () screwdriver Pliers Level Hole saw, 1.2 in (30 mm) & 5/8 in (16 mm) Drill and bits Box cutter (or other sharp knife) Wire cutter and wire stripper
2594905_F_EN_2404_Condair_RH_SIOM
Product Overview
Steam hose
Steam distributor
Drain valve
Power button & LED
Steam cylinder
Water inlet
Drain outlet
Control board
2594905_F_EN_2404_Condair_RH_SIOM
3
Installation Overview (Furnace)
7
1
3
2 4
8 5
6
1 Steam distributor 2 Water shut off valve (not supplied) 3 On/Off wall humidistat *
4 Relative humidity (RH) duct sensor * 5 Electrical disconnect switch (not supplied) 6 Drain (not supplied)
- only an on/off humidistat (not supplied) OR RH sensor (supplied) should be installed.
7 Safety devices: i.e high limit humidistat and air proving switch are
recommended, installed in series on Terminal X3 (both not supplied)
8 Fan enable/activation
Note: It is recommended to install a high limit humidistat and an air proving switch for safety. The high limit humidistat can be ordered under PN# 2597935 and the air proving switch under PN# 2598427.
4
2594905_F_EN_2404_Condair_RH_SIOM
Installation Overview (HRV)
1
4 2
3 6
5
1 Steam distributor 2 Water shut off valve (not supplied)
3 On/Off wall humidistat 4 Relative humidity (RH) duct sensor
- only an on/off humidistat (not supplied) OR RH sensor (supplied) should be installed.
5 Electrical disconnect switch (not supplied) 6 Drain (not supplied)
2594905_F_EN_2404_Condair_RH_SIOM
5
Location and Clearances
165i2n mm
167.59 minm
12054inmm
93165inmm
21605.4minm
1486.7439mi61nm5inmm 62140inmm
The Condair HumiLife RH may be installed on a wall and remotely connect to
your ventilation system, or directly onto the ventilation duct.
When choosing the location for your humidifier, ensure there is enough
clearance for servicing and maintenance, and for the installation of the steam
line and steam distributor.
For remote installations, you will require a longer steam hose, so consider
the steam line recommendations below for efficient humidification.
For installations on a wall, mount the unit on wall studs (2×4 or equivalent).
For installations directly on the duct, use the mounting template (supplied)
to locate pilot holes for mounting the unit and installing the steam
distributor.
(Recommended) Install the distributor first. The location of the distributor
will define the location of the humidifier.
5.3 in 135 mm
4.6 in 118 mm
Net / Full Weight lb (kg)
19 / 26 lb (8.6 / 11.8 kg)
Dimensions HxWxD in (mm)
18.4 x 10.4 x 6.9 in (467 x 265 x 175 mm)
Clearance dimensions shown are for reference only and are the minimum required
for maintenance of the humidifier. Consult local and national code before
final location and installation. Condair does not accept responsibility for
installation code violations.
Important Considerations for the Steam Line
· Install the humidifier below the steam distributor. · Install support
brackets (one supplied with the humidifier) to prevent sagging in the steam
line. If sagging occurs,
use additional support brackets. · Install the humidifier as close as possible
to the steam distributor. Short distances minimize condensate losses
and reduces the possibility of back pressure in the steam line. · Bend radius:
6 in (150 mm) minimum. · Length: 15 ft (4.5 m) maximum. · Slope: 15° min. (up-
slope), 2° max. (down-slope).
Note: install condensate traps at low points if the steam line has any down-
slope. · Steam line material: Condair steam hose (supplied), or properly
insulated stainless steel or copper, with max.
surface temperature at 140 ° F (60 °C). · Clamp torque: 12 in-lb (1.36 Nm)
(max. at humidifier outlet).
6
2594905_F_EN_2404_Condair_RH_SIOM
Installing the Steam Distributor
8 in (204 mm) Vertical Duct
Horizontal Duct
2/3 (ØØ310.2minm)
1/2 Ø18.2inin((2Ø0430mmmmm))
Create a 1.18 in (30 mm) hole in the duct. Install distributor on the supply
duct, after the cooling coil, and before any bends or obstructions.
For horizontal ducts, cut the hole at roughly 2/3 of duct height, from the
top.
For vertical ducts, cut the hole halfway between the two sides of the duct.
Place a gasket over the steam distributor and insert the distributor into the duct. Ensure that the arrows on the distributor are pointing up. Secure the distributor to the duct with self-tapping screws.
Removing the Steam Cylinder
Open the door to the humidifier.
Pull the lever upwards. The lever will push the cylinder out.
Pull the cylinder out of the humidifier.
2594905_F_EN_2404_Condair_RH_SIOM
7
template
Duct or Wall Stud
Mounting Your Humidifier
A
A
A
B B
Open the door to the humidifier. Remove the steam cylinder if it is installed. Tip: For installations directly on the duct, place the mounting template on the duct and secure with tape. The template will show you where to cut a hole for the distributor.
On the wall stud (2×4 or equivalent) or duct, mark the location for the key hole A (on the back of the humidifier). Insert a screw at A. Leave space on the screw to hang the humidifier.
A
A
B B
Raise and hang the humidifier on the screw A. Ensure the unit is level.
Through the inside of the humidifier, insert and tighten a screw into the lower mounting hole B. Tighten the top screw at A.
8
2594905_F_EN_2404_Condair_RH_SIOM
Installing the Steam Line
1
1 in (2.5 cm)
15°
7.5 2
2°
12 0.5
6 in (15 cm)
6 in (15 cm)
2 3
12 in (30 cm)
Remote Mounted Installation with Steam Distributor (horizontal duct shown)
1 Insulation (recommended)
2 Brackets, support (supplied by others)
3 T-connector, condensate trap (supplied by others)
Ø 2Ø51mpmo
Ø 2Ø51mpmo
Ø Ø
125pomm
15°
Ø Ø
125pomm
Installation de la conduite et du distributeur de vapeur
2594905_F_EN_2404_Condair_RH_SIOM
9
Water Supply and Drain Connections
4 16400- -120102°C°F 2
3
1
1 Water shut off valve 2 Inlet, quick connect (supplied)
Water Supply and Drain Connection 3 Inlet water line, 1/4 in (6.4 mm) (supplied) 4 Drain line, 3/4 in (20 mm) I.D. (supplied)
Water Supply Requirements
Quality Pressure Temperature Conductivity Other
Potable water (do not use reverse osmosis or deionized water) 30 – 80 psig (2 – 5.5 bar) 39 – 86 °F (4 – 30 °C), cold water 125 – 1250 S/cm · Water shut-off valve installed before the humidifier (for service). · Installed according to national and local plumbing code.
Drain Requirements
The Condair HumiLife RH produces hot water during operation. Upon normal
drainage, the drain water is automatically cooled to 140 °F (60 °C).
IMPORTANT! Drain water may reach high temperatures 212 °F (100 °C) in cases
where the supply water is not cold, or obstructed.
Considerations for the drain connection · Ensure that drain line is made of a
material rated to handle hot temperatures, 212 °F (100 °C). · (Recommended)
Use the drain line hose supplied with the humidifier. For longer runs, use
copper pipe with the
same inner diameter as the drain line hose supplied with the humidifier, inner
diameter: 3/4 in (20 mm). · Ensure that the internal diameter throughout the
drain line is constant. · Ensure that the drain line is adequately sized. A
restricted drain line may result in higher mineral concentrations
in the water and can result in poor performance. · Ensure that the drain line
is routed to a floor drain (or where plumbing codes permit). If the drain is
far from the
humidifier, use a condensate pump rated for hot drain water. · Ensure that the
drain line has a consistent, downward slope (1.2°) to the drain.
10
2594905_F_EN_2404_Condair_RH_SIOM
Installing the Electrical Connection and Controls
Power supply Controls/Sensors
Model
Condair RH-NAP, 22
Voltage V
110-120 208
220-240
Power kW 1.4 2.5 2.9
Current Phase Max Ext Fuse A (MCA) Frequency A (MOCP)
12.0
Phase 1 50-60 Hz
15
Humidity sensor *
Electrical disconnect switch
Fan activation
- for other control devices, refer to installation manual. ** route cables and wires though strain relief clamps.
AB
C
208 VAC
–
120 VAC 230 VAC
A: Humidity control sensor or controller
RG
B: Jumper (refer to installation manual
Q1
Q1
for more information)
X1
C: Fan activation, connect to HVAC
GF RF
GT
E XT 2 4 VD C X5
GND
X4
X3
X2
system
HOT
HOT
L1
Q1: External disconnect or breaker
N
HOT
L2/ N
LIM
2 4 VD C
SC
SC
GND
H UM
2 4 VD C
GND
GND
GND/ PE
Consult the Installation Manual for electrical connection requirements and guidelines.
2594905_F_EN_2404_Condair_RH_SIOM
11
Electrical Wiring Diagram
POWER
SUPPLY /
+V
-V
Source
GND
d’alimentation
N
principale
L
Black/Noir Red/Rouge Green-Yellow/Vert-Jaune Blue/Bleu Brown/Brun
Switch
Run Wifi LEDs Cyl Spent Fault
G R
C1
A2
-
B1B2
A3
A1
OR
WIFI
MODULE
J4
1AT
X14 GND 2 4 VD C
CY L R PL C
P4
J1 P1P2
X13 G ND
24V DC
X12
L1
F1
L2/ N GN D/ PE
GF
RF
GT
DRAIN/Vidange
Black/Noir Blue/Bleu
EXT
GND/Terre
24VDC INLET/Remplissage
X5
GND/Terre
GND
LIM
Red/Rouge Gray/Gris
X6 MAX LVL X11
24VDC
CYLINDER/Cylindre
X10
X4
SC
SC
X3 GND
16A T
F2
HUM
24VDC
X2
L1 L2 / N GND / PE
Ground/ Mise à la terre
X9
CYLINDER/ Cylindre
X1
X7 X8
Black/Noir Red/Rouge
Fill Valve / Vanne de remplissage Orange/Orange Black/Noir Black/Noir
Drain Valve/ Vanne de vidange
On/Off
208-240 VAC
Q1
120 VAC
Q1
HOT
N
HOT
GND
Note: The Condair RH is not provided with a jumper on safety loop contacts of terminal block X3. Refer to B1/B2 for safety recommendations. If no safety devices are installed, then a jumper must be installed on contacts of terminal block X3 in order for the Condair RH to run.
GFCI Plate/ Plaque du DDFT
GND
HOT
Wiring Diagram
A1 Humidity control sensor or controller B1/B2 Air proving switche, safety high limit F1 Fuse 1AT (5×20 mm)
(Install either A1 or A3)
A2 High limit control sensor or controller (highly recommended)
humidistat, or external contact. Jumper, use if air proving switch or furnace fan not installed.
F2 Fuse 16AT, SPT (5×20 mm) Q1 External disconnect or breaker
A3 Humidistat (On/Off). Install either A1 C1 Fan activation, connect to HVAC sys-
or A3
tem
12
2594905_F_EN_2404_Condair_RH_SIOM
Different Humilife RH Configurations
Configuration 1: Contractor App Setup, No-WiFi Connection, External/Demand
Controls · The humidifier will operate according to the external controls ·
The user will control the humidifier from the external controls · The user
will need to check the humidifier periodically to identify if the cylinder
needs to be changed (Yellow
Light) · The cold-weather setback feature is unavailable (requires WiFi)
Configuration 2: Contractor App Setup, No-WiFi Connection, Sensor Controls ·
The humidifier will operate according to the sensor signal and the default
setpoint 40 % Relative humidity · The user will not have control over the
humidity · The user will need to check the humidifier periodically to identify
if the cylinder needs to be changed (yellow light) · The cold-weather setback
feature is unavailable (requires WiFi)
Configuration 3: WiFi Connection, External/Demand Controls · The humidifier
will operate according to the external controls · The user will control the
humidifier from the external controls · The user will receive notifications
via the app when the cylinder change is needed · All features are available to
the user (Note: Sensor settings must be changed if the homeowner wants to
control
the unit through the app instead)
Configuration 4: WiFi Connection, Sensor Controls · The humidifier will
operate according to the sensor controls · The user will control the
humidifier from the app · The user will receive notifications via the app when
the cylinder change is needed · All features are available to the user
Operation Summary Table
To turn On/Off the humidifier: To reset the error/warning: To connect the unit
to your device:
Press the power button for 2 seconds.
Press and hold the power button for 3 seconds.
Press and hold the power button until the WiFi LED flashes green (around 5
seconds)
2594905_F_EN_2404_Condair_RH_SIOM
13
Download Condair HumiLife App
Download the Condair HumiLife App either from the “Google Play Store” or the
“Apple App Store”. The app can be found by searching “Condair HumiLife” or by
using the following QR codes:
Commissioning with App in Professional Mode (for contractors/installers for
quick connect and configuration)
Start the Condair HumiLife app. 1
For contractors/installers: Enter username “RH” and login without a password.
This will allow the installer to access and modify the settings only This
will not connect the unit to WiFi or the cloud).
14
2594905_F_EN_2404_Condair_RH_SIOM
2
On/Off switch Operating status LED WIFI status LED Steam cylinder status LED
Warning/Fault LED
3
Call up the WLAN settings in the smartphone’s device settings
Search for the WLAN Condair _”serial number”.
“serial number” corresponds to a 7-digit number.
On/Off switch Operating status LED WIFI status LED Steam cylinder status LED Warning/Fault LED
2594905_F_EN_2404_Condair_RH_SIOM
15
4
On/Off switch Operating status LED WIFI status LED Steam cylinder status LED
Warning/Fault LED
On/Off switch Operating status LED WIFI status LED Steam cylinder status LED Warning/Fault LED
16
2594905_F_EN_2404_Condair_RH_SIOM
Status will show as online only when the homeowner connects the unit to their
home Wifi network
Change Sensor Settings
Check actual Warnings and Errors
Change existing WLAN configuration
Reset cylinder hours
2594905_F_EN_2404_Condair_RH_SIOM
17
Commissioning with App (for homeowners to connect through WiFi)
· Start the Condair HumiLife App on your mobile device. · Turn on the
humidifier by pressing the power button for 2 seconds.
Now proceed proceed as follows:
1
2
3
Select “Create an Account”.
Fill new user details and register.
Registration successful, select “Back to Login”.
18
2594905_F_EN_2404_Condair_RH_SIOM
4
5
6
Enter registered email address and Select “Add device”. password and login to account.
Select “My devices”.
2594905_F_EN_2404_Condair_RH_SIOM
19
7
8
9
DO NOT press “Continue” yet
Select “Add new device”.
Press the power button on the unit until WiFi LED flashes green, then select “Continue” on the app.
When this page is prompted, DO NOT select “Continue”. Go to your WIFI setting and select “Condair_Serial number”.
20
2594905_F_EN_2404_Condair_RH_SIOM
10
11
12
Select the “Condair_serial number” network, each unit will have a diffferent serial number.
The network connection will still show as loading (buffering), go back to the app once it shows the “Unsecured Network”. The Wifi LED on the device should be solid green, which indicates it is successfully connected.
Select “Continue”.
2594905_F_EN_2404_Condair_RH_SIOM
21
For some Android users depending on their devices, please note the below steps:
11a
11b
11c
In some cases, a notification will pop up after few seconds of connecting to the unit. Please select “Tap for options”. Note: The notification layout might vary depending on your android device.
Tick the box and select “Yes”, then go back to the app and press continue.
Select “Always connect”, then go back to the app and press “Continue”.
22
2594905_F_EN_2404_Condair_RH_SIOM
13
14
15
Wait for the app to connect to the unit.
Connection successfull, select “Continue network configuration” to connect to local WiFi.
Select your local WiFi network and press “Connect”. Note: in case your Wifi signal is not Visible, then please select on “The WLAN is not listed” and enter it manually.
2594905_F_EN_2404_Condair_RH_SIOM
23
16
17
18
Enter you local WiFi network password (make sure it is entered correctly), then press on “Save and connect”.
After completing the network configuration, select “Continue to confirmation”.
Wait for few seconds for the app to receive a confirmation from the device.
24
2594905_F_EN_2404_Condair_RH_SIOM
19
20
21
Once confirmation is successful, wait for a few seconds for the app to connect to the cloud.
Successfully connected to the cloud, select “Finished” to proceed. The Wifi LED on unit should now change to solid Blue.
The Home screen is shown. Select “More” for more options (WiFi symbol on unit should be solid blue).
Note 1: When deciding where to install the unit, please make sure the unit is
installed close enough to the wifi router to receive proper wifi signal. If
this is not possible, a “Repeater” or a “Signal booster” may be required.
Contact your internet provider for more information.
Note 2: Regarding step 21, in some cases it might take a while (Up to 15 mins)
for wifi symbol to turn solid blue on the unit. Please check the status on the
app; if the status is online, then the unit is connected and LED will turn
solid blue soon. If the status shows offline, and reconnecting the unit
doesn’t solve the issue, please reach out to Technical Support on
1.866.667.8321 to verify that the unit connected to cloud successfully.
2594905_F_EN_2404_Condair_RH_SIOM
25
Temperature Setback Feature
The Temperature Setback Feature will allow the homeowner to set their
humidifiers location. The feature will work similar to an outdoor temperature
sensor, but the temperature is from the online weather data. To set your
location, the Zip Code / Postal Code is sufficient to be entered.
26
2594905_F_EN_2404_Condair_RH_SIOM
Warnings and Remedies
Code W1
W2
W3 W4 W5 W6
Warning
Description
LED unit
Indication Possible causes App
Remedy
lights yellow
W1
Overcurrent detected.
The measured heating current is greater than 115% (but less than 130%) of the permissible maxi-
mum current over a certain period of time. The heating circuit is deactivated. After a set time, the
Condair RH will restart and return to normal operation.
Humidity demand dropped too quickly.
Automatic adjustment of the working point.
Drain valve defective.
Check/replace drain valve.
Drain obstructed in the steam cylinder.
Replace steam cylinder.
Used cylinder not recognized.
Replace steam cylinder.
Steam cylinder fills too fast.
Check/replace inlet valve.
blinks blue
W2
External safety loop open.
The Condair RH is stopped. The Condair RH automatically returns to normal operation as soon
as the external safety loop is closed, there is no system error and the unit is switched on again via
the HumiLife app.
Ventilation switched off.
Check/switch on ventilation.
High limit humidistat or air flow monitor has Check the setting of the high limit humidistat or
responded.
the flow monitor.
Wiring to the high limit humidistat interrupted or Check the wiring of the high limit humidistat. incorrectly wired.
High limit humidistat defective.
Check/replace high limit humidistat.
Wiring to the air flow monitor interrupted or Check the wiring of the air flow monitor. incorrectly wired.
Air flow monitor defective.
Check/replace air flow monitor.
W3
No signal from the humidity sensor.
lights yellow
Wiring to the humidity sensor interrupted or incorrectly wired.
Humidity sensor defective.
Check the wiring of the humidity sensor. Check/replace humidity sensor.
W4
No signal from the limiter sensor.
lights yellow
Wiring to the limiter sensor interrupted or incor- Check the wiring of the limiter sensor. rectly wired.
Limiter sensor defective.
Check/replace limiter sensor (humidity sensor in the supply air duct.
lights yellow
W5
The end of service life of the steam cylinder is soon reached. The steam cylinder has to be replaced
in the near future.
No WiFi signal
lights red
WiFi signal interrupted.
Disconnect the device from the power supply and reconnect.
Reconnect unit.
2594905_F_EN_2404_Condair_RH_SIOM
27
Errors and Remedies
Code E1
E2
E3 E4 E5 E6
Error
Description
LED unit
Indication Possible causes App
Remedy
lights red
E1
Overcurrent detected.
The measured heating current is greater than 130% of the permissible maximum current over a
certain period of time. The Condair RH is stopped.
Humidity demand dropped too quickly
Automatic adjustment of the working point.
Drain valve defective.
Check/replace drain valve.
Drain obstructed in the steam cylinder.
Replace steam cylinder.
Used cylinder not recognized.
Replace steam cylinder.
Steam cylinder fills too fast.
Check/replace inlet valve.
lights red
E2
Problem with inlet or drain.
No heating current was measured for 30 minutes, although there is a humidity demand present.
Water supply interrupted (shut-off valve closed) Check water supply (open shut-off valve,
or obstructed.
check water pressure).
Strainer in the inlet valve clogged or inlet valve Check/clean the strainer in the inlet valve or
defective.
replace the valve.
Drain valve leaking or defective.
Check/clean or replace the drain valve.
Fuses on the driver board defective.
Check/replace fuses on the driver board.
Heating cable harness defective.
Check/replace heating cable harness.
Loss of water in the water system (via fill cup Check steam installation: steam line not too long, overflow) due to excessive back pressure in the not kinked, no condensate pocket. steam line.
lights red
E3
No heating current detected.
No heating current was detected, although the max. level sensor has been activated.
Inlet valve not closing or leaking.
Check whether inlet valve is closing, e.g. in standby mode. Replace valve if required.
Max. level sensor not working properly.
Check max. level sensor state when cylinder is empty.
Heating cable harness defective.
Check/replace heating cable harness.
lights red
E4
Unexpected heating current detected:
The control measures a heating current although there is no humidity demand. The Condair RH
is stopped.
Fuse of the heating circuit on the driver board Check/replace fuse. is defective
Driver board defective.
Replace driver board.
lights red
E5
End of life of the steam cylinder reached. The steam cylinder must be replaced. The Condair RH
is stopped.
lights red lights red lights red
E6
Invalid cylinder installed.
Cylinder not installed correctly (contact cylinder Install cylinder correctly. fuse bad).
The controller cannot verify the newly installed Contact your Condair representative. cylinder.
28
2594905_F_EN_2404_Condair_RH_SIOM
Notes
Disclaimer
This Quick Start Guide (the “QSG”) provides basic product and installation
overview of the Condair HumiLife Humidifier (the “HumiLife Humidifier”) and is
for general information purposes only. The general installation guidelines
contained herein do not purport to cover all details of the HumiLife
Humidifier nor do they provide for every contingency met in connection with
installation. Please consult the complete Installation Manual and Operation
Manual for a more comprehensive installation guide and for general operation,
maintenance, and troubleshooting information, including Condair’s suggested
storage, packaging, and transportation guidelines. The Installation Manual and
Operation Manual contain specific system, accessories, and components. Copies
of the complete Installation Manual and Operation Manual can be found at:
www.condair.com/residential . Please read all Cautions and Warnings before
installing and using the HumiLife Humidifier.
All electrical connections must be installed in accordance with local and
national electrical code requirements by a licensed electrician.
All water supply and drain line connections must be installed in accordance
with local plumbing codes by a licensed plumber.
Condair does not accept any liability for installations of humidity equipment
installed by unqualified personnel or the use of parts/components/equipment
that are not authorized or approved by Condair.
Compliance
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation.
If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the
following measures:
· Reorient or relocate the receiving antenna. · Increase the separation
between the equipment and receiver. · Connect the equipment into an outlet on
a circuit different from that to which the receiver is connected. · Consult
the dealer or an experienced radio/TV technician for help.
Warranty
Condair Inc. or Condair Ltd. (depending on the entity that supplied the
product, and hereinafter collectively referred to as CONDAIR) warrant for a
period of two years after installation or 30 months from the manufacturer’s
ship date, whichever date is earlier, that CONDAIR’s manufactured and
assembled products, not otherwise expressly warranted, are free from defects
in materials and workmanship. Notwithstanding the foregoing, the products
listed below have an alternate warranty period: · GSTC Series heat
exchanger(s) are warranted to be free from defects in materials and
workmanship for a period of 3 years
from installation or 40 months from the manufacturer’s ship date, whichever is
earlier. · SAM-e Short Absorption Manifolds, except for the coupling seals,
are warranted to be free from defects in materials and
workmanship for a total period of 10 years from the manufacturer’s ship date.
· Humilife RH humidifiers are warranted to be free from defects in materials
and workmanship for a period of 5 years from the
manufacturer’s ship date. CONDAIR may, at its discretion, replace individual
components or Humilife RH units as a whole. · Spare Parts used for repairs are
warranted for the balance of the term of the warranty on the original
humidifier or 90 days,
whichever is longer. · No warranty is made against corrosion, deterioration,
or suitability of substituted materials used as a result of compliance
with government regulations.
CONDAIR’s obligations and liabilities under this warranty are limited to
furnishing replacement parts to the customer, F.O.B. CONDAIR’s factory. The
replacement parts are warranted for the balance of the term of the warranty on
the original humidifier or 90 days, whichever is longer. Procedure: 1.
Customer Requests Warranty as per instructions on the CONDAIR Warranty Form.
2. CONDAIR reviews the warranty claim and will respond in one of two ways:
a. Warranty Accepted Replacement Part or credit granted. b. Warranty
Declined Response with justification will be provided to the customer. 3. In
some cases, CONDAIR may request the part to be returned, freight prepaid by
the customer, as part of the warranty acceptance or warranty determination
process. Some reasons include: a. Part must be analyzed to determine the root
cause of failure. b. Part must be returned to the supplier for
claim/investigation.
When parts are requested to be returned, replacement parts will be sent by
CONDAIR to the customer against an invoice from CONDAIR paid by the customer.
The cost of the replacement parts will be reimbursed to the customer with a
credit note after the parts are received and analyzed by CONDAIR, if the
warranty is accepted.
The warranties set forth herein are in lieu of all other warranties expressed
or implied by law. No liability whatsoever shall be attached to CONDAIR until
said products have been paid for in full and then said liability shall be
limited to the original purchase price for the product. Any further warranty,
with the exception of a purchased extended warranty described below, must be
in writing, and signed by an officer of CONDAIR.
CONDAIR makes no warranty and assumes no liability unless the equipment is
installed in strict accordance with the installation manual in effect at the
date of purchase, and by properly qualified and licensed professionals capable
of installing such equipment.
CONDAIR makes no warranty and assumes no liability whatsoever for
consequential damage or damage resulting directly from misapplication,
incorrect sizing, or lack of proper maintenance of the equipment.
CONDAIR makes no warranty and assumes no liability whatsoever for damage to
the products, humidifier, supply lines, drain lines, steam distribution
systems, or the building as a whole caused by freezing.
CONDAIR reserves the right to change the design, specifications, and
performance criteria of its products without notice or obligation.
Extended Warranty
Extended warranties are available to purchase under the conditions listed
above. Extended warranties must be purchased at the time of the original
equipment order.
www.condairparts.com
Buy authentic Condair parts factory direct.