First Co CDX Series AquaTherm Ceiling Fan Coil Instruction Manual
- June 4, 2024
- First Co
Table of Contents
- First Co CDX Series AquaTherm Ceiling Fan Coil
- General description
- STANDARD FEATURES
- OPTIONAL ACCESSORIES
- CIRCUIT BOARD FEATURES
- MODEL NOMENCLATURE
- PHYSICAL DIMENSIONS
- CEILING ACCESS PANELS
- 966-M8, 967-M8 (accepts 2-20x20x1 filter) # 967-6-M8 (accepts 2-20x25x1
- 967-8-M8 (accepts 2-20x30x1 filter)
- ENCLOSURE INSTALLATION SUPPORT FRAMING
- ENCLOSURE CONNECTION LOCATIONS
- CDX Series – Without pump 1-1/2 THROUGH 3 TONS
- CDX Series – Without pump 1-1/2 THROUGH 3 TONS
- CDX Series 1-1/2 THROUGH 3 TONS
- CDX Series – Without pump 1-1/2 THROUGH 3 TONS
- CDX Series – With pump 1-1/2 THROUGH 3 TONS
- GUIDE SPECIFICATIONS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
First Co CDX Series AquaTherm Ceiling Fan Coil
General description
The space-saving CDX series fan coil is only 10” high (11” with enclosure),
thus allowing it to recess in a ceiling. Recessed ceiling fan coils save
valuable floor space and eliminate costly “equipment” closets. All CDX fan
coils include a 120/24V transformer and are completely prewired. A sloped
drain pan allows positive drainage of condensate. These fan coils are
compatible with any source of hot water that doesn’t exceed 180º F and is
NSF/ANSI certified for use with domestic water.
(1) First Co’s customer is ultimately responsible for confirming which fan
coil models are compatible with selected outdoor unit(s) and which expansion
valves (if any) are required. To determine certified indoor/outdoor matches,
go to www.firstco.com or contact the factory.
STANDARD FEATURES
- Factory installed service switch
- Freeze protector on HW coil
- Freeze protector on the DX coil
- Two speed fan operation
- Drain pan has 3/4” NPT primary and secondary (overflow) fittings
- 120V motor, 24V controls
- Highly efficient copper tube/aluminum fin heating and cooling coils. Cooling coil has a piston-type metering device or factory or field installed R410A TXV’s (non-bleed type). Contact factory for correct match with outdoor unit.
- Insulated and coated galvanized steel drain pan is sloped for proper drainage
- Effective January 2016, Cabinet air leakage is no more than 2% when tested in accordance with ASHRAE 193.
OPTIONAL ACCESSORIES
- Attractive off-white return air / access panel with captive screws (panels can be field painted)
- IAQ filter panels (see P. 3)
- Fully insulated enclosure with matching ceiling panel (enclosure can be pre-installed). Also allows for ducted return air.
- Factory or field installed TXV’s (non-bleed type)
- Condensate overflow switch (field installed) (# SS3)
CIRCUIT BOARD FEATURES
WHEN B IS ADDED TO MODEL NUMBER
Multi-function microprocessor circuit board with:
- Automatic pump timer (heating mode) – purge mode (60 seconds every 6 hours)
- Blower-on fan delay (heating mode) – preheats the HW coil for 45 seconds.
- Blower-off fan delay (heating and cooling modes) blower continues to operate for 15 seconds after the thermostat is satisfied for increased efficiency.
MODEL NOMENCLATURE
In keeping with its policy of continuous progress and product improvement, First Co. reserves the right to make changes without notice. Maintenance for all First Co. products is available under “Product Maintenance” at www.firstco.com.
- ST – standard coil
- HE – high efficiency coil
- ME – maximum efficiency coil
PHYSICAL DIMENSIONS
UNCASED VERSION NO PUMP
PHYSICAL DIMENSIONS
UNIT MODEL| A| B| C| D
18/19CDX| 38-1/8| 37-1/4| 30-1/8| 34-3/4
20/25CDX| 44-1/8| 43-1/4| 36-1/8| 40-3/4
26/31CDX| 50-1/8| 49-1/4| 42-1/8| 46-3/4
32/37CDX| 57-1/8| 56-1/4| 49-1/8| 53-3/4
UNCASED VERSION WITH PUMP
PHYSICAL DIMENSIONS
UNIT MODEL| A| B| C| D
18/19CDXQ| 45-1/8| 37-1/4| 30-1/8| 34-3/4
20-25CDXQ| 51-1/8| 43-1/4| 36-1/8| 40-3/4
26/31CDXQ| 57-1/8| 49-1/4| 42-1/8| 46-3/4
32/37CDXQ| 64-1/8| 56-1/4| 49-1/8| 53-3/4
CASED VERSION
KNOCKOUT FOR DUCTED RETURN Ducted return requires remote filter grille (field supplied) and non-louvered panel
ENCLOSURE DIMENSIONS| PANEL NO. (STD.)| PANEL
NO. (IAQ)| DESCRIPTION| CEILING PANEL OPENING| PANEL
FRAME DIMS (OUTSIDE)
---|---|---|---|---|---
FOR MODEL| ENCLOSURE| A| B| C| | | (2)|
W| L| W| L
19CDX| 9ECDX01 (1)| 45-3/4| 30-7/8| 34| 966| 966-M8|
LOUVERED| 24-1/2| 46| 27-1/2| 49
966-1| NA| NON-LOUVERED| 24-1/2| 46| 27-1/2| 49
20/25CDX| 9ECDX02 (1)| 51-3/4| 36-7/8| 40| 967|
967-M8| LOUVERED| 24-1/2| 52-1/2| 27-1/2| 55-1/2
967-1| NA| NON-LOUVERED| 24-1/2| 52-1/2| 27-1/2| 55-1/2
26/31CDX| 9ECDX03 (1)| 58-1/2| 42-7/8| 46-3/4| 967-6|
967-6-M8| LOUVERED| 24-1/2| 60| 27-1/2| 63
967-7| NA| NON-LOUVERED| 24-1/2| 60| 27-1/2| 63
32/37CDX| 9ECDX04 (1)| 66-1/2| 49-7/8| 54-3/4| 967-8|
967-8-M8| LOUVERED| 24-1/2| 67| 27-1/2| 70
967-5| NA| NON-LOUVERED| 24-1/2| 67| 27-1/2| 70
CEILING ACCESS PANELS
CEILING ACCESS PANELS
FOR MODEL| PANELNO. (STD.)| PANELNO. (IAQ)|
DESCRIPTION| CEILING PANEL OPEINING| PANEL FRAME DIMS (OUTSIDE)
19CDX| 966| 966- M8| LOUVERED| 24-1/2| 46| 27-1/2| 49
966-1| NA| NON-LOUVERED| 24-1/2| 46| 27-1/2| 49
20/25CDX| 967| 967- M8| LOUVERED| 24-1/2| 52-1/2| 27-1/2|
55-1/2
967-1| NA| NON-LOUVERED| 24-1/2| 52-1/2| 27-1/2| 55-1/2
26/31CDX| 967-6| 967-6-M8| LOUVERED| 24-1/2| 60| 27-1/2| 63
967-7| NA| NON-LOUVERED| 24-1/2| 60| 27-1/2| 63
32/37CDX| 967-8| 967-8-MA| LOUVERED| 24-1/2| 67| 27-1/2| 70
967-5| NA| NON-LOUVERED| 24-1/2| 67| 27-1/2| 70
STANDARD PANELS
IAQ PANELS
966-M8, 967-M8 (accepts 2-20x20x1 filter) # 967-6-M8 (accepts 2-20x25x1
filter)
967-8-M8 (accepts 2-20x30x1 filter)
(GlasFloss ® Industries Series HV filter or equivalent is recommended)
Picture shown is a “-C” model with installed CDX (Available from the factory as a complete unit)
ENCLOSURE INSTALLATION SUPPORT FRAMING
ENCLOSURE CONNECTION LOCATIONS
CDX Series – Without pump 1-1/2 THROUGH 3 TONS
PERFORMANCE DATA
PERFORMANCE DATA CDX-HW
UNIT MODEL
| NOMINAL COOLING BTUH| PRESS. DROP (FT. WTR)| BTUH (1000) AT ENTERING
WATER TEMPERATURE Delta -T 20ºF & GPM
120ºF| GPM| 140ºF| GPM| 180ºF| GPM
19CDX-HW
| ****
18,000
| 0.7
2.0
3.3
| 10.3
12.0
12.9
| 1.0
1.2
1.3
| 14.4
16.8
18.0
| 1.4
1.7
1.8
| 22.6
26.4
28.3
| 2.3
2.6
2.8
20CDX-HW
| ****
18,000
| 0.8
2.1
4.1
| 10.9
12.9
13.7
| 1.1
1.3
1.4
| 15.3
18.0
19.2
| 1.5
1.8
1.9
| 24.0
28.3
30.2
| 2.4
2.8
3.0
25CDX-HW
| ****
24,000
| 2.1
4.1
6.6
| 14.7
15.9
16.5
| 1.5
1.6
1.7
| 20.6
22.2
23.1
| 2.1
2.2
2.3
| 32.4
34.9
36.3
| 3.2
3.5
3.6
26CDX-HW
| ****
24,000
| 2.2
4.3
6.8
| 15.7
17.0
17.6
| 1.6
1.7
1.8
| 22.0
23.8
24.7
| 2.2
2.4
2.5
| 34.6
37.4
38.8
| 3.5
3.7
3.9
31CDX-HW
| ****
30,000
| 2.2
4.3
6.8
| 17.3
18.8
19.6
| 1.7
1.9
2.0
| 24.2
26.3
27.5
| 2.4
2.6
2.8
| 38.0
41.3
43.2
| 3.8
4.1
4.3
32CDX-HW
| ****
30,000
| 2.8
5.4
8.5
| 18.4
20.1
21.1
| 1.8
2.0
2.1
| 25.8
28.2
29.5
| 2.6
2.8
3.0
| 40.5
44.3
46.4
| 4.1
4.4
4.6
37CDX-HW
| ****
36,000
| 2.8
5.4
8.5
| 19.7
21.7
22.8
| 2.0
2.2
2.3
| 27.6
30.4
31.9
| 2.8
3.0
3.2
| 43.4
47.8
50.1
| 4.3
4.8
5.0
PERFORMANCE DATA CDXX- HW
UNIT MODEL
| NOMINAL COOLING BTUH| PRESS. DROP (FT. WTR)| BTUH (1000) AT ENTERING WATER TEMPERATURE
Delta-T-20ºF & GPM
120ºF| GPM| 140ºF| GPM| 180ºF| GPM
12CDXX-HW
| 12,000| 0.7
2.0
3.3
| 8.4
9.6
10.1
| 0.1
1.0
1.0
| 11.7
13.4
14.2
| 1.2
1.3
1.4
| 18.4
21.1
22.4
| 1.8
2.1
2.2
19CDXX-HW
| 18,000| 0.7
2.0
3.3
| 10.3
12.0
12.9
| 1.0
1.2
1.3
| 14.4
16.8
18.0
| 1.4
1.7
1.8
| 22.6
26.4
28.3
| 2.3
2.6
2.8
20CDXX-HW
| 18,000| 0.8
2.1
4.1
| 10.9
12.9
13.7
| 1.1
1.3
1.4
| 15.3
18.0
19.2
| 1.5
1.8
1.9
| 24.0
28.3
30.2
| 2.4
2.8
3.0
25CDXX-HW
| 24,000| 2.1
4.1
6.6
| 14.7
15.9
16.5
| 1.5
1.6
1.7
| 20.6
22.2
23.1
| 2.1
2.2
2.3
| 32.4
34.9
36.3
| 3.2
3.5
3.6
26CDXX-HW
| 24,000| 2.2
4.3
6.8
| 15.7
17.0
17.6
| 1.7
1.9
2.0
| 22.0
23.8
24.7
| 2.4
2.6
2.8
| 34.6
37.4
38.8
| 3.8
4.1
4.3
31CDXX-HW
| 30,000| 2.2
4.3
6.8
| 17.3
18.8
19.6
| 1.7
1.9
2.0
| 24.2
26.3
27.5
| 2.4
2.6
2.8
| 38.0
41.3
43.2
| 3.8
4.1
4.3
32CDXX-HW
| 30,000| 2.8
5.4
8.5
| 18.4
20.1
21.1
| 1.8
2.0
2.1
| 25.8
28.2
29.5
| 2.6
2.8
3.0
| 40.5
44.3
46.4
| 4.1
4.4
4.6
37CDXX-HW
| 36,000| 2.8
5.4
8.5
| 19.7
21.7
22.8
| 2.0
2.2
2.3
| 27.6
30.4
31.9
| 2.8
3.0
3.2
| 43.4
47.8
50.1
| 4.3
4.8
5.0
NOTES:
- Heat BTUH is at 70º F EAT.
- Based on 20ºF Delta – T. Velocity not to exceed 4ft./sec.
- 120 degree and 180 degree data is supplied for boiler applications.
- Heating BTUH output will not exceed output of water heater.
- Approved for installation with 0″ clearance to combustible material.
- Use the capacities when First Co. “Flow Control Module” is used (# 940-3CV)
- Freeze protection standard on hot water and DX coils.
CDX Series – Without pump 1-1/2 THROUGH 3 TONS
PERFORMANCE DATA
PERFORMANCE DATA CDXQ
UNIT MODEL
| NOMINAL COOLING BTUH| PRESS. DROP (FT. WTR)|
BTUH (1000) AT ENTERING WATER TEMPERATURE Delta-T 20ºF & GPM
120ºF| GPM| 130ºF| GPM| 140ºF| GPM| 180ºF|
GPM
19CDXQ| 18,000| 3.3| 12.9| 1.3| 15.4| 1.5| 18.0| 1.8| 28.3| 2.8
20CDXQ| 18,000| 4.1| 13.7| 1.4| 16.5| 1.7| 19.2| 1.9| 30.2| 3.0
24/25CDXQ| 24,000| 4.1| 15.9| 1.6| 19.0| 1.9| 22.2| 2.2| 34.9| 3.5
26CDXQ| 24,000| 4.3| 17.0| 1.7| 20.4| 2.0| 23.8| 2.4| 37.4| 3.7
31CDXQ| 30,000| 4.3| 18.8| 1.9| 22.5| 2.3| 26.3| 2.6| 41.3| 4.1
32CDXQ| 30,000| 5.4| 20.1| 2.0| 24.2| 2.4| 28.2| 2.8| 44.3| 4.4
**37CDXQ***| 36,000| 5.4| 21.7| 2.2| 26.1| 2.6| 30.4| 3.0| 47.8| 4.8
PERFORMANCE DATA CDXQX
UNIT MODEL
| NOMINAL COOLING BTUH| PRESS. DROP (FT. WTR)|
BTUH (1000) AT ENTERING WATER TEMPERATURE Delta-T 20ºF & GPM
120ºF| GPM| 130ºF| GPM| 140ºF| GPM| 180ºF|
GPM
12CDXQX| 12,000| 3.3| 10.1| 1.0| 12.2| 1.2| 14.2| 1.4| 22.4| 2.2
19CDXQX| 18,000| 3.3| 12.9| 1.3| 15.4| 1.5| 18.0| 1.8| 28.3| 2.8
20CDXQX| 18,000| 4.1| 13.7| 1.4| 16.5| 1.7| 19.2| 1.9| 30.2| 3.0
25CDXQX| 24,000| 4.1| 15.9| 1.6| 19.0| 1.9| 22.2| 2.2| 34.9| 3.5
26CDXQX| 24,000| 4.3| 17.0| 1.7| 20.4| 2.0| 23.8| 2.4| 37.4| 3.7
31CDXQX| 30,000| 4.3| 18.8| 1.9| 22.5| 2.3| 26.3| 2.6| 41.3| 4.1
32CDXQX| 30,000| 5.4| 20.1| 2.0| 24.2| 2.4| 28.2| 2.8| 44.3| 4.4
37CDXQX| 36,000| 5.4| 21.7| 2.2| 26.1| 2.6| 30.4| 3.0| 47.8| 4.8
NOTES:
- Heat BTUH is at 70º F EAT.
- 120º F and 180º F data is supplied for boiler applications.
- Heating BTUH output will not exceed output of water heater.
- Approved for installation with 0″ clearance to combustible material.
- Freeze protection on hot water and DX coils.
- Based on 20º Delta-T,Velocity not to exceed 4ft./sec.
CDX Series 1-1/2 THROUGH 3 TONS
BLOWER DATA
BLOWER DATA WITH PSC MOTOR
UNIT MODEL| MOTOR (1)| MOTOR HP (120V)| MIN.
CKT. AMPACITY (120V)| MAX. CKT. PROTECTION| CFM vs.
EXTERNAL STATIC PRESSURE (3)
RPM| AMPS| 0.05| 0.10| 0.15| 0.20| 0.25|
0.30| 0.35| 0.40
19/20CDX| 1550| 2.3| 1/5| 3| 15| 710| 680| 650| 620| 590| 560| 530| 500
25/26CDX| 1550| 3.6| 1/4| 5| 15| 880| 840| 800| 760| 720| 680| 640| 600
31CDX| 1550| 4.6| 1/5| 6| 15| 1100| 1060| 1020| 980| 930| 880| 830| 780
32CDX| 1550| 4.6| 1/5| 6| 15| 1160| 1130| 1095| 1060| 1025| 990| 950|
910
37CDX| 1550| 4.6| 1/5| 6| 15| 1310| 1260| 1210| 1160| 1110| 1060| 1000|
940
NOTES:
- Units should not be applied to a system with less than 350 CFM/Ton airflow.
- Motors are 120V and operate on high speed for cool and low speed for heating.
- CFM vs. static at high motor speed.
- Add .05 static when enclosure and/or ceiling panel are used.
- 31, 32 and 37 CDX-HW have two motors and four blowers.
BLOWER DATA WITH ECM MOTOR
UNIT MODEL| MOTOR HP| SPEED TAP| TAP COLOR|
BHP| MOTOR AMPS| CFM vs. EXTERNAL STATIC
PRESSURE
0.10| 0.15| 0.20| 0.25| 0.30| 0.35| 0.40
12CDXX-HW
|
1/7
| OPTIONAL HIGH| GREEN| 0.08| 1.3| 565| 545| 525| 505| 485| 470| 450
STD. HIGH| ORANGE| 0.06| 1.0| 485| 460| 440| 420| 400| 385| 365
STD. LOW| YELLOW| 0.04| 0.5| 300| 275| 250| 225| 205| 185| —
19/20CDXX-HW
|
1/2
| OPTIONAL HIGH| GREEN| 0.22| 2.8| 760| 745| 730| 715| 700| 685| 670
STD. HIGH| ORANGE| 0.17| 2.1| 670| 650| 630| 615| 600| 588| 570
STD. LOW| YELLOW| 0.14| 1.6| 570| 555| 540| 520| 500| 480| —
25/26CDXX- HW
|
1/2
| OPTIONAL HIGH| GREEN| 0.30| 3.8| 980| 960| 940| 920| 900| 875| 850
STD. HIGH| ORANGE| 0.25| 3.0| 890| 870| 850| 830| 810| 790| 770
STD. LOW| YELLOW| 0.21| 2.5| 800| 775| 750| 725| 700| 675| —
31CDXX-HW
|
1/2
| OPTIONAL HIGH| WHITE| 0.40| 4.7| 1160| 1145| 1130| 1115| 1100| 1080| 1060
STD. HIGH| GREEN| 0.33| 3.8| 1060| 1040| 1020| 1005| 990| 975| 960
OPTIONAL MED| ORANGE| 0.28| 3.2| 970| 955| 940| 920| 900| 880| 860
STD. LOW| YELLOW| 0.23| 2.6| 870| 850| 830| 810| 790| 770| —
32CDXX-HW
|
1/2
| OPTIONAL HIGH| WHITE| 0.39| 4.8| 1220| 1200| 1180| 1155| 1125| 1095| 1065
STD. HIGH| GREEN| 0.27| 3.2| 1030| 1005| 985| 960| 940| 920| 900
STD. LOW| ORANGE| 0.22| 2.5| 905| 885| 860| 840| 820| 800| —
OPTIONAL LOW| YELLOW| 0.16| 1.8| 725| 705| 685| 670| 650| 630| —
37CDXX-HW
|
1/2 (2)
| OPTIONAL HIGH| WHITE| 0.45| 5.6| 1380| 1360| 1340| 1320| 1300| 1280| 1260
STD. HIGH| GREEN| 0.38| 4.7| 1290| 1270| 1250| 1225| 1200| 1175| 1150
STD. LOW| ORANGE| 0.31| 3.7| 1130| 1105| 1080| 1055| 1030| 1010| —
NOTES:
- Units should not be applied to a system with less than 350 CFM/Ton airflow.
- Shaded speeds are factory settings.
- Add .05 static when enclosure and/or ceiling panel are used.
- 37 CDXX have two motors and four blowers.
CDX Series – Without pump 1-1/2 THROUGH 3 TONS
ELECTRICAL DATA
ELECTRICAL DATA WITH PSC MOTOR
UNIT MODEL| MOTOR (1)| MOTOR HP (120V)| MIN.
CKT. AMPACITY (120V)| MAX. CKT. PROTECTION
RPM| AMPS
19/20CDX-HW| 1550| 2.3| 1/5| 3| 15
25/26CDX-HW| 1550| 3.6| 1/4| 5| 15
31CDX-HW| 1550| 4.6| 1/5| 6| 15
32CDX-HW| 1550| 4.6| 1/5| 6| 15
37CDX-HW| 1550| 4.6| 1/5| 6| 15
ELECTRICAL DATA WITH ECM MOTOR
UNIT MODEL
| MOTOR HP| AMPS| MIN. CIR AMPACITY| MAX CIR
PROTECTION
MOTOR
12CDXX-HW| 1/7| 2.0| 3| 15
19/20CDXX-HW| 1/2| 7.0| 9| 15
25/26CDXX-HW| 1/2| 7.0| 9| 15
31CDXX-HW| 1/2| 7.0| 9| 15
32CDXX-HW| 1/2| 7.0| 9| 15
37CDXX-HW| 1/2 (2)| 7.0| 16| 20
CDX Series – With pump 1-1/2 THROUGH 3 TONS
ELECTRICAL DATA
ELECTRICAL DATA WITH PSC MOTOR STANDARD PUMP
UNIT MODEL| MOTOR HP (120V)| AMPS (120V)| MIN.
CIR AMPACITY| MAX CIR PROTECTION
MOTOR| PUMP
19/20CDXQ| 1/5| 2.3| 0.57| 4| 15
24CDXQ| 1/5| 3.0| 0.57| 5| 15
25/26CDXQ| 1/4| 3.6| 0.57| 6| 15
31CDXQ| 1/5| 4.6| 0.57| 7| 15
32CDXQ| 1/5| 4.6| 0.57| 7| 15
37CDXQ| 1/5| 4.6| 0.57| 7| 15
ELECTRICAL DATA WITH PSC MOTOR AND UPGRADED PUMP
UNIT MODEL| MOTOR HP (120V)| AMPS (120V)| MIN.
CIR AMPACITY| MAX CIR PROTECTION
MOTOR| PUMP
19/20CDXQ| 1/5| 2.3| 0.84| 4| 15
25/26CDXQ| 1/4| 3.6| 0.84| 6| 15
31CDXQ| 1/5 (2)| 4.6| 0.84| 7| 15
32CDXQ| 1/5 (2)| 4.6| 0.84| 7| 15
**37CDXQ***| 1/5 (2)| 4.6| 0.84| 7| 15
ELECTRICAL DATA WITH ECM MOTOR AND STANDARD PUMP
UNIT MODEL| MOTOR HP| AMPS| MIN. CIR AMPACITY|
MAX CIR PROTECTION
MOTOR| PUMP
12CDXQX| 1/7| 2.0| 0.57| 4| 15
19/20CDXQX| 1/2| 7.0| 0.57| 10| 15
25/26CDXQX| 1/2| 7.0| 0.57| 10| 15
31CDXQX| 1/2| 7.0| 0.57| 10| 15
32CDXQX| 1/2| 7.0| 0.57| 10| 15
37CDXQX| 1/2 (2)| 7.0| 0.57| 17| 20
ELECTRICAL DATA WITH ECM MOTOR AND UPGRADED PUMP
UNIT MODEL| MOTOR HP| AMPS| MIN. CIR AMPACITY|
MAX CIR PROTECTION
MOTOR| PUMP
12CDXQX| 1/7| 2.0| .84| 4| 15
19/20CDXQX| 1/2| 7.0| .84| 10| 15
25/26CDXQX| 1/2| 7.0| .84| 10| 15
31CDXQX| 1/2| 7.0| .84| 10| 15
32CDXQX| 1/2| 7.0| .84| 10| 15
37CDXQX| 1/2 (2)| 7.0| .84| 17| 20
GUIDE SPECIFICATIONS
UNIT
All fan coils are manufactured with 20 to 22-gauge galvanized steel to resist
corrosion. All units are approved for installation with “0” clearance to
combustible material. Piping, drain, and wiring connections are readily
accessible and mounting holes and/or slots are predrilled to save installation
time and field labor expense. Exposed units and/or panels have a baked-on
powder coat finish.
COILS
Coils have 3/8” O.D. copper tubing expanded to high-efficiency aluminum fins.
Each Coil is factory tested to 450 psig.
DRAIN PANS
Drain pan is made from heavy gauge galvanized steel with “ folded corner
joints” Drain pan is insulated with a U.L. Listed closed cell fire retardant
foam insulation to prevent sweating.
BLOWER ASSEMBLIES
All blower wheels are centrifugal, forward curved, and dynamically balanced
for smooth, quiet operation. Blower assemblies can be easily removed for
service.
MOTORS
Standard motors are PSC type with internal thermal overload protection. Motors
have permanently lubricated sleeve bearings for long life. All motors are
resiliently mounted with rubber bushings to assure quiet, vibration-free
operation and are easily removed. Ecm motors should have multi-speed
connections or speed jumper changes. Motors have permanently lubricated sleeve
bearings for long life. All motors are resiliently mounted with rubber
bushings to assure quiet, vibration-free operation and are easily removed.
Water coils and pumps shall be NSF/ASNI 169:2016 certified for public health
and should contain less than 2% lead. All water coils should have a check
valve internal to the pump and have a air purge valve factory installed.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>