Logic Combi ESP1 and Logic Code Combi ESP1
Maximum permissible horizontal concentric flue length
combining both horizontal flue and flue extensions (measured from centreline
of the turret to the outside of the wall terminal)
Up to 26 kW appliances | Maximum: 9m – minus any extensions or bends |
---|---|
30 & 32 kW appliances | Maximum: 8m – minus any extensions or bends |
35 & 38 kW appliances | Maximum: 6m – minus any extensions or bends |
Maximum permissible vertical flue length
combining both vertical flue terminal and flue extensions
24 – 38 kW appliances | Maximum: 7.5m – minus any extensions or bends |
---|
Vertical flue loft air inlet
24 – 38 kW appliances| Up to 4.7m concentric flue and 20m single flue pipe.
For additional configurations and details refer to the installation
instructions supplied with 203136 Vertical flue loft air inlet
90° bend Ø60/100 – Equivalent flue length resistance = 1m
45° bend Ø60/100 – Equivalent flue length resistance = 0.6m
FLUE OPTIONS
HORIZONTAL CONCENTRIC 100MM DIAMETER
FLUE | PART NO. |
---|---|
Horizontal flue non-telescopic 0.6m | 208171 |
Flue extension 1m with bracket | 203129 |
ALTERNATIVE FLUE TERMINALS | PART NO. |
Horizontal flue telescopic 0.5m | 208169 |
Horizontal flue telescopic 0.7m | 208174 |
Horizontal flue non-telescopic 0.8m | 217442 |
HORIZONTAL FLUE WITH 1 X 90° BEND
FLUE | PART NO. |
---|---|
Horizontal flue non-telescopic 0.6m | 208171 |
Flue extension 1m with bracket | 203129 |
Flue bend 90° | 203130 |
HORIZONTAL FLUE WITH 2 X 90° BEND
FLUE | PART NO. |
---|---|
Horizontal flue non-telescopic 0.6m | 208171 |
Flue extension 1m with bracket | 203129 |
Flue bend 90° | 203130 |
HORIZONTAL FLUE WITH 2 X 45° BEND
FLUE | PART NO. |
---|---|
Horizontal flue non-telescopic 0.6m | 208171 |
Flue extension 1m with bracket | 203129 |
Flue bend 45° pair | 203131 |
VERTICAL FLUE SYSTEM
FLUE | PART NO. |
---|---|
Vertical flue terminal and connector | 211039 |
Flue extension 1m with bracket | 203129 |
Flat roof weather collar | 152259 |
VERTICAL FLUE SYSTEM WITH 2 X 45° BEND
FLUE | PART NO. |
---|---|
Vertical flue terminal and connector | 211039 |
Flue extension 1m with bracket | 203129 |
Flue elbow 45° pair (Ø60/100) | 203131 |
Flat roof weather collar | 152259 |
VERTICAL FLUE WITH LOFT AIR INLET
FLUE | PART NO. |
---|---|
Air inlet for vertical flue | 203136 |
Flue vertical connector | 208175 |
Vertical flue terminal | 203134 |
Weather collar pitched roof | 152258 |
Flue extension 1m with bracket | 203129 |
Flue extension 1m pair (Ø80mm) | 203142 |
NOTE: Allows the boiler to be sited in a position where no access to an outside wall is available. Permits the concentric flue to run vertically from the top of the boiler and obtain air supply within the roof space, the secondary flue continuing to the external flue terminal. Offset applications are permissible though the maximum length is reduced.
HIGH LEVEL FLUE OUTLET KIT
These easy to install kits allow the boiler flue outlet to be extended
external to the building, upwards to provide a flue exit at high level,
overcoming problems associated with plume emission. The kit is simple to
retrofit if necessary.
An external 60mm diameter flue leads from the boiler terminal (which includes
a 90° bend at the flue exit) to terminate with a 90° bend complete with
grille. Push fit 1m extension pipes are used as required, and the fixing clips
supplied support the system from the wall. Both 90° and 45° bend are available
to provide routing options.
The kit comprises:
Flue bend – 1 off
60mm flue exit bend – 1 off
60mm horizontal flue exit – 1 off
60mm x 500mm flue extension pipe – 1 off
This kit is for use with horizontal non-telescopic and telescopic flue kits
208169, 208171, 208174 and 217442.
The standard terminal nose is replaced with the high level terminal.
FLUE | PART NO. |
---|---|
Horizontal flue non-telescopic 0.6m | 208171 |
High level flue outlet kit (Ø60mm) | 208178 |
Flue extension 1m for high level flue outlet (Ø60mm) | 203228 |
High level flue bend 90° (Ø60mm) | 203229 |
High level flue bend 45° (Ø60mm) | 203230 |
Diagram representative only
NOTE: Please refer to the installation and service manual for assistance
in calculating flue lengths. Adequate support must be provided for the flue in
accordance with the installation instructions. If additional elbows to those
supplied in the High Level Flue Outlet kit are used, deduct the following
resistances (metres) from the maximum boiler flue length.
FLUE ACCESSORIES FOR HIGH RISE INSTALLATIONS
LOGIC COMBI ESP1 AND LOGIC CODE COMBI ESP1
The Building Regulations (Amendment) 2018 for England directs that combustible
materials must not be used in the external walls of high-rise residential
buildings, i.e. those above 18m tall (typically 6 stories). The ‘external
wall’ includes anything located within any space forming part of the wall.
This is relevant to the installation of all new gas boilers with horizontal
flues in high-rise residential buildings, as the ban now excludes those flues
that contain combustible materials such as a polypropylene plastic inner flue
duct. Similar regulations also apply in Wales and Northern Ireland, with
Scotland having their own regulations.
Ideal Heating have a range of high rise flues and accessories which comply
with the revised regulations for high-rise buildings.
Introduced from October 2019, they are direct replacements for the standard
horizontal flues and accessories. The main difference is that the inner flue
duct is aluminium rather than polypropylene plastic. Aluminium is classed as
having class A fire resistance according to European Standard prEN1856-1 May
2019 which covers metal chimneys and flues, and by Europe Decision Document
96/603/EC covering construction products.
Externally the high rise flues look similar to the previous generation Ideal
Logic flue (pre 2013) and the flue terminal is still black plastic. However,
the outer air duct is no longer powder coated white and has a galvanised
finish; but only a small length of this will be seen above the boiler. The
elbow and wall seals have not changed. As the terminal, elbow and wall seals
are not part of the make-up of the external wall their materials are not
affected by the revised regulations. The flue terminal design has the air
inlet underneath and the aluminium flue duct can be seen through the air
inlet.
The high-rise horizontal flue terminals do not have a removable terminal nose
so cannot be used with flue accessories 208178 High level flue outlet kit,
211302 Soffit kit, 208177 Balcony flue outlet kit and 208176 Flue deflector.
However, new dedicated high-rise accessories are available to cover more
installation configurations. These all have aluminium flue ducts to comply
with the amended regulations.
FLUE SITING
There are a substantial number of flue options available, giving excellent
siting flexibility for almost all applications.
The range of options include standard and telescopic flues as well as vertical
and raised horizontal options.
To ensure siting issues are kept to a minimum, High Level Flue Outlet kit
options and Flue Deflectors are available.
| FLUE TERMINAL POSITION| MIN. SPACING
---|---|---
1| Directly below, above or alongside an opening. 300 mm| 300mm
2| Below guttering, drain pipes or soil pipes.| 75mm
25mm
3| Below eaves.| 200mm
25mm
4| Below balconies or car port roof.| 200mm
25mm
5| From vertical drain pipes or soil pipes.| 150mm
25mm
6| From an internal or external corner or to a boundary alongside the
terminal.| 300mm
25mm*
7| Above ground, roof or balcony level.| 300mm
8| From a surface or a boundary facing a terminal.| 600mm
9| From a terminal facing a terminal.| 1200mm
10| From an opening in a car port into dwelling.| 1200mm
11| Vertically from a terminal on the same wall.| 1500mm
12| Horizontally from a terminal wall.| 300mm
13| Horizontally from an adjacent window| 600mm
14| Facing an opening into an adjacent building| 2000mm
15| At an angle to the boundary
90°
45°| 300mm
600mm
16| Parallel to a boundary| 300mm
17| Below ground level – open light well
a) Below ground
b)Above floor level
c) From side
d) From facing surface| <1,000 mm
300mm
300mm
600mm
*Only one reduction down to 25mm is allowed per installation.
INSTALLATION ACCESSORIES
Our range of installation accessories are widely available due to our excellent distribution network. Our installation accessories include a range of brackets and stand off kits as well as a range of kits to help you deal with any situation.
STAND OFF KIT
INSTALLATION ACCESSORY | PART NO. |
---|---|
Stand-off kit Logic Combi ESP1 | 211103 |
Stand-off kit Logic Code Combi ESP1 | 211335 |
STAND OFF KIT WITH PIPES
INSTALLATION ACCESSORY | PART NO. |
---|---|
Stand-off kit with pipes Logic Combi ESP1 | 211101 |
Stand-off kit with pipes Logic Code Combi ESP1 | 211333 |
SECONDARY PRESSURE RELIEF VALVE KIT
INSTALLATION ACCESSORY | PART NO. |
---|---|
Secondary pressure relief valve | 234642 |
PRV OUTLET PIPE
INSTALLATION ACCESSORY | PART NO. |
---|---|
PRV outlet pipe | 205126 |
DHW EXPANSION VESSEL KIT
INSTALLATION ACCESSORY | PART NO. |
---|---|
DHW expansion vessel | 205419 |
IDEAL SYSTEM FILTER
INSTALLATION ACCESSORY | PART NO. |
---|---|
Ideal system filter | 236531 |
Flushing adaptor for system filter | 237010 |
Camlock Magnaclense adaptors | 237516 |
CONDENSATE PUMP KIT
INSTALLATION ACCESSORY | PART NO. |
---|---|
Condensate pump kit | 159991 |
Customer Service:
01482 498660
Technical Help:
01482 498663
Ideal Heating, PO Box 103, National Avenue,
Kingston upon Hull, East Yorkshire, HU5 4JN
E: enquiries@idealheating.com
idealheating.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>