SmartGen HMC4000RM Remote Monitoring Controller User Manual

September 4, 2024
SmartGen

SmartGen HMC4000RM Remote Monitoring Controller User Manual

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Content
2017-08-29 1.0 Original release
2018-05-19 1.1 Change installation dimensions drawing.
2021-04-01 1.2 Change “A-phase power factor” described in 4th Screen of

Screen Display to “C-phase power factor”.
2023-12-05| 1.3| Change lamp test description;Add contents and ranges of parameter setting.

OVERVIEW

HMC4000RM remote monitoring controller integrates digitisation, internationalisation and network technology which are used for remote monitoring system of single unit to achieve remote start/stop functions. It fit with LCD display, and optional Chinese/English languages interface. It is reliable and easy to use.

PERFORMANCE AND CHARACTERISTICS

Main features are as follows:

  • 132*64 LCD with backbit, optional Chinese/English interface display, and push-button operation;
  • Hard-screen acrylic material been used to protect screen with great wear-resisting and scratch-resisting functions;
  • Silicone panel and buttons with great performance to work in high/low temperature ambient;
  • Connect to host controller via RS485 port to achieve remote start/stop control in remote control mode;
  • With LCD brilliance level (5 levels) adjusting button, it is convenient to use in different occasion;
  • Waterproof security level IP65 due to rubber seal installed between the controller enclosure and panel fascia.
  • Metal fixing clips are used;
  • Modular design, self extinguishing ABS plastic enclosure and embedded installation way; small size and compact structure with easy mounting.

SPECIFICATION

Table 2 Technical Parameters

Items Content
Working Voltage DC8.0V to DC35.0V, uninterrupted power supply.
Power Consumption <2W
RS485 Communication Baud Rate 2400bps/4800bps/9600bps/19200bps/38400bps can

be set
Case Dimension| 135mm x 110mm x 44mm
Panel Cutout| 116mm x 90mm
Working Temperature| (-25~+70)ºC
Working Humidity| (20~93)%RH
Storage Temperature| (-25~+70)ºC
Protection Level| Front panel IP65
**** Insulation Intensity| Apply AC2.2kV voltage between high voltage terminal and low voltage terminal;The leakage current is not more than 3mA within 1min.
Weight| 0.22kg

OPERATION

Table 3 Push buttons Description

Icons Function Description
Stop Stop running generator in remote control mode;When generator set is

at rest, pressing and holding the button for 3 seconds will test indicator lights (lamp test);
| Start| In remote control mode, press this button will start generator-set.
| Dimmer +| Press this button to increase LCD brightness.
| Dimmer –|
Press this button to decrease LCD brightness.
| Lamp Test| After pressing this button, LCD highlighted with black and all LEDs on the front panel are illuminated. Hold and press this button to eliminate the alarm information of local controller.
| Set/Confirm| Function is standby.
| Up/Increase| Press this button to scroll the screen up.
| Down/Decrease| Press this button to scroll the screen down.

SCREENS DISPLAY

Table 4 Screen Display

1st Screen Description

Generator is running screen display
| Engine speed, generator-set UA/UAB voltage
Oil pressure, Load power
Engine status
Generator is at rest screen display
| Engine speed, water temperature
Oil pressure, power supply voltage
** Engine status
2nd Screen| Description
| Engine water temperature, controller power supply
Engine oil temperature, charger voltage
Engine total running time
Engine start attempts, controller currently mode
3rd Screen| Description
| Wire voltage: Uab,Ubc,Uca
Phase voltage: Ua, Ub,Uc
Load current: IA,IB,IC
Load active power, load reactive power
Power facter, frequency
4th Screen| Description
| Active power, reactive power, apparent power display
A-phase kW, A-phase kvar, A-phase kvA
B-phase kW, B-phase kvar, B-phase kvA
C-phase kW, C-phase kvar, C-phase kvA
A-phase power factor, C-phase power factor, C-phase power factor
5th Screen| Description
| **
Accumulated active electric energy
** Accumulated reactive electric energy
6th Screen| Description
| Input port name
Input port status
Output port name
Output port status
system present time
7th Screen| Description**
| Alarm type
Alarm name

Remark: if there is no electric parameters display, the 3rd, 4th, and 5th screen will be shielded automatically.

CONTROLLER PANEL AND OPERATION

**CONTROLLER PANEL

Fig.1 HMC4000RM Front Panel**

NOTE : Part of indicator lights illustration:
Alarm Indicators: slowly flash when warning alarms occurred; fast flash when shutdown alarms occurred; light is off when there are no alarms.
Status Indicators: Light is off when gen set is standby; flash once per second during start up or shut down; always on when normal running.

REMOTE START/STOP OPERATION

ILLUSTRATION

Press of the host controller HMC4000 to enter into remote control mode, after remote control mode is active, users can remotely control HMC4000RM start/stop operation.

REMOTE START SEQUENCE

  • When remote start command is active, “Start Delay” timer is initiated;
  • “Start Delay” countdown will be displayed on LCD;
  • When start delay is over, preheat relay energizes (if configured), “preheat delay XX s” information will be displayed on LCD;
  • After the above delay, the Fuel Relay is energised, and then one second later, the Start Relay is engaged. Genset is cranked for a pre-set time. If genset fails to fire during this cranking attempt then the fuel relay and start relay are disengaged for the pre-set rest period; “crank rest time” begins and wait for the next crank attempt.
  • Should this start sequence continue beyond the set number of attempts, the start sequence will be terminated, and Fail to Start fault alarm will be displayed on the alarm page of LCD.
  • In case of successful crank attempt, the “Safety On” timer is activated. As soon as this delay is over, “start idle” delay is initiated (if configured).
  • After the start idle, controller enters into hi-speed “Warning Up” delay (if configured).
  • After “Warning Up” delay expired, the generator will enter into Normal Running status directly.

REMOTE STOP SEQUENCE

  • When the remote stop command is active, controller starts hi-speed “Cooling” delay (if configured).
  • Once this “Cooling” delay has expired, the “Stop Idle” is initiated. During “Stop Idle” Delay (if configured), idle relay is energised.
  • Once this “Stop Idle” has expired, the “ETS Solenoid Hold” begins, and whether or not stop completely will be judged automatically. ETS relay is energized while fuel relay is de-energized.
  • Once this “ETS Solenoid Hold” has expired, the “Wait for Stop Delay” begins. Complete stop is detected automatically.
  • Generator is placed into its standby mode after its complete stop. Otherwise, fail to stop alarm is initiated and the corresponding alarm information is displayed on LCD (If generator is stop successfully after “fail to stop” alarm has initiated, engine will enter into standby status)

WIRING CONNECTION

**HMC4000RM controller back panel layout:

Fig.2 Controller Back Panel
**

Table 5 Description of Terminal Connection

No. Function Cable Size Remark
1 B- 2.5mm2 Connected with negative of power supply.
2 B+ 2.5mm2 Connected with positive of power supply.
3 NC Not used
4 CAN H 0.5mm2 **** This port is expand monitoring interface and reserved

temporarily.Shielding line is recommended if used.
5| CAN L| 0.5mm2
6| CAN Common Ground| 0.5mm2
7| RS485 Common Ground| /| Impedance-120Ω shielding wire is recommended, itssingle-end earthed. This interface is used to connect with host controller HMC4000.
8| RS485+| 0.5mm2
9| RS485-| 0.5mm2

NOTE : USB port in the back is system upgrade port.

RANGES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

Table 6 Contents and Ranges of Parameter Setting

No. Item Range Default Description

Module Setting
1| RS485 Baud Rate| (0-4)| 2| 0: 9600bps
1: 2400bps2: 4800bps
3: 19200bps
4: 38400bps
2| Stop Bit| (0-1)| 0| 0:2 Bits
1:1 Bit

TYPICAL APPLICATION

Fig.3 HMC4000RM Typical Application Diagram

INSTALLATION

FIXING CLIPS

  • Controller is panel built-in design; it is fixed by clips when installed.
  • Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
  • Pull the fixing clip backwards (towards the back of the module) ensuring two clips are inside their allotted slots.
  • Turn the fixing clip screws clockwise until they are fixed on the panel.

NOTE : Care should be taken not to over tighten the screws of fixing clips.

OVERALL DIMENSIONS AND CUTOUT

Fig.4 Case Dimensions and Panel Cutout

TROUBLESHOOTING

Table 7 Troubleshooting

Problem Possible Solution
Controller no response with power. Check starting batteries;

Check controller connection wiring;
Check DC fuse.
Communication failure| Check whether RS485 connections are correct;Check whether communication baud rate and stop bit are consistent.


References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals