Thermal protection thermostat (PTC sensor)
Dear Customer,
Bock refrigerating compressors are high-quality, reliable, and service-
friendly quality products. To guarantee the ongoing trouble-free operation of
your system, please comply with the following instructions. If you have any
queries, contact our technical customer service department your refrigeration
wholesaler, or our agent. The Bock service team can be contacted by e-mail:
service@bock.de
SAFETY INSTRUCTIONS
Caution! Refrigerating compressors are pressurized machines and therefore
require particularly careful handling.
- Only qualified staff are allowed to handle refrigerating compressors.
- Local safety regulations, accident prevention regulations, technical rules, and other valid specifications must be observed.
- The maximum tolerable operating overpressure may not be exceeded (not even for test purposes).
- Before starting the compressor, the pressure shut-off valve and suction shut-off valve are to be opened.
- Before starting up, check that all components mounted by the user have been properly mounted and connected pressure-tight with the compressor (e.g. pipelines, bungs, union nuts, replaced parts, etc.)
- When starting up, do not start the compressor in a vacuum. Only operate the compressor when the whole system has been filled.
General
These installation instructions describe the main procedure involved in retrofitting a thermal protection thermostat (PTC sensor) to compressor HA/HG.
Scope of delivery
- Assembly kit no.* 097B08921
- Assembly kit no.* 097B80907
The cable holder and cable clip (items 2 + 3) are already pre-mounted.
- Bitte um Beachtung, dass die ehemaligen Bock ref.
- Nummern ohne 097B sind.
Installation
- Decommission the compressor in compliance with the safety instructions stated above and enclosed. Then (see figs.):
- Loosen the marked cylinder cover screws.
- Place the cable holder with the cable clip under the screw head of the cylinder cover.
- Tighten the cylinder screws again with torque M=51 Nm.
- Bend the cable holder until it is horizontal (to the standing plane).
- At the intended connection point L, remove the NPTF 1/8″ bung from the cylinder cover, insert the thermal protection thermostat and screw tight.
- Then fix the connection cable in the cable clips.
- Fig. 6 shows how the cable is routed along the cylinder cover of the compressor.
Electrical connection
Connection to trigger device MP 10:
- Remove the cable bridge from terminals 3 and 4 of the trigger device.
- Insert the cable ends of the thermal protection thermostat to terminals 3 and 4 as per fig. 7.
- When using larger compressors (series HA/HG 4 – 7), it is advisable to use thermal protection thermostats at every single pair of cylinders.
- The thermostats are then connected up in series to a connector block (see fig. 8) in the terminal box.
Retrofitting older compressors
Older compressors are equipped with the motor protection trigger device INT 69
VS. Here the thermostats are to be connected to the terminal board:
Remove lead 2 – 2 (xxx)
Insert one cable end from the thermal protection thermostat to the terminal
board and the other to the trigger device, each at terminal 2 (see fig. 9).
Danfoss A/S
Climate Solutions danfoss.com +45 7488 2222
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved. Any information, including, but not limited to information on
the selection of the product, its application or use, product design, weight,
dimensions, capacity, or any other technical data in product manuals, catalog
descriptions, advertisements, etc., and whether made available in writing,
orally, electronically, online or via download, shall be considered
informative and is only binding if and to the extent, explicit reference is
made in a quotation or order confirmation.
Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos, and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to the form, fit, or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.