Danfoss DN 40-50 Novo Con Mactuator User Guide

August 20, 2024
Danfoss

Danfoss DN 40-50 Novo Con Mactuator

Product Information

Specifications:

  • Actuator Model: AB-QM DN40-100
  • Control Signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA
  • Power Supply: 24VAC/DC, 50/60Hz
  • Force: 550N
  • Stroke: 20mm
  • Speed: 3-24s/mm
  • Consumption: 3.5VA running, Standby 0.9W
  • Protection Rating: IP54/40
  • Temperature Range: -10°C to 55°C
  • Manufacturer: Made in Slovenia

Product Usage Instructions

Connection Setup:

  1. Ensure power is switched off before starting any wiring.
  2. Connect the actuator following the specified terminal connections for your application mode.
  3. If using a flow sensor, connect it to the designated terminals.

Initial Configuration:

  1. Set the DIP switch according to the desired application mode and valve type.
  2. Ensure the correct calibration state or perform manual calibration as needed.

Firmware Update:
It is recommended to check and update the firmware version before installation. Visit www.novocon.com and download the latest firmware under the Support files tab.

FAQ:

  • Q: What should I do before wiring the actuator?
    A: To avoid any risks, ensure the power line is switched off before starting any wiring process.

  • Q: How can I update the firmware of the actuator?
    A: You can check and download the latest firmware version from www.novocon.com by accessing the Support files section.

Models

Using Instruction

Optional step (connecting flow sensor)

The serial number and QR code can be removed from the NovoCon® M label and added to the installation drawing.

  • Dip switches for addressing and bus protocol selection are located under the lid of the actuator.
  • Dip switches 1 to 7 are used to assign the MAC address manually. The default MAC address assignment method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU.
  • Dip switch 8 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON).
  • When the protocol is changed on DIP Switch 8, a power cycle is required.
  • For termination of the last unit on the field bus, turn the DIP Switch R located between the connectors to ON.

Initial configuration

Safety Instruction

Safety Note

  • To avoid injury and damage to persons and devices, these instructions must be carefully read and observed before assembly and commissioning.
  • Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained, and authorized personnel.
  • Switch off the power line before wiring the actuator.
  • If the NovoCon® M network is supplied with two or more AC power boosters, caution must be observed when disconnecting one of the transformers from the high-voltage power line. As the NovoCons are connected in a daisy chain, there may be high voltage on the primary side of the disconnected power supply. Disconnect always on both the primary and secondary side of the transformer.

Firmware update

  • We recommend validating the firmware version before installation.
  • The latest firmware can be downloaded at www.novocon.com by selecting the tab: Support files.

Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222.

Any information, including, but not limited to information on the selection of the product, its application or use, product design, weight, dimensions, capacity, or any other technical data in product manuals, catalog descriptions, advertisements, etc., and whether made available in writing, orally, electronically, online or via download, shall be considered informative and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos, and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to the form, fit, or function of the product.

All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals