Traditional Wiring – No Fieldbus:
In this system configuration, connections between the drive and PLC require
one wire for each input that needs to be controlled or monitored. While
individual components are relatively inexpensive, this system can be costly to
install and extend. Each additional device or signal requires new wiring,
additional PLC hardware, and programming, resulting in higher capital costs
and limited flexibility.
Serial Fieldbus Connectivity:
A classical fieldbus system uses twisted pair connections to communicate
over serial protocols. Although components may have a higher cost, advantages
include fewer cable connection points, faster commissioning, and reduced risk
of faults. Programming new inputs into the PLC is faster, safer, and more
cost-effective than in hardwired systems.
Fieldbus over Ethernet:
Ethernet-based systems offer improved system control using speed and
connectivity versatility. While component costs may be slightly higher than in
serial systems, benefits include easier installation and reduced connection
errors. The control hierarchy can be bypassed, allowing direct communication
with components or through the PLC as needed.
Fast installation easy integration
Dedicated Danfoss fieldbus hardware and software solutions save time and
provide efficient control and monitoring.
20+ fieldbus technologies supported by Danfoss AC drives
Freedom to communicate
Real time information is becoming increasingly important in industrial
automation and control systems as we progress further into Industry 4.0.
Immediate access to data increases transparency in production facilities,
while making it possible to optimize system performance, collect and analyze
system data and provide remote support around the clock from anywhere in the
world.
Regardless of your application or your preferred communication protocol, both VLT® and VACON® drives have an extremely wide variety of communication protocols to select from. In this way you can ensure that the AC drive integrates seamlessly into your chosen system providing you the freedom to communicate however you see fit.
Traditional wiring No fieldbus
In this system configuration, connections between the drive and PLC require one wire for each input that needs to be controlled or monitored. The advantage of such a system is that the individual components themselves are relatively inexpensive.
This, however, comes at a price, as such systems are often expensive to install and extend. Each additional device or signal requires new wiring, can require additional PLC hardware, and always requires additional PLC programming and verification. For owners this means higher capital costs and restricted flexibility. At the same time the risk of error is high as the number of I/O and wires increase.
Serial fieldbus connectivity
A classical fieldbus system only uses twisted pair connections to communicate over serial protocols. Compared to systems wired without fieldbus connections, serial fieldbus connectivity has a higher cost of components. Overall, fieldbus solutions offer several advantages: fewer cable connection points, faster commissioning and a reduced risk of faults.
The addition of other components in the system requires programming only the new inputs into the PLC, which is both faster, safer and at significantly lower cost than a hardwired system.
Fieldbus over Ethernet
Ethernet-based systems use the speed and versatility of connectivity to improve overall system control. While component costs are slightly higher than in serial systems, large gains are made in ease of installation and a reduction of connection errors. In Ethernet-based systems, the control hierarchy can be bypassed, sending messages directly to the components or through the PLC as needed. Additional drives can be connected in ring topologies, in series over dual-port solutions or directly with the network through external switches. External access is routed through a secure firewall, enabling communication directly with the drive or with the web server built into some of the fieldbus options. Not only does this provide a high degree of flexibility during commissioning, it also provides advantages such as external monitoring and application support.
Danfoss AC drives support all leading industry fieldbuses
Increase productivity
Fieldbus communication reduces capital costs in production plants. In addition
to the initial savings achieved through the significant reduction in wiring
and control boxes, fieldbus networks are easier to maintain, while providing
improved systems performance.
Fieldbus configuration files for easy PLC integration
Integrating a drive into an existing bus system can be time consuming and
complicated. To make this process easy and more efficient, Danfoss Drives
offers fieldbus drivers and PLC examples, which can be downloaded for free
from the Danfoss Drives website. After installation of these fieldbus
configuration files, the remaining bus parameters can be set directly in the
drive.
User friendly and fast setup
Danfoss fieldbuses can be configured via the drive’s local control panel,
which features a user friendly interface with support for many user languages.
The drive and fieldbus can also be configured using the software tools that
support each drive family. The time saving setup procedure is identical for
VLT and VACON.
Global fieldbus experts
Danfoss’ global sales and support organization is trained in the market’s many
PLC systems. With in-depth knowledge about the challenges in modern production
plants, they are perfectly equipped to provide advice and help so your Danfoss
AC drives perform optimally.
Factory fitted or plug-and-play
Delivered with the chosen communication protocol installed from the factory,
Danfoss drives are easy to integrate with PLC systems and motors regardless of
manufacturer. Danfoss fieldbus options can also be installed as a plug-and-
play solution if required at a later stage if the production layout demands a
new communication platform.
Fieldbus Overview
PROFINET
PROFINET uniquely combines the highest performance with the highest degree of openness. The option is designed so that many of the features from the PROFIBUS can be reused, minimizing user effort to migrate PROFINET and securing the investment in a PLC program.
- Same PPO types as PROFIBUS for easy migration to PROFINET
- Support of MRP
- Support of DP-V1 Diagnostic allows easy, fast, and standardized handling of warning and fault information into the PLC, improving bandwidth in the system
- Implementation in accordance with Conformance Class B
VLT PROFINET MCA 120
Order code
- 130B1135 standard, dual-port
- 130B1235 coated, dual-port
VACON PROFINET
- VACON NXP : Slots D, E
- VACON NXS : Slots D, E
- VACON 100 : Slots D, E
Order code
- OPT-CP-V coated, single-port
- OPT-E9-V coated, dual-port
- Order with +FBIE for VACON 100 single-port
EtherNet/IP
Ethernet is the future standard for communication at the factory floor. EtherNet/IP is based on the newest technology available for industrial use and handles even the most demanding requirements. EtherNet/IP extends commercial off-the-shelf Ethernet to the Common Industrial Protocol (CIP™) – the same upper-layer protocol and object model found in DeviceNet.
The option offers advanced features such as:
- Built-in high-performance switch enabling line-topology, and eliminating the need for external switches
- DLR Ring
- Advanced switch and diagnosis functions
- Built-in web server
- E-mail client for service notification
- Unicast and Multicast communication
VLT EtherNet/IP MCA 121
Order code
- 130B1119 standard, dual-port
- 130B1219 coated, dual-port
VACON EtherNet/IP
- VACON NXP : Slots D, E
- VACON NXS : Slots D, E
- VACON 100 : Slots D, E
Order code
- OPT-CQ-V coated, single-port
- OPT-E9-V coated, dual-port
- Order with +FBIE for VACON® 100 single-port
EtherCAT
The EtherCAT offers connectivity to EtherCAT® based networks via the EtherCAT
Protocol.
The option handles the EtherCAT line communication in full speed, and
connection towards the drive with an interval down to 4 ms in both directions.
This allows the option to participate in networks ranging from low performance
up to servo applications.
- EoE Ethernet over EtherCAT support
- HTTP (Hypertext Transfer Protocol) for diagnosis via built-in web server
- CoE (CAN Over Ethernet) for access to drive parameters
- SMTP (Simple Mail Transfer Protocol) for e-mail notification
- TCP/IP for easy access to drive configuration data from MCT 10
VLT EtherCAT MCA 124
Order code
- 130B5546 standard
- 130B5646 coated
VACON EtherCAT
- VACON NXP : Slots D, E
- VACON 100: Slots D, E
Order code
- OPT-EC-V coated
BACnet/IP
The BACnet/IP option optimizes the use of VLT® HVAC Drive together with
building management systems (BMS) using the BACnet/IP protocol or running
BACnet on Ethernet. BACnet/IP makes it easy to control or to monitor points
required in typical HVAC applications, reducing overall cost of ownership.
Other features:
- COV, Change Of Value
- Read/WritePropertyMultiple
- Alarm/Warning notifications
- PID Loop object
- Segmented data transfer
- Trend Objects
- Schedule Objects
VLT BACnet/IP MCA 125
Order code
- 134B1586 coated, dual-port
VACON BACnet/IP
Order code
- VACON 100 : included, single port
Modbus TCP
Modbus TCP is the first industrial Ethernet-based protocol for automation.
Modbus TCP is able to handle connection intervals down to 5 ms in both
directions, positioning it among the fastest performing Modbus TCP devices in
the market. For master redundancy, it features hot swapping between two
masters.
Other features:
- Dual Master PLC connection for redundancy in dual port options (MCA 122 only)
VLT Modbus TCP MCA 122
Order code
- 130B1196 standard, dual-port
- 130B1296 coated, dual-port
VACON Modbus TCP
- VACON NXP : Slots D, E
- VACON NXS : Slots D, E
- VACON 100 : Slots D, E
Order code
- OPT-CI-V coated, single-port
- OPT-E9-V coated, dual-port
- VACON 100 : included, single port
POWERLINK
POWERLINK represents the second generation of fieldbus. The high bit rate of
industrial Ethernet can now be used to make the full power of IT technologies
used in the automation world available for the factory world. POWERLINK
provides high-performance real-time and time synchronization features. Due to
its CANopen-based communication models, network management, and device
description model, it offers much more than just a fast communication network.
The perfect solution for:
- Dynamic motion control applications
- Material handling
- Synchronization and positioning applications
Order code
- 130B1489 standard, dual-port
- 130B1490 coated, dual-port
PROFIBUS DP
Operating the AC drive via a fieldbus enables you to reduce the cost of your
system, communicate faster and more efficiently, and benefit from an easier
user interface.
Other features:
- Wide compatibility, a high level of availability, support for all major PLC vendors, and compatibility with future versions
- Fast, efficient communication, transparent installation, advanced diagnosis and parameterization, and auto-configuration of process data via GSD-file
- Acyclic parameterization using PROFIBUS DP-V1, PROFIdrive or Danfoss FC (MCA101 only) profile state machines, PROFIBUS DP-V1, Master Class 1 and 2
VLT PROFIBUS DP MCA 101
Order code
- 130B1100 standard
- 130B1200 coated
VACON PROFIBUS DP
- VACON NXP : Slots D, E
- VACON NXS : Slots D, E
- VACON 100 : Slots D, E
Order code
- OPT-C3-V coated, terminals, DP-V0
- OPT-C5-V coated, D9 connector, DP-V0
- OPT-E3-V coated, terminals*, DP-V1
- OPT-E5-V coated, D9 connector*, DP-V1
DeviceNet
DeviceNet offers robust, efficient data handling thanks to advanced Producer/Consumer technology.
- Support of ODVA’s AC drive profile supported via I/O instance 20/70 and 21/71 secures compatibility with existing systems
- Benefit from ODVA’s strong conformance testing policies, which ensure that products are interoperable
VLT DeviceNet MCA 104
Order code
- 130B1102 standard
- 130B1202 coated
VACON DeviceNet
- VACON NXP : Slots D, E
- VACON NXS : Slots D, E
- VACON 100 : Slots D, E
Order code
- OPT-C7-V coated
- OPT-E7-V coated
CANopen
High flexibility and low cost are two of the “cornerstones” for CANopen. The CANopen option is fully equipped with both high-priority access to control and status of the drive (PDO Communication) and access to all parameters through acyclic data (SDO Communication). For interoperability, the option has implemented the DSP402 AC drive Profile. These features all guarantee standardized handling, interoperability, and low cost.
VLT CANopen MCA 105
Order code
- 130B1103 standard
- 130B1205 coated
VACON CANopen
- VACON NXP : Slots D, E
- VACON NXS : Slots D, E
- VACON 100 : Slots D, E
Order code
- OPT-C6 standard
- OPT-C6-V coated
- OPT-E6-V coated
BACnet MS/TP
The BACnet protocol is an international protocol that efficiently integrates
all parts of building automation equipment from the actuator level to the
building management system. Via the BACnet option, it is possible to read all
analog and digital inputs and control all analog and digital outputs of the
VLT HVAC Drive and VACON NXS. All inputs and outputs can be operated
independently of the functions of the drive, and thus work as remote I/O:
Other features:
- COV (Change of Value)
- Synchronization of RTC from BACnet
- Read/write property multiple
- Alarm/warning handling
VLT BACnet MCA 109
Order code
- 130B1144 standard
- 130B1244 coated
VACON BACnet MS/TP
- VACON NXS: Slots D, E
Order code
- OPT-CJ-V coated
- VACON 100 : included
Modbus RTU
Modbus RTU gives the possibility to easily upgrade the hardware structure of an industrial network, without the need for large changes in the software. A device can also communicate with several Modbus nodes at once, even if they are connected with different interface types, without the need to use a different protocol for every connection.
Included as standard in VLT AC Drives
Included as standard in VACON 20 family AC Drives
- Included as standard in VACON 100 family AC drives
- Included as standard in VACON 3000 Medium Voltage AC drives
VACON
- VACON NXP : Slots D, E
- VACON NXS : Slots D, E
Order code
- OPT-C2 uncoated, terminals
- OPT-C2-V coated, terminals
- OPT-C8 coated, D9 connector
- OPT-C8-V coated, D9 connector
Metasys N2
The Metasys N2 communications protocol is used by Johnson Controls and others to connect terminal unit controllers to supervisory controllers. It is open to any manufacturer and based upon a simple ASCII protocol widely used in the process control industry. Data is partitioned into common HVAC control objects, such as analog input, analog output, binary input, and binary output. Messaging supports the reading, writing, and overriding of these points.
VLT
Order code
- VLT HVAC Drive: included
VACON
- VACON NXS : Slots D, E
Order code
- OPT-C2 uncoated, terminals
- OPT-C2-V coated, terminals
- OPT-C8 coated, D9 connector
- OPT-C8-V coated, D9 connector
- VACON 100: included
LonWorks
LonWorks is a fieldbus system developed for building automation. It enables communication between individual units in the same system (peer-to-peer) and thus supports decentralizing of control.
- No need for main station (master-follower)
- Supports echelon free-topology interface
- Supports embedded I/O and I/O options
- Sensor signals can quickly be moved to another controller via bus cables
- Certified as compliant with LonMark ver. 3.4 specifications (VLT® LonWorks MCA 108 only)
VLT LonWorks MCA 108
Order code
- 130B1106 standard
- 130B1206 coated
VACON LonWorks
- VACON NXS : Slots D, E
- VACON 100 : Slots D, E
Order code
- OPT-C4-V coated
AK-LonWorks
VLT AK-LonWorks MCA 107 is a complete electronic refrigeration and control system for monitoring and controlling refrigeration plants. Connecting this drive to a Danfoss ADAP-KOOL® Lon network is a simple process that needs only a network address.
VLT AK-LonWorks MCA 107
Order code
- 130B1169 standard
- 130B1269 coated
ASi Bus
The Actuator Sensor Interface (AS-Interface or AS-i) is an economical system for the lower automation level. It is not a universal Fieldbus for all areas of automation. The AS-Interface is optimized to network binary sensors and actuators to the higher control level.
VLT
Order code
- FCD 302 : included
VACON
Order code
- OPT-BK-V coated
Interbus
For communication on the remote bus, the Interbus system provides two different types of communication: Process Data and PCP (Peripherals Communication Protocol). The Process Data is cyclic communication to devices with high priority such as digital and analog I/O or control words and references to AC drives. PCP communication is used for communications that do not require high speed and typically only are activated on request from the user-written program.
VLT Interbus MCA 110
Order code
- 130B1211 coated
VLT Web Server
Several options within the VLT® portfolio offer the capability to connect
to the AC drives via a built-in web server.
- Remote diagnosis and reading out basic drive parameters
- Email notification can be configured to send an email message to one or more recipients when certain alarms or warnings occur or are cleared
VLT options with web server support:
- VLT Modbus TCP MCA 122
- VLT Ethernet/IP MCA 121
- VLT BACnet/IP MCA 125
PROFISAFE
PROFISAFE is a functional safety communication protocol that utilizes the PROFINET protocol in safety applications. With the VLT AutomationDrive FC 302, users can command the STO function over PROFISAFE.
VLT
- Requires PROFINET and MCB 152 option
VLT PROFIBUS Converter MCA 113
- The VLT PROFIBUS Converter MCA 113 is a special version of the PROFIBUS options that emulates the VLT® 3000 commands in the VLT® AutomationDrive.
- The VLT 3000 can be replaced by the VLT AutomationDrive, or an existing system can be expanded without costly change of the PLC program.
Order code
- 130B1245 coated
VLT PROFIBUS Converter MCA 114
- The VLT PROFIBUS Converter MCA 114 is a special version of the PROFIBUS options that emulates the VLT 5000 commands in the VLT AutomationDrive.
- The VLT 5000 can be replaced by the VLT AutomationDrive, or an existing system can be expanded without costly change of the PLC program. The option supports DPV1.
Order code
- 130B1246 coated
VLT DeviceNet Converter MCA 194
The VLT DeviceNet Converter MCA 194 emulates VLT® 5000 commands in the VLT® AutomationDrive. This means that a VLT 5000 drive can be replaced by the VLT AutomationDrive, or a system can be expanded without costly change of the PLC program. The option emulates I/O instances and explicit messages of a VLT 5000.
Order code
- 130B5601 coated
Engineering and setup for VLT and VACON
VLT Motion Control Tool MCT 10
VLT drives can all be configured and monitored with VLT® MCT 10. This
provides plant managers with a comprehensive overview over the system at any
point in time, adding a new level of flexibility in configuration, monitoring,
and troubleshooting. MCT 10 is a Windows-based engineering tool with a clearly
structured interface that provides an instant overview of all the drives in a
system of any size. Parameter configuration is possible both online on a
connected drive and offline in the tool itself, and the software can be
configured to link
to the system’s electrical diagrams or operating manuals. This helps to reduce
the risk of incorrect configuration while offering fast access to
troubleshooting.
VACON NC Tools
VACON NXP drives and their options can be configured and monitored with
VACON NCDrive, VACON NC Load, and VACON NC IPConfig. Additionally, updating
application software and firmware for both the drive and the fieldbus options
can be done in the field over the built-in RS-232 connection.
VACON Live and VACON Loader
VACON 20 and VACON 100 family drives and their options can be configured and
monitored with VACON® Live. Additionally, updating application software and
firmware for both the drive and the fieldbus options can be done with VACON
Loader in the field over the built-in RS-485 connection behind the keypad
using an RS485-to-USB converter cable for the VACON® 100 product family or
with the MCA kit for VACON ®20.
Order code
- Cable Only : VACON-CAB-USB-RS485
- MCA Kit : VACON-MCAA-KIT
Easy communication
Besides single point-to-point connections, both VLT MCT 10 and VACON Live are
able to connect to several drives in a single serial network, such as through
existing PROFIBUS networks. Additionally, connections through Ethernet based
technologies allow for simultaneous connection to all of the drives connected
on the host network.
VLT Motion Control Tool MCT 10 supports
- VLT PROFIBUS DP-V1 MCA 101
- VLT PROFIBUS Converter MCA 114
- VLT PROFINET MCA 120
- VLT EtherNet/IP MCA 121
- VLT Modbus TCP MCA 122
- VLT POWERLINK MCA 123
- FC RS485 Protocol
- USB port on FC 102/FC 103/ FC 202/FC 301/FC 302/FCD 302
VACON NCTools and VACON Live support
- VACON OPT-C7/E7 DeviceNet
- VACON OPT-C2/C8 and T-E2/E8 RS-485
- VACON OPT-C3/C5 and OPT-E3/E5 PROFIBUS DP
- VACON OPT-C6/E6 CANopen
- VACON OPT-EC EtherCAT
- VACON OPT-E9 Dual Port Ethernet
A better tomorrow is driven by drives
Danfoss Drives is a world leader in variable speed control of electric motors.
We offer you an unparalleled competitive edge through quality, application-
optimized products, and a comprehensive range of product lifecycle services.
You can rely on us to share your goals. Striving for the best possible performance in your applications is our focus. We achieve this by providing the innovative products and application know-how required to optimize efficiency, enhance usability, and reduce complexity. From supplying individual drive components to planning and delivering complete drive systems; our experts are ready to support you all the way.
You will find it easy to do business with us. Online, and locally in more than 50 countries, our experts are never far away, reacting fast when you need them. You gain the benefit of decades of experience, since 1968. Our low- voltage and medium-voltage AC drives are used with all major motor brands and technologies in power sizes from small to large.
VACON drives combine innovation and high durability for the sustainable industries of tomorrow. For a long lifetime, top performance, and full- throttle process throughput, equip your demanding process industries and marine applications with VACON® single or system drives.
- Marine and Offshore
- Oil and Gas
- Metals
- Mining and Minerals
- Pulp and Paper
- Energy
- Elevators and Escalators
- Chemical
- Other heavy-duty industries
VLT drives play a key role in rapid urbanization through an uninterrupted cold chain, fresh food supply, building comfort, clean water, and environmental protection. Outmaneuvering other precision drives, they excel, with remarkable fit, functionality, and diverse connectivity.
- Food and Beverage
- Water and Wastewater
- HVAC
- Refrigeration
- Material Handling
- Textile
Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All riahts reserved.
DKDD.PB.401.A4.02
© Copyright Danfoss Drives 2017.02
FAQ’S
Q: What are the advantages of using fieldbus communication in industrial
automation?
A: Fieldbus communication reduces capital costs by minimizing wiring
needs, simplifying control systems, and improving overall system performance.
Q: How does fieldbus over Ethernet differ from traditional wiring systems?
A: Fieldbus over Ethernet systems utilize the speed and versatility of
Ethernet connectivity to enhance system control, offering benefits such as
easier installation, reduced connection errors, and direct communication with
components.