APC BR1200GI Power Saving Back-UPS Pro 1200 230V Instruction Manual
- June 2, 2024
- APC
Table of Contents
- Inventory
- Important Safety Messages
- Connect the Battery
- Install PowerChute™ Personal Edition Software
- Connect the Equipment
- Operation
- Alerts and System Events
- Function Button Quick Reference
- Troubleshooting
- Specifications
- Replace Battery
- Service
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Installation and Operation
Back-UPS™ Pro 1200/1500 230V
Inventory
Important Safety Messages
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
- This UPS is intended for indoor use only.
- Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
- Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
- The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality AC power, and frequent short duration discharges will shorten battery life.
- Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
- Replace the battery at least every 5 years or at the end of its service life, whichever is earlier.
- Replace the battery immediately when the UPS indicates battery replacement is necessary.
- Replace batteries with the same number and type of batteries as originally installed in the equipment.
- Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
Failure to follow these instructions can result in minor or moderate injury and equipment damage.
Connect the Battery
Install PowerChute™ Personal Edition Software
Use PowerChute Personal Edition software to configure the UPS settings,
protect your computer and other equipment during a utility power outage.
During a power outage,
PowerChute will save any open files on your computer and shut it down. When
utility power is restored, it will restart the computer.
NOTE: PowerChute is only compatible with a Windows operating system. If
you are using Mac OSX, use the native shutdown feature to protect your system.
See the documentation provided with your computer.
Installation
Use the USB cable to connect the Data port on the UPS to the USB port on your
computer. Download PowerChute™ Personal Edition Software from
www.apc.com/pcpe. Select the appropriate operating
system and follow directions to download the software.
Connect the Equipment
Battery Backup and Surge Protected outlets
When the Back-UPS is receiving input power, the Battery Backup with Surge
Protection outlets will supply power to connected equipment. During a power
outage or other utility problems, the Battery Backup outlets receive power for
a limitedtime from the Back-UPS.
Connect equipment such as printers, fax machines, scanners, or other
peripherals that do not need battery backup power to the Surge Protection Only
outlets. These outlets provide full-time protection from surges even if the
Back-UPS is switched OFF.
Master and Controlled outlets
To conserve electricity, when the device connected to Master Outlet goes into
Sleep or Standby mode, or turns Off, the Controlled device(s) will shut down
as well, saving electricity.
Connect a master device, such as a desktop computer or audio/ visual receiver
to the Master outlet. Connect peripheral devices such as a printer, speakers,
or a scanner to the Controlled outlets.
1| USB and Serial Data port| To use PowerChute Personal Edition, connect a
serial cable or USB cable.
---|---|---
2| Telephone cable surge- protected ports| Connect a telephone cable to the IN
port, and connect a modem to the OUT port.
3| Ground screw| Connect the ground lead of additional surge suppression
devices such as network and data line surge protectors.
4| Surge Protected outlets, controlled by the Master outlet| These outlets are
protected from electrical surges, and will disconnect from utility power
during a power outage, or if the Master device goes into Sleep or Standby
mode.
5| Surge Protected outlets| These outlets provide full-time protection from
surges, even if the Back-UPS is off. Connect equipment such as printers and
scanners that do not require battery backup protection.
6| AC power outlet| Connect the unit to utility power, use the supplied power
cord.
7| Battery Backup outlets with Surge Protection| During a power outage or
other utility problems, the Battery Backup outlets receive power for a limited
time from the Back-UPS. Connect critical equipment such as desktop computer,
computer monitor, modem or other data sensitive devices into these outlets.
8| Battery Backup outlet with Surge Protection, controlled by the Master
outlet| These outlets will supply battery power to the connected equipment
during a power outage. Power will be disconnected to these outlets if the
Master device goes into Sleep or Standby mode. Connect equipment such as a
computer monitor to these outlets.
9| Master outlet| Connect the master device to this outlet, in most scenarios,
this will be the main computer.
10| External Battery Pack connector (BR1500GI only)| Connect an external
battery pack to provide additional battery backup runtime (Back-UPS Pro 1500
only).
11| In & Out Ethernet surge- protected ports| Use an ethernet cable to connect
a cable modem to the IN port, and connect a computer to the OUT port.
Operation
Power-Saving Function
To conserve electricity, configure the Back-UPS to recognize a Master device,
such as a desktop computer or an A/V receiver, and Controlled peripheral
devices, such as a printer, speakers, or a scanner. When the Master device
goes into Sleep or Standby mode, or is switched OFF, the Controlled device(s)
will be switched off as well, saving electricity.
Enable the Power-Saving function. Press and hold MUTE and DISPLAY
simultaneously for two seconds. The Back-UPS will beep to indicate that the
feature is enabled. The leaf icon on the display will illuminate.
Disable the Power-Saving function. Press and hold MUTE and DISPLAY
simultaneously for two seconds. The Back-UPS will beep to indicate that the
feature is disabled. The leaf icon on the display will darken.
Setting the threshold. The amount of power used by a device in Sleep or
Standby mode varies between devices. It may be necessary to adjust the
threshold at which the Master outlet signals the Controlled outlets to shut
down.
- Ensure a master device is connected to the Master outlet. Put that device into Sleep or Standby mode, or turn it OFF.
- Press DISPLAY and MUTE simultaneously and hold for six seconds, until the leaf icon flashes three times and the Back-UPS beeps three times.
- The Back-UPS will now recognize the threshold level of the Master device and save it as the new threshold setting.
Power-Saving Display
The display interface can be configured to be continuously illuminated, or to
save energy, it can be configured to darken after a period of inactivity.
- Full Time Mode: Press and hold DISPLAY for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full-Time mode.
- Power-Saving Mode: Press and hold DISPLAY for two seconds. The display will darken and the Back-UPS will beep to confirm the Power-Saving mode. While in Power-Saving Mode, the display will illuminate if a button is pressed, it then darkens after 60 seconds of no activity.
Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to
battery power; the higher the sensitivity, the more often the Back-UPS will
switch to battery power.
- Ensure the Back-UPS is connected to utility power, but is OFF.
- Press and hold the POWER button for six seconds. The LOAD CAPACITY bar will flash on and off, indicating that the Back-UPS is in programming mode.
- Press POWER again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection.
Front Panel Buttons and Display Interface
Use the three buttons on the front panel of the Back-UPS and the display
interface to configure the Back-UPS.
Front panel
- Mute button
- Power On/Off button
- Display button
- Display interface
| On Line: The Back-UPS is supplying conditioned utility power to
connected equipment
---|---
| Power-Saving : Master and Controlled outlets are enabled, saving power
when the master device goes into
sleep or standby mode
| Load Capacity : The load is indicated by the number of sections
illuminated, one to five. Each bar represents
20% of the load.
| Battery Charge: The battery charge level is indicated by the number of
sections illuminated. When all five
blocks are illuminated, the Back-UPS is at full charge. When one block is
filled, the Back-UPS is near the end of its battery capacity, the indicator
will flash and the Back-UPS will beep continuously.
| Overload: The power demand from the load has exceeded the capacity of
the Back-UPS.
| Event: The event counter shows the number of events that occurred that
caused the Back-UPS to switch to onbattery operation.
| Automatic Voltage Regulation: The Back-UPS can compensate for high or
low input voltage.
When illuminated, the Back-UPS is compensating for low input voltage.
When illuminated, the Back-UPS is compensating for high input voltage.
| Input voltage.
Output voltage.
| System Events : The system has detected an event. The event number will
illuminate on the display interface.
See “System Events” on page 5.
| Mute: If the line through the speaker icon is illuminated, the audible
alarm has been turned off.
| Replace Battery : The battery is not connected or is nearing the end of
its useful life. Replace the battery.
| On Battery: The Back-UPS is supplying battery backup power to the
connected equipment, it will beep four
times every 30 seconds.
Alerts and System Events
Audible Warnings
Four Beeps Every 30 Seconds| Back-UPS is running on battery. You should
consider saving any work in progress.
---|---
Continuous Beeping| Low battery condition and battery run-time is very low.
Promptly save any work in progress, exit all open applications, and shut down
the operating system.
Continuous tone| Battery Backup outputs are overloaded.
Chirps for 1 Minute every 5 hours| Battery is not able to pass the automatic
diagnostic test and should be replaced.
Alerts Icons
If these icons are illuminated… | This may be the problem. |
---|---|
The Back-UPS is operating on utility power, but is overloaded. Disconnect |
one of the items connected to the Back-UPS. If the Overload icon stops
flashing, the Back-UPS is no longer overloaded and will continue to operate
normally.
| The Back-UPS is operating on battery power, but is overloaded. Disconnect
one of the items connected to the Back-UPS. If the Overload icon stops
flashing, the Back-UPS is no longer overloaded and will continue to operate
normally.
| The Back-UPS is operating on utility power, but the battery is not
functioning properly. Contact APC Customer Service to order a replacement
battery. See Warranty on page 8.
| The Back-UPS is operating on battery power and the battery power is getting
low. Shut down all connected equipment to avoid losing an unsaved data. When
possible, connect the Back-UPS to utility power to recharge the battery.
System Events
The Back-UPS will display these event messages. For events F01 and F02,
contact APC Technical Support.
F01| On-Battery Overload| Turn the Back-UPS off. Disconnect non-essential
equipment from the Battery Backup outlets and the turn Back-UPS on.
---|---|---
F02| On-Battery Output Short| Turn the Back-UPS off. Disconnect non-essential
equipment from the Battery Backup outlets and the turn Back-UPS on.
F03| On-Battery Xcap Overload| Events F03-F09 cannot be corrected by the user,
contact APC Technical Support for assistance.
F04| Clamp Short
F05| Charge Status
F06| Relay Welding
F07| Temperature
F08| Fan Condition
F09| Internal Event
Function Button Quick Reference
Function| Button| Timing
(seconds)| UPS
Status| Description
---|---|---|---|---
Power
Power On| | 0.2| Off| Press POWER to start receiving input utility power. If
A/C input power is not
available, the Back-UPS will run on battery power.
Power Off| | 2| On| The Back-UPS is not receiving input utility power, but is
providing surge
protection.
Display
Status Inquiry| | 0.2| On| Verify the status or condition of the Back-UPS. The
LCD will illuminate for 60
seconds.
Full-Time/PowerSaving
mode| | 2| On| The LCD will illuminate and the Back-UPS will beep to confirm
the Full-Time
mode. The LCD will darken and the Back-UPS will beep to confirm the
Power-Saving mode. While in Power-Saving Mode, the LCD will illuminate if
a button is pressed, then darkens after 60 seconds of no activity.
Mute
Event Specific| | 0.2| On| Disable any audible alarms caused by an event.
General Status Enable/
Disable| | 2| On| Enable or disable the audible alarms. The Mute icon will
illuminate and the
Back-UPS will beep one time. The Mute function will not activate unless the
Back-UPS is operating on battery power.
Sensitivity| | 6| Off| The Load Capacity icon will blink, indicating that the
Back-UPS is in
programming mode. Use the POWER button to scroll through Low, Medium,
and High, stop at selected sensitivity. The Back-UPS will beep to confirm
selection. See Configuration for details.
Master/Controlled
outlet Enable/Disable| | 2| On| The leaf icon will darken indicating that the
Master Outlet feature is disabled
or illuminate to indicate the Master Outlet feature is enabled. The Back-UPS
will beep once.
Master/Enable
Threshold Calibration| | 6| On| While calibrating the threshold setting, the
device connected to the Master
Outlet should be turned off or placed in Standby or Sleep mode. Upon
completion, Power-Saving icon will flash 3 and beep 3 times.
Self-Test (manual)| | 6| On| The Back-UPS will perform a test of the internal
battery. Note: This will
happen automatically when the Back-UPS is turned ON.
Event Reset| | 0.2| On| When the Event screen is visible, press and hold
DISPLAY, then press
POWER, to clear the utility event counter.
Status Reset| | 2| Even| After an event has been detected and identified,
press POWER to remove the
visual indication and return to standby status.
Troubleshooting
Problem | Possible Cause | Corrective Action |
---|---|---|
Back-UPS will not switch on. | The Back-UPS is not connected to utility power. |
Ensure that the Back-UPS is securely connected to an AC outlet.
The circuit breaker has been tripped.| Disconnect non-essential equipment from
the Back-UPS. Reset the circuit breaker. Re-connect equipment one item at a
time. If the circuit breaker is tripped again, disconnect the device that
caused the trip.
The internal battery is not connected.| Connect the battery.
The utility input voltage is out of range.| Adjust the transfer voltage and
sensitivity range.
The Back-UPS does not provide power during a utilitypower outage.| Ensure that
essential equipment is not plugged into a SURGE ONLY outlet.| Disconnect
equipment from the SURGE ONLY outlet and re-connect to a Battery Backup
outlet.
The Back-UPS is operating on battery power, while connected to utility power.|
The plug has partially pulled out of the wall outlet, the wall outlet is no
longer receiving utility power, or the circuit breaker has been tripped.|
Ensure that the plug is fully inserted into the wall outlet. Ensure that the
wall outlet is receiving utility power by checking it with another device.
The Back-UPS is performing an automatic self test.| No action is necessary.
The utility input voltage is out of range, the frequency is out of range. or
the waveform is distorted.| Adjust the transfer voltage and sensitivity range.
The Back-UPS does not provide the expected amount of backup time.| Battery
Backup outlets may be fully or improperly loaded.| Disconnect non-essential
equipment from the Battery Backup outlets and connect the equipment to SURGE
ONLY outlets.
The battery was recently discharged due to a power outage and has not fully
recharged.| Charge the battery cartridge for 16 hours.
The battery has reached the end of its useful life.| Replace the battery.
The REPLACE BATTERY Indicator is Illuminated.| The battery has reached the end
of its useful life.| Replace the battery.
The OVERLOAD indicator Is Illuminated.| The equipment connected to the Back-
UPS is drawing more power than the Back-UPS can provide.| Disconnect non-
essential equipment from the Battery Backup outlets and connect the equipment
to SURGE ONLY outlets.
The SYSTEM EVENT indicator Is Illuminated, all the front panel Indicators are
flashing.| There is an internal detected event| Determine which internal
detected event message is displayed by matching the number displayed on the
LCD with the corresponding Event Message (see System Events) and contact APC
Technical Support.
Power is not supplied to some outlets.| Power to the Controlled outlets has
intentionally been turned oft| Confirm that the correct peripherals are
connected to Controlled outlets. If this feature is not desired, disable the
Power-Saving Master and Controlled outlets.
The Controlled outlets are not supplying pow er. even though the aster device
is not In sleep mode.| The Master Outlet threshold may be incorrectly set.|
Adjust the threshold when the Master outlet signals the Controlled outlets to
shut down.
Specifications
Model | BR1200GI | BR1500G1 |
---|---|---|
VA | 1200 VA | 1500 VA |
Maximum Load | 720 W | 865 W |
Nominal Input Voltage | 230 V | |
Online Input Voltage Range | 176 – 294 V | |
Automatic Voltage Regulation | (188-216) +11.2% (252-282) -11.2% | |
Frequency Range | 50/60 Hz ± 1 Hz | |
On-battery Waveshape | Step-approximated sine-wave | |
Typical Recharge Time | 8 hours | |
Transfer Time | 10 ms, maximum | |
Operating Temperature | 0°C to 40°C (32°to 104°F) | |
Storage Temperature | -15°C to 45°C (23°to 113°F) | |
Unit Dimensions | 30.1 x 11.2 x 38.2 cm (11.9 x 4.4 x 15.0 in) | |
Unit Weight | 12.8 kg (28.2 Ibs) | 13.4 kg (29.5 Ibs) |
Interface | Serial, USB | |
On-Battery Runtime | Go to: www.apc.com | |
Humidity | 0 to 95 % relative humidity, non-conder | |
Pollution Degree | 2 | |
Overvoltage Category | II | |
Applicable power grid power distribution system | TN Power system | |
International Protection Code | IP20 | |
Applicable Standard | IEC 62040-1 |
Replace Battery
Deliver the used battery to a recycling facility.
Replace the used battery with an APC by Schneider Electric approved battery.
Replacement batteries can be ordered through the APC by Schneider Electric Web
site, www.apc.com.
Battery replacement part for Back-UPS Pro BR1200GI and BR1500GI is APCRBC124.
Service
If the Back-UPS arrived damaged, notify the carrier.
If the Back-UPS requires service, do not return it to the dealer.
- Consult the Troubleshooting section to eliminate common problems.
- If the problem persists, go to http://www.apc.com/support/.
- If the problem still persists, contact APC Technical Support.
Have the Back-UPS model number, serial number and date of purchase available.
Be prepared to troubleshoot the problem with an APC Technical Support
representative.
If this is not successful, APC will issue a Return Merchandise Authorization
(RMA) number and a shipping address.
Warranty
The standard warranty is three (3) years from the date of purchase, valid in European Community. For all other regions, the standard warranty is two (2) years from the date of purchase. APC’s standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement unit to the customer.
APC by Schneider Electric IT Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web
site, www.apc.com Customer support and warranty
information is available at the APC by Schneider Electric Web site,
www.apc.com.
© 2022 APC by Schneider Electric. APC, the APC logo, and PowerChute are owned
by Schneider Electric Industries S.A.S., or their affiliated companies. All
other trademarks are property of their respective owners.
References
- APC, a flagship brand of Schneider Electric - APC USA
- APC, a flagship brand of Schneider Electric - APC USA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>