Symbols
P1 | Pressure regulation for stage 1 |
---|---|
P2 | Pressure regulation for stage 2 |
S | Suction line G 1/4 in |
G | Return line G 1/4 in |
Nozzle conn. G 1/8 in | |
F | Cartridge filter |
Vacuum meter conn. G 1/8 in | |
Pressure gauge conn. G 1/8 in |
Installation
Fuel gas oil 6 mm2/s (cSt)
H
m
| Ø4 mm| Ø5 mm| Ø6 mm| Ø4 mm| Ø5 mm| Ø6 mm| Ø5 mm| Ø6 mm| Ø8 mm
---|---|---|---|---|---|---|---|---|---
4,0| 51| 100| 100| 26| 62| 100| 31| 65| 100
3,5| 45| 100| 100| 22| 55| 100| 27| 57| 100
3,0| 38| 94| 100| 19| 47| 97| 23| 49| 100
2,5| 32| 78| 100| 16| 39| 81| 20| 40| 100
2,0| 26| 62| 100| 13| 31| 65| 16| 32| 100
1,5| 19| 47| 97| 10| 23| 49| 12| 24| 77
1,0| 13| 31| 65| 6| 16| 32| 8| 16| 51
0,5| 6| 16| 32| 3| 8| 16| 4| 8| 26
Nozzle capacity| 2,5 kg/h| 5 kg/h| 10 kg/h
Fuel gas oil 6 mm2/s (cSt)
H
m
| Ø4 mm| Ø5 mm| Ø6 mm| Ø4 mm| Ø5 mm| Ø6 mm| Ø5 mm| Ø6 mm| Ø8 mm
---|---|---|---|---|---|---|---|---|---
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
| 100
95
89
83
77
71
64
58
| 100
100
100
100
100
100
100
100
| 100
100
100
100
100
100
100
100
| 51
48
45
41
38
35
32
29
| 100
100
100
100
94
86
79
71
| 100
100
100
100
100
100
100
100
| 62
58
54
51
47
43
39
35
| 100
100
100
100
97
89
81
73
| 100
100
100
100
100
100
100
100
Nozzle capacity| 2,5 kg/h| 5 kg/h| 10 kg/h
Fuel gas oil 6 mm2/s (cSt)
H
m
| Ø4 mm| Ø5 mm| Ø6 mm| Ø 4 mm| Ø 5 mm| Ø 6 mm| Ø 5 mm| Ø 6 mm| ØÆ 8 mm
---|---|---|---|---|---|---|---|---|---
0| 52| 100| 100| 26| 63| 100| 32| 66| 100
–0,5| 46| 100| 100| 23| 56| 100| 28| 58| 100
–1,0| 40| 97| 100| 20| 48| 100| 24| 50| 100
–1,5| 33| 81| 100| 17| 41| 84| 20| 42| 100
–2,0| 27| 66| 100| 14| 33| 69| 17| 34| 100
Nozzle capacity| 2,5 kg/h| 5 kg/h| 10 kg/h
Fuel gas oil 6 mm2/s (cSt)
H
m
| 2800 min–1
---|---
BFP 3| BFP 5
Ø6 mm| Ø8 mm| Ø 10 mm| Ø 6 mm| 8 mm| Ø 10 mm
4,0| 33| 100| 100| 21| 67| 100
3,5| 31| 98| 100| 20| 63| 100
3,0| 29| 91| 100| 19| 59| 100
2,5| 27| 85| 100| 17| 55| 100
2,0| 25| 79| 100| 16| 51| 100
1,5| 23| 72| 100| 15| 46| 100
1,0| 21| 66| 100| 13| 42| 100
0,5| 19| 60| 100| 12| 38| 94
0| 17| 53| 100| 11| 34| 84
–0,5| 15| 47| 100| 10| 30| 74
–1,0| 13| 41| 99| 8| 26| 64
–1,5| 11| 34| 84| 7| 22| 54
–2,0| 9| 28| 68| 6| 18| 44
–2,5| 7| 22| 53| 4| 14| 34
–3,0| 5| 15| 37| 3| 10| 24
–3,5| 3| 9| 22| 2| 6| 14
–4,0| 1| 3| 6| 1| 2| 4
Technical data
Oil types| Standard fuel gas oil and fuel gas oil acc. to DIN V 51603-6 EL A
Bio 10
---|---
Viscosity range| (1,3) 1,8-12 mm2/s (cSt)
Speed| 2400-3450 min-1
Pressure range1 Factory setting| 7-25 bar
Stage 1: 10 bar
Stage 2: 13 bar
Coil voltage| Stated on coils
Max. 12 bar to 1.3 cSt., max. 15 bar to 1,8 cSt.
Connections
Connections (fig. 1)
Bleeding
- Bleeding the oil pump is only necessary on 1-pipe systems.
- Bleeding is only possible at the P-port. On 2-pipe systems, the pump is automatically bled through the return pipe.
Filter replacement with cartridge filter (fig. 2)
- Unscrew the filter plug in the cover with a 4 mm key and pull out the cartridge filter. Insert if necessary a screwdriver between the filter and plug and carefully twist the filterout. Scrap the filter and press a new filter onto the plug!
- Reassemble the cartridge filter and tighten it slightly.
Conversion from 1 to 2-pipe operation
Conversion from 1 to 2-pipe operation (fig. 3)
-
1-pipe operation: without screw
-
2-pipe operation: screw fitted
Suction line lengths in meters
- The table is applicable for standard gas oil (Heizöl-EL) having a normal trade quality per applicable standards.
- When starting up a system with an empty pipe, the oil pump should not operate without oil for any more than 5 min. It is presumed that the pump contains some oil before starting up.
Attention
The oil pumps are used only for oil burners.
Please note that the solenoid valve must be replaced after 250.000 operations or 10 years (approved life expectancy).
Danfoss A/S
Heating Segment • heating.danfoss.com • +45 7488 2222 • E-Mail:
heating@danfoss.com.
Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are the property of the respective companies. Danfoss and all Danfoss logotypes are trademarks of Danfoss A/S. All rights reserved.
© Danfoss | DHS-SDDT/DK | 2019.05.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>