First Co 12HYB4 High Performance Ceiling Fan Coils Owner’s Manual
- September 17, 2024
- First Co
Table of Contents
- First Co 12HYB4 High Performance Ceiling Fan Coils
- Product Information
- Product Usage Instructions
- FAQs
- HYB PSC MOTOR
- HYB DIMENSIONS
- PHYB PSC MOTOR
- PHYB DIMENSIONS
- BLOWER DATA
- COOLING DATA
- HEATING DATA
- VALVE CLUSTERS
- Accurate, Efficient, and Quiet Fan Coil Operation
- T200/T201 Thermostat Features
- GUIDE SPECIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
First Co 12HYB4 High Performance Ceiling Fan Coils
Product Information
- Model: HYB/PHYB
- Type: High Performance Ceiling Fan Coils
- CFM: 500 – 2000
- Motor: Multi-Speed 120V Motors – No Controls
Product Usage Instructions
Features
- Motor Type: PSC Motor
Blower Data (4-row coil)
Unit Model| HP| Amps*| Min. Ckt. Ampacity| Max. Ckt. Protection| CFM vs.
External Static Pressure| Blower Speed
---|---|---|---|---|---|---
FAQs
What is the difference between HYB and PHYB models?
The HYB model is hydronic, while the PHYB model is hydronic with a plenum.
How do I determine the correct blower speed for my desired CFM?
Refer to the CFM vs. External Static Pressure table in the manual and adjust the blower speed accordingly.
Can I use these ceiling fan coils without external controls?
Yes, these models come with multi-speed 120V motors but do not include external controls.
HYB PSC MOTOR
FEATURES
- Manual air vents
- 4-speed direct drive motors
- 1/2” copper tubing
- Primary and secondary condensate drains on one end
- 120/1/60Hz. motors (2)
- 3-row and 6-row models available
- Rubber isolation grommets
- Insulated and coated drain pan
HYB BLOWER DATA (4-row coil)
UNIT MODEL| __
HP
| __
**AMPS***
| MIN.
CKT. AMPACITY
| MAX.
CKT. PROTECTION
| CFM vs. EXTERNAL STATIC PRESSURE
BLOWER SPEED| 0.10| 0.20| 0.30| 0.40| 0.50|
0.60
| | | | | HIGH| 1595| 1510| 1410| 1310| 1180| 1010
12HYB4| 1/5| 5.2| 7| 15| MED. HI MED. LOW| 1310
1010
| 1250
980
| 1190
940
| 1100
860
| 1000
760
| 850
640
| | | | | LOW| 690| 640| 580| 510| 440| 340
| | | | | HIGH| 1820| 1740| 1660| 1560| 1440| 1300
16HYB4| 1/5| 5.2| 7| 15| MED. HI MED. LOW| 1420
1060
| 1380
1020
| 1320
960
| 1260
900
| 1160
800
| 1040
700
| | | | | LOW| 720| 660| 580| 500| 400| 260
| | | | | HIGH| 2510| 2230| 2260| 2120| 1960| 1760
20HYB4| 1/4| 8.8| 12| 15| MED. HI MED. LOW| 2040
1580
| 2040
1580
| 1960
1540
| 1850
1480
| 1720
1380
| 1540
1180
| | | | | LOW| 1200| 1190| 1160| 1100| 1010| 880
- 120V-1PH-60HZ
- Amps is total for (2) motors
- 3-row coil – deduct 0.05 to ESP shown
- 6-row coil – add 0.10 from ESP shown
HYB DIMENSIONS
NOTES:
- ALL DIMENSIONS IN INCHES.
- COIL CONNECTION TOLERANCE ± 1/4”.
- RIGHT-HAND UNIT SHOWN, LEFT-HAND MIRROR IMAGE.
SHIPPING WEIGHTS
MODEL| WEIGHT (lbs.)
12HYB| 105
16HYB| 150
20HYB| 160
GENERAL DIMENSIONS
MODEL| A| B| C| D
12HYB| 41| 32-1/2| 28| 31-1/4
16HYB| 51| 42-1/2| 38| 41-1/4
20HYB| 60| 51-1/2| 47| 50-1/4
HYB PIPE LOCATIONS
RIGHT HAND| X1| Y1| X2| X3| Y3| Y4
3 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
4 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
6 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
3/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 5-7/16| 9-11/16
3/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
HYB PIPE LOCATIONS
LEFT HAND| X1| Y1| X2| X3| Y3| Y4
3 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
4 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
6 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
3/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 5-7/16| 8-7/16
3/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
PHYB PSC MOTOR
FEATURES
- Manual air vents
- 4-speed direct drive motors
- 1/2” copper tubing
- Primary and secondary condensate drains on one end
- Return air plenum – field convertible from end return to bottom return
- Throw away filter
- 120/1/60Hz. motors (2)
- 3-row and 6-row models available
- Rubber isolation grommets
PHYB BLOWER DATA (4-row coil)
UNIT MODEL| __
HP
| __
**AMPS***
| MIN. CKT.
AMPACITY
| MAX. CKT.
PROTECTION
| CFM vs. EXTERNAL STATIC PRESSURE
BLOWER SPEED| 0.10| 0.20| 0.30| 0.40| 0.50|
0.60
| | | | | HIGH| 1400| 1320| 1220| 1110| 980| 820
12PHYB4| 1/5| 5.2| 7| 15| MED. HI MED. LOW| 1220
980
| 1150
930
| 1080
860
| 980
790
| 860
680
| 710
560
| | | | | LOW| 600| 600| 550| 490| 420| 340
| | | | | HIGH| 1700| 1620| 1520| 1420| 1290| 1130
16PHYB4| 1/5| 5.2| 7| 15| MED. HI MED. LOW| 1370
1030
| 1320
980
| 1260
920
| 1180
850
| 1060
760
| 910
640
| | | | | LOW| 690| 630| 560| 480| 380| 230
| | | | | HIGH| 2160| 2160| 2020| 1880| 1720| 1520
20PHYB4| 1/4| 8.8| 12| 15| MED. HI MED. LOW| 2000
1570
| 1900
1520
| 1800
1470
| 1680
1380
| 1520
1230
| 1310
1000
| | | | | LOW| 1170| 1140| 1100| 1040| 940| 800
- 120V-1PH-60HZ
- Amps is total for (2) motors
- 3-row coil – deduct 0.05 to ESP shown
- 6-row coil – add 0.10 from ESP shown
PHYB DIMENSIONS
NOTES:
- ALL DIMENSIONS IN INCHES.
- COIL CONNECTION TOLERANCE ± 1/4”.
- RIGHT-HAND UNIT SHOWN, LEFT-HAND MIRROR IMAGE.
SHIPPING WEIGHTS
MODEL| WEIGHT (lbs.)
12PHYB| 125
16PHYB| 170
20PHYB| 180
GENERAL DIMENSIONS
MODEL| A| B| C| D| E| F| FILTER
SIZE
12PHYB| 41| 32-
1/2
| 28| 31-1/4| 28-1/4| 28| 14 x 28 x 1
16PHYB| 51| 42-
1/2
| 38| 41-1/4| 38-1/4| 38| 14 x 38 x 1
20PHYB| 60| 51-
1/2
| 47| 50-1/4| 47-1/4| 47| 14 x 47 x 1
PHYB PIPE LOCATIONS
RIGHT HAND| X1| Y1| X2| X3| Y3| Y4
3 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
4 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
6 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
3/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 5-7/16| 9-11/16
3/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
PHYB PIPE LOCATIONS
LEFT HAND| X1| Y1| X2| X3| Y3| Y4
3 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
4 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
6 ROW| 5-1/4| 7-9/16| 8-1/4| – – –| – – –| – – –
3/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 5-7/16| 8-7/16
3/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/1 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
4/2 ROW| 5-1/4| 7-9/16| 8-1/4| 13-1/4| 6-1/16| 9-1/16
BLOWER DATA
HYB/PHYB 12 ECM BLOWER DATA
Coil| Voltage| Motor Speed| FLA| Max. Breaker|
0| 0.1| 0.2| 0.3| 0.4| 0.5
---|---|---|---|---|---|---|---|---|---|---
__
__
__
__
__
3 Row
| __
120V
| High| __
9.6
| __
15
| 1400| 1330| 1310| 1240| 1190| 1100
Med.| 1110| 1040| 990| 930| 860| 800
Low| 890| 780| 690| 600| 530| 460
__
230V
| High| __
5.6
| __
15
| 1370| 1310| 1270| 1230| 1190| 1140
Med.| 1090| 1040| 990| 930| 860| 800
Low| 840| 770| 700| 620| 530| 460
__
265V
| High| __
5.2
| __
15
| 1400| 1330| 1270| 1230| 1180| 1120
Med.| 1140| 1070| 1000| 930| 880| 820
Low| 900| 790| 710| 640| 550| 460
__
__
__
__
__
4 Row
| __
120V
| High| __
9.6
| __
15
| 1320| 1290| 1250| 1190| 1150| 1090
Med.| 1070| 1010| 940| 890| 840| 760
Low| 830| 750| 680| 600| 510| 470
__
230V
| High| __
5.6
| __
15
| 1350| 1300| 1250| 1210| 1150| 1110
Med.| 1080| 1020| 950| 890| 840| 770
Low| 830| 760| 670| 600| 510| 450
__
265V
| High| __
5.2
| __
15
| 1330| 1280| 1240| 1190| 1140| 1090
Med.| 1090| 1030| 960| 890| 840| 780
Low| 830| 760| 690| 620| 520| 440
__
__
__
__
__
5 Row
| __
120V
| High| __
9.6
| __
15
| 1330| 1270| 1240| 1190| 1140| 1050
Med.| 1040| 970| 930| 860| 830| 740
Low| 790| 720| 650| 570| 510| 430
__
230V
| High| __
5.6
| __
15
| 1310| 1260| 1220| 1160| 1120| 1080
Med.| 1030| 980| 930| 870| 790| 740
Low| 790| 720| 640| 570| 500| 440
__
265V
| High| __
5.2
| __
15
| 1300| 1260| 1220| 1170| 1110| 1030
Med.| 1070| 1000| 940| 890| 830| 750
Low| 810| 730| 680| 580| 500| 440
__
__
__
__
__
6 Row
| __
120V
| High| __
9.6
| __
15
| 1310| 1260| 1210| 1170| 1110| 1030
Med.| 1020| 980| 920| 850| 800| 720
Low| 780| 720| 630| 560| 490| 420
__
230V
| High| __
5.6
| __
15
| 1300| 1250| 1210| 1160| 1120| 1070
Med.| 1030| 970| 910| 860| 800| 740
Low| 790| 720| 650| 570| 500| 430
__
265V
| High| __
5.2
| __
15
| 1300| 1260| 1210| 1160| 1110| 1030
Med.| 1060| 1000| 930| 880| 820| 750
Low| 800| 740| 670| 580| 500| 430
Amps based on 2 -1/3HP motors per unit
HYB/PHYB 16 ECM BLOWER DATA
Coil| Voltage| Motor Speed| FLA| Max. Breaker|
0| 0.1| 0.2| 0.3| 0.4| 0.5
---|---|---|---|---|---|---|---|---|---|---
__
__
__
__
__
3 Row
| __
120V
| High| __
9.6
| __
15
| 1760| 1720| 1650| 1610| 1540| 1480
Med. Low| 1440| 1410| 1340| 1280| 1230| 1150
Low| 1210| 1160| 1060| 1000| 910| 860
__
230V
| High| __
5.6
| __
15
| 1780| 1730| 1670| 1610| 1550| 1500
Med. Low| 1500| 1440| 1380| 1310| 1250| 1190
Low| 1260| 1180| 1100| 1020| 940| 860
__
265V
| High| __
5.2
| __
15
| 1770| 1700| 1650| 1600| 1540| 1470
Med. Low| 1510| 1430| 1370| 1300| 1230| 1170
Low| 1260| 1180| 1090| 1010| 930| 860
__
__
__
__
__
4 Row
| __
120V
| High| __
9.6
| __
15
| 1760| 1700| 1650| 1600| 1550| 1490
Med. Low| 1470| 1420| 1350| 1290| 1230| 1170
Low| 1200| 1130| 1070| 1010| 930| 870
__
230V
| High| __
5.6
| __
15
| 1750| 1710| 1640| 1600| 1540| 1490
Med. Low| 1490| 1430| 1370| 1300| 1250| 1190
Low| 1240| 1170| 1090| 1010| 940| 860
__
265V
| High| __
5.2
| __
15
| 1750| 1700| 1650| 1590| 1550| 1480
Med. Low| 1480| 1420| 1370| 1300| 1230| 1180
Low| 1250| 1160| 1090| 1010| 950| 870
__
__
__
__
__
5 Row
| __
120V
| High| __
9.6
| __
15
| 1700| 1640| 1600| 1550| 1500| 1450
Med. Low| 1420| 1370| 1300| 1240| 1190| 1140
Low| 1170| 1100| 1030| 980| 890| 820
__
230V
| High| __
5.6
| __
15
| 1710| 1660| 1610| 1570| 1510| 1460
Med. Low| 1450| 1390| 1330| 1270| 1220| 1170
Low| 1210| 1120| 1060| 990| 920| 840
__
265V
| High| __
5.2
| __
15
| 1700| 1640| 1590| 1540| 1490| 1440
Med. Low| 1430| 1370| 1320| 1260| 1200| 1140
Low| 1210| 1120| 1040| 980| 910| 820
__
__
__
__
__
6 Row
| __
120V
| High| __
9.6
| __
15
| 1680| 1630| 1570| 1540| 1470| 1420
Med. Low| 1390| 1350| 1290| 1250| 1180| 1130
Low| 1150| 1080| 1020| 960| 890| 810
__
230V
| High| __
5.6
| __
15
| 1680| 1630| 1580| 1530| 1490| 1430
Med. Low| 1420| 1360| 1320| 1260| 1200| 1130
Low| 1180| 1110| 1040| 970| 910| 830
__
265V
| High| __
5.2
| __
15
| 1670| 1620| 1560| 1520| 1480| 1420
Med. Low| 1420| 1360| 1300| 1240| 1190| 1140
Low| 1180| 1100| 1030| 980| 910| 830
Amps based on 2 -1/3HP motors per unit
HYB/PHYB 20 ECM BLOWER DATA
Coil| Voltage| Motor Speed| FLA| Max. Breaker|
0| 0.1| 0.2| 0.3| 0.4| 0.5
---|---|---|---|---|---|---|---|---|---|---
__
__
__
__
__
3 Row
| __
120V
| High| __
9.6
| __
15
| 2200| 2140| 2080| 2020| 1970| 1900
Med.| 1830| 1760| 1700| 1640| 1560| 1480
Low| 1600| 1390| 1320| 1260| 1150| 1070
__
230V
| High| __
5.6
| __
15
| 2130| 2070| 2030| 1950| 1900| 1820
Med.| 1770| 1690| 1630| 1540| 1470| 1390
Low| 1460| 1310| 1220| 1140| 1040| 950
__
265V
| High| __
5.2
| __
15
| 2160| 2100| 2040| 1970| 1910| 1850
Med.| 1790| 1710| 1640| 1560| 1480| 1400
Low| 1570| 1360| 1260| 1160| 1050| 970
__
__
__
__
__
4 Row
| __
120V
| High| __
9.6
| __
15
| 2100| 2040| 1990| 1930| 1880| 1810
Med.| 1750| 1670| 1620| 1550| 1480| 1420
Low| 1430| 1340| 1250| 1190| 1110| 1000
__
230V
| High| __
5.6
| __
15
| 2180| 2100| 2040| 1990| 1930| 1860
Med.| 1790| 1710| 1640| 1570| 1490| 1420
Low| 1420| 1330| 1240| 1150| 1060| 970
__
265V
| High| __
5.2
| __
15
| 2170| 2110| 2040| 1980| 1920| 1850
Med.| 1790| 1710| 1650| 1570| 1500| 1420
Low| 1480| 1350| 1250| 1170| 1060| 970
__
__
__
__
5 Row (4/1 – 4 pipe)
| __
120V
| High| __
9.6
| __
15
| 2140| 2070| 2010| 1960| 1900| 1840
Med.| 1770| 1690| 1640| 1570| 1500| 1450
Low| 1460| 1370| 1270| 1210| 1120| 1030
__
230V
| High| __
5.6
| __
15
| 2100| 2040| 1970| 1910| 1860| 1800
Med.| 1730| 1650| 1580| 1510| 1440| 1370
Low| 1370| 1280| 1190| 1110| 1020| 930
__
265V
| High| __
5.2
| __
15
| 2110| 2050| 2000| 1930| 1870| 1810
Med.| 1760| 1670| 1610| 1530| 1460| 1390
Low| 1440| 1310| 1230| 1140| 1040| 970
__
__
__
__
__
6 Row
| __
120V
| High| __
9.6
| __
15
| 2070| 2000| 1950| 1890| 1830| 1730
Med.| 1710| 1650| 1590| 1520| 1460| 1390
Low| 1400| 1310| 1250| 1170| 1100| 990
__
230V
| High| __
5.6
| __
15
| 2050| 1990| 1930| 1870| 1810| 1750
Med.| 1680| 1600| 1530| 1490| 1400| 1340
Low| 1330| 1250| 1170| 1090| 990| 900
__
265V
| High| __
5.2
| __
15
| 2010| 1950| 1890| 1840| 1790| 1700
Med.| 1650| 1580| 1510| 1450| 1390| 1320
Low| 1330| 1240| 1160| 1080| 980| 910
Amps based on 2 -1/3HP motors per unit
COOLING DATA
HYB/PHYB-3
(3-Row Coil) All capacities are based on nominal CFM.
COOLING CAPACITY (1000 BTUH)
MODEL (CFM)
| 45° ENTERING WATER| 42° ENTERING WATER
GPM
|
P.D. (FT. WTR.)
| o 80o DB
67 WB
| o 75o DB
63 WB
|
GPM
|
P.D. (FT. WTR.)
| o 80o DB
67 WB
| o 75o DB
63 WB
TH| SH| TR| TH| SH| TR| TH| SH|
TR| TH| SH| TR
12HYB-3 (1200)| 5
7
9
| 2.6
4.7
7.4
| 30.1
34.5
37.3
| 24.2
25.8
26.9
| 12.0
10.0
8.3
| 23.0
26.4
28.5
| 21.4
22.7
23.5
| 9.2
7.5
6.3
| 6
8
10
| 3.6
6.0
9.0
| 35.5
39.3
41.7
| 26.2
27.6
28.5
| 11.8
9.8
8.3
| 27.1
30.0
31.8
| 23.0
24.1
24.8
| 9.0
7.5
6.4
16HYB-3 (1600)| 6
9
12
| 1.8
3.7
6.3
| 37.6
44.9
49.4
| 31.4
34.1
35.8
| 12.5
10.0
8.2
| 32.5
34.3
37.8
| 32.5
30.0
31.3
| 10.8
7.6
6.3
| 7
10
13
| 2.4
4.5
7.3
| 44.1
50.9
55.1
| 33.8
36.3
37.9
| 12.6
10.2
8.5
| 33.7
38.9
42.1
| 29.8
31.8
33.0
| 9.6
7.8
6.5
20HYB-3 (2000)| 8
11
14
| 2.1
3.8
5.9
| 54.8
57.7
59.7
| 39.5
42.1
43.9
| 11.9
10.0
8.5
| 35.0
41.9
45.6
| 35.0
37.1
38.5
| 8.5
7.6
6.5
| 10
13
16
| 3.2
5.2
7.6
| 57.5
63.5
67.7
| 43.1
45.3
46.9
| 11.5
9.8
8.5
| 43.9
48.5
51.7
| 37.9
39.6
40.9
| 8.8
7.5
6.5
HYB/PHYB-4
(4-Row Coil) All capacities are based on nominal CFM.
COOLING CAPACITY (1000 BTUH)
MODEL (CFM)
| 45° ENTERING WATER| 42° ENTERING WATER
GPM
|
P.D. (FT. WTR.)
| o 80o DB
67 WB
| o 75o DB
63 WB
|
GPM
|
P.D. (FT. WTR.)
| o 80o DB
67 WB
| o 75o DB
63 WB
TH| SH| TR| TH| SH| TR| TH| SH|
TR| TH| SH| TR
12HYB-4 (1200)| 6.5
8.5
11.5
| 5.2
8.5
14.7
| 39.3
42.9
45.9
| 29.5
30.8
32.0
| 12.1
10.1
8.0
| 30.0
32.8
35.1
| 25.8
26.9
27.8
| 9.2
7.7
6.1
| 7.5
9.5
13.0
| 6.7
10.4
18.4
| 45.0
48.2
51.0
| 31.7
32.9
34.0
| 12.0
10.1
8.0
| 34.4
36.8
39.0
| 57.6
28.5
29.4
| 9.2
7.7
6.0
16HYB-4 (1600)| 8.5
11.5
15.0
| 4.2
7.3
11.8
| 51.3
57.0
61.0
| 38.9
41.1
42.6
| 12.1
9.9
8.1
| 39.2
43.5
46.6
| 34.1
35.9
37.1
| 9.2
7.6
6.2
| 10.0
13.0
17.0
| 5.6
9.1
14.9
| 59.4
64.3
68.0
| 41.9
43.9
45.3
| 11.9
9.9
8.0
| 45.4
49.1
51.9
| 36.6
38.1
39.2
| 9.1
7.6
6.1
20HYB-4 (2000)| 10.5
14.0
19.0
| 4.6
7.7
13.4
| 62.8
69.8
75.7
| 48.1
50.7
23.0
| 12.0
10.0
8.0
| 48.0
53.3
57.8
| 42.3
44.4
46.1
| 9.1
7.7
6.1
| 12.0
16.0
21.0
| 5.9
9.8
16.0
| 72.1
79.1
84.1
| 51.7
54.3
56.3
| 12.0
9.9
8.0
| 55.1
60.4
64.3
| 45.1
47.2
48.7
| 9.2
7.6
6.1
HYB/PHYB-6
(6-Row Coil) All capacities are based on nominal CFM.
COOLING CAPACITY (1000 BTUH)
MODEL (CFM)
| 45° ENTERING WATER| 42° ENTERING WATER
GPM
|
P.D. (FT. WTR.)
| o 80o DB
67 WB
| o 75o DB
63 WB
|
GPM
|
P.D. (FT. WTR.)
| o 80o DB
67 WB
| o 75o DB
63 WB
TH| SH| TR| TH| SH| TR| TH| SH|
TR| TH| SH| TR
12HYB-6 (1200)| 8.0
10.0
13.0
| 10.2
15.3
24.6
| 48.0
50.9
53.3
| 33.0
34.1
35.1
| 12.0
10.2
8.2
| 36.7
38.9
40.7
| 28.6
29.5
30.3
| 9.2
7.8
6.3
| 9.0
11.5
14.5
| 12.6
19.1
30.1
| 54.1
57.0
59.0
| 35.4
36.6
37.4
| 12.0
9.9
8.1
| 41.3
43.6
45.1
| 30.5
31.4
32.1
| 9.2
7.6
6.2
16HYB-6 (1600)| 10.5
13.5
18.0
| 7.3
11.4
19.2
| 63.0
67.7
71.6
| 43.6
45.0
47.0
| 12.0
10.0
8.0
| 48.1
51.7
54.7
| 37.9
39.3
40.5
| 9.2
7.7
6.1
| 12.0
15.0
20.0
| 9.2
13.8
23.2
| 71.6
75.6
79.2
| 47.0
48.6
50.1
| 11.9
10.1
7.9
| 54.7
57.7
60.5
| 40.5
41.8
42.9
| 9.1
7.7
6.0
20HYB-6 (2000)| 12.0
17.0
22.0
| 9.1
14.9
23.8
| 77.5
83.9
88.6
| 54.0
56.5
58.4
| 11.9
9.9
8.1
| 59.2
64.1
67.6
| 46.9
48.9
50.4
| 9.1
7.5
6.1
| 14.5
19.0
24.5
| 11.1
18.2
29.0
| 87.5
93.9
98.1
| 58.0
60.5
62.3
| 12.1
9.9
8.0
| 66.8
71.7
74.9
| 50.0
52.0
53.4
| 9.2
7.5
6.1
HEATING DATA
HYB/PHYB-3
3-Row Coil / 2-Pipe
HEATING CAPACITY (1000 BTUH)
MODEL (CFM)
|
GPM
| P.D.
(FT.
WTR.)
| ENTERING WATER TEMP.
180oF| 160oF| 140oF| 120oF
12HYB-3 (1200)| 7
10
13
| 4.7
9.0
14.4
| 96
100
101
| 78
82
83
| 61
63
64
| 43
45
46
16HYB-3 (1600)| 10
13
15
| 4.5
7.3
9.5
| 129
133
135
| 105
109
110
| 82
85
86
| 59
60
61
20HYB-3 (2000)| 12
16
20
| 4.5
7.6
11.5
| 159
165
168
| 130
135
137
| 101
105
107
| 72
75
76
HYB/PHYB-4
4-Row Coil / 2-Pipe
HEATING CAPACITY (1000 BTUH)
MODEL (CFM)
|
GPM
| P.D.
(FT.
WTR.)
| ENTERING WATER TEMP.
180oF| 160oF| 140oF| 120oF
12HYB-4 (1200)| 6
8
10
| 4.5
7.6
15.9
| 107
111
115
| 88
91
94
| 68
71
73
| 49
50
52
16HYB-4 (1600)| 8
12
15
| 3.7
7.9
11.8
| 142
150
153
| 116
123
125
| 90
95
97
| 64
68
70
20HYB-4 (2000)| 10
14
18
| 4.2
7.7
12.2
| 176
185
190
| 144
151
155
| 112
118
121
| 80
84
86
HYB/PHYB-6
6-Row Coil/2-Pipe
HEATING CAPACITY (1000 BTUH)
MODEL (CFM)
|
GPM
| P.D.
(FT.
WTR.)
| ENTERING WATER TEMP.
180oF| 160oF| 140oF| 120oF
12HYB-6 (1200)| 8
10
14
| 10.2
15.3
28.2
| 124
127
130
| 101
104
106
| 79
81
83
| 56
58
59
16HYB-6 (1600)| 10
14
18
| 6.7
12.2
19.2
| 165
171
174
| 135
140
142
| 105
109
111
| 75
78
79
20HYB-6 (2000)| 12
17
22
| 7.9
14.9
23.8
| 203
212
216
| 166
173
177
| 129
135
137
| 92
96
98
HYB/PHYB-1
1-Row Coil / 4-Pipe
HEATING CAPACITY (1000 BTUH)
MODEL (CFM)
|
GPM
| P.D.
(FT.
WTR.)
| ENTERING WATER TEMP.
180oF| 160oF| 140oF| 120oF
12HYB (1200)| 1.0
2.5
4.0
| 1.8
8.7
19.8
| 30
39
42
| 24
32
34
| 19
25
27
| 14
18
19
16HYB (1600)| 1.0
2.5
4.0
| 2.5
11.8
26.1
| 38
49
54
| 31
40
44
| 24
31
34
| 17
22
24
20HYB (2000)| 1.0
2.5
4.0
| 3.1
14.6
32.4
| 45
58
65
| 37
47
53
| 29
37
41
| 20
26
30
HYB/PHYB-2
2-Row Coil / 4-Pipe
HEATING CAPACITY (1000 BTUH)
MODEL (CFM)
|
GPM
| P.D.
(FT.
WTR.)
| ENTERING WATER TEMP.
180oF| 160oF| 140oF| 120oF
12HYB (1200)| 4
8
12
| 1.5
5.2
11.0
| 69
77
80
| 56
63
65
| 44
49
51
| 31
35
36
16HYB (1600)| 8
12
16
| 2.7
5.5
9.3
| 99
105
108
| 81
86
88
| 63
67
69
| 45
48
49
20HYB (2000)| 12
16
20
| 4.1
6.7
10.0
| 126
131
134
| 103
107
110
| 80
83
85
| 57
60
61
CFM FACTORS
% NOMINAL CFM| TOTAL COOLING| SENSIBLE COOLING|
HEATING
50| 0.68| 0.60| 0.58
75| 0.85| 0.81| 0.81
100| 1.00| 1.00| 1.00
125| 1.12| 1.17| 1.16
150| 1.21| 1.33| 1.18
NOTES:
- Ratings at 70 degrees entering air temp.
- Contact the factory for capacities at other conditions
VALVE CLUSTERS
FIELD INSTALLED
| Assembled Valve Clusters: (factory-assembled and field installed)
Components are factory piped together (order power heads separately).
Contact the factory for other valve clusters.
---|---
Right Hand| Left Hand| Description (all 3/4″) – For HYB, PHYB
| 9VBR2BV| 9VBL2BV| 2-pipe, 2-hand valves only
| 9VBR2BC| 9VBL2BC| 2-pipe, 1 hand valve and circuit setters
| 9VBR22B| 9VBL22B| 2-pipe, one 2-way valve body, and 2 hand valves
2
pipe
| 9VBR22C
9VBR23B
9VBR23D
| 9VBL22C
9VBL23B
9VBL23D
| 2-pipe, one 2-way valve body, 1 hand valve and circuit setter 2-pipe, one 3-way valve body and 2 hand valves
2-pipe, one 3-way valve body, 2 hand valves and aquastat
| 9VBR23C| 9VBL23C| 2-pipe, one 3-way valve body, 1 hand valve, and
circuit setter
| 9VBR23BC| 9VBL23BC| 2-pipe, one 3-way valve body, and 3 hand valves
| 9VBR23DC| 9VBL23DC| 2-pipe, one 3-way valve body, 3 hand valves, and
aquastat
| 9VBR4BV| 9VBL4BV| 4-pipe, 4-hand valves only
4
pipe
| 9VBR42B
9VBL42C
9VBR43B
| 9VBL42B
9VBL42C
9VBL43B
| 4-pipe, two 2-way valve bodies, and 4 hand valves
4-pipe, two 2-way valve bodies, 2 hand valves, and 2 circuit setters 4-pipe, two 3-way valve bodies and 4 hand valves
| 9VBR43BC| 9VBL43BC| 4-pipe, two 3-way valve bodies, and 6 hand valves
| Power Heads: (two power heads required for 4-pipe) – For all units
E50131180| 24V
E50132180| 110V/50Hz – 120V/60 Hz
E50137180| 277V
E50138180| 220V/50 Hz – 230V/60 Hz
Separate Valve Bodies: (order power heads separately)
E421317| 3/4″ 2-way – For HYB, PHYB
E431317| 3/4″ 3-way – For HYB, PHYB
Hand Valves: (Combination balance/shut-off) (2 usually req’d per coil)
CP90| 3/4″
Circuit setters and Strainers
CP6011| 3/4″ Circuit setter (Taco)
CP6031| 3/4″ Strainer (Kitz)
945-8| Disconnect (120V)
Autospeed 24V TM Thermostats
(Part #’s T200/T201)
Accurate, Efficient, and Quiet Fan Coil Operation
The new Autospeed 24V™ thermostat (parts # T200 and T201) provides 24V AC single-stage temperature control of 2-pipe and 4-pipe fan coil applications. The T200/T201 thermostat offers maximum comfort and efficiency by automatically selecting the appropriate High, Medium, or Low fan speed, depending on room temperature and thermostat temperature setting. This automatic fan speed control not only brings the room temperature to the desired set point quickly, but it also maintains the room temperature with the most efficient fan speed selection. Once the desired room temperature is achieved the fan coil operates on low speed for extremely quiet operation. The fan coil control board (which is factory-installed in all CW units) is a circuit board that provides control of a 3-speed line voltage fan motor. The control board allows the thermostat to control the fan motor even though, by itself, the thermostat does not have the amperage capability nor the voltage rating capability to control the fan motor.
T200/T201 Thermostat Features
- Compatible with 2-pipe and 4-pipe fan coils:
- Series HBC/PHBC/RHBC/CHBC,
- MB/MB-HW, HYB/PHYB, and CW/CW-HW
- Cycle fan or continuous fan operation
- T200-Manual Heat / Cool changeover switch
- T201-Automatic Heat / Cool changeover switch
- Large LED digital display
- Allows less expensive 24V control wiring from the fan coil to the thermostat, rather than larger, more expensive line voltage wiring.
- 3-speed fan operation, with speed indicator lights
- Fan speed determination:
- If the room temperature is 4 degrees (F.) of the thermostat set point, the fan will operate at High speed.
- If 3 degrees offset point, the fan will operate at Medium speed.
- If within 2 degrees of set point, the fan will operate at Low speed.
- One or 3-hour Auto override – Fan speed defaults to “Auto” mode after 1 hour if the user manually changes it to a particular fan speed.
- Temperature set range: 64-88 degrees F.
- Adjustable high and low-temperature set points
- Selectable Fahrenheit / Centigrade display
- The power switch turns the system off/on
- Requires 7-wire 24V thermostat wire
- No batteries required
- Set points are permanently retained in memory in case of power interruption
- Simple operation
- Mercury Free
- Wall plate included
DISPLAY CODES
DISPLAY| STEADY| FLASHING
P1| Auto fan timer – 1 hour (default)| Auto fan timer – 3 hour
P2| Continuous fan (default)| Cycled fan
P3| oF (default)| oC
P4| Cycled fan standard| Cycled fan overdrive (default)
P5| Low temp limit 64 oF (default)| Low temp limit 67 oF
P6| Hi-temp limit 88 oF (default)| Hi-temp limit 84 oF
GUIDE SPECIFICATIONS
Furnish and install First Co. horizontal fan coils as indicated on the plans and specifications. Types, sizes, and performance shall be as indicated in the schedule.
-
Basic Unit
- All units shall be manufactured with heavy gauge galvanized steel to resist corrosion.
- All piping, drain, and wiring connections shall be readily accessible. Mounting holes with rubber grommets shall be provided to save installation time and expense.
-
Electrical Box
The unit shall have an electrical box providing a single location for line voltage field wiring connections. -
Coils
Coils shall have high-efficiency aluminum fins with mechanically expanded 1/2″ O.D. copper tubes. All coils shall have a manual air vent. Coil performance shall be as indicated in the schedule. -
Fan Assembly
Fans shall be centrifugal, forward curved, and dynamically balanced for smooth, quiet operation. Fan housings shall be fabricated of heavy gauge galvanized steel and be easily removed, thus allowing complete service access to the fans and motors. -
Motors
All units shall have (120/1/60) (220/1/50) four-speed motors with permanently lubricated sleeve bearings, permanent split capacitor, inherent thermal overload protection with automatic reset, and resilient rubber motor mounts. -
Drain Pan
Drain pans shall be insulated to prevent sweating. Drain pans shall be coated to reduce corrosion. Threaded primary and secondary drain connections shall be factory-installed. -
Return Plenum/Filter
All PHYB models shall have factory-installed return air plenums. These plenums shall be capable of being field converted from end return to bottom return. One-inch throwaway filters shall be installed within the plenums.
FIRST CO.
P.O. BOX 270969 – DALLAS, TEXAS 75227 PH.
214-388-5751 | FAX
214-388-2255
WWW.FIRSTCO.COM.
JUNE 2024