SENVA RoFlex Universal Output Current TransducerC-3146 RoFlex Universal Output Current Transducer Instruction Manual
- September 14, 2024
- SENVA
Table of Contents
SENVA RoFlex Universal Output Current TransducerC-3146 RoFlex Universal
Output Current Transducer
FAQs
- Symptom: No output signal
- Possible Solution: Check wiring connections and ensure proper setup of the sensor as per installation instructions.
- Symptom: Wrong output current
- Possible Solution: Verify the selector switch setting matches the monitored current range and recalibrate if necessary.
PRODUCT INFORMATION
DANGER: Failure to follow these instructions will result in death or serious injury.
- Hazard of electrical shock, explosion, and arc flash
- Follow ALL requirements in NFPA 70E for safe work practices and Personal Protective Equipment (USA) and other applicable local codes when installing this product
- Only qualified electrical personnel should install this product.
- Read, understand, and follow all instructions thoroughly
- Install only on insulated conductors
- Lock out and tag out all power sources before installation. Use properly rated voltage sensing instrument to determine no voltage is present
WARNING: Failure to follow these instructions could result in death or serious injury.
- Automated equipment may start without warning
- Equipment monitored/operated by this device may start without warning. Keep clear of apparatus at all times
IMPORTANT WARNINGS
- Only qualified trade installers should install this product
- This product is not intended for life-safety applications
- Do not install in hazardous or classified locations
- The installer is responsible for all applicable codes
- This product must be installed in a suitable electrical enclo-sure
INSTALLATION
Disconnect, lock out, and tag out all power supplies during installation
- Determine a mounting location for the sensor near the conductor to be monitored. The sensor should be located AT LEAST 1/2” from any uninsulated- ed conductor.
- The sensor features a flexible coil that wraps around and allows the sensor to hang on the conductor if local codes permit. The enclosure is provided with 2 slots for securing the sensor using zip ties.
- Wrap coil around an INSULAT- ED CONDUCTOR ONLY, 600VAC MAX to be monitored.
- Wire the output of the sensor to a control panel analog input appropriate for the output type selected. See wiring examples. Tighten terminals to 3.5 in-lb.
SETUP
- The Sensor is factory-calibrated to three ranges. No field calibration is required.
- Move the selector switch to the desired factory-calibrated range. The selected range should be greater than the maximum expected monitored current.
WIRING EXAMPLES
PRODUCT APPLICATION LIMITATION: Senva products are not designed for life or safety applications. Senva products are not intended for use in critical applications such as nuclear facilities, human implantable devices, or life support. Senva is not liable, in whole or in part, for any claims or damages arising from such uses.
OPERATION
The RoFlexTM provides a universal output signal proportional to the monitored current. A switch allows field selection of desired ampreage range.
Typical load status applications include:
- Load trending
- Monitoring process motors and pumps
- Heater current monitoring
ORDERING
Troubleshooting
Symptom | Causes | Remedy |
---|---|---|
No output signal | No excitation voltage Backward wiring | Check excitation |
voltage Check polarity
Wrong output current| Incorrect scaling| Verify controller scaling
SPECIFICATIONS
Amperage Range | Varies by model 50 to 6000A |
---|---|
Output Type | Universal (2-wire 4-20mA, 3-wire 0-5V/0-10V/4-20mA) |
Accuracy | +/-2% F.S. over 10 to 100% range |
Temperature Rating | Maximum surrounding air, 60 ° C |
Insulation Class | 600V RMS. For use on insulated conductors only. Use minimum |
75 ° C insulated conductors Must be installed at least 1/2” away from any
uninsulated conductor
Sensor Power| 12 to 30VDC/24VAC
Frequency Range| 50/60Hz
Dimensions ( LxWxH)| 3.5” x 1.6” x 0.8”
Terminal Tightening Torque| 0.5 N*m
Wire| 21-24 AWG Copper
Compliance| cUL, UL, CE, RoHS
For use in Pollution Degree 2 Environment Revised 07/1/2024 Document
152-0210-0D