first Co SHW SERIES Hydronic 2-20 Tons Horizontal Chilled Water Instruction Manual

October 29, 2023
First Co

SHW SERIES Hydronic 2-20 Tons
Instruction Manualfirst Co SHW SERIES Hydronic 2 20 Tons Horizontal
Chilled Water - Figure 1

SHW SERIES Hydronic 2-20 Tons Horizontal Chilled Water

All motors are factory installed
Sloped and insulated drain pan
Galvanized steel cabinet
Insulation meets IAQ standards
Manual air vents
Hanger brackets (2 – 5 ton only)
Adjustable pulleys
Various motor options
Factory installed filters

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - logo
2www.ahridirectory.org
Unitary Small AC AHRI Standard 210/240
Certification applies only when the complete system is listed with AHRI.

First Co. commercial – duty SHW chilled or hot water blower coil units are designed for installation within the conditioned area or as remote units with duct systems.

SHW SERIES

First Co. commercial – duty SHW chilled or hot water blower coil units are designed for installation within the conditioned area or as remote units with duct systems. Standard 4 row coils can be used for cooling or heating. These air handlers are compact, with large removable panels for installation and ease of service. Separate filter panels are provided on both sides of unit. Optional accessories include 6 row cooling coils, hot water coils, various motor options, mixing boxes, motor starters, and discharge plenums. All models feature positive slope drain pans. Standard models are available in 8 popular sizes 800 through 8000 nominal CFM (2 through 20 tons). All standard models are ETL listed and rated in accordance with ARI Standard 430.
CABINET –
Fabricated of heavy gauge galvanized steel. Seismic resistant mounting brackets are standard on 2-5 ton models.
BLOWER –
Resiliently mounted, heavy duty, double inlet, forward curved blade, centrifugal type. Each wheel is dynamically balanced for smooth, quiet operation. All blowers are belt driven with field adjustable pulleys to permit variations in static pressure and air requirements. All blowers have ball bearings.
COILS –
Fabricated of 3/8” or 1/2” OD seamless copper tubes mechanically expanded to highly efficient aluminum fins to maximize heat transfer. All coils have manual air vents. All models have positive slope drain pans.
INSULATION
The entire interior of the cabinet is insulated with one (1) inch insulation.
FILTER –
One inch throw away filters are provided as standard in all 2 – 5 ton units. One inch permanent filters are provided as standard in all 7-1/2 – 20 ton units.
Filters can be changed without tools. Space available for 2”.
FACTORY WIRED –
All standard motors are field or factory installed and wired at voltage specified by customer. (If not specified, multi-voltage motors will be wired at highest voltage)
MOTOR –
Standard motor is 1725 RPM. The adjustable motor mount permits easy belt adjustment. A variable pitch pulley allows balancing of the system to the desired CFM. Standard motors have internal overload protection. Therefore, units shipped with standard motors will be ETL listed. Most non-standard motors (i.e. 575V, 2-speed, TEFC, some 50 Hz., etc.) are not available with internal overload protection. Therefore, most units shipped with non-standard motors can be ETL listed with the addition of a factory installed motor starter (contact the factory for starter information and ETL verification.)
MISCELLANEOUS –
Slotted mounting rails for easy installation (2 -5 ton SHW only). Rails are turned down 1/2” on each end for safer and easier installation.

  • 4 x 4 junction box accepts a field installed (24/120V) relay / transformer for low voltage control.

  • 3/4 inch NPT drain connections on both sides of cabinet.

  • Header connections on the right side as standard.
    Knockouts are provided for conversion to the left side. (Looking with air flow).

  • Drain pans are coated for corrosion protection.

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled
Water

Options:
Contact the factory

  1. 6 row cooling coil instead of standard 4 row coil (factory installed only).
  2. Stainless steel drain pan.
  3. Motor starters.
  4. Hot water coil can be field or factory installed in either the reheat or pre-heat position (reheat is standard).
    PART NUMBER| FOR UNIT MODEL| MANIFOLD CONNECTIONS
    ---|---|---
    24HWK| 24SHW/SVW| 7/8” OD
    36HWK| 36SHW/SVW
    48HWK| 48SHW/SVW
    60HWK| 60SHW/SVW
    90HWK| 90SHW/SVW| 1-1/8” OD
    120HWK| 120SHW/SVW| 1-3/8” OD
    180HWK| 180SHW/SVW
    240HWK| 230SHW/SVW

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
2

  1. Discharge plenum with four way double – deflection grille (field installed)
    PART NUMBER| FOR UNIT MODEL| DEPTH (1)
    ---|---|---
    24DP| 24SHW| 6”
    36DP| 36SHW
    48DP| 48SHW
    60DP| 60SHW
    90DP| 90SHW
    120DP| 120SHW
    180DP| 180SHW
    240DP| 230SHW

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
3(1) Height and width are the same as the unit being attached to.

  1. Relay / Transformer mounts directly on 4 x 4 junction box on each unit.
    Part number is 310-E301 (24/120V), 310-E302 (24.208-230V) and 310-E303 (24/277V) – (for 2-5 ton models only)

Mixing Boxes

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
4

Dimensions:

MODEL| FOR UNIT MODEL| A| B| C| D| E| F| DAMPER SIZE (NOM)| SHIPPING WEIGHT
---|---|---|---|---|---|---|---|---|---
24MB| 24SH, SV| 16| 16-3/8| 18-1/8| 8| 6| 1-1/16| 2-16 x 8| 40
36MB| 36SH, SV| 16| 16-3/8| 27-5/8| 8| 6| 1-1/16| 2-26 x 8| 58
48MB| 48SH, SV| 18| 20-3/8| 29-1/8| 10| 8| 1-1/16| 2-27 x 10| 65
60MB| 60SH, SV| 18| 20-3/8| 36-1/8| 10| 8| 1-1/16| 2-34 x 10| 78
90MB| 90SH, SV| 18| 25-3/8| 45-1/8| 10| 8| 1-1/16| 2-42 x 10| 110
120MB| 120SH, SV| 20| 30-3/8| 48-1/8| 12| 10| 1-1/16| 2-46 x 12| 135
180MB| 180SH, SV| 22| 37-7/8| 57-1/8| 14| 12| 1-9/16| 2-54 x 14| 190
240MB| 240SH, SV| 22| 50-1/2| 57-1/8| 14| 24| 1-9/16| 2-54 x 14| 210

Features:

  1. Cabinet fully insulated – 3/4 inch.
  2. Embossed galvanized cabinet on 24-230MB.
  3. Crank arms and linkage rod for damper connection are furnished. Connections can be made on either side of mixing boxes. The balance of necessary linkage hardware, damper motor, and controls to be field supplied.
  4. Dampers can be positioned for either rear/top or rear/bottom locations.
  5. 1” duct flanges provided on damper openings.
  6. Dampers have air seals on the edges for positive closing. 24-90MB have single horizontal damper blades. 120-230MB have double horizontal damper blades.
  7. When used with water coil units, a “freeze stat” must be installed to prevent coil damage caused by low ambient conditions.

COMPONENT STATIC RESISTANCE

MODEL| NOMINAL CFM| COMPONENT STATIC RESISTANCE (INCHES OF WATER)
---|---|---
CABINET| **COOLING COIL*| HEATING COIL| FILTER
4 ROW| 6 ROW| 2 ROW
| 600| 0.09| 0.14| 0.22| 0.07| 0.04
| 700| 0.10| 0.18| 0.27| 0.09| 0.05
24SHW| 800| 0.11| 0.23| 0.34| 0.12| 0.06
| 900| 0.12| 0.28| 0.42| 0.14| 0.07
| 1000| 0.13| 0.33| 0.50| 0.18| 0.08
| 1000| 0.09| 0.17| 0.25| 0.08| 0.04
| 1100| 0.10| 0.19| 0.28| 0.10| 0.05
36SHW| 1200| 0.11| 0.23| 0.34| 0.12| 0.06
| 1300| 0.12| 0.26| 0.39| 0.13| 0.07
| 1400| 0.13| 0.30| 0.45| 0.15| 0.08
| 1400| 0.09| 0.18| 0.27| 0.09| 0.05
| 1500| 0.10| 0.20| 0.31| 0.10| 0.06
48SHW| 1600| 0.11| 0.23| 0.34| 0.11| 0.06
| 1700| 0.12| 0.25| 0.38| 0.12| 0.07
| 1800| 0.13| 0.28| 0.42| 0.13| 0.08
| 1800| 0.10| 0.20| 0.28| 0.09| 0.05
| 1900| 0.11| 0.21| 0.31| 0.10| 0.06
60SHW**| 2000| 0.12| 0.23| 0.34| 0.11| 0.06
| 2100| 0.13| 0.25| 0.37| 0.12| 0.07
| 2200| 0.15| 0.28| 0.40| 0.13| 0.08


MODEL

| ****

NOMINAL CFM

| COMPONENT STATIC RESISTANCE (INCHES OF WATER)
---|---|---
CABINET| **COOLING COIL*| HEATING COIL| FILTER
4 ROW| 6 ROW| 2 ROW
| 2500| 0.12| 0.26| 0.39| 0.13| 0.04
| 2750| 0.14| 0.30| 0.45| 0.16| 0.05
90SHW| 3000| 0.16| 0.34| 0.51| 0.18| 0.06
| 3250| 0.17| 0.39| 0.58| 0.21| 0.07
| 3500| 0.19| 0.44| 0.65| 0.24| 0.08
| 3400| 0.14| 0.29| 0.43| 0.14| 0.05
| 3700| 0.15| 0.33| 0.48| 0.16| 0.06
120SHW| 4000| 0.17| 0.37| 0.54| 0.19| 0.07
| 4300| 0.19| 0.41| 0.61| 0.21| 0.08
| 4600| 0.21| 0.45| 0.67| 0.24| 0.09
| 5200| 0.16| 0.30| 0.44| 0.14| 0.05
| 5600| 0.17| 033| 0.49| 0.16| 0.06
180SHW| 6000| 0.19| 0.37| 0.55| 0.18| 0.07
| 6400| 0.21| 0.41| 0.61| 0.20| 0.08
| 6800| 0.23| 0.45| 0.66| 0.23| 0.09
| 6000| 0.11| 0.21| 0.31| 0.10| 0.04
| 7000| 0.16| 0.30| 0.44| 0.14| 0.05
240SHW**| 8000| 0.19| 0.37| 0.55| 0.18| 0.07
| 9000| 0.23| 0.45| 0.66| 0.23| 0.09
| 10000| 0.29| 0.58| 0.86| 0.28| 0.11

* Wet Coil (Dry Coil P.D. = Wet P.D. x .70)

UNIT SELECTION PROCEDURE

  1. Complete as much of the “INFORMATION REQUIRED FOR UNIT SELECTION” on page 2 as possible.
    Example:
    INFORMATION REQUIRED FOR UNIT SELECTION
    System Type ( circle one) : 2 – pipe (1 coil ) or 4 – pipe ( sep. htg. & clg. coils )
    CFM 3900
    E.S.P. .80 MOTOR: HP:____VOLTAGE:230PHASE:3
    COOLING: INDOOR: DB __ WB OUTDOOR:
    DB__
    TOTAL BTUH158,000SENS. BTUH GPM __EWT 45
    HEATING:
    TOTAL BTUH
    GPM____EWT____EAT____
    MISC: ____

  2. Select the unit model that meets the required total MBH cooling and heating at the required conditions from tables on pages 16 – 23 (capacities and air are the same for SHW and SVW models).
    Example: Required clg. capacity = 158,000 BTUH clg. @ 45 degree EWT Unit selected = 120SHW6

  3. Refer to page 7 for the balance of the selection procedure: If the required CFM falls within the range for the selected model, proceed to number 4. If not, use the First Co. Computer Selection Program or contact the factory for assistance.

  4. Determine the required motor horsepower by matching the selected model (i.e. 120SHW6) with the closest CFM at the required External Static Pressure (ESP).
    Note the horsepower (HP) at the top of the CFM range that is needed.
    Example: Required CFM is 3900 at .80 ESP.
    HP required = 2 HP

  5. Select the motor voltage, phase, and horsepower and then the appropriate Motor Drive Assembly Number that applies.
    Example: Above example requires Motor Drive Assembly Number 984120-G3

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
5

SHW MOTOR DRIVE ASSEMBLY SELECTION CHART

Model CFM Available External Static Range Total Static In.
2 Row 4 Row 4R/2R
Coil Coil Coil
*24S()W** *24S()W2** *24S()W4**
*24S()W62**
– 1/4 HP –
700 0.13 – 0.80 0.04 – 0.71

1.04
800| 0.00 – 0.63| 0.00 – 0.52| 0.00 – 0.41| 0.00 – 0.41| 0.00 – 0.29| 0.33 – 0.92
900| 0.00 – 0.44| 0.00 – 0.30| 0.00 – 0.16| 0.00 – 0.16| 0.00 – 0.02| 0.28 – 0.77
| | | | | |
– 1/3 HP –|
700| 0.36 – 1.23| 0.27 – 1.14| 0.18 – 1.05| 0.17 – 1.04| 0.09 – 0.96| 0.60 – 1.47
800| 0.29 – 1.03| 0.18 – 0.92| 0.07 – 0.81| 0.07 – 0.81| 0.00 – 0.69| 0.58 – 1.32
900| 0.21 – 0.83| 0.07 – 0.69| 0.00 – 0.55| 0.00 – 0.55| 0.00 – 0.41| 0.54 – 1.16
| | | | | |
– 1/2 HP –|
700| 0.64 -1.62| 0.55 – 1.53| 0.46 – 1.44| 0.45 – 1.43| 0.37 – 1.35| 0.88 – 1.86
800| 0.59 -1.62| 0.48 – 1.51| 0.37 – 1.40| 0.37 – 1.40| 0.25 – 1.28| 0.88 – 1.91
900| 0.54 -1.52| 0.40 – 1.38| 0.26 – 1.24| 0.26 – 1.24| 0.12 – 1.10| 0.87 – 1.85
| | | | | |
– 3/4 HP –|
700| 0.90 – 1.62| 0.81 – 1.53| 0.72 – 1.44| 0.71 – 1.43| 0.63 – 1.35| 1.14 – 1.86
800| 0.87 – 1.62| 0.76 – 1.51| 0.65 – 1.40| 0.65 – 1.40| 0.53 – 1.28| 1.16 – 1.91
900| 0.84 – 1.61| 0.70 – 1.47| 0.56 – 1.33| 0.56 – 1.33| 0.42 – 1.19| 1.17 – 1.94
| | | | | |
36S()W| 36S()W2| 36S()W4| 36S()W42| 36S()W6| 36S()W62|
– 1/3 HP –|
1000| 0.13 – 0.74| 0.00 – 0.65| 0.00 – 0.57| 0.00 – 0.57| 0.00 – 0.49| 0.34 – 0.95
1100| 0.07 – 0.61| 0.00 – 0.52| 0.00 – 0.42| 0.00 – 0.43| 0.00 – 0.33| 0.32 – 0.86
1200| 0.00 – 0.47| 0.00 – 0.36| 0.00 – 0.24| 0.00 – 0.25| 0.00 – 0.13| 0.29 – 0.76
1300| 0.00 – 0.34| 0.00 – 0.21| 0.00 – 0.08| 0.00 – 0.08| 0.00 – 0.00| 0.26 – 0.66
| | | | | |
– 1/2 HP –|
1000| 0.34 – 1.34| 0.25 – 1.25| 0.17 – 1.17| 0.17 – 1.17| 0.09 – 1.09| 0.55 – 1.55
1100| 0.29 – 1.19| 0.20 – 1.10| 0.10 – 1.00| 0.11 – 1.01| 0.00 – 0.91| 0.54 – 1.44
1200| 0.24 – 1.04| 0.13 – 0.93| 0.00 – 0.81| 0.00 – 0.82| 0.00 – 0.70| 0.53 – 1.33
1300| 0.18 – 0.90| 0.05 – 0.77| 0.00 – 0.64| 0.00 – 0.64| 0.00 – 0.51| 0.50 – 1.22
| | | | | |
– 3/4 HP –|
1000| 0.88 – 1.55| 0.79 – 1.46| 0.71 – 1.38| 0.71 – 1.38| 0.63 – 1.30| 1.09 – 1.76
1100| 0.86 – 1.55| 0.77 – 1.46| 0.67 – 1.36| 0.68 – 1.37| 0.58 – 1.27| 1.11 – 1.80
1200| 0.82 – 1.54| 0.71 – 1.43| 0.59 – 1.31| 0.60 – 1.32| 0.48 – 1.20| 1.11 – 1.83
1300| 0.78 – 1.51| 0.65 – 1.38| 0.52 – 1.25| 0.52 – 1.25| 0.39 – 1.12| 1.10 – 1.83
| | | | | |
48S()W| 48S()W2| 48S()W4| 48S()W42| 48S()W6| 48S()W62|
– 1/2 HP –|
1500| 0.17 – 0.75| 0.07 – 0.65| 0.00 – 0.55| 0.00 – 0.54| 0.00 – 0.44| 0.43 – 1.01
1600| 0.12 – 0.66| 0.00 – 0.54| 0.00 – 0.43| 0.00 – 0.43| 0.00 – 0.32| 0.40 – 0.94
1700| 0.06 – 0.55| 0.00 – 0.42| 0.00 – 0.30| 0.00 – 0.29| 0.00 – 0.17| 0.37 – 0.86
| | | | | |
– 3/4 HP –|
1500| 0.46 – 1.37| 0.36 – 1.27| 0.26 – 1.17| 0.25 – 1.16| 0.15 – 1.06| 0.72 – 1.63
1600| 0.42 – 1.26| 0.30 – 1.14| 0.19 – 1.03| 0.19 – 1.03| 0.08 – 0.92| 0.70 – 1.54
1700| 0.37 – 1.15| 0.24 – 1.02| 0.12 – 0.90| 0.11 – 0.89| 0.00 – 0.77| 0.68 – 1.46
| | | | | |
– 1 HP –|
1500| 0.88 – 1.63| 0.78 – 1.53| 0.68 – 1.43| 0.67 – 1.42| 0.57 – 1.32| 1.14 – 1.89
1600| 0.85 – 1.63| 0.73 – 1.51| 0.62 – 1.40| 0.62 – 1.40| 0.51 – 1.29| 1.13 – 1.91
1700| 0.81 – 1.61| 0.68 – 1.48| 0.56 – 1.36| 0.55 – 1.35| 0.43 – 1.23| 1.12 – 1.92
| | | | | |
60S()W| 60S()W2| 60S()W4| 60S()W42| 60S()W6| 60S()W62|
– 1/2 HP –|
1900| 0.15 – 0.59| 0.00 – 0.48| 0.00 – 0.38| 0.00 – 0.38| 0.00 – 0.28| 0.42 – 0.86
2000| 0.11 – 0.51| 0.00 – 0.39| 0.00 – 0.28| 0.00 – 0.28| 0.00 – 0.17| 0.40 – 0.80
12100| 0.06 – 0.42| 0.00 – 0.29| 0.00 – 0.17| 0.00 – 0.17| 0.00 – 0.05| 0.38 – 0.74
| | | | | |
– 3/4 HP –|
1900| 0.44 – 1.16| 0.33 – 1.05| 0.23 – 0.95| 0.23 – 0.95| 0.13 – 0.85| 0.71 – 1.43
2000| 0.42 – 1.08| 0.30 – 0.96| 0.19 – 0.85| 0.19 – 0.85| 0.08 – 0.74| 0.71 – 1.37
2100| 0.38 – 0.99| 0.25 – 0.86| 0.13 – 0.74| 0.13 – 0.74| 0.00 – 0.62| 0.70 – 1.31
| | | | | |
– 1 HP –|
1900| 0.77 – 1.57| 0.66 – 1.46| 0.56 – 1.36| 0.56 – 1.36| 0.46 – 1.26| 1.04 – 1.84
2000| 0.76 – 1.51| 0.64 – 1.39| 0.53 – 1.28| 0.53 – 1.28| 0.42 – 1.17| 1.05 – 1.80
2100| 0.74 – 1.43| 0.61 – 1.30| 0.49 – 1.18| 0.49 – 1.18| 0.37 – 1.06| 1.06 – 1.75
| | | | | |
– 1-1/2 HP –|
1900| 1.10 – 1.91| 0.99 – 1.80| 0.89 – 1.70| 0.89 – 1.70| 0.79 – 1.60| 1.37 – 2.18
2000| 1.09 – 1.91| 0.97 – 1.79| 0.86 – 1.68| 0.86 – 1.68| 0.75 – 1.57| 1.38 – 2.20
2100| 1.07 – 1.90| 0.94 – 1.77| 0.82 – 1.65| 0.82 – 1.65| 0.70 – 1.53| 1.39 – 2.22
H = Horizontal, V = Vertical
Model CFM| Available External Static Range| Total Static In.
---|---|---
2 Row| 4 Row| 4R/2R| 6 Row| 6R/2R
Coil| Coil| Coil| Coil| Coil
90S(
)W
| 90S()W2| 90S()W4| 90S()W42| 90S()W6| 90S()W62|
– 3/4 HP –|
2800| 0.00 – 0.73| 0.00 – 0.58| 0.00 – 0.42| 0.00 – 0.43| 0.00 – 0.27| 0.34 – 1.09
3000| 0.00 – 0.51| 0.00 – 0.35| 0.00 – 0.17| 0.00 – 0.18| 0.00 – 0.00| 0.33 – 0.91
3200| 0.00 – 0.30| 0.00 – 0.13| 0.00 – 0.00| 0.00 – 0.00| 0.00 – 0.00| 0.31 – 0.74
| | | | | |
– 1 HP –|
2800| 0.38 – 1.17| 0.23 – 1.02| 0.07 – 0.86| 0.08 – 0.87| 0.00 – 0.71| 0.74 – 1.53
3000| 0.33 – 0.92| 0.17 – 0.76| 0.00 – 0.58| 0.00 – 0.59| 0.00 – 0.41| 0.73 – 1.32
3200| 0.27 – 0.70| 0.10 – 0.53| 0.00 – 0.32| 0.00 – 0.34| 0.00 – 0.14| 0.71 – 1.14
| | | | | |
– 1-1/2 HP –|
2800| 0.63 -1.80| 0.48 – 1.65| 0.32 – 1.49| 0.33 – 1.50| 0.17 – 1.34| 0.99 – 2.16
3000| 0.59 -1.74| 0.43 – 1.58| 0.25 – 1.40| 0.26 – 1.41| 0.08 – 1.23| 0.99 – 2.14
3200| | | | | |
| | | | | |
– 2 HP –|
2800| 1.01 – 1.80| 0.86 – 1.65| 0.70 – 1.49| 0.71 – 1.50| 0.55 – 1.34| 1.37 – 2.16
3000| 0.97 – 0.75| 0.81 – 1.63| 0.63 – 1.45| 0.64 – 1.46| 0.46 – 1.28| 1.37 – 2.19
3200| 0.93 – 1.77| 0.76 – 1.60| 0.55 – 1.39| 0.57 – 1.41| 0.37 – 1.21| 1.37 – 2.21
| | | | | |
120S(
)W
| 120S()W2| 120S()W4| 120S()W42| 120S()W6| 120S()W62|
– 1-1/2 HP –|
3800| 0.02 – 0.97| 0.00 – 0.80| 0.00 – 0.63| 0.00 – 0.64| 0.00 – 0.47| 0.41 – 1.36
4000| 0.00 – 0.75| 0.00 – 0.57| 0.00 – 0.38| 0.00 – 0.40| 0.00 – 0.21| 0.37 – 1.18
4200| 0.00 – 0.55| 0.00 – 0.35| 0.00 – 0.15| 0.00 – 0.17| 0.00 – 0.00| 0.33 – 1.01
| | | | | |
– 2 HP –|
3800| 0.51 – 1.65| 0.34 – 1.48| 0.17 – 1.31| 0.18 – 1.32| 0.01 – 1.15| 0.90 – 2.04
4000| 0.43 – 1.42| 0.25 – 1.24| 0.06 – 1.05| 0.08 – 1.07| 0.00 – 0.88| 0.86 – 1.85
4200| 0.36 – 1.20| 0.16 – 1.00| 0.00 – 0.80| 0.00 – 0.82| 0.00 – 0.61| 0.82 – 1.66
| | | | | |
– 3 HP –|
3800| | | | | |
4000| 0.92 – 1.52| 0.74 – 1.34| 0.55 – 1.15| 0.57 – 1.17| 0.38 – 0.98| 1.35 – 1.95
4200| 0.85 – 1.47| 0.65 – 1.27| 0.45 – 1.07| 0.47 – 1.09| 0.28 – 0.88| 1.31 – 1.93
| | | | | |
180S(
)W
| 180S()W2| 180S()W4| 180S()W42| 180S()W6| 180S()W62|
– 2 HP –|
5800| 0.24 – 0.92| 0.06 – 0.74| 0.00 – 0.57| 0.00 – 0.57| 0.00 – 0.40| 0.66 – 1.34
6000| 0.20 – 0.77| 0.00 – 0.58| 0.00 – 0.40| 0.00 – 0.40| 0.00 – 0.22| 0.64 – 1.21
6200| 0.16 – 0.63| 0.00 – 0.43| 0.00 – 0.24| 0.00 – 0.24| 0.00 – 0.05| 0.62 – 1.09
| | | | | |
– 3 HP –|
5800| 0.50 – 1.62| 0.32 – 1.44| 0.15 – 1.27| 0.15 – 1.27| 0.00 – 1.10| 0.92 – 2.04
6000| 0.46 – 1.60| 0.27 – 1.41| 0.09 – 1.23| 0.09 – 1.23| 0.00 – 1.05| 0.90 – 2.04
6200| 0.42 – 1.47| 0.22 – 1.27| 0.03 – 1.08| 0.00 – 1.08| 0.00 – 0.89| 0.88 – 1.93
| | | | | |
240S(
)W
| 230S()W2| 230S()W4| 230S()W42| 230S()W6| 230S(*)W62|
– 3 HP –|
7500| 0.08 – 0.79| 0.00 – 0.61| 0.00 – 0.45| 0.00 – 0.45| 0.00 – 0.31| 0.47 – 1.18
8000| 0.00 – 0.45| 0.00 – 0.26| 0.00 – 0.08| 0.00 – 0.08| 0.00 – 0.00| 0.39 – 0.89
8500| 0.00 – 0.13| 0.00 – 0.00| 0.00 – 0.00| 0.00 – 0.00| 0.00 – 0.00| 0.29 – 0.62
| | | | | |
– 5 HP –*|
7500| 0.20 – 1.79| 0.00 – 1.61| 0.00 – 1.45| 0.00 – 1.45| 0.00 – 1.31| 0.59 – 2.18
8000| 0.07 – 1.71| 0.00 – 1.52| 0.00 – 1.34| 0.00 – 1.34| 0.00 – 1.17| 0.51 – 2.15
8500| 0.00 – 1.39| 0.00 – 1.18| 0.00 – 0.98| 0.00 – 0.99| 0.00 – 0.79| 0.42 – 1.88
| | | | | |
H = Horizontal, V = Vertical**

Physical Data – Models 24SHW – 60SHW

UNIT DIMENSIONS

MODEL| UNIT CABINET| OUTLET| ETURN RETURN DUCT
CONNECTION
---|---|---|---
AA| BB| CC| DD| EE| FF| GG| HH
24SHW4| 37| 32-1/2| 27| 18-7/8| 8-3/4| 10-7/8| 18| 16-1/4
36SHW4| 37| 42| 36-1/2| 18-7/8| 12-1/4| 10-7/8| 27-1/2| 16-1/4
48SHW4| 39| 43-1/2| 38| 22-7/8| 13-5/8| 11-7/8| 29| 20-1/4
60SHW4| 42| 50-1/2| 45| 22-7/8| 16| 13-7/8| 36| 20-1/4
24SHW6| 37| 32-1/2| 27| 18-7/8| 8-3/4| 10-7/8| 18| 16-1/4
36SHW6| 37| 42| 36-1/2| 18-7/8| 12-1/4| 10-7/8| 27-1/2| 16-1/4
48SHW6| 39| 43-1/2| 38| 22-7/8| 13-5/8| 11-7/8| 29| 20-1/4
60SHW6| 42| 50-1/2| 48| 22-7/8| 16| 13-7/8| 36| 20-1/4

STUBOUT LOCATION FOR WATER COILS

A| B| C| D| E| F| G| H| J| K
11-1/4| 6-5/16| 4-1/2| 6-1/2| 4-1/2| 3-15/16| 1| 8-15/16| 10| 12
11-1/4| 6-5/16| 4-1/2| 6-1/2| 4-1/2| 3-15/16| 1| 8-15/16| 10| 12
11-1/4| 6-5/16| 3-3/4| 5-3/4| 4-1/2| 3-15/16| 1| 8-15/16| 10| 12
11-1/4| 6-5/16| 3-3/4| 5-3/4| 4-1/2| 3-15/16| 1| 8-15/16| 10| 12
12-15/16| 6-5/16| 4-1/2| 6-1/2| 4-1/2| 3-15/16| 1| 10-5/8| 10| 13-3/4
12-15/16| 6-5/16| 4-1/2| 6-1/2| 4-1/2| 3-15/16| 1| 10-5/8| 10| 13-3/4
12-15/16| 6-5/16| 3-3/4| 5-3/4| 4-1/2| 3-15/16| 1| 10-5/8| 10| 13-3/4
12-15/16| 6-5/16| 3-3/4| 5-3/4| 4-1/2| 3-15/16| 1| 10-5/8| 10| 13-3/4

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
7

Notes:

  1. All drain connections are 3/4” MPT and located on same side as coil connections.
  2. All units have knockouts on both sides for either (standard) or left side coil stub outs. (Looking with airflow) All coil connections must be on the same side of the unit.

GENERAL SPECIFICATIONS

MODEL| NOM. COOL TONS| FACE AREA SQ. FT.| TUBE SIZE| STD. MOTOR HP| VOLTS| PHASE
---|---|---|---|---|---|---
24SHW| 2| 2.05| 3/8| 1/4| 115| 1
36SHW| 3| 3.05| 3/8| 1/3| 115| 1
48SHW| 4| 4.0| 3/8| 1/2| 115| 1
60SHW| 5| 5.0| 3/8| 1/2| 115| 1

BLOWER SIZE FILTER SIZE 4 ROW COIL 6 ROW COIL

MANIFOLD
CONNECTION
| SHIPPING
WEIGHT
| MANIFOLD
CONNECTION
| SHIPPING
WEIGHT

9 X 6| 16 X 25| 7/8” O/D (SWT)| 185| 7/8” O/D (SWT)| 205
9 X 9| 16 X 16 (2)| 7/8” O/D (SWT)| 205| 7/8” O/D (SWT)| 225
10 X 10| 16 X 20 (2)| 7/8” O/D (SWT)| 230| 7/8” O/D (SWT)| 265
12 X 12| 20 X 20 (2)| 1-1/8” O/D (SWT)| 290| 1-1/8” O/D (SWT)| 310

Notes:

  1. All technical specifications subject to change without notice.

  2. Additional charge for optional motors.

  3. When SHW units are used with hot water coil the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout air lower LAT. Contact factory for information.

  4. Contact factory for electric heat information (supplied by others)

Physical Data – Models 90SHW – 240SHW
UNIT DIMENSIONS

MODEL UNIT CABINET BLOWER OUTLET RETURN DUCT CONNECTION
AA BB CC EE
90SHW4 52-1/2 54 27
120SHW4 52-1/2 57 32
180SHW4 56-1/2 66 39-1/2
240SHW4 62-1/2 66 52
90SHW6 52-1/2 54 27
120SHW6 52-1/2 57 32
180SHW6 56-1/2 66 39-1/2
240SHW6 62-1/2 66 52

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
9

STUBOUT LOCATION FOR WATER COILS

A| B| C| D| E| F| G| H| J| K| L
11-1/8| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 9-3/8| 10-1/4| 12-5/8| 1
11-1/8| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 9-3/8| 10-1/4| 12-5/8| C 6
11-1/8| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 9-3/8| 10-1/4| 12-5/8| 9-5/16
11-1/8| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 9-3/8| 10-1/4| 12-5/8| 21-3/4
13-5/16| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 11-1/2| 10-1/4| 14-13/16| 1
13-5/16| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 11-1/2| 10-1/4| 14-13/16| 6
13-5/16| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 11-1/2| 10-1/4| 14-13/16| 9-5/16
13-5/16| 6-1/8| 2-7/16| 5-1/8| 6-7/16| 6-7/16| 1| 11-1/2| 10-1/4| 14-13/16| 21-3/4

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
10 Notes:

  1. All drain connections are 3/4” MPT and located on same side as coil connections.

  2. All units have knockouts on both sides for either (standard) or left side coil stub outs.
    (Looking with airflow) All coil connections must be on the same side of the unit.

  3. 180SHW and 230SHW models have two blowers. Blower opening size is 16-3/8 X 16-5/8

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
11

GENERAL SPECIFICATIONS

MODEL| NOM.
COOL
TONS| FACE
AREA
SQ. FT.| S SIZE| STD.
MOTOR
HP| TUBE
VOLTS
| PHASE| B LO ER
SIZE
---|---|---|---|---|---|---|---
90SHW| 7-1/2| 7.5| 1/2| 3/4| 115/230| 1| 15 X 15
120SHW| 10| 9.6| 1/2| 1-1/2| 230/460| 3| 15 X 15
180SHW| 15| 14.3| 1/2| 1-1/2| 230/460| 3| 15 X 12 (2)
240SHW| 20| 19.1| 1/2| 3| 230/460| 3| 15 X 12 (2
BLOWER SIZE| FILTER SIZE| 4 ROW COIL| 6 ROW COIL
---|---|---|---
MANIFOLD CONNECTION| SHIPPING WEIGHT| MANIFOLD CONNECTION| SHIPPING WEIGHT
15 X 15| 24 X 25 (2)| 1-1/8″ O/D (SWT)| 450| 1-1/8″ O/D (SWT)| 475
15 X 15| 26 X 29 (2)| 1-3/8″ O/D (SWT)| 490| 1-3/8″ O/D (SWT)| 535
15 X 12 (2)| 20 X 36.5 (3)| 1-3/8″ O/D (SWT)| 670| 1-3/8″ O/D (SWT)| 710
15 X 12 (2| 20 X 49 (3)| 1-3/8″ O/D (SWT)| 835| 1-3/8″ O/D (SWT)| 880

Notes:

  1. All technical specifications subject to change without notice.

  2. Additional charge for optional motors.

  3. When SHW units are used with hot water coil the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout air lower LAT. Contact factory for information.

  4. Contact factory for electric heat information (supplied by others)

first Co SHW SERIES Hydronic 2 20 Tons Horizontal Chilled Water - Figure
12

SHW SERIES
2 – 5 TON FAN PERFORMANCE

MODEL| NOMINAL
CFM| COIL FACE
VELOCITY
FPM| TOTAL STATIC PRESSURE – INCHES OF WATER
---|---|---|---
0.5| 0.6| 0.7| 0.8| 0.9
RPM| HP| RPM| HP| RPM| HP| RPM| HP| RPM| HP
24SHW| 600| 300| 770| 1/6| 840| 1/6| 900| 1/6| 990| 1/4| 1050| 1/4
700| 350| 780| 1/6| 850| 1/6| 910| 1/4| 990| 1/4| 1040| 1/4
800| 400| 800| 1/4| 860| 1/4| 910| 1/4| 990| 1/4| 1040| 1/4
900| 450| 810| 1/4| 880| 1/4| 925| 1/4| 1000| 1/4| 1050| 1/3
1000| 500| 830| 1/4| 900| 1/4| 950| 1/3| 1000| 1/3| 1060| 1/3
36SHW| 1000| 333| 805| 1/4| 880| 1/4| 940| 1/3| 1000| 1/3| 1060| 1/3
1100| 367| 810| 1/4| 890| 1/3| 940| 1/3| 1000| 1/3| 1050| 1/2
1200| 400| 820| 1/3| 900| 1/3| 950| 1/3| 1005| 1/2| 1050| 1/2
1300| 434| 840| 1/3| 905| 1/3| 960| 1/3| 1010| 1/2| 1060| 1/2
1400| 466| 870| 1/3| 920| 1/3| 980| 1/2| 1020| 1/2| 1090| 1/2
48SHW| 1400| 350| 720| 1/3| 775| 1/3| 825| 1/2| 870| 1/3| 910| 1/2
1500| 375| 740| 1/3| 785| 1/2| 830| 1/2| 875| 1/2| 920| 1/2
1600| 400| 750| 1/2| 800| 1/2| 840| 1/2| 890| 1/2| 925| 3/4
1700| 425| 770| 1/2| 810| 1/2| 860| 1/2| 895| 1/2| 930| 3/4
1800| 450| 785| 1/2| 825| 1/2| 870| 1/2| 910| 1/2| 945| 3/4
60SHW| 1800| 360| 580| 1/2| 630| 1/2| 680| 1/2| 725| 1/2| 770| 3/4
1900| 380| 580| 1/2| 630| 1/2| 680| 1/2| 725| 1/2| 775| 3/4
2000| 400| 590| 1/2| 635| 1/2| 680| 1/2| 730| 1/2| 770| 3/4
2100| 420| 600| 1/2| 640| 1/2| 690| 1/2| 730| 3/4| 770| 3/4
2200| 440| 600| 1/2| 645| 1/2| 690| 1/2| 735| 3/4| 775| 3/4

NOMINAL CFM

| COIL FACE VELOCITY FPM| TOTAL STATIC PRESSURE – INCHES OF WATER
---|---|---
1.0| 1.2| 1.4| 1.6| 1.8| 2.0
RPM| HP| RPM| HP| RPM| HP| RPM| HP| RPM| HP| RPM| HP
600| 300| 1105| 1/4| 1210| 1/3| 1310| 1/3| 1420| 1/3| 1510| 1/2| – – –| – – –
700| 350| 1100| 1/4| 1200| 1/3| 1300| 1/3| 1405| 1/2| 1500| 1/2| – – –| – – –
800| 400| 1100| 1/3| 1195| 1/3| 1295| 1/2| 1395| 1/2| 1470| 1/2| – – –| – – –
900| 450| 1100| 1/3| 1190| 1/3| 1290| 1/2| 1390| 1/2| 1460| 1/2| – – –| – – –
1000| 500| 1110| 1/3| 1200| 1/2| 1295| 1/2| 1390| 1/2| 1450| 3/4| – – –| – – –
1000| 333| 1110| 1/2| 1230| 1/2| 1335| 1/2| 1440| 3/4| 1540| 3/4| – – –| – – –
1100| 367| 1110| 1/2| 1215| 1/2| 1325| 1/2| 1425| 3/4| 1520| 3/4| – – –| – – –
1200| 400| 1110| 1/2| 1210| 1/2| 1315| 3/4| 1415| 3/4| 1500| 3/4| – – –| – – –
1300| 434| 1110| 1/2| 1220| 1/2| 1315| 3/4| 1410| 3/4| 1490| 3/4| – – –| – – –
1400| 466| 1120| 1/2| 1220| 3/4| 1320| 3/4| 1410| 3/4| 1500| 3/4| – – –| – – –
1400| 350| 955| 1/2| 1050| 3/4| 1135| 3/4| 1215| 3/4| 1300| 1| 1380| 1
1500| 375| 960| 1/2| 1050| 3/4| 1135| 3/4| 1210| 3/4| 1295| 1| 1370| 1
1600| 400| 970| 3/4| 1050| 3/4| 1140| 3/4| 1210| 3/4| 1290| 1| 1360| 1
1700| 425| 980| 3/4| 1065| 3/4| 1140| 3/4| 1210| 3/4| 1290| 1| 1350| 1
1800| 450| 985| 3/4| 1070| 3/4| 1150| 3/4| 1215| 1| 1280| 1| – – –| – – –
1800| 360| 820| 3/4| 900| 3/4| 975| 3/4| 1050| 1| 1125| 1| 1200| 1-1/2
1900| 380| 815| 3/4| 895| 3/4| 970| 3/4| 1045| 1| 1120| 1| 1190| 1-1/2
2000| 400| 815| 3/4| 890| 3/4| 965| 1| 1040| 1| 1110| 1| 1180| 1-1/2
2100| 420| 815| 3/4| 885| 3/4| 960| 1| 1035| 1| 1105| 1-1/2| 1175| 1-1/2
2200| 440| 815| 3/4| 885| 3/4| 960| 1| 1030| 1| 1100| 1-1/2| 1165| 1-1/2

7-1/2 – 20 TON FAN PERFORMANCE

MODEL

| NOMINAL CFM| COIL FACE VELOCITY FPM| TOTAL STATIC PRESSURE – INCHES OF WATER
---|---|---|---
0.6| 0.7| 0.8| 0.9| 1.0
RPM| HP| RPM| HP| RPM| HP| RPM| HP| RPM| HP



90SHW

| 2500| 333| 580| 1/2| 600| 3/4| 640| 3/4| 690| 3/4| 710| 3/4
2750| 366| 580| 1/2| 605| 3/4| 640| 3/4| 690| 3/4| 710| 3/4
3000| 400| 580| 3/4| 610| 3/4| 640| 3/4| 680| 3/4| 710| 1
3250| 433| 590| 3/4| 630| 1| 660| 1| 700| 1| 715| 1
3500| 466| 605| 1| 635| 1| 670| 1| 700| 1| 720| 1



120SHW

| 3400| 354| 600| 1| 630| 1| 670| 1| 700| 1| 730| 1-1/2
3700| 385| 610| 1| 650| 1| 680| 1-1/2| 705| 1-1/2| 740| 1-1/2
4000| 417| 630| 1-1/2| 670| 1-1/2| 695| 1-1/2| 710| 1-1/2| 750| 1-1/2
4300| 448| 650| 1-1/2| 685| 1-1/2| 705| 1-1/2| 730| 1-1/2| 770| 2
4600| 480| 670| 1-1/2| 700| 2| 720| 2| 760| 2| 790| 2



180SHW

| 5200| 364| 590| 1-1/2| 620| 1-1/2| 650| 1-1/2| 690| 1-1/2| 710| 1-1/2
5600| 391| 600| 1-1/2| 630| 1-1/2| 670| 1-1/2| 700| 1-1/2| 720| 2
6000| 420| 610| 1-1/2| 640| 1-1/2| 680| 1-1/2| 700| 2| 730| 2
6400| 447| 625| 2| 660| 2| 690| 2| 710| 2| 740| 3
6800| 475| 640| 2| 680| 2| 700| 3| 720| 3| 760| 3



240SHW

| 6000| 314| 610| 1-1/2| 640| 1-1/2| 670| 1-1/2| 700| 2| 730| 2
7000| 366| 640| 2| 690| 2| 710| 3| 740| 3| 760| 3
8000| 419| 700| 3| 720| 3| 750| 3| 790| 3| 800| 3
9000| 470| 730| 5| 760| 5| 800| 5| 810| 5| 830| 5
10000| 500| 800| 5| 820| 5| 840| 5| 880| 5| 900| 5

NOMINAL CFM

| COIL FACE VELOCITY FPM| TOTAL STATIC PRESSURE – INCHES OF WATER
---|---|---
1.2| 1.4| 1.6| 1.8| 2.0
RPM| HP| RPM| HP| RPM| HP| RPM| HP| RPM| HP
2500| 333| 790| 3/4| 850| 1| 915| 1-1/2| 990| 1-1/2| 1030| 1-1/2
2750| 366| 780| 1| 840| 1| 905| 1-1/2| 980| 1-1/2| 1020| 1-1/2
3000| 400| 780| 1| 835| 1-1/2| 900| 1-1/2| 970| 1-1/2| 1010| 1-1/2
3250| 433| 790| 1-1/2| 840| 1-1/2| 900| 1-1/2| 950| 1-1/2| 1005| 2
3500| 466| 790| 1-1/2| 845| 1-1/2| 900| 1-1/2| 950| 2| 1005| 2
3400| 354| 790| 1-1/2| 850| 1-1/2| 900| 1-1/2| 950| 2| 1005| 2
3700| 385| 800| 1-1/2| 855| 1-1/2| 905| 2| 950| 2| 1005| 2
4000| 417| 805| 1-1/2| 860| 2| 910| 2| 960| 2| 1005| 2
4300| 448| 820| 2| 875| 2| 915| 3| 970| 3| 1010| 3
4600| 480| 830| 2| 890| 3| 930| 3| 980| 3| 1015| 3
5200| 364| 780| 2| 830| 2| 900| 2| 950| 3| 1000| 3
5600| 391| 790| 2| 840| 2| 905| 3| 950| 3| 1000| 3
6000| 420| 795| 2| 850| 3| 910| 3| 960| 3| 1000| 3
6400| 447| 800| 3| 860| 3| 915| 3| 970| 3| 1000| 5
6800| 475| 810| 3| 870| 3| 920| 5| 975| 5| 1005| 5
6000| 314| 795| 2| 850| 3| 910| 3| 960| 3| 1000| 3
7000| 366| 810| 3| 880| 3| 920| 5| 960| 5| 1000| 5
8000| 419| 850| 5| 900| 5| 940| 5| 990| 5| 1020| 5
9000| 470| 890| 5| 920| 5| 980| 5| – – –| – – –| – – –| – – –
10000| 500| – – –| – – –| – – –| – – –| – – –| – – –| – – –| – – –| – – –| – – –

Notes:

  1. Shaded area indicates the R.P.M. and C.F.M. range of the standard motor and pulleys.

  2. To determine available brake horsepower (BHP), take above nominal HP and multiply as follows:
    For 1/4 HP to 3/4 HP motors: BHP = nominal X 1.25
    For 1 HP to 5 HP motors: BHP = nominal X 1.15

  3. Special pulleys and motors can be factory furnished at an additional charge.

  4. Horsepower tabulated indicates minimum recommended motor H.P.

  5. Rated in accordance with ARI Standard 430.

24SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 1

HOT WATER HEATING CAPACITIES

24SHW4 / 24SVW4 (4 ROW COIL)

180 O F ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR O F| LVG. WTR O F
600
800
1000| 3.0| 1.2| 47.5
56.4
64.3| 143
135
130| 148
142
137
600
800
1000| 6.0| 4.4| 52.0
63.2
73.3| 150
143
138| 163
159
156
600
800
1000| 9.0| 9.3| 53.6
65.8
76.8| 153
146
141| 168
165
163

* 70 degree return air

24HWK (2 ROW COIL)

180 O F ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR O F| LVG. WTR O F
600
800
1000| 3.0| 0.9| 33.3
38.4
42.9| 121
115
110| 158
154
151
600
800
1000| 6.0| 3.2| 36.6
43.2
49.0| 126
120
115| 168
166
164
600
800
1000| 9.0| 6.7| 37.9
45.3
51.8| 128
122
118| 172
170
168

Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coils can be factory or field installed.
  4. When these units are used for hot water heating the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

36SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 2

HOT WATER HEATING CAPACITIES

36SHW4 / 36SVW4 (4 ROW COIL)

180 O F ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
1000
1200
1400| 4.0| 2.0| 75.5
83.9
91.7| 140
135
131| 142
138
134
1000
1200
1400| 8.0| 7.5| 83.9
94.7
105.1| 148
143
140| 159
156
154
1000
1200
1400| 12.0| 16.3| 86.8
98.9
110.1| 150
146
143| 165
163
162

* 70 degree return air

36HWK (2 ROW COIL)

180 O F ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR O F| LVG. WTR O F
1000
1200
1400| 4.0| 1.6| 53.3
58.7
65.4| 119
115
112| 153
150
148
1000
1200
1400| 8.0| 6.1| 59.4
66.2
72.5| 125
121
118| 165
164
162
1000
1200
1400| 12.0| 13.1| 61.5
68.7
75.4| 127
123
120| 170
168
167

*  70 degree return air

Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coils can be factory or field installed.
  4.  When these units are used for hot water heating the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

48SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 3

HOT WATER HEATING CAPACITIES

48SHW4 / 48SVW4 (4 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
1400
1600
1800| 6.0| 3.9| 106.3
114.9
123.3| 140
137
133| 145
142
139
1400
1600
1800| 10.0| 10.3| 114.9
125.3
135.3| 146
143
140| 157
155
153
1400
1600
1800| 13.0| 17.0| 118.0
129.4
140.0| 148
145
142| 162
160
158

* 70 degree return air

48HWK (2 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
1400
1600
1800| 5.0| 2.0| 72.8
78.0
82.7| 118
115
113| 151
149
147
1400
1600
1800| 8.0| 4.8| 79.2
85.4
91.4| 122
119
117| 160
159
157
1400
1600
1800| 12.0| 10.4| 83.3
90.2
97.0| 125
122
120| 166
165
164

* 70 degree return air
Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coils can be factory or field installed.
  4. When these units are used for hot water heating the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

60SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 4

HOT WATER HEATING CAPACITIES

60SHW4 / 60SVW4 (4 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
1800
2000
2200| 6.0| 1.8| 128.0
136.2
143.8| 136
133
131| 137
135
132
1800
2000
2200| 11.0| 5.7| 142.6
152.9
162.6| 143
141
138| 154
152
150
1800
2000
2200| 16.0| 11.6| 149.6
160.8
171.4| 147
144
142| 161
160
159

* 70 degree return air

60HWK (2 ROW COIL)

180 OF ENTERING WATER TEMPERATURE

CFM

| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
1800
2000
2200| 6.0| 3.1| 93.1
98.2
103.1| 118
116
113| 149
147
145
1800
2000
2200| 9.0| 6.6| 100.4
106.5
112.6| 122
119
117| 158
156
155
1800
2000
2200| 12.0| 11.5| 104.4
111.0
117.7| 124
121
120| 163
162
160

* 70 degree return air
Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coils can be factory or field installed.
  4. When these units are used for hot water heating the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

90SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 5

HOT WATER HEATING CAPACITIES

90SHW4 / 90SVW4 (4 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
2500
3000
3500| 10.0| 2.2| 207.8
232.4
255.2| 147
142
137| 138
133
129
2500
3000
3500| 15.0| 4.7| 222.4
251.1
278.5| 152
148
144| 150
146
143
2500
3000
3500| 22.0| 9.8| 232.8
265.1
295.7| 156
152
148| 159
156
153

* 70 degree return air

90HWK (2 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
2500
3000
3500| 8.0| 1.0| 146.2
160.5
171.5| 124
120
115| 143
140
137
2500
3000
3500| 14.0| 2.8| 162.3
180.4
196.2| 130
126
122| 157
154
153
2500
3000
3500| 21.0| 6.1| 171.1
191.2
209.1| 133
129
125| 164
162
160

* 70 degree return air
Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coil can be factory installed in either the reheat (std.) or preheat positions.
  4. When these units are used with hot water coil the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

120SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 6

HOT WATER HEATING CAPACITIES

120SHW4 / 120SVW4 (4 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
3400
4000
4600| 12.0| 2.0| 273.2
302.6
328.3| 144
140
136| 135
130
125
3400
4000
4600| 21.0| 5.8| 301.4
337.0
370.7| 152
148
144| 151
148
145
3400
4000
4600| 30.0| 11.4| 314.4
352.9
389.8| 155
152
148| 159
156
154

*  70 degree return air

120HWK (2 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
3400
4000
4600| 11.0| 1.0| 198.5
215.8
229.4| 124
120
116| 144
140
138
3400
4000
4600| 18.0| 2.8| 217.8
239.8
257.8| 129
125
122| 156
153
151
3400
4000
4600| 25.0| 5.3| 227.8
251.9
272.0| 132
128
125| 162
160
158

* 70 degree return air
Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coil can be factory installed in either the reheat (std.) or preheat positions.
  4. When these units are used with hot water coil the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

180SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 7

HOT WATER HEATING CAPACITIES

180SHW4 / 180SVW4 (4 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
5200
6000
6800| 18.0| 2.0| 411.0
449.4
483.2| 143
139
136| 134
130
126
5200
6000
6800| 30.0| 5.3| 450.7
496.
540.5| 150
147
143| 150
147
144
5200
6000
6800| 42.0| 10.1| 471.7
521.8
570.0| 154
150
148| 157
155
153

* 70 degree return air

180HWK (2 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
5200
6000
6800| 17.0| 1.9| 308.7
332.3
352.6| 125
121
118| 144
141
138
5200
6000
6800| 25.0| 4.1| 332.3
360.2
386.1| 129
125
123| 153
151
149
5200
6000
6800| 35.0| 8.0| 347.8
378.5
407.5| 132
128
125| 160
158
157

Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coil can be factory installed in either the reheat (std.) or preheat positions.
  4. When these units are used with hot water coil the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

240SHW
CHILLED WATER COOLING CAPACITIESfirst Co SHW SERIES Hydronic 2 20 Tons
Horizontal Chilled Water - Table 8

HOT WATER HEATING CAPACITIES

240SHW4 / 230SVW4 (4 ROW COIL)

180 OF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR
O F| LVG. WTR
O F
6000
8000
10000| 40.0| 5.2| 547
664
768| 154
147
141| 153
147
142
6000
8000
10000| 50.0| 8.0| 561
687
799| 157
150
144| 158
153
148
6000
8000
10000| 60.0| 11.3| 571
702
819| 158
151
146| 161
157
153

***** 70 degree return air

240HWK (2 ROW COIL)

180ºF ENTERING WATER TEMPERATURE
CFM| GPM| WTR. P.D. FT.| TOTAL MBH| LVG. AIR O F| LVG. WTR O F
6000
8000
10000| 15.0| 0.9| 323
369
415| 120
113
108| 137
131
125
6000
8000
10000| 25.0| 2.3| 361
420
457| 126
119
112| 151
146
144
6000
8000
10000| 35.0| 4.3| 382
449
494| 192
122
116| 158
154
152

* 70 degree return air
Notes:

  1. See page 22 for hot water heating correction factors.
  2. Optional 6 row coils should not be used for heating.
  3. Optional 2 row hot water coil can be factory installed in either the reheat (std.) or preheat positions.
  4. When these units are used with hot water coil the leaving air temperature must not exceed 150 degrees.
    At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

HOT WATER HEATING CORRECTION FACTORS

ENTERING AIR
TEMP. (ºF)| ENTERING WATER TEMPERATURE (ºF)
---|---
100| 110| 120| 130| 140| 150| 160| 170| 180
50| 0.455| 0.545| 0.636| 0.727| 0.818| 0.909| 1.000| 1.091| 1.182
55| 0.409| 0.500| 0.591| 0.682| 0.773| 0.864| 0.955| 1.045| 1.136
60| 0.363| 0.455| 0.545| 0.636| 0.727| 0.818| 0.909| 1.000| 1.091
65| 0.318| 0.409| 0.500| 0.591| 0.682| 0.773| 0.864| 0.955| 1.045
70| 0.272| 0.363| 0.455| 0.545| 0.636| 0.727| 0.818| 0.909| 1.000
75| 0.227| 0.318| 0.409| 0.500| 0.591| 0.682| 0.773| 0.864| 0.955
80| 0.182| 0.272| 0.363| 0.455| 0.545| 0.636| 0.727| 0.818| 0.909

Notes:

  1. To determine heating capacity at other than 180 deg. E.W.T. and 70 deg. E.A.T. multiply the selected heating capacity at 180 deg. times the appropriate correction factor from above chart.
  2. These correction factors may be used on all First Co. published 180 deg. heating capacities.
  3. When SHW units are used for hot water heating the leaving air temperature must not exceed 150 degrees. At high altitude conditions, blower motor may cutout at a lower LAT. Contact factory for information.

GUIDE SPECIFICATIONS
Furnish and install First Co. SHW Series Blower – Coil units as indicated on the plans.
CABI N ETS
Cabinets shall be manufactured of heavy gauge galvanized steel. The entire interior of the cabinet shall be insulated with one inch thick IAQ type insulation. Removable access panels shall be provided on both sides of the cabinet for maintenance and service. All cabinets shall have 2” supply and 1” return flanges.
INSULATION
The entire interior of the cabinet shall be insulated with one (1) inch insulation. This insulation must meet the requirements of ASTM C 1071, ASTM G 21, ASTM G 22, NFPA 90A, UL-181, and the cleaning practices of NAIMA.
MOTOR / BLOWERS
Blowers shall be resiliently mounted, with ball bearings, forward curved blade, and of centrifugal type. Each wheel shall be dynamically balanced for smooth, quiet operation. Blowers shall be belt driven with field adjustable pulleys to permit variations in static pressure and air requirements. Standard motors are 1725 RPM either single or three phase. All motors to be field or factory installed and wired at voltage specified by customer.
COILS
All SVW series coils shall consist of aluminum fins mechanically bonded onto 3/8” or 1/2” OD seamless copper tubing. All coils shall be leak tested at 350 PSIG minimum air pressure. Manual air vents shall be standard on all coils. Drain pans shall be coated for corrosion protection.
FILTERS
One inch throw away filters are standard in 2-5 ton SHW units. One inch permanent filters are provided as standard in 7-20 ton SHW units. Filters shall be accessible without tools.
LISTING
All standard motors are ETL Listed. All air handlers shall be rated in accordance with ARI Standard 430. Standard motors have internal overload protection. Therefore, units shipped with standard motors will be ETL listed. Most non-standard motors (i.e. 575V, 2-speed, TEFC, some 50 Hz., etc.) are not available with internal overload protection.  Therefore, most units shipped with non-standard motors can be ETL listed with the addition of a factory installed motor starter (contact the factory for starter information and ETL verification.)

FIRST CO.
P.O. BOX 270969 – DALLAS, TEXAS 75227
PH. (214) 388-5751 | [email protected]
WWW.FIRSTCO.COM