Carrier 48LC Single Package Rooftop Unit User Manual
- August 30, 2024
- Carrier
Table of Contents
- 48LC Single Package Rooftop Unit
- Product Specifications:
- Product Usage Instructions:
- Safety Considerations:
- To Light Unit:
- To Shut Off Unit:
- Routine Maintenance & Care:
- Regular Dealer Maintenance:
- Before You Call for Service:
- Q: What should I do if I smell gas near the unit?
- Q: How can I ensure safety during maintenance?
48LC Single Package Rooftop Unit
“`html
Product Specifications:
- Model: 48LC
- Type: Single-Package Rooftop Unit (RTU)
- Heating: Gas
- Cooling: Electric
- Nominal Tons: 6 to 23
- Refrigerant: Puronr (R-410A)
Product Usage Instructions:
Safety Considerations:
Proper installation, adjustment, and maintenance are crucial to
prevent fire, electrical shock, or other hazards. Always consult a
qualified professional for assistance and use authorized kits or
accessories for modifications. Follow safety codes, wear safety
glasses, and have a fire extinguisher available. Refer to local
building codes for special requirements.
To Light Unit:
-
Ensure gas supply is on and functioning properly.
-
Follow the unit’s specific lighting instructions provided in
the manual. -
If using an electric cooling function, ensure the electrical
supply is connected and operational.
To Shut Off Unit:
-
In case of gas supply failure or overheating, shut off the gas
valve to the furnace first. -
Then, turn off the electrical supply to the unit.
Routine Maintenance & Care:
Regular maintenance is essential for optimal performance.
Equipment owners should follow maintenance guidelines provided in
the manual. Ensure the main power switch to the unit is turned off
and locked out before performing any maintenance tasks.
Regular Dealer Maintenance:
For more complex maintenance tasks, it is recommended to seek
assistance from authorized dealers or service agencies. They can
provide specialized care to keep the unit in top condition.
Before You Call for Service:
Before contacting service personnel, check for common issues and
troubleshooting tips outlined in the manual. This may help identify
simple problems that can be resolved without professional
assistance.
FAQ:
Q: What should I do if I smell gas near the unit?
A: If you detect a gas odor, leave the building
immediately, do not operate any electrical switches, and contact
your gas supplier or fire department for further instructions.
Q: How can I ensure safety during maintenance?
A: Before conducting any maintenance, always
turn off the main power switch to the unit and follow proper
lockout procedures to prevent electrical shock hazards.
“`
48LC
Single — Package Rooftop Unit (RTU) Gas Heating/Electric Cooling Units 6 to 23
Nominal Tons with Puronr (R — 410A) Refrigerant
User’s Information Manual
NOTE: Read the entire instruction manual before starting the installation.
! WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings
exactly could result in dangerous operation, serious injury, death or property
damage. Improper servicing could result in dangerous operation, serious
injury, death or property damage. S Before servicing, disconnect all
electrical power to
the unit.
S When servicing controls, label all wires prior to disconnecting. Reconnect
wires correctly.
S Verify proper operation after servicing.
NOTE TO INSTALLER:
This manual should be left with the equipment owner.
TABLE OF CONTENTS
PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1 TO LIGHT
UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 TO SHUT OFF
UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 ROUTINE
MAINTENANCE & CARE FOR THE EQUIPMENT OWNER . . . . . . . . . . . . . . . . . 5
REGULAR DEALER MAINTENANCE . . . . . . . . . . . . 7 BEFORE YOU CALL FOR
SERVICE . . . . . . . . . . . . . 8
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use
can cause fire, electrical shock, or other conditions which may cause personal
injury or property damage. Consult a qualified installer, service agency or
your distributor or branch for information or assistance. The qualified
installer or agency must use factory- authorized kits or accessories when
modifying
this product. Refer to the individual instructions packaged with the kits or
accessories when installing.
Follow all safety codes and wear safety glasses. Have fire extinguisher
available. Read these instructions thoroughly and follow all warnings or
cautions attached to the unit. Consult local and state building codes and
Sheet Metal and Air Conditioning National Association (SMACNA) for special
installation requirements.
Recognize safety information. This is the safety- alert symbol . When you see
this symbol on the unit or in instructions and manuals, be alert to the
potential for personal injury. Understand the signal words DANGER, WARNING,
and CAUTION. These words are used with the safety- alert symbol. DANGER
identifies the most serious hazards, which will result in severe personal
injury or death. WARNING signifies hazards, which could result in personal
injury or death. CAUTION is used to identify unsafe practices, which may
result in minor personal injury or product and property damage. NOTE is used
to highlight suggestions which will result in enhanced installation,
reliability, or operation.
Should the gas supply fail to shut off or if overheating occurs, shut off the
gas valve to the furnace (see Figs. 2 through 4) before shutting off the
electrical supply.
! WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death. What
to do if you smell gas: S Leave the building.
S Do not try to light any appliance.
S Do not touch any electrical switch; do not use any phone in your building.
S Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
S If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
! WARNING
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal
injury, death and/or property damage. Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
! WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in
personal injury, death and/or property damage. Before performing maintenance,
be sure main power switch to unit is turned off and lockout tag is installed.
There may be more than one power switch.
! WARNING
ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in
personal injury, death and/or property damage. Do not use this equipment if
any part has been under water. A flood- damaged equipment is extremely
dangerous. Attempts to use the equipment can result in fire or explosion. A
qualified service agency should be contacted to inspect the equipment and to
replace all gas controls, control system parts, electrical parts that have
been wet or the equipment if deemed necessary.
Your rooftop heating/cooling unit is equipped with an automatic, direct spark
ignitor and an induced- draft, combustion blower.
! WARNING
PERSONAL INJURY HAZARD Failure to follow this warning could result in personal
injury, death and/or property damage. Burners will light automatically. Do not
attempt to light by hand.
! CAUTION
CUT HAZARD Failure to follow this caution may result in personal injury. When
removing access panels or performing maintenance functions inside your unit,
be aware of sharp sheet metal parts and screws. Although special care has been
taken to reduce sharp edges inside the unit, be extremely careful when
handling parts or reaching into the unit.
IMPORTANT FACTS
S DO: READ AND UNDERSTAND THIS MANUAL.
S DO: Have your equipment and vent system inspected annually by a qualified
service technician.
S DO: Inspect your filter monthly and clean or replace when needed.
S DO: Provide adequate airflow to the equipment for efficient combustion and
safe ventilation.
S DO Make sure: 1. All flue and vent connections are clear and free of
obstructions, are leak free, and not damaged. 2. Duct connections are leak
free and physically sound. 3. The unit base support is free of cracks, gaps,
etc. 4. There are no signs of furnace deterioration. 5. Burners are aligned
correctly. 6. Follow routine maintenance inspection. S DO NOT: Keep
combustible materials, gasoline, and other flammable liquids or vapors around
your equipment.
S DO NOT: Cover your equipment in any manner.
S DO NOT: Store anything (including trash or debris) near your equipment.
S DO NOT: In any way block or restrict airflow around your equipment.
S DO NOT: Contaminate the air used for combustion of your equipment with any
kind of chemical or fumes. This could also cause heat exchangers, metal vent
systems or components to deteriorate.
TO LIGHT UNIT
! WARNING
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal
injury, death and/or property damage.
1. Do not turn off the electrical power to unit without first turning off the
gas supply.
2. Before attempting to start the gas heating section, familiarize yourself
with all the procedures that must be followed.
3. Never attempt to manually light the burners on the unit with a match,
lighter, or any other flame. If the electric sparking device fails to light
the burners, refer to the shutdown procedures, then call your dealer as soon
as possible.
Step 1 — Set room thermostat/unit controller to the lowest temperature setting
and set the SYSTEM switch to HEAT or AUTO position. See Fig. 1.
2
MAIN ON
®
Fig. 1 – Thermostat/Unit Controller
C09296
Step 2 — Turn off the gas supply by closing the gas supply shut- off valve
(external to RTU unit). See Fig. 2 and 3 (depending on the size of the unit)
for locations.
Gas Supply Shut Off Valve (Field Supplied)
OFF
LOCK-OUT TAG
C07331
Fig. 5 – RTU Main Disconnect – Electrical Supply
Step 4 — Remove the gas component access panel. For location of the gas
component access panel, see Fig. 6 and 7 (depending on the size of the unit).
CONTROL BOX & GAS COMPONENT ACCESS PANEL
C07358
Fig. 2 – Gas Supply Shut- Off Valve Location 6 to 10 Ton Units (Thru the base
gas supply shown.)
RTU GAS VALVE
C13212
Fig. 6 – Access Panel Locations 6 to 10 Ton Units
Gas Supply Shut Off Valve (Field Supplied)
C08485
Fig. 3 – Gas Supply Shut- Off Valve Location 12.5 to 23 Ton Units
GAS COMPONENT ACCESS PANEL
FILTER ACCESS PANEL
CONTROL BOX ACCESS PANEL
C12002
Fig. 7 – Access Panel Locations 12.5 to 23 Ton Units
Fig. 4 – Gas Supply Shut Off Valve
C07330
Step 3 — Turn off the electrical supply to the unit by switching the RTU main disconnect to OFF. Then, ensure personal safety by installing a lockout tag on the disconnect.
C08487
Fig. 8 – Gas Component Access Panel Removal
3
Step 5 — Move the RTU gas valve on/off switch to the OFF position and wait 5 minutes.
Single-Stage RTU gas valve
Two-Stage RTU gas valve
300k BTU/Hr Two-Stage RTU gas valve
On/Off Switch
On/Off Switch
OFF
ON
C08469
Fig. 9 – Single- and Two- Stage RTU Gas Valves
Step 6 — Move the RTU gas valve on/off switch to the ON position. Step 7 —
Replace the gas component access panel.
C08490
Fig. 10 – Replacing the Gas Component Access Panel Step 8 — Remove disconnect
lockout tag and restore power to the unit by switching the RTU main disconnect
to ON.
C07336
Fig. 11 – RTU Main Disconnect – Electrical Supply Step 9 — Turn on the gas
supply by opening the gas supply shut- off valve.
! WARNING
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal
injury, death or property damage. If the main burners fail to light, or the
blower fails to come on, shut down gas heating section and call your dealer
for service.
Step 11 — Set the room thermostat/unit controller heating setpoint to desired
temperature setting.
TO SHUT UNIT OFF
! WARNING
FIRE, EXPLOSION HAZARD Failure to follow this warning could result in personal
injury, death and/or property damage.
1. Turn off gas supply by closing the gas line supply valve. Then, turn off
the electrical power supply to the unit by switching the disconnect to off.
Install lockout tag before servicing or performing maintenance.
2. Do not turn off the electrical power to unit without first turning off the
gas supply.
Should overheating occur, or the gas supply fail to shut off, shut off the gas
valve in the unit (by moving on/off switch to off) before shutting off the
electrical supply. Step 1 — Set room thermostat/unit controller heat setpoint
to the lowest temperature setting and set the SYSTEM switch to OFF.
Fig. 12 – Gas Supply Shut Off Valve
C07337
Step 10 — To start unit, set room thermostat/unit controller heat setpoint to slightly above room temperature. The induced- draft combustion air fan will start. The RTU gas valve will open and main burners should ignite within 5 seconds. If the burners do not light, there is a 22- second delay. Burners will attempt to ignite within 5- seconds. Each time the burner fails to light, the 22- second time delay is repeated. If the burner does not light within 15 minutes, the unit will lockout the gas heat. To reset after a lockout, turn off the main electrical supply to the unit by switching the RTU main disconnect to OFF for a minimum of five seconds. Repeat Steps 1- 10. If burners still do not light, call for service.
®
C09296
Fig. 13 – Thermostat/Unit Controller
Step 2 — Turn off gas supply by closing the gas supply shut- off valve
(external to RTU unit). See Fig. 2 and 3 (depending on the size of the unit)
for locations.
Fig. 14 – Gas Supply Shut Off Valve
C07330
4
Step 3 — Turn off the electrical supply to the unit by switching the RTU main
disconnect to off. Then, ensure personal safety by installing a lockout tag on
the disconnect.
MAIN ON
OFF
LOCK-OUT TAG
C07331
Fig. 15 – RTU Main Disconnect – Electrical Supply
Step 4 — Remove the gas component access panel. See Fig. 6 and 7 (depending on
the size of the unit) for locations.
C08487
Fig. 16 – Gas Component Access Panel Removal
Step 5 — Move the RTU gas valve on/off switch to the OFF position and wait 5 minutes.
Single-Stage RTU gas valve
Two-Stage RTU gas valve
300k BTU/Hr Two-Stage RTU gas valve
On/Off Switch
On/Off Switch
OFF
ON
C08469
Fig. 17 – Single- and Two- Stage Gas Valves
Step 6 — Replace the gas component access panel.
C08490
Fig. 18 – Replacing the Gas Component Access Panel
Step 7 — If the unit is being shut down because of a malfunction, contact your
dealer as soon as possible. DO NOT proceed to step 8.
Step 8 — If the unit is being shut down because the heating season has ended,
remove the disconnect lockout tag and restore electrical power to the unit by
switching the RTU main disconnect to ON and then set thermostat/unit
controller to the COOL position to ensure operation of the cooling system
during the cooling season.
C07336
Fig. 19 – RTU Main Disconnect – Electrical Supply
ROUTINE MAINTENANCE & CARE FOR THE EQUIPMENT OWNER
While some maintenance can be performed by laymen, most should be performed by
skilled, experienced personnel. Follow the recommended service maintenance
schedule, and modify it as necessary for your application/environment. For
instance, dusty areas may require more frequent filter changes.
After performing any maintenance or service on the unit, be sure all panels
are securely fastened in place to prevent rain from entering unit cabinet and
to prevent disruption of the correct unit airflow pattern.
! WARNING
FIRE AND EQUIPMENT DAMAGE HAZARD Failure to follow this warning could result
in personal injury and damage to equipment. Do not use this unit if any part
has been under water. Immediately call a qualified service technician to
inspect the unit and to replace any part of the control system and gas control
that has been under water.
To ensure proper functioning of the unit, flow of combustion and ventilating
air must not be obstructed from reaching the unit. Follow service and
performance clearances as listed in the product data.
Consider the following information before maintaining or servicing equipment:
Compressor
All compressors are factory supplied with a normal charge of the correct type
refrigeration- grade oil in them and should not require additional oil.
5
Indoor Air Filter(s)
! WARNING
FIRE AND EQUIPMENT DAMAGE HAZARD Failure to follow this warning could result
in personal injury and damage to equipment. Never operate unit without filters
in place. The accumulation of dirt, dust or lint on the internal parts of your
unit can cause fire or a loss of efficiency. Damage to the blower motor and/or
compressors could also result.
Indoor air filter(s) should be checked every 3 or 4 weeks (application
dependant) and changed or cleaned when necessary. See Figs. 20 and 21
(depending on size of unit) for air filter access panel location. See Table 1
for replacement filter dimensions. S Remove the screws securing the filter
access panel. S While holding filters, tilt upper filter rack. S Remove
filters by pulling up and out toward you from
the track. S Inspect filters. Clean or replace as necessary. S Follow
direction of airflow arrows as noted on filter
frame when returning filters to rack. S Reinstall air filter access panel. If
you have difficulty in locating your air filter or if you have questions
concerning proper filter maintenance, contact your dealer for instructions.
When replacing your unit filters, always use the same size and type of filter
that was originally supplied by the installer.
FILTER ACCESS PANEL
INDOOR COIL ACCESS PANEL
C13095
Fig. 20 – Air Filter Access Panel — 6 to 10 Ton Units
GAS COMPONENT ACCESS PANEL FILTER ACCESS PANEL
CO8486
Fig. 21 – Air Filter Access Panel — 12.5 to 23 Ton Units
Table 1 Replacement Filters – Size and Quantity
Unit 48LC_007 48LC_008 48LC_009 48LC_012 48LC_014 48LC_017 48LC_020 48LC_024 48LC_026
Capacity 6 tons 7.5 tons 8.5 tons 10 tons
12.5 tons 15 tons 17.5 tons 20 tons 23 tons
Filter Size (Qty) 19 5/8 x 19 5/8 x 1 3/4 (4)
18 x 24 x 2 (6) 18 x 24 x 2 (7) 20 x 25 x 2 (6)
16 x 25 x 2 (9)
NOTE: Filter sizes in Table 1 are in inches. Numbers in ( ) denote filter quantity.
Units with outdoor air capability have a cleanable filter for the outdoor air. This filter should be checked semi- annually and cleaned as necessary with steam or hot water and a mild detergent. Do not use throwaway filters in place of cleanable filters.
Condenser Fan
! WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury.
Do not poke sticks, screwdrivers, or other object into revolving fan blades.
Electrical Controls and Wiring
Ensure wires do not contact refrigerant tubing or sharp edges. Electrical
controls are difficult to check without proper instrumentation. If inadequate
cooling is suspected, contact your qualified local dealer for service.
6
Combustion Area and Vent System
The combustion area and vent system should be visually inspected before each
heating season.
! WARNING
FIRE HAZARD Failure to follow this warning could result in personal injury
equipment damage. If your unit makes any unusual or especially loud noises
during heating, shut down the heating section and call your qualified service
technician.
Proceed as follows to inspect the combustion area and power- venting system of
your unit. S Turn off gas supply to your unit. S Turn off electrical power to
your unit; install lockout tag. S Remove gas component access panel. S Using a
flashlight, carefully inspect the burner areas for
dirt, soot, or scale.
! CAUTION
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in damage to
equipment. If dirt, soot, rust or scale accumulations are found, call your
service technician and do not operate your heating section.
S When you have completed your inspection, follow the start- up procedures in
this manual to restore your unit to operation.
! WARNING
PERSONAL INJURY HAZARD Failure to follow this warning could result in personal
injury. Components in heat section may be hot after unit has been started up.
When observing flame, be careful not to get close to or touch heating
components.
S Observe unit heating operation. Watch the burner flame to see if it is
bright blue. If you observe a suspected malfunction or that the burner flame
is not bright blue, shut down the unit and call your dealer.
S Replace gas component access panel.
Integrated Gas Controller (IGC)
The IGC board incorporates an LED that emits a flashing light to indicate an
alarm code. If the furnace section will not operate and the LED is flashing a
code (1 to 9 flashes in succession), contact your dealer and request service.
NOTE: Make note of the flash code before powering off the unit. The alarm
codes clear after power cycle.
Unit Panels
After performing any maintenance or service on the unit, be sure all panels
are securely fastened in place to prevent rain from entering unit cabinet and
to prevent disruption of the correct unit airflow pattern.
REGULAR DEALER MAINTENANCE
Heat Exchanger
NOTE: To ensure dependable and efficient heating operation, the heat exchanger
should be checked by a qualified maintenance person before each heating
season, and cleaned when necessary.
! CAUTION
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in damage to
equipment. This checkout should not be attempted by anyone not having the
required expertise and equipment to do the job properly.
Checking and/or cleaning the heat exchanger involves removing the gas controls
assembly and the flue collector box cover. When finished, the gas controls
must be reinstalled for proper operation. Also, the flue collector box cover
must be replaced correctly, with “red” RTV, so that a proper seal is
maintained. Contact your dealer for the required periodic maintenance. At the
beginning of each cooling/heating season and as conditions require.
Fans and Belts, and Fan Motor
Check quarterly the condition of fan wheels and housings, belt tension and fan
motor shaft bearings. No lubrication of condenser or evaporator fan bearings
or motors is required or recommended.
Evaporator and Condenser Coils
Cleaning of the coils should be done by qualified service personnel. This
procedure should be performed prior to cooling operation or more frequently
should conditions require. Contact you dealer for the required annual
maintenance.
Condensate Drain
The drain pan and condensate drain line should be checked and cleaned at the
same time the cooling coils are checked by your dealer.
In addition to the type of routine maintenance you might be willing to
perform, your unit should be inspected regularly by a properly trained and
qualified service technician. An inspection (preferably each heating/cooling
season, but at least every year) should include the following:
S Inspection of all flue product passages, including the burners, heat
exchanger, and flue collector box.
7
S Inspection of all combustion- and ventilation- air passages and openings.
S Close inspection of all gas pipes leading to and inside your unit.
S Inspection and if required, cleaning of the condenser and evaporator coils.
S Inspection, and if required, cleaning of the condensate drain pan.
S Inspection and cleaning of blower wheel housing and motor.
S Inspection of all supply- and return- air ducts for leaks, obstructions, and
insulation integrity. Any problems found should be resolved at the time of
inspection.
S Inspection of the unit base for cracks, gaps, etc., which may cause a
hazardous condition.
S Inspection of the unit casing for signs of deterioration.
S Inspection of all electrical wiring and components to ensure proper
connection.
S Inspection for leaks in the refrigerant circuit. Pressure check to determine
appropriate refrigerant charge.
S Inspection of fan wheels and housings, belt tension, and fan motor shaft
bearings.
S Operational check of the unit to determine working conditions. Repair or
adjustment should be made at the time of inspection. Your servicing dealer may
offer an economical service contract that covers seasonal inspections. Ask for
further details.
Complete service instructions can be found in the unit Installation, Start- Up
and Service Instructions.
BEFORE YOU CALL FOR SERVICE, CHECK FOR PROBLEMS THAT CAN BE EASILY SOLVED
If insufficient heating or cooling is suspected:
( ) Check for sufficient airflow. Check the air filter for dirt Check for
blocked return- or supply- air grilles. Be sure they are open and
unobstructed. If these checks do not reveal the cause, call your servicing
dealer.
If your unit is not operating at all, check the following list for easy
solutions:
( ) Check to be sure that your thermostat/unit controller temperature selector
is set above the indoor temperature during the heating season, or below the
indoor temperature during the cooling season. Be sure the SYSTEM switch in the
proper HEAT or COOL position and not in the OFF position.
( ) Is the electrical supply switch ON? Are any fuses blown, or has the
circuit breaker tripped?
( ) During the heating season, check the external manual shutoff valve. Is
this lever parallel with the pipe, indicating that the valve is open? Or is
the lever at the right angle, indicating that the valve is closed? If closed,
has the gas been shut off for safety reasons? Otherwise, you may open the
valve and follow the start- up procedures listed in this manual.
NOTE: Before proceeding with the next check, turn OFF the electrical power
supply to the unit. Remove the gas component access panel.
( ) During the heating season, check the control switch on the gas valve. Is
it in the ON position? If it is not, be sure it has not been turned off for
the purpose of safety. If no safety hazards are present, follow the start- up
procedures in this manual.
( ) If your unit still fails to operate, call your servicing dealer for
troubleshooting and repairs. Specify the model and serial numbers of your
unit. (Record them in this manual in the space provided.) If the dealer knows
exactly which unit you have, he may be able to offer suggestions over the
phone, or save valuable time through knowledgeable preparation for the service
call.
IN CASE OF TROUBLE
If, after performing the above checks, unit performance is unsatisfactory,
shut off the unit and call your dealer.
Dealer’s Name
Telephone No.
Unit Model
Unit Serial Number
Copyright 2013 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
Edition Date: 04/13
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8
Catalog No: OM—48LC —02
Replaces: New
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>