Installation and operating instructions
Cable connection
Mounting
Master/Slave function
Description of microwave sensor
- Detection zone Max.(D x H): 12m x 6m
- Detection sensitivity: 50% or 100%, adjustable
- Daylight Off: 25-150Lux, adjustable or disable
- Stand-by Period: 0sec-+∞ adjustable (Refer to ”Low light”)
- Stand-by Dim Level : 10% or 25%, adjustable //
- Ceiling Mounting height: Max. 6m
- Motion detection: 0.3~3m/s
- Detection angle: 150° (wall installation), 360° (ceiling installation)
Parameter setting of microwave sensor
Detection Area
This determines the effective range of the motion detector and is set by
DIP switches at the sensor itself, refer to figure. Note that reducing the
sensitivity will also narrow the detection range.
Daylight
This allows the sensor to switch the unit on or off when ambient light is
either full day light, low daylight, or after dark. It also allows the sensor
to be disabled.
Stand-by Dim Level
This refers to the brightness of “Low light period”, It is set with DIP
switches at the sensor itself, refer to figure.
Hold Time
This determines the time the fitting remains at 100% level on motion detection
and is set with DIP switches at the sensor itself, refer to figure. The walk
test setting is useful when installing the fitting to establish correct
operation and range.
Stand-by Period
This refers to “Low light period”, when it is set to +∞, the luminaire gives
photocell prioritized function, meaning the luminaire is off when ambient
brightness accesses the set threshold, and automatically on to a low light
level when ambient brightness is lower than the set threshold, and turns to
high light level when it detects a movement. It is set with DIP switches at
the sensor itself, refer to figure. When it is set to +∞ on “Stand-by Period”,
the default setting is 10% and can’t be changed.
Selectable brightness
Different brightness settings by DIP switches on the driver.
Selectable colour temperature
Different colour temperature settings by DIP switches on the LED plates.
Maintenance
- Cut off the mains power first.
- Don’t use chemical reagent to clean lamp.
Disassembly
- Remove the diffuser.
- Remove the light source and driver by loosening the screws.
Battery system automatic testing
Test | Starting time | Duration | Occurrence | Result | LED indicator |
---|---|---|---|---|---|
1 | Emergency driver/ battery/loading | First connection to mains | Continuous | ||
Continuous | Normal / Failed | Green / Red flashing | |||
2 | Rated duration time | 30 days after first |
connection to mains
| 1h| 1 year| Normal / Failed / Test in progress| Green / Red flashing
/ Amber
3| Emergency function| 60 days after first
connection to mains
| 1 min.| 1 month| Normal / Failed / Test in progress| Green / Red flashing
/ Amber
Test failure
Emergency driver| Red light flashes quick
Battery| Red light flashes slow
Loading| Red light on continously
Technical data
- LU335.1500/DW/1M LiFePO4 6.4V 600mAh
- LU335R.1500/DW/1M LiFePO4 6.4V 600mAh
- LU335.2300/DW/1M LiFePO4 6.4V 600mAh
- LU335R.2300/DW/1M LiFePO4 6.4V 600mAh
Cable connection
Emergency Back-up Version + Sensor
The installation must only be done by an electrician with the appropriate
qualifications. Keep this manual for future installation and service.
This product contains a light source of energy efficiency class E.
WARNING
Danger of electric shock! Risk of fire!
- Improper installation can cause personal injury and property damage.
- Switch off the current before installation or maintenance.
- The control circuit must be separated from mains voltage by basic insulation.
- Use only starters, light sources and rated wattage as marked in the luminaire.
- The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
Do not dispose of electrical and electronic devices including their accessories with the house-hold waste. When the luminaire is at the end of its life cycle, it must be disposed of according to local recycling guidelines.
References
- Ensto – Leading Expert for Distribution System Operators
- Ensto – Leading Expert for Distribution System Operators
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>