APC BR1500MS2 Back-UPS Pro User Manual
- August 16, 2024
- APC
Table of Contents
- APC BR1500MS2 Back-UPS Pro
- Important Safety Instructions
- Inventory
- Connect the Battery
- Install PowerChute™ Personal Edition Software
- Connect the Equipment
- Operation
- Detected Alarms and System Errors
- Function Button Quick Reference
- Troubleshooting
- Specifications
- Warranty
- EMC Compliance
- FAQs
- Video-APC BR1500MS2 Back-UPS Pro
- Reference Link
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
APC BR1500MS2 Back-UPS Pro
Important Safety Instructions
Inspect the package contents upon receipt. Notify the carrier and dealer if
there is any damage.
SAVE THESE INSTRUCTIONS – This section contains important
instructions that should be followed during installation and maintenance of
the UPS and batteries.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- This UPS is intended for indoor use only.
- Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
- Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
- Connect the UPS power cable directly to a wall outlet.
Failure to follow these instructions will result in death or serious injury.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
- Replace the battery at least every 5 years or at the end of its service life, whichever is earlier.
- Replace the battery immediately when the UPS indicates battery replacement is necessary.
- Replace batteries with the same number and type of batteries as originally installed in the equipment.
- Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
Failure to follow these instructions could result in minor or moderate injury and equipment damage.
Inventory
Connect the Battery
The UPS is shipped with the battery disconnected.
-
Lay the UPS with the battery door facing up.
The arrows point to the locking tabs of the battery compartment. -
Press the tabs downwards and pull the battery door away from the unit to access the battery modules.
-
Using the handles on both sides of the battery, lift the battery 30 degrees upward to expose the battery connector. Connect the red wire as shown above.
-
Push the battery into the unit.
-
Replace the battery door.
Install PowerChute™ Personal Edition Software
Use PowerChute Personal Edition software to configure the UPS settings. During
a power outage, PowerChute will save any open files on your computer and shut
it down. When power is restored, it will restart the computer.
Note: PowerChute is only compatible with a Windows operating system. If
you are using Mac OSX, use the native shutdown feature to help protect your
system. See the documentation provided with your computer.
Installation
Use the USB communication cable supplied with the Back-UPS to connect the data
port on the Back-UPS to the USB port on your computer. On the computer, go to
www.apc.com Search for “PowerChute Personal Edition”
then click on “View Details” to download the latest version of PCPE software.
Click the download link and select Software product. Select the appropriate
operating system. Follow directions to download the software.
Connect the Equipment
Battery Backup and Surge Protected outlets
When the Back-UPS is receiving input power, the Battery Backup with Surge
Protection outlets will supply power to connected equipment. During a power
outage or other detected AC problems, the Battery Backup outlets receive power
for a limited time from the Back-UPS. Connect equipment such as printers, fax
machines, scanners, or other peripherals that do not need battery backup power
to the Surge Protection Only outlets. These outlets provide full-time
protection from surges even if the Back-UPS is switched OFF.
-
USB and Serial Data port
To use PowerChute Personal Edition, connect the supplied USB communication cable or an optional serial cable (not supplied). -
Ground screw
Connect the ground lead from an additional surge suppression device such as a stand-alone data line surge protector. -
Building Wiring Fault indicator
If this indicator is illuminated, there is a detected problem with the wiring in the building. Contact an electrician immediately and do not use the Back- UPS. -
Coaxial ports with surge protection
Connect a cable modem or other equipment with coaxial jacks. -
Circuit Breaker
Use to reset the system after an overload condition has occurred causing the circuit breaker to trip. -
Surge Protected outlets
These outlets provide full-time protection from surges, even if the Back-UPS is off. Connect equipment such as printers and scanners that do not require battery backup protection. -
In/Out Ethernet surge-protected ports
Use an Ethernet cable to connect a cable modem to the IN port, and connect a computer to the OUT port. -
Battery Backup outlets with Surge Protection
During a power outage or other detected AC problems, the Battery Backup outlets receive power for a limited time from the backup. Connect critical equipment such as desktop computers, computer monitor, modems or other data sensitive devices into these outlets.
Operation
Power Saving Display
The display interface can be configured to be continuously illuminated, or to
save energy, it can be configured to darken after a period of inactivity.
- Full Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full Time mode.
- Power Saving Mode: Press and hold DISPLAY for two seconds. The display will darken and the Back-UPS will beep to confirm the Power Saving mode. While in Power Saving Mode, the display will illuminate if a button is pressed, it then darkens after 60 seconds of no activity.
Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to
battery power; the higher the sensitivity, the more often the Back-UPS will
switch to battery power.
- Ensure the Back-UPS is connected to AC power but is OFF.
- Press and hold the POWER button for six seconds. The LOAD CAPACITY bar will flash on and off, indicating that the Back-UPS is in programming mode.
- Press POWER again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection.
Front Panel Buttons and Display Interface
Use the three buttons on the front panel of the Back-UPS and the display
interface to configure the Back-UPS.
Front panel
- DISPLAY button
- POWER ON/OFF button
- MUTE button
- Display interface
- USB charging ports:
The 2 USB ports provide a total of 15 W of DC power, and will provide power evenwhen the UPS is on battery.
- On-Line: The Back-UPS is supplying conditioned AC power to connected equipment.
- Load Capacity: The load is indicated by the number of sections illuminated, one to five. Each bar represents 20% of the load.
- Battery Capacity: The battery charge level is indicated by the number of sections illuminated. When all five blocks are illuminated, the Back-UPS is at full charge. When one block is filled, the Back-UPS is near the end of its battery capacity, the indicator will flash and the Back-UPS will beep continuously.
- Low Battery: When battery capacity reaches the empty level, the Back-UPS is nearing shutdown and the indicator will flash accompanied by a continuous beep.
- Replace Battery: The battery is nearing the end of its useful life. When the display shows a flashing Replace Battery icon and an empty Battery Capacity icon, replace the battery as early as possible.
- On Battery: The Back-UPS is supplying battery backup power to the connected equipment, it will beep four times every 30 seconds.
- Event: The event counter shows the number of events that occurred that caused the Back-UPS to switch to on-battery operation.
- System Error Detected: The system has detected error. The error number will illuminate on the display interface. See “Detected System Errors” on page 8.
- Overload: The power demand from the load has exceeded the capacity of the Back-UPS.
- Mute: If the line through the speaker icon is illuminated, the audible alarm has been turned off.
- Out: Output voltage, frequency.
- In: Input voltage.
- Automatic Voltage Regulation:
- When illuminated, the Back-UPS is compensating for low input voltage.
- When illuminated, the Back-UPS is compensating for high input voltage.
- Estimated Run Time: This indicates the battery runtime minutes that remain if the Back-UPS switches to battery power.
- Load: The total load in watts (W) or percentage (%) used by the devices connected to the Battery Backup outlets.
Detected Alarms and System Errors
Audible Indicators
- Four Beeps Every 30 Seconds: Back-UPS is running on battery. You should consider saving any work in progress.
- Continuous Beeping: Low battery condition and battery run-time is very low. Promptly save any work in progress, exit all open applications, and shut down the operating system.
- Continuous tone: Battery Backup outputs are overloaded.
- Chirps every 2: Seconds Battery is disconnected.
- Continuous chirping: Battery did not pass the automatic diagnostic test and should be replaced as early as possible. Pressing the MUTE button pauses the chirping.
Status Icons
If these icons are flashing… This may be the problem.
- The Back-UPS is overloaded. Disconnect one of the items connected to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no longer overloaded and will continue to operate normally.
- The Back-UPS is operating on AC power, but the battery is not functioning properly. Contact Schneider Electric IT (SEIT) CustomerService to order a replacement battery. See “Replacement Battery” on page 11.
- The Back-UPS is operating on battery power and the battery power is getting low. Shut down all connected equipment to avoid losing an unsaved data. When possible, connect the Back-UPS to AC power to recharge the battery.
- The battery is not connected. See “Connect the Battery” on page 2 to make sure battery wires are connected properly.
Detected System Errors
The Back-UPS will display these error messages. Except for errors F01 and F02,
contact SEIT Technical Support.
Error Code | Error Description | Action Required |
---|---|---|
F01 | On-Battery Overload | Turn the Back-UPS off. Disconnect non-essential |
equipment from the Battery Backup outlets and then turn the Back-UPS on.
F02| On-Battery Output Short| Turn the Back-UPS off. Disconnect all equipment
from the Battery Backup outlets and then turn the Back-UPS on. Re-connect
equipment one item at a time. If the output is tripped again, disconnect the
device that caused the detected error.
F04| Clamp Short| Cannot be corrected by the user. Contact SEIT Technical
Support for assistance.
F05| Charge Error| Cannot be corrected by the user. Contact SEIT Technical
Support for assistance.
F06| Relay Welding| Cannot be corrected by the user. Contact SEIT Technical
Support for assistance.
F07| Temperature Error| Cannot be corrected by the user. Contact SEIT
Technical Support for assistance.
F08| Fan Error| Cannot be corrected by the user. Contact SEIT Technical
Support for assistance.
F09| Internal Error| Cannot be corrected by the user. Contact SEIT Technical
Support for assistance.
Function Button Quick Reference
Troubleshooting
Problem | Possible Cause | Corrective Action |
---|---|---|
Back-UPS will not switch on. | The Back-UPS is not connected to AC | |
power. | Ensure that the Back-UPS is securely connected to an AC outlet. | |
The circuit breaker has been tripped. | Disconnect non-essential equipment |
from the Back-UPS. Reset the circuit breaker. Reconnect equipment one item at
a time. If the circuit breaker is tripped again, disconnect the device that
caused the trip.
| The internal battery is not connected.| Connect the battery.
| The AC input voltage is out of range.| Adjust the transfer voltage and
sensitivity range.
Back-UPS does not provide power during an AC power outage.| Essential
equipment is plugged into a SURGE ONLY outlet.| Disconnect equipment from the
SURGE ONLY outlet and reconnect to a Battery Backup outlet.
Back-UPS is operating on battery power, while connected to AC power.|
The plug has partially pulled out of the wall outlet, the wall outlet is no
longer receiving AC power, or the circuit breaker has been tripped.| Ensure
that the plug is fully inserted into the wall outlet. Ensure that the wall
outlet is receiving AC power by checking it with another device.
| The Back-UPS is performing an automatic self-test.| No action is necessary.
| The AC input voltage is out of range, the frequency is out of range, or the
waveform is distorted.| Adjust the transfer voltage and sensitivity range.
Back-UPS does not provide the expected amount of backup time.| Battery
Backup outlets may be fully or improperly loaded.| Disconnect non-essential
equipment from the Battery Backup outlets and connect the equipment to SURGE
outlets.
| The battery was recently discharged due to a power outage and has not fully
recharged.| Charge the battery cartridge for 16 hours.
| The battery has reached the end of its useful life.| Replace the battery.
REPLACE BATTERY indicator is illuminated.| The battery has reached the
end of its useful life.| Replace the battery as early as possible.
OVERLOAD indicator is illuminated.| The equipment connected to the Back-
UPS is drawing more power than the Back-UPS can provide.| Disconnect non-
essential equipment from the Battery Backup outlets and connect the equipment
to SURGE outlets.
SYSTEM ERROR indicator is illuminated, all the front panel indicators are
flashing.| There is an internal error detected.| Determine which internally
detected error message is displayed by matching the number displayed on the
LCD with the corresponding Error Message (see “Detected System Errors”) and
contact SEIT Technical Support.
Specifications
VA | 1500 VA |
---|---|
Maximum Load | 900 W |
Nominal Input Voltage | 120 V |
Online Input Voltage Range | 88 – 147 V |
Automatic Voltage Regulation | Boost by +11.5% when input voltage drops |
below limit
Trim by -11.5% when input voltage exceeds limit
Frequency Range| 60 Hz ± 3 Hz
On-battery Waveshape| Sine-wave
USB charging port| Type C1, Type A1 (15 W in total)
Typical Recharge Time| 16 hours
Transfer Time| 8 ms, maximum
Operating Temperature| 32 to 104 o F (0 ~ 40 oC)
Storage Temperature| 23 to 113 oF (-15 ~ 40 oC)
Unit Dimensions| 11.9 × 4.4 × 15.0 in (368 × 100 × 260 mm)
Unit Weight| 27.6 lb (12.5 kg)
Interface| USB and Simple Signal (Serial Data Port)
On-Battery Runtime| Go to: http://www.apc.com/product
International Protection Code| IP20
Replacement Battery
The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Battery replacement parts for Back- UPS Pro BR1500MS2 is APCRBC163. Delaying the replacement of parts may corrode the batteries in the cartridge. Recycle spent battery cartridges.
Warranty
The standard warranty is three (3) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory-reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.
APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web
site, www.apc.com.
Select models are ENERGY STAR® qualified. For more information on your
specific model go to APC by Schneider Electric Web site,
www.apc.com. Select models are compliant with California
(CEC) Battery Charger regulations.
For more information on your specific model go to APC by Schneider Electric
Web site, www.apc.com.
EMC Compliance
This equipment has been tested and found to comply with the limits for a Class B digital device, under part 15 of the FCC Rules. These limits are designed to protect reasonably against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used by the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. Suppose this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on. In that case, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and the receiver.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
© 2020 APC by Schneider Electric. APC, the APC logo, and Back-UPS are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are the property of their respective owners.
FAQs
What is the power capacity of the APC BR1500MS2 Back-UPS Pro?
The APC BR1500MS2 Back-UPS Pro has a power capacity of 1500VA / 900W.
How many outlets does the APC BR1500MS2 Back-UPS Pro have?
The APC BR1500MS2 Back-UPS Pro has a total of 10 outlets, with 6 providing both surge protection and battery backup and 4 offering surge protection only.
What type of waveform does the APC BR1500MS2 Back-UPS Pro provide?
The APC BR1500MS2 Back-UPS Pro provides a sinewave output, ideal for high-end electronics.
What devices are best protected by the APC BR1500MS2 Back-UPS Pro?
The APC BR1500MS2 Back-UPS Pro is ideal for protecting home Wi-Fi, computers, and office electronics.
How does the LCD screen on the APC BR1500MS2 Back-UPS Pro help users?
The LCD screen on the APC BR1500MS2 Back-UPS Pro provides real-time information on battery status, load capacity, and more, helping users monitor their UPS easily.
What is the recharge time for the APC BR1500MS2 Back-UPS Pro battery?
The typical recharge time for the APC BR1500MS2 Back-UPS Pro battery is around 8 hours.
What software is recommended for managing the APC BR1500MS2 Back-UPS Pro on Windows computers?
The APC BR1500MS2 Back-UPS Pro can be managed using the PowerChute UPS management software on Windows 10 and Windows 11.
How often should the battery in the APC BR1500MS2 Back-UPS Pro be replaced?
The battery in the APC BR1500MS2 Back-UPS Pro should typically be replaced every 3-5 years, or when the UPS indicates battery failure.
What is the ideal environment for placing the APC BR1500MS2 Back-UPS Pro?
The APC BR1500MS2 Back-UPS Pro should be placed in a well-ventilated area, away from excessive dust and heat, to ensure optimal performance.
How many outlets does the APC BR1500MS2 have?
The APC BR1500MS2 features a total of 10 outlets, including 5 battery backup outlets and 5 surge protection-only outlets.
What is the weight of the APC BR1500MS2?
The APC BR1500MS2 weighs approximately 31.5 lbs, making it relatively easy to position within a home or office.
Video-APC BR1500MS2 Back-UPS Pro
Download this Manual:APC BR1500MS2 Back-UPS Pro User Manual
Reference Link
APC BR1500MS2 Back-UPS Pro User Manual- Device.report
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>