LEDLux LL0167 WiFi Fan Coil Unit Thermostat Instruction Manual
- June 3, 2024
- LEDLUX
Table of Contents
LEDLux LL0167 WiFi Fan Coil Unit Thermostat
Search for “Smart RM” or “Smart Life” Download the Wifi App from Google Play or APP Store
| Turn on the thermostat, press and hold the key combination Activate
WIFI distribution network icon
---|---
Technical data
Voltage: AC 90 ~240V
Output:On/off type
Current: 3A
Display temperature range:0~70°C
Accuracy: ±0.5ºC
Work environment: -10~60°C
Setting range: 5ºC – 35ºC
SizeSize:86 * 86mm
Sensor:: NTC(10k)1%
Button
Program mode setting
Thermostat support set different time and different temperature Compatible with 5+2,6+1,7days
Program mode type
| Time section| Icon| Time (default)| Temperature(default)|
---|---|---|---|---|---
| Monday to Sunday| 1| | 06:00| 20°C
2| | 08:00| 15°C
3| | 17:30| 22°C
4| | 22:00| 15°C
| | | | |
Advanced Option
Turn off thermostat, long press 5S to enter advance d setting options, Short press to set next item , press ” or ” to set item data
Symbol | Item | Parameter | Default |
---|---|---|---|
A1 | Temperature |
Calibration
| -9-+9℃| -1℃
A2
|
Children Lock
| 0:half lock;(It is available to turn on/off and adjust temperature) 1:full lock|
0
A3
| Setting the lowest
limit temperature
| 5-15℃| 5℃
A4
| Setting the highest
limit temperature
| 16-50℃| 35℃
A5
| Fan energy saving
control
| 0: valve off, fan off
1: valve off, fan always on
| 0
A6| Programmable| 0=5+2
1=6+1
2=7 (everyday all the same)
| 0
A7| Choose valve output| 2:2pipe
4:4 pipe
| 4
A8| Choose sensor| N1: inner sensor
N2: external sensor
N3: Double sensor when choose N3,In the heating state, normally only valve is
opened, and the fan is turned on when the external temperature is detected to
be ≥X°C.
When the temperature is detected
| N1
| | to be lower than (X-2) °C, the fan is
turned off.
|
---|---|---|---
A9
| Set temperature for
external sensor
| 20-60°C| 38°C
AA| Standby bright| 0: off
1: weak bright
2: brighter
| 1
AB| Reset| Display Ao, press key until
whole show
| Ao
Cautions on Installation
- To prevent the thermostat display from a high fluctuation, special treatment has been made to the program. Therefore, it is normal that the thermostat cannot immediately display a sudden change of temperature.
- The thermostat installed on 1.5m above the ground.
- For the thermostat installed,please take care not to install it to the wall corner, door/window side or behind the door or in such unheated area as exterior wall. Avoid hot/ cold air duct, radiator, flue or thermal pipe
- When install the power supply, make sure that the power cable is well insulated.
- Don’t open the internal circuit board..
- HYAC series thermostat design for the standard 75x75x 35mm wall mount box installed. Follow the instructions to open the rear cover base, mount it on the wall and wire it.
- Before installing the thermostat, make sure that the system is disconnected. The maximum voltage of the system shall meet the requirements specified in the Instruction Manual (Max. AC Voltage: 250V).