SmartGen HGM9310MPU Genset Controller User Manual
- August 16, 2024
- SmartGen
Table of Contents
SmartGen HGM9310MPU Genset Controller
Specifications
- Models: HGM9310MPU, HGM9320MPU, HGM9310CAN, HGM9320CAN
- Dimension: Varies based on model
- LCD Pixel: Varies based on model
- AMF Input Port Number: Varies based on model
- Output Port Number: Varies based on model
- Sensor Number: Varies based on model
- Neutral (Earth) Current Schedule Function: Yes
- RS485, GSM, J1939, USB: Yes
- Real-time Clock: Yes
- Event Log: Yes
Overview
The HGM9300MPU(CAN) Series Genset Controller is designed for single automation systems. The HGM9310MPU(CAN) allows for auto start/stop of the unit using remote signals. The HGM9320MPU(CAN) includes all functions of the HGM9310MPU(CAN) and adds automatic mains failure function (AMF), making it suitable for automation systems with both mains and generator power sources.
Performance and Characteristics
The HGM9310MPU(CAN) is ideal for applications where single automation systems require remote signal control for unit start/stop functionality. The HGM9320MPU(CAN) is suitable for automation systems that need to seamlessly switch between mains and generator power sources in case of a mains failure.
FAQs
What are the key functions of the HGM9300MPU(CAN) Series Genset
Controller?
The key functions include auto start/stop of the unit using remote signals,
automatic mains failure function (AMF), input and output ports, sensor
configurations, and real-time clock functionality.
What is the difference between the HGM9310MPU and HGM9320MPU models?
The HGM9320MPU model includes all the functions of the HGM9310MPU and adds AMF
capability for seamless switching between mains and generator power sources.
Table 1 Software Version
Note Original release 1. Add timer setting of gas gen-set. 2. Add functions of
input ports and output ports. Update user manual format and parameter limit
values. Change company logo and manual format. 1. Added notes for master-
standby running enable and balanced running enable; 2. Added functions of
input ports and parameter configurations.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 2 of 70
This manual is suitable for HGM9310MPU, HGM9320MPU, HGM9310CAN and HGM9320CAN series controller only.
OVERVIEW
HGM93XXMPU(CAN) series genset controllers are used for genset automation and monitor control system of single unit to achieve automatic start/stop, data measure, alarm protection and “three remote” (remote control, remote measuring and remote communication). The controller adopts large liquid crystal display (LCD) and selectable Chinese, English or other languages interface with easy and reliable operation. HGM93XXMPU(CAN) series genset controllers adopt 32-bit micro-processor technology with precision parameters measuring, fixed value adjustment, time setting and threshold adjusting, etc. The majority of parameters can be set using front panel and all the parameters can be set using PC (via USB port) and can be adjusted and monitored with the help of RS485 port. It can be widely used in a number of automatic genset control system with compact structure, simple connections and high reliability.
NOTE: (1) Two of the output ports are fixed: start output and fuel output. (2) The analog sensors are composed by 3 fixed sensors (temperature, pressure, fuel level) and 2 flexible sensors.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 6 of 70
PERFORMANCE AND CHARACTERISTICS
HGM9310MPU(CAN), used for single automation systems, auto start/stop of the unit are performed
with the help of remote signal.
HGM9320MPU(CAN), has all functions of HGM9310MPU(CAN) as well as automatic mains failure
function (AMF), particularly well suits for single automation systems that include mains and generator.
Key characteristics,
With ARM-based 32-bit SCM, highly integrated hardware, new reliability level;
480×272 TFT LCD with backlight, multilingual interface (including English,
Chinese or other
languages) which can be chosen at the site, making commissioning convenient for factory
personnel;
Improved LCD wear-resistance and scratch resistance due to hard screen
acrylic; Silicon panel and pushbuttons for better operation in high/low
temperature environment; RS485 communication port enabling remote control,
remote measuring, remote communication
via ModBus protocol (RS485 communication port is needed);
Equipped with SMS (Short Message Service) function. When genset is alarming,
controller can
send short messages via SMS automatically to max. 5 telephone numbers. besides, generator
status can be controlled and checked using SMS (GSM port is needed);
Equipped with CANBUS port and can communicate with J1939 genset. Not only can
you
monitoring frequently-used data (such as water temperature, oil pressure, speed, fuel
consumption and so on) of ECU machine, but also control start, stop, speed raise and speed drop
via CANBUS port (CAN BUS port is needed);
Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with
voltage 120/240V and frequency 50/60Hz;
Collects and shows AC 3-phase voltage, current, power parameter and frequency of generator; Collects and shows DC voltage, current, and power of generator;
Mains
Generator
Line voltage (Uab, Ubc, and Uca)
Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc)
Phase voltage (Ua, Ub, and Uc)
Phase sequence
Phase sequence
Frequency Hz
Frequency Hz
Load Current IA, IB, IC Each phase and total active power kW Each phase and total reactive power kvar Each phase and total apparent power kVA Each phase and average power factor PF Accumulate total generator power kWh, kvarh, kVAh
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 7 of 70
Earth current A
For generator, controller has over and under voltage, over and under frequency, over current, over
power, reverse power, loss of phase and phase sequence wrong functions;
3 fixed analog sensors (temperature, oil pressure and fuel level);
2 flexible sensors can be set as temperature sensor, oil pressure sensor or level sensor; Precision measure and display parameters about Engine,
Temp. (WT)
°C/°F both be displayed
Oil pressure (OP)
kPa/psi/bar all be displayed
Fuel level (FL)
%(unit)
Speed (SPD)
r/min (unit)
Battery Voltage (VB) V (unit)
Charger Voltage (VD) V (unit)
Hour count (HC) can accumulate to max. 65535 hours.
Start times can accumulate to max. 65535 times.
Protection: automatic start/stop of the genset, ATS (Auto Transfer Switch) control with perfect
failure indication and protection function;
All output ports are relay-out;
Parameter setting: parameters can be modified and stored in internal FLASH memory and cannot
be lost even in case of power outage; most of them can be adjusted using front panel of the
controller and all of them can be modified using PC via USB or RS485 ports.
More kinds of curves of temperature, oil pressure, fuel level can be used directly and users can
define the sensor curves by themselves;
Multiple crank disconnect conditions (generator frequency, engine speed oil pressure) are
optional;
Widely power supply range DC(8~35)V, suitable to different start battery voltage environment;
Event log, real-time clock, scheduled start & stop generator (can be set as start genset once a
day/week/month whether with load or not);
PLC (programmable logic control) function allows for specific function can be user-defined.
Logon wallpaper and display time are user-defined.
Can be used on pumping units and as an indicating instrument (indicate and alarm are enable
only, relay is inhibited);
With maintenance function. Actions (warning or shutdown) can be set when maintenance time
due;
All parameters used digital adjustment, instead of conventional analog modulation with normal
potentiometer, more reliability and stability;
Waterproof security level IP65 due to rubber seal installed between the controller enclosure and
panel fascia;
Metal fixing clips enable perfect in high temperature environment;
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 8 of 70
Modular design, self-extinguishing ABS plastic enclosure, pluggable connection
terminals and
embedded installation way; compact structure with easy mounting
Accumulative total run time and total electric energy of A and B. Users can
reset it as 0 and
re-accumulative the value which make convenience to users to count the total
value as their wish.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 9 of 70
4 SPECIFICATION
Item Operating Voltage Power Consumption Alternator Input Range 3-Phase 4-Wire
3-Phase 3-Wire Single Phase 2-Wire 2-Phase 3-Wire Alternator Frequency Speed
Sensor Voltage Speed Sensor Frequency Start Relay Output Fuel Relay Output
Auxiliary Relay Output (1) Auxiliary Relay Output (2) Auxiliary Relay Output
(3) Auxiliary Relay Output (4) Auxiliary Relay Output (5) Auxiliary Relay
Output (6) Case Dimension Panel Cutout C.T. Secondary Working Temperature
Working Humidity Storage Temperature Protection Level
Insulating Intensity
Weight
Table 4 Specification
Content DC8.0V to DC35.0V, Continuous Power Supply. <4W (standby 2W)
AC15V – AC 360V (ph-N) AC30V – AC620V (ph-ph) AC15V – AC360V (ph-N) AC15V –
AC360V (ph-N) 50Hz/60Hz 1.0V to 24.0V (RMS) 10,000 Hz (max.) 16A DC28V supply
output 16A DC28V supply output 7A DC28V supply output 7A DC28V supply output
7A DC28V supply output 7A AC250V voltage free output 7A AC250V voltage free
output 7A AC250V voltage free output 237mm x 172mm x 45mm 214mm x160mm 5A
rated (-25~+70)°C (20~93)%RH (-25~+70)°C IP65 Gasket Apply AC2.2kV voltage
between high voltage terminal and low voltage terminal; The leakage current is
not more than 3mA within 1min. 0.85kg
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 10 of 70
5 OPERATION 5.1 INDICATOR LIGHT
Fig.1 HGM9310MPU/HGM9310CAN Front Panel
Fig.2 HGM9320MPU/HGM9320CAN Front Panel
Table 5 Warning Indicator and Alarm Indicator
Alarm Type Warning Alarm Trip Alarm Shutdown Alarm Trip and Stop Alarm
Warning Indicator Slow flashing Slow flashing Off Off
Alarm Indicator Slow flashing Slow flashing Fast flashing Fast flashing
NOTE: Selected light indicators description: Running indicator: It is illuminated from crank disconnect to ETS while extinguished during other periods. Generator normal indicator: It is illuminated when generator is normal; flashing when generator state is abnormal; extinguished when there is no generator power.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 11 of 70
5.2 KEY FUNCTIONS
Icons
Keys Stop
Start
Table 6 Key Description
Description Stop running generator in Auto/Manual mode; Reset alarms in stop
mode; Lamp test (press at least 3 seconds); During stopping process, press
this button again to stop generator immediately.
Start genset in Manual mode.
Manual Mode
Press this key and controller enters in Manual mode.
Auto Mode
Press this key and controller enters in Auto mode.
Mute/Reset Alarm Gen Close/Open Mains Close/Open Close Open Up/Increase Down/Decrease Left
Alarming sound off; If there is trip alarm, pressing the button at least 3
seconds can reset this alarm.
Can control generator to switch on or off in manual mode. (HGM9310MPU,
HGM9310CAN without)
Can control mains to switch on or off in manual mode. (HGM9310MPU, HGM9310CAN
without).
Can close breaker in manual mode (HGM9320MPU, HGM9320CAN without).
Can open breaker in manual mode (HGM9320MPU, HGM9320CAN without). 1) Screen
scroll; 2) Up cursor and increase value in setting menu. 1) Screen scroll; 2)
Down cursor and decrease value in setting menu.
- Screen scroll; 2) Left move cursor in setting menu.
Right Set/Confirm Exit
- Screen scroll; 2) Right move cursor in setting menu.
Entering into parameter setting page after pressing this key for more than 3s; Confirm information in setting page. 1. Returns to the main menu; 2. In settings menu returns to the previous menu.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 12 of 70
NOTE: In manual mode, pressing
and
simultaneously will force generator to crank. Successful
start will not be judged according to crank disconnect conditions, operator will have to crank the starter motor manually; when operator decides that the engine has fired, he/she should release the button and start output will be deactivated, safety on delay will start.
WARNING: Default password is 00318, user can change it in case of others
change the advanced parameters setting. Please clearly remember the password
after changing. If you forget it, please contact SmartGen services and send
all PD information in the controller page of “ABOUT” to us.
5.3 LCD DISPLAY 5.3.1 MAIN DISPLAY
Main screen show pages; use
to scroll the pages and
to scroll the screen.
a) Main screen, including as below: Generator: voltage, frequency, current, active power, reactive power;
Mains: voltage;
Engine: speed, temperature, oil pressure, battery voltage;
Other some status b) Status, including as below,
Status of genset, mains, and switch.
c) Engine, including as below,
Speed, engine temperature, engine oil pressure, fuel level, config analog 1, config analog 2, battery voltage,
charger voltage, accumulated run time, accumulated start times, user’s total run time A, user’s total run
time B.
NOTE: If connected with J1939 engine via CANBUS port, this page also includes:
coolant pressure, coolant level, fuel
temperature, inlet head temperature, exhaust head temperature, turbo pressure,
fuel consumption, total fuel consumption and so on. (Different engine with
different parameters)
d) Generator, including as below, Phase voltage, line voltage, frequency,
phase sequence. e) Load, including as below, Current of each phase, each phase
and total active power (positive and negative), each phase and total reactive
power (positive and negative), each phase and total apparent power, each phase
and average power factor (positive and negative), accumulated energy, earth
current, total electric energy A and B.
NOTE: Power factor shows as following,
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 13 of 70
Remark: P stands for active power Q stands for reactive power
Table 7 Power Factor
Power Factor Conditions
COS>0L
P>0,Q>0
COS>0C
P>0,Q<0
Active power Input Input
Reactive power Input Output
COS<0L
P<0,Q>0 Output
Input
COS<0C
P<0,Q<0 Output
Output
Remark Load is inductive resistance. Load is capacitance resistance. Load equals to one under excitation generator Load equals to one over excitation generator.
NOTE: Input active power: generator supplies electricity to load; Output
active power: load supplies electricity to generator; Input reactive power:
generator sends reactive power to load; Output reactive power: load sends
reactive power to generator.
f) Mains, including as below, Phase voltage, line voltage, frequency, phase
sequence. g) Alarm:
Display all alarm information. E.g. warning alarm, shutdown alarm, trip alarm
and trip and stop alarm.
NOTE: For ECU alarms and shutdown alarms, if the alarm information is displayed, check engine according to it,
otherwise, please check the manual of generator according to SPN alarm code.
h) Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or stop) and the
real time and genset status when alarm occurs. i) Others, including, Time and Date, and input/output ports status. j) About, including, Issue time of software and hardware version, product PD number.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 14 of 70
PARAMETERS SETTING MENU
Press and hold
for more than 3 seconds to enter into user menu;
a) Parameter After entering the correct password (factory default password is
00318) you can enter parameter
settings screen. After entering the correct password (09300) you can enter
basic parameter settings screen which can
meet the demands of most users as the basic parameters can be set in sequence.
b) Language Selectable Simplified Chinese, English and others (default:
Simplified Chinese). c) Commissioning On load, off load or custom
commissioning can be chosen. Custom commissioning can configure on load or not
during commissioning, when to commissioning and select the mode after
commissioning (manual mode, auto mode and stop mode). d) Clear users’
accumulation Can clear total run time A and B, total electric energy A and B.
DETAILED PARAMETERS SETTING
Mains settings Timer settings Engine settings Generator settings Load settings Switch settings Temperature sensor settings Oil pressure sensor settings Level sensor settings Flexible sensor 1 Flexible sensor 2 Input port settings Output port settings Module settings Scheduling and maintenance settings GSM settings Exp. input settings
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 15 of 70
Exp. output setting Exp. AIN24 1 settings Exp. AIN24 2 settings
Example, Return Mains Timers > Engine Generator Load Switch Temp. Sensor OP Sensor Level Sensor Flexible Sensor 1
Start Delay >Return Delay >Preheat Delay >Cranking Time >Crank Rest Time Safety On Time >Start Idle Time >Warming Up Time >Cooling Time >Stop Idle Time >ETS Hold Time
Return Mains Timers > Engine Generator Load Switch Temp. Sensor OP Sensor Level Sensor Flexible Sensor 1
Start Delay > Return Delay > Preheat Delay > Cranking Time > Crank Rest Time Safety On Time > Start Idle Time > Warming Up Time > Cooling Time > Stop Idle Time > ETS Hold Time
Return Mains
Timers > Engine Generator Load Switch Temp. Sensor OP Sensor Level Sensor
Flexible Sensor 1
Start Delay > Return Delay > Preheat Delay
Cranking Time > Crank Rest Time > Safety On Time > Start Idle Time > Warming Up Time > Cooling Time > Stop Idle Time > ETS Hold Time
Screen1: Use
to scroll settings,
to
enter settings (Screen 2), menu.
to exit settings
Screen 2: Use
to scroll settings,
to enter
settings (Screen 4), menu. (Screen 1).
to return to previous
Screen 3: Use
to scroll settings,
to enter
settings (Screen 4), menu. (Screen 1).
to return to previous
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 16 of 70
Start Delay > Return Delay > Preheat Delay > Cranking Time >Crank Rest Time Safety On Time > Start Idle Time > Warming Up Time > Cooling Time > Stop Idle Time > ETS Hold Time
00008s
Screen 4
Press
to enter settings (Screen 5),
to
return to previous menu. (Screen 6).
Start Delay > Return Delay >Preheat Delay > Cranking Time > Crank Rest Time Safety On Time > Start Idle Time > Warming Up Time > Cooling Time > Stop Idle Time > ETS Hold Time
00008s
Screen 5:
Press
to change cursor position,
are used for changing cursor value, Confirm
setting (Interface 4),
exit setting (Screen 4).
Start Delay > Return Delay > Preheat Delay > Cranking Time > Crank Rest Time Safety On Time > Start Idle Time > Warming Up Time > Cooling Time > Stop Idle Time > ETS Hold Time
00008s
Screen 6: Use
to scroll settings.
to enter
settings (Screen 4), (Screen 1).
to return to previous menu.
NOTE: Pressing
can exit setting directly during setting.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 17 of 70
5.4 AUTO START/STOP OPERATION 5.4.1 ILLUSTRATION
Auto mode is selected by pressing the operation.
button; a LED beside it will illuminate to confirm the
AUTOMATIC START SEQUENCE
a) HGM9320MPU(CAN): When Mains is abnormal (over and under voltage, over and
under frequency, loss of phase, phase sequence wrong), it enters into mains
“Abnormal Delay” and LCD display count down time. When mains abnormal delay is
over, it enters into “Start Delay”; it also enters into this mode when “Remote
Start On Load” is active.
b) HGM9310MPU(CAN): When “Remote Start (on load)” is active, “Start Delay”
timer is initiated; c) “Start Delay” countdown will be displayed on LCD; d)
When start delay is over, preheat relay energizes (if configured), “Preheat
Delay XX s” information will
be displayed on the downmost line of LCD; e) After the above delay, the Fuel
Relay (if configured) is energized, and then one second later, the Start
Relay is engaged. The engine is cranked for a pre-set time. If the engine
fails to fire during this cranking attempt then the fuel relay and start relay
are disengaged for the pre-set rest period; “Crank Rest Time” begins and wait
for the next crank attempt. f) Should this start sequence continue beyond the
set number of attempts, the start sequence will be terminated, the first line
of LCD display will be highlighted with black and “Fail to Start” fault will
be displayed. g) In case of successful crank attempt, the “Safety On” timer is
activated, allowing Low Oil Pressure, High Temperature, under speed and Charge
Alternator Failure inputs to stabilize without triggering the fault. As soon
as this delay is over, “Start Idle” delay is initiated (if configured). h)
During “Start Idle” delay, under speed, under frequency, under voltage alarms
are inhibited. When this delay is over, “Warming Up” delay is initiated (if
configured). i) After the “Warming Up” delay has expired, if generator status
is normal, its indicator will be illuminated. If generator voltage and
frequency have reached on-load requirements, then the generator close relay
will be energized; genset will take load; generator power indicator will
illuminate and generator will enter into Normal Running status. If voltage or
frequency is abnormal, the controller will initiate shutdown alarm (alarm
information will be displayed on LCD).
NOTE: When started via “Remote Start (off Load)” input, same procedures as
above but generator close relay deactivated, moreover, genset off load.
5.4.3 AUTOMATIC STOP SEQUENCE
a) HGM9320MPU(CAN), when mains return normal during genset running, enters
into mains voltage
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 18 of 70
“Normal Delay” and its indicator illuminated. When mains normal delay is over,
enter into “stop delay”; also can be into this mode when “Remote Start On
Load” is inactive. b) HGM9310MPU(CAN): When the “Remote Start” signal is
removed, “Stop Delay” is initiated. c) Once this “Stop Delay” has expired, the
Generator Breaker will open and the “Cooling Delay” is then initiated. After
“Transfer Delay”, close mains relay is energized and mains will take load.
Generator indicator extinguish while mains indicator lights. d) During “Stop
Idle” Delay (if configured), idle relay is energized. e) “ETS Solenoid Hold”
delay begins, ETS relay is energized while fuel relay is de-energized,
complete stop is detected automatically. f) “Wait for Stop Delay” begins,
complete stop is detected automatically. g) When generator is stop completely,
“After Stop” delay will be initiated. Otherwise, fail to stop alarm is
initiated and the corresponding alarm information is displayed on LCD. (If
generator is stop successfully after “fail to stop” alarm has initiated,
“After Stop” delay will be initiated and the alarm will be removed) h)
Generator is placed into its standby mode after its “After Stop” delay.
5.5 MANUAL START/STOP OPERATION
a) MANUAL START: Manual mode is selected by pressing the
button; a LED besides the button
will illuminate to confirm the operation; then press
button to start the gen-set; can detect
crank disconnect condition and generator accelerates to high-speed running automatically. With high
temperature, low oil pressure, over speed and abnormal voltage during generator running, controller
can protect genset to stop quickly. (please refer to 5.4.2, d)~5.4.2, i)).
b) MANUAL STOP: Press
can stop the running generators. (please refer to 5.4.3, c)~5.4.3, h)).
5.6 SWITCH CONTROL PROCEDURES
5.6.1 HGM9320MPU(CAN) SWITCH CONTROL PROCEDURES
Manual transfer procedures: When controller is in Manual mode, the switch
control procedures will start through manual transfer
process. Users can control the loading transfer of ATS via pressing button to
switch on or off.
A. If “Open breaker detect” is “SELECT Disable” Press generator switch on or
off key , if generator has taken load, will send unload signal; if taken no
load, generator will send load signal; if mains has taken load, will send
unload signal, and then generator will take load after the mains “open delay”.
Press mains switch on or off key , if mains has taken load, will send unload
signal; if taken no
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 19 of 70
load, mains will send load signal; if generator has taken load, will send unload signal, and then mains will take load after the generator “open delay”.
If “Open breaker detect” is “SELECT Enable”
To transfer load from mains to generator need to press mains switch off key
firstly. After
open delay, press generator switch on key , and generator will take load (there is no action when
pressing switch on key directly). The way to transfer from generator to mains is as same as above. Auto transfer procedures: When controller is in AUTO mode, switch control procedures will start through automatic transfer. 1) If input port is configured as Close Mains Auxiliary A. If “Open breaker detect” is “SELECT Enable” When transferring load from mains to generator, controller begins detecting “fail to transfer”, then
the open delay and transfer rest delay will begin. When detecting time out, if switch open failed, the
generator will not switch on, otherwise, generator switch on. Detecting transfer failure while
generator switches on. When detecting time out, if switch on fail, it is need to wait for generator to
switch on. If transfer failed and warning “SELECT Enable”, there is alarming signal whatever switch
on or off failure. The way to transfer from generator load to mains load is as same as above. B. If “Open breaker detect” is “SELECT Disable” Mains load is transferred into generator load, after the delay of switch off and transfer interval,
generator switch on. Detecting transfer fail while generator switches on. After detecting time out, if
switch on fail, then wait for generator switch on. If transfer fail and warning “SELECT Enable”, there
is alarming signal. 2) If input port is not configured as Close Mains
Auxiliary
Mains load is transferred into generator load, after switch off and transfer
interval delay, generator switch on.
The way to transfer generator load to mains load is as same as above.
5.6.2 HGM9310MPU(CAN) SWITCH CONTROL PROCEDURES
Manual control procedures, When controller is in Manual mode, manual control will be executive. Users can control switch on or off by pressing panel key. Press generator switch on key
, generator will
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 20 of 70
output load signal. Press generator switch off key , generator will output
unload signal. Auto control procedures, When controller is in auto mode,
switch control procedures will start auto transfer. 1) If input port is
configured as Close Mains Auxiliary A. If “Open breaker detect” is select
“Enable”
Generator load is transferred into generator unload, after the open delay, the
controller detects “transfer failure” while open signal is outputting. When
detecting time out, if open failed, it will wait for breaker opened.
Otherwise, breaker open is completed. Generator unload is transferred into
generator load, after the close delay, the controller detects “transfer
failure” while close signal is outputting. When detecting time out, if close
failed, it will wait for breaker closed. Otherwise, breaker close is
completed. If transfer failed and warning select “Enable”, there is alarming
signal whatever breaker open or close failure. B. If “Open breaker detect” is
select “Disable” Generator unload is transferred into generator load, after
the close delay, the controller detects “transfer failure” while close signal
is outputting. When detecting time out, if close failed, it will wait for
breaker closed. Otherwise, breaker close is completed. If transfer failed and
warning select “Enable”, there is alarming signal whatever breaker open or
close failure. 2) If input port is not configured as Close Mains Auxiliary
Generator un-load is transferred into generator load, close generator output.
Generator load is transferred into generator un-load, open generator output.
NOTE: When using ATS of no interposition, “Open breaker detect” should
“Disable”; When using ATS of having interposition, “Open breaker detect”
select “Disable” or “Enable” both are OK. If select “Enable”, breaker open
output should be configured; When using AC contactor, “Open breaker detect”
should select “Enable”.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 21 of 70
6 PROTECTION 6.1 WARNINGS
When controller detects warning signals, it only sends warning without shutdown.
Table 8 Warning Alarms
No
Type
Description
1 Over Speed
When the controller detects that the engine speed has exceeded the pre-set value, it will initiate a warning alarm.
2 Under Speed
When the controller detects that the engine speed has fallen below the pre-set value, it will initiate a warning alarm.
3 Loss of Speed
When the controller detects that the engine speed is 0 and the action select “Warning”, it will initiate a warning alarm.
4 Over Frequency
When the controller detects that the genset frequency has exceeded the pre-set value, it will initiate a warning alarm.
5 Under Frequency
When the controller detects that the genset frequency has fallen below the pre-set value, it will initiate a warning alarm.
6 Over Voltage
When the controller detects that the generator voltage has exceeded the pre- set value, the controller will initiate a warning alarm.
7 Under Voltage
When the controller detects that the genset voltage has fallen below the pre- set value, it will initiate a warning alarm.
When the controller detects that the genset current has exceeded the
8 Over Current
pre-set value and the action select “Warning”, it will initiate a warning
alarm.
9 Fail To Stop
After “fail to stop” delay, if gen-set does not stop completely, it will initiate a warning alarm.
Charge 10
Failure
Alternator When the controller detects that charger voltage has fallen below the pre-set value, it will initiate a warning alarm.
11 Battery High Voltage
When the controller detects that start battery voltage has exceeded the pre- set value, it will initiate a warning alarm.
12 Battery Low Voltage
When the controller detects that start battery voltage has fallen below the pre-set value, it will initiate a warning alarm.
13 Maintenance Due
When count down time is 0 and the action select “Warning”, it will initiate a warning alarm.
If reverse power detection is enabled, when the controller detects
14 Reverse Power
that the reverse power value (power is negative) has fallen below the pre-set value and the action select “Warning”, it will initiate a warning
alarm.
If over power detection is enabled, when the controller detects that
15 Over Power
the over power value (power is positive) has exceeded the pre-set
value and the action select “Warning”, it will initiate a warning alarm.
16 ECU Warn
If an error message is received from ECU via J1939, it will initiate a warning alarm.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 22 of 70
No
Type
Description
17 Gen Loss of Phase
If loss of phase detection is enabled, When controller detects the generator loss phase, it will initiate a warning alarm.
Gen Phase Sequence When the controller detects a phase rotation error, it will initiate a
18
Wrong
warning alarm.
When the controller detects that the breaker close or open failure
19 Switch Fail Warn
occurs, and the action select “Warning”, it will initiate a warning
alarm.
Temperature Sensor When the controller detects that the temperature sensor is open
20
Open Circuit
circuit and the action select “Warning”, it will initiate a warning alarm.
High 21
Warn
Temperature When the controller detects that engine temperature has exceeded the pre-set value, it will initiate a warning alarm.
Low 22
Warn
Temperature When the controller detects that engine temperature has fallen below the pre-set value, it will initiate a warning alarm.
Oil Pressure Open When the controller detects that the oil pressure sensor is open
23
Circuit
circuit and the action select “Warning”, it will initiate a warning alarm.
When the controller detects that the oil pressure has fallen below the 24 Low
Oil Pressure Warn
pre-set value, it will initiate a warning alarm.
Level Sensor Open When the controller detects that the level sensor is open circuit and
25
Circuit
the action select “Warning”, it will initiate a warning alarm.
26 Low Fuel Level Warn
When the controller detects that the fuel level has fallen below the pre-set value, it will initiate a warning alarm.
Flexible Sensor 1 Open When the controller detects that the flexible sensor 1 is open circuit
27
Circuit
and the action select “Warning”, it will initiate a warning alarm.
When the controller detects that the sensor 1 value has exceeded the 28
Flexible Sensor 1 High
pre-set value, it will initiate a warning alarm.
When the controller detects that the sensor 1 value has fallen below 29
Flexible Sensor 1 Low
the pre-set value, it will initiate a warning alarm.
Flexible Sensor 2 Open When the controller detects that the flexible sensor 2 is open circuit
30
Circuit
and the action select “Warning”, it will initiate a warning alarm.
When the controller detects that the sensor 2 value has exceeded the 31
Flexible Sensor 2 High
pre-set value, it will initiate a warning alarm.
When the controller detects that the sensor 2 value has fallen below 32
Flexible Sensor 2 Low
the pre-set value, it will initiate a warning alarm.
33 Digital Input
When digit input port is set as warning and the alarm is active, it will initiate a warning alarm.
34 GSM Com Fail
When select GSM enable but the controller couldn’t detect GSM model, controller sends corresponding warning signal.
If earth fault detection is enabled, when the controller detects that
35 Earth Fault
the earth fault current has exceeded the pre-set value and the action
select “Warn”, it will initiate a warning alarm.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 23 of 70
6.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and shut down generator.
Table 9 Shutdown Alarms
No
Type
Description
1 Emergency Stop
When the controller detects an emergency stop alarm signal, it will initiate a shutdown alarm.
2 Over Speed
When the controller detects that the generator speed has exceeded the pre-set value, it will initiate a shutdown alarm.
3 Under Speed
When the controller detects that the generator speed has fallen below the pre- set value, it will initiate a shutdown alarm.
4 Loss of Speed Signal
When the controller detects that the engine speed is 0 and the action select “Shutdown”, it will initiate a shutdown alarm.
5 Over Frequency
When the controller detects that the genset frequency has exceeded the pre-set value, it will initiate a shutdown alarm.
6 Under Frequency
When the controller detects that the genset frequency has fallen below the pre-set value, it will initiate a shutdown alarm.
7 Over Voltage
When the controller detects that the generator voltage has exceeded the pre- set value, the controller will initiate a shutdown alarm.
8 Under Voltage
When the controller detects that the genset voltage has fallen below the pre- set value, it will initiate a shutdown alarm.
9 Fail To Start
If the engine does not fire after the pre-set number of attempts, it will initiate a shutdown alarm.
When the controller detects that the genset current has exceeded the
10 Over Current
pre-set value and the action select “Shutdown”, it will initiate a
shutdown alarm.
11 Maintenance 1 Due
When count down time is 0 and the action select “Shutdown”, it will initiate a shutdown alarm.
12 ECU Shutdown
If an error message is received from ECU via J1939, it will initiate a shutdown alarm.
13 ECU Fail
If the module does not detect the ECU data, it will initiate a shutdown alarm.
If reverse power detection is enabled, when the controller detects
Reverse 14
Shutdown
Power that the reverse power value (power is negative) has fallen below the pre-set value and the action select “Shutdown”, it will initiate a
shutdown alarm.
If over power detection is enabled, when the controller detects that
15 Over Power Shutdown
the over power value (power is positive) has exceeded the pre-set value and the action select “Shutdown”, it will initiate a shutdown
alarm.
Temperature 16
Open Circuit
Sensor
When the controller detects that the temperature sensor is open circuit and the action select “Shutdown”, it will initiate a shutdown alarm.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 24 of 70
No
Type
Description
High
Temperature When the controller detects that engine temperature has exceeded
17
Shutdown
the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the oil pressure sensor is open
Oil Pressure Open
18 Circuit
circuit and the action select “Shutdown”, it will initiate a shutdown
alarm.
Low Oil 19
Shutdown
Pressure When the controller detects that the oil pressure has fallen below the pre-set value, it will initiate a shutdown alarm.
Level Sensor Open When the controller detects that the level sensor is open circuit and
20
Circuit
the action select “Shutdown”, it will initiate a shutdown alarm.
Flexible Sensor 1 Open When the controller detects that the flexible sensor 1 is open circuit
21
Circuit
and the action select “Shutdown”, it will initiate a shutdown alarm.
22 Flexible Sensor 1 High
When the controller detects that the sensor 1 value has exceeded the pre-set value, it will initiate a shutdown alarm.
23 Flexible Sensor 1 Low
When the controller detects that the sensor 1 value has fallen below the pre- set value, it will initiate a shutdown alarm.
Flexible Sensor 2 Open When the controller detects that the flexible sensor 2 is open circuit
24
Circuit
and the action select “Shutdown”, it will initiate a shutdown alarm.
25 Flexible Sensor 2 High
When the controller detects that the sensor 2 value has exceeded the pre-set value, it will initiate a shutdown alarm.
26 Flexible Sensor 2 Low
When the controller detects that the sensor 2 value has fallen below the pre- set value, it will initiate a shutdown alarm.
27 Digital Input
When digit input port is set as shutdown and the alarm is active, it will initiate a shutdown alarm.
If earth fault detection is enabled, when the controller detects that
28 Earth Fault
the earth fault current has exceeded the pre-set value and the action
select “Shutdown”, it will initiate a shutdown alarm.
29 Low Coolant Level
Controller initiate shutdown alarm after digital input port been configured as low coolant level shutdown (is active).
30 Detonation Shutdown
Controller initiate shutdown alarm after digital input port been configured as detonation shutdown (is active).
31 Gas Leak Shutdown
Controller initiate shutdown alarm after digital input port been configured as gas leak shutdown (is active).
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 25 of 70
6.3 TRIP AND STOP ALARM
When controller detects trip and stop alarm, it will disconnect “Close Generator” Output and shut down the genset.
Table 10 Trip and Stop Alarms
No
Type
1 Over Current
2 Reverse Power
3 Over Power 4 Digital Input 5 Earth Fault
Description When the controller detects that the genset current has exceeded the pre-set value and the action select “Trip and Stop”, it will initiate a trip and stop alarm. If reverse power detection is enabled, when the controller detects that the reverse power value (power is negative) has fallen below the pre-set value and the action select “Trip and Stop”, it will initiate a trip and stop alarm. If over power detection is enabled, when the controller detects that the over power value (power is positive) has exceeded the pre-set value and the action select “Trip and Stop”, it will initiate a trip and stop alarm. When digit input port is set as “Trip and Stop” and the alarm is active, it will initiate a trip and stop alarm. If earth fault detection is enabled, when the controller detects that the earth fault current has exceeded the pre-set value and the action select “Trip and Stop”, it will initiate a trip and stop alarm.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 26 of 70
6.4 TRIP ALARM
When controller detects stop alarm, it will disconnect “Close Generator” Output and not shut down the genset.
Table 11 Trip Alarms
No
Type
1 Over Current
2 Reverse Power
3 Over Power 4 Digital Input 5 Earth Fault
Description When the controller detects that the genset current has exceeded the pre-set value and the action select “Trip”, it will initiate a trip alarm. If reverse power detection is enabled, when the controller detects that the reverse power value (power is negative) has fallen below the pre-set value and the action select “Trip”, it will initiate a trip alarm. If over power detection is enabled, when the controller detects that the over power value (power is positive) has exceeded the pre-set value and the action select “Trip”, it will initiate a trip alarm. When digit input port is set as “Trip” and the alarm is active, it will initiate a trip alarm. If earth fault detection is enabled, when the controller detects that the earth fault current has exceeded the pre-set value and the action select “Trip”, it will initiate a trip alarm.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 27 of 70
7 WIRINGS CONNECTION HGM93XXMPU(CAN) series controller’s rear as following:
Fig.3 Rear Panel
Table 12 Description of Terminal Connection
No. 1 B-
Function
2 B+
3 Emergency stop 4 Fuel relay output
5 Crank relay output
6 Aux. Output 1
7 Aux. Output 2
8 Aux. Output 3
9 Charger (D+) 10 Aux. Input 1
Size 2.5mm2
2.5mm2
2.5mm2 1.5mm2 1.5mm2
1.5mm2
1.5mm2
1.5mm2
1.0mm2 1.0mm2
Remarks
Connected with negative of starter battery.
Connected with positive of starter battery. If wire
length is over 30m, better to double wires in parallel.
Max. 20A fuse is recommended.
Connected with B+ via emergency stop button.
B+ is supplied by No.3 terminal, rated 16A.
B+ is supplied by No.3 terminal, Connected
to
rated 16A.
starter coil.
B+ is supplied by No.2 terminal,
rated 7A.
B+ is supplied by No.2 terminal, rated 7A.
Details see table 13.
B+ is supplied by No.2 terminal,
rated 7A.
Connected with charger starter’s D+ (WL) terminals.
Being hang up If there is no this terminal.
Ground connected is active (B-). Details see table14
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 28 of 70
No.
Function
Size
Remarks
11 Aux. Input 2
1.0mm2 Ground connected is active (B-).
12 Aux. Input 3
1.0mm2 Ground connected is active (B-).
13 Aux. Input 4
1.0mm2 Ground connected is active (B-).
14 Aux. Input 5
1.0mm2 Ground connected is active (B-).
15 Aux. Input 6
1.0mm2 Ground connected is active (B-).
16 Magnetic Pickup 17 Magnetic Pickup 2
Connected with Speed sensor, shielding line is 0.5mm2 recommended. (B-) has already connected with speed
18 Magnetic Pickup 1
sensor 2.
19 Aux. Input 7
1.0mm2 Ground connected is active (B-). Details see table 14.
20
Normally close output, rated 7A.
21 Aux. Output 4
1.5mm2 Public points of relay.
Details see table 13.
22
Normally open output, rated 7A.
23 ECU SCR 24 ECU CAN H 25 ECU CAN L
/ 0.5mm2 0.5mm2
Impedance-120 shielding wire is recommended, its single-end earthed.
26 RESERVE
/
Empty terminal
33 RS485 SCR 34 RS485A(+) 35 RS485B(-)
/ 0.5mm2 0.5mm2
Impedance-120 shielding wire is recommended, its single-end earthed.
36
2.5mm2 Normally close output, rated 7A.
37 Aux. Output 5
2.5mm2 Normally open output, rated 7A.
38
2.5mm2 Public points of relay.
Details see table 13.
39 Aux. Output 6
40
2.5mm2 Normally open output, rated 7A. 2.5mm2 Public points of relay.
41
Mains
L1-phase
voltage input
1.0mm2
Connected to A-phase of mains (2A fuse is recommended). (HGM9310MPU, HGM9310CAN without).
42
Mains
L2-phase
voltage input
1.0mm2
Connected to B-phase of mains (2A fuse is recommended).
(HGM9310MPU, HGM9310CAN without).
43
Mains
L3-phase
voltage input
1.0mm2
Connected to C-phase of mains (2A fuse is recommended).
(HGM9310MPU, HGM9310CAN without).
44 Mains N-wire input
1.0mm2 Connected to N-wire of mains. (HGM9310MPU, HGM9310CAN without).
Genset 45
L1-phase 1.0mm2 Connected to A-phase of genset (2A fuse is
voltage input
recommended).
Genset 46
L2-phase 1.0mm2 Connected to B-phase of genset (2A fuse is
voltage input
recommended).
Genset 47
L3-phase 1.0mm2 Connected to C-phase of genset (2A fuse is
voltage input
recommended).
48 Genset N-wire input 1.0mm2 Connected to N-wire of gen-set.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 29 of 70
No.
Function
49 CT 1 input
50 CT 2 input
51 CT 3 input
52 CT COM 53
Earth Current 54 55 Aux. Input 8 56 Aux. sensor 1 57 Aux. sensor 2
58 Oil pressure sensor
59 Temperature sensor
60 Fuel level sensor 61 Sensor COM 62 RS232 GND 63 RS232 RX 64 RS232 TX
Size
1.5mm2
1.5mm2
1.5mm2
1.5mm2 1.5mm2 1.5mm2 1.0mm2 1.0mm2 1.0mm2
1.0mm2
1.0mm2
1.0mm2 /
0.5mm2 0.5mm2 0.5mm2
Remarks
Outside connected to secondary coil of current transformer (rated 5A). Outside connected to secondary coil of current transformer (rated 5A). Outside connected to secondary coil of current transformer (rated 5A).
See following installation instruction.
Outside connected to secondary coil of current transformer (rated 5A).
Ground connected is active (B-). Details see table 14.
Connected to temperature, oil pressure or level sensors.
Connected sensor. Connected sensor.
to oil pressure Details see table 15.
to temperature
Connected to fuel level sensor.
Public terminal of sensor, (B-) has already connected.
Connected to GSM module.
NOTE: USB ports in controller rear panel are programmable parameter ports,
user can directly configure controller via PC.
NOTE: Please refer to the Module Comparison in this manual for more details.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 30 of 70
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS 8.1 CONTENTS AND SCOPES OF PARAMETERS
Table 13 Parameters Description
No.
Items
Mains
1
AC System
2
Rated Voltage
Parameters (0~3) (30~30000)V
3
Rated Frequency (10.0~75.0)Hz
4
Normal Delay
(0~3600)s
5
Abnormal Delay (0~3600)s
(0~1)
6
Volt. Trans.(PT) (30-30000)V
(30-1000)V
7
Over Voltage
(0~200)%
8
Under Voltage
(0~200)%
9
Over Frequency (0~200)%
10 Under Frequency (0~200)%
11 Loss of Phase Phase Sequence
12 Wrong
Timers
(0~1) (0~1)
1
Start Delay
(0~3600)s
2
Stop Delay
(0~3600)s
3
Pre-heat Delay (0~3600)s
4
Cranking Time (3~60)s
5
Crank Rest Time (3~60)s
6
Safety On Delay (0~3600)s
Defaults
Description
0
0: 3P4W; 1: 3P3W; 2: 2P3W; 3: 1P2W.
Standard for checking mains over/under
230
voltage. (It is primary voltage when using
voltage transformer).
Standard for checking mains over/under 50.0
frequency.
The delay from mains abnormal to 10
normal.
The delay from mains normal to 5
abnormal.
0
0: Disable; 1: Enable
100
PT primary.
100
PT secondary.
120
Setting value is mains rated voltage’s
percentage, and return value (Over
Voltage default: 116; Under Voltage 80
default: 84) and delay value (default: 5s)
can be set.
114
Setting value is mains rated frequency’s
percentage, return value (Over Frequency
default: 110; Under Frequency default: 90
94) and delay value (default: 5s) can be
set.
1
0: Disable; 1: Enable 1
Time from mains abnormal or remote 1
start signal is active to start genset.
Time from mains normal or remote start 1
signal is deactivated to stop genset.
Time of pre-powering heat plug before 0
starter is powered up.
8
Time of starter power up.
The waiting time before second power up 10
when engine start fail.
10
Alarms for low oil pressure, high
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 31 of 70
No.
Items
Parameters
7
Start Idle Time (0~3600)s
Warming Up 8
Time
(0~3600)s
9
Cooling Time
(0~3600)s
10 Stop Idle Time (0~3600)s
ETS Solenoid
11
(0~3600)s
Hold
12 Fail to Stop Delay (0~3600)s
13 After Stop Time (0~3600)s
Gas
Engine
14
(0~1)
Timers
15 Choke On Time (0~60)s
16 Gas On Delay
(0~60)s
17 Ignition Off Delay (0~60)s
18 Speed Raise Time (0~60)s
19 Fuel Output Time (0~60)s Engine
1
Engine Type
(0~39)
2
Flywheel Teeth (10~300)
3
Rated Speed
(0~6000)r/min
Defaults
0 10 10 0 20
0
0 0 0 0 0 0 1
Description temperature, under speed, under frequency /voltage, charge fail are inactive. Idle running time of genset when starting. Warming time between genset switch on and normal running. Radiating time before genset stop, after it unloads. Idle running time when genset stop. The time of powering up the electromagnet during stop procedure. Time between ending of genset idle delay and stopped when “ETS time” is set as 0; Time between ending of ETS hold delay and stopped when “ETS Hold output time” is not 0. Time between genset stopped and standby 0: Enable 1: Disable When gas engine timer enabled, fuel oil output is used for controlling gas valve. Gas enrichment control output time when start engine. When engine started, it starts to output after the preset time delay. When gas valve closed, it stops to output after the preset delay. The time that gas ignition continues to output when the genset receives the stop signal The continuous fuel output time when the genset starts
0 118 1500
Default: Conventional genset (not J1939)
When connected to J1939 engine,
choose the corresponding type.
Tooth number of the engine, which used
for judging of crank disconnect
conditions and inspecting of engine
speed. See the installation instructions.
Offer
standard
to
judge
over/under/loading speed.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 32 of 70
No.
Items
Parameters
4
Loading Speed (0~100)%
Loss of Speed
5
(0~1)
Signal Action
Over
Speed
6
(0~200)%
Shutdown
Under Speed
7
(0~200)%
Shutdown
8
Over Speed Warn (0~200)%
Under Speed
9
(0~200)%
Warn
Battery Rated
10
(0~60.0)V
Voltage
Battery
Over
11
(0~200)%
Voltage Alarm
Battery Under
12
(0~200)%
Voltage Alarm
Charge Alternator
13
(0~60.0)V
Failure
14 Start Attempts (1~10)
15 Crank Disconnect (0~6)
Disconnect
16
(0~200)%
Generator Freq.
Disconnect 17
Engine Speed
(0~200)%
Disconnect Oil
18
(0~1000)kPa
Pressure
Defaults 90
Description Setting value is percentage of rated speed. Controller detects when it is ready to load. It won’t switch on when speed is under loading speed.
0
0: Warn; 1: Shutdown
Setting value is percentage of rated 114
speed and delay value (Over Speed
default: 2s; Under Speed default: 3s) can
80
be set.
110
Setting value is percentage of rated
speed. Delay value (default: 5s) and
86
return value (Over Speed default: 108;
Under Speed default: 90) also can be set.
Standard for detecting over/under 24.0
voltage of battery.
Setting value is percentage of rated 120
voltage of battery. Delay value (default:
60s) & return value (Over Volts default:
85
115; Under Volts default: 90) can be set.
In normal running, when charger D+ (WL)
8.0
voltage under this value, charge failure
alarms.
Max. Crank times of crank attempts.
3
When reach this number, controller will
send start failure signal.
See Table 17.
There are 3 conditions of disconnecting
starter with engine. Each condition can 2
be used alone and simultaneously to
separating the start motor and genset as
soon as possible.
When generator frequency higher than
the set value, starter will be 24
disconnected. See the installation
instruction.
When generator speeds higher than the
24
set value, starter will be disconnected.
See the installation instruction.
When generator oil pressure higher than
200
the set value, starter will be disconnected.
See the installation instruction.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 33 of 70
No.
Items
Parameters
Low Urea Level
19
(0~1)
Warning
Generator
1
AC System
(0~3)
2
Poles
(2~64)
3
Rated Voltage
(30~30000)V
4
Loading Voltage (0~200)%
5
Rated Frequency (10.0~600.0)Hz
Loading 6
Frequency
(0~200)%
(0~1)
7 Volt. Trans.(PT) (30-30000)V
(30-1000)V
Over Voltage
8
(0~200)%
Shutdown
Under Voltage
9
(0~200)%
Shutdown
Over Frequency
10
(0~200)%
Shutdown
Under Frequency
11
(0~200)%
Shutdown
Over Voltage
12
(0~200)%
Warn
Under Voltage
13
(0~200)%
Warn
Over Frequency
14
(0~200)%
Warn
Defaults 1
Description The warning can be set as enabled or disabled. The threshold percentage, return value and delay time of the warning also can be set.
0
0: 3P4W; 1: 3P3W; 2: 2P3W; 3: 1P2W.
Numbers of generator pole, used for
4
calculating starter rotate speed when
without speed sensor.
To offer standards for detecting of
230
generator’ over/under voltage and
loading voltage. (It is primary voltage
when using voltage transformer).
Setting value is percentage of generator
rated voltage. Detect when controller
85
ready to loading. If generator voltage
under load voltage, won’t enter into
normally running.
To offer standards for detecting of 50.0
over/under/load frequency.
Setting value is percentage of generator
rated frequency. Detect when controller
85
ready to loading. When generator
frequency under load frequency, it won’t
enter into normal running.
0
0: Disable; 1: Enable
100
PT primary.
100
PT secondary.
120
Setting value is percentage of generator
rated volt. Delay value (default: 3s) can
80
be set.
114
Setting value is percentage of generator
rated freq. Delay value (Over Freq.
default: 2s; Under Freq. default: 3s) can 80
be set.
Setting value is percentage of generator 110
rated volt. Delay value (default: 5s) and
return value (Over Volt. default: 108;
84
Under Volt. default: 86) can be set.
Setting value is percentage of generator 110
rated frequency. Delay value (default: 5s)
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 34 of 70
No. 15 16 17 Load 1
Items Under Frequency Warn Loss of Phase Phase Sequence Wrong
Current Transform
Parameters (0~200)% (0~1) (0~1)
(5~6000)/5
2
Rated Current
(5~6000)A
3
Rated Power
(0~6000)kW
Generator
4
(0~200)%
Current Alarms
(0~1)
Reverse Power
5
Protection
(0-200)%
Reverse Power
6
(0-3)
Action
(0-1)
Over
Load
7
Protection
(0-200)%
8
Over Load Action (0-3)
(0~1)
9
Earth Fault
Earth 10
Action Switch
Fault
(0-100)% (0-1.6) (0-6000) (0-3)
1
Close Time
(0~20.0)s
2
Open Time
(0~20.0)s
Defaults 84 1 1
Description and return value (Over Freq. default: 108; Under Freq. default:
86) can be set.
0: Disable 1: Enable
500
The ratio of external CT.
Generator’s rated current, standard of 500
load current.
276
Generator’s rated power, standard of load
power.
Setting value is percentage of generator
rated full current. Delay value can be set 120
as definite time and inverse definite
minimum time.
0
0: Disable 1: Enable
Setting value is percentage of rated
power, return value (factory default: 5) 10
and delay value (factory default: 5s) can
be set.
0: Warning; 1: Shutdown; 2: Trip and Stop; 0
3: Trip
0
0: Disable 1: Enable
Setting value is percentage of rated
power, return value (factory default: 105) 110
and delay value (factory default: 5s) can
be set.
0: Warning; 1: Shutdown; 2: Trip and Stop; 0
3: Trip
0
0: Disable 1: Enable
Setting value is percentage of rated 10
current.
0.1
Ratio.
500
Current transformer ratio.
0: Warning; 1: Shutdown; 2: Trip and Stop; 0
3: Trip
Pulse width of mains/generator switch 5.0
on. When it is 0, means output constantly. Pulse width of mains/generator
switch 3.0 off.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 35 of 70
No.
Items
3
Transfer Time
Parameters (0~7200)s
4
Check Time
(0~20.0)s
5
Check Enable
6
Warning Enable
Immediate Mains 7
Dropout
Module
(0~1) (0~1)
(0~1)
1
Power on Mode (0~2)
2
Module Address (1~254)
3
Language
(0~2)
4
Password
(0~65535)
5
Date and Time
6
Temperature Unit (0-1)
7
Pressure Unit
(0-2)
Module Mute
8
(0-1)
Enable
9
User Page Enable (0-1)
10 User Page Time (0-20.0)s
11 12 GSM 1
LCD Color Status Enable
Color
GSM Enable
(0-37) (0-1)
(0~1)
2
Phone Number Max.20 digits
Scheduling And Maintenance
1
Scheduled Run (0~1)
Scheduled Not
2
(0~1)
Run
Master-Standby
3
(0~1)
Running Enable
4
MSC Comm. Port (0~1)
5
Balanced
(0~1)
Defaults 5
5.0 0 0
Description Interval time from mains switch off to generator switch on; or from generator switch off to mains switch on. Time of detecting switch auxiliary contacts after transferred. 0: Disable 1: Enable 0: Disable 1: Enable
1
0: Disable 1: Enable
0 1 0 00318
0 0 0 0 3.0 24 1
0: Stop mode 1: Manual mode 2: Auto mode Controller’s address during remote
sensing. 0: Simplified Chinese 1: English 2: Others For entering advanced
parameters setting. Current date and time that user defined. 0: °C; 1: °F 0:
kPa; 1: Psi; 2: Bar.
0: Disable 1: Enable
0: Disable 1: Enable If “User Page Time” is enabled, the user-set time will be
displayed continuously. F(White)/B(B)
0: Disable; 1: Enable
0
0: Disable; 1: Enable
Its national and area’s cods must be added. E.g. China: 8613666666666.
0
0: Disable; 1: Enable
0
0: Disable; 1: Enable.
0: Disable; 1: Enable 0
See details in NOTE 1.
0
0: CAN; 1: RS485
0
0: Disable; 1: Enable
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 36 of 70
No.
Items
Running Enable
Balanced 6
Running Time
7
Maintenance 1
8
Maintenance 2
9
Maintenance 3
Sensors
Temperature Sensor
1
Curve Type
Open Circuit 2
Action
Parameters
(0~100.0)h (0~1) (0~1) (0~1)
(0~15) (0~2)
High
Temp.
3
(0~300)ºC
Shutdown
High
Temp.
4
(0~300) ºC
Warning
Low
Temp.
5
(0-300) ºC
Warn
6
Custom Curve
Oil Pressure Sensor
1
Curve Type
Open
Circuit
2
Action
(0~15) (0~2)
Low Oil Pressure
3
(0~1000)kPa
Shutdown
Low Oil Pressure
4
(0~1000)kPa
Warning
5
Custom Curve
Defaults
3.0 0 0 0
Description See details in NOTE 2. The continuous running time of each genset when it is in the balanced running mode. 0: Disable; 1: Enable 0: Disable; 1: Enable 0: Disable; 1: Enable
7
SGX. See Table 16.
0: Warn; 1: Shutdown; 0
2: No action
Shutdown when sensor temperature
higher than this value. Detecting only 98
after safety delay is over. The delay value
(default: 3s) can be set.
Warn when sensor temperature higher
than this value. Detecting only after
95
safety delay is over. The delay value
(default: 5s) and return value (default: 93)
can be set.
Warn when sensor temperature lower
than this value. Detecting only after
70
safety delay is over. The delay value
(default: 5s) and return value (default: 75)
can be set.
Setting curves according to sensors’
performance.
7
SGX. See Table 16.
0: Warning 1: Shutdown 0
2: No action
Shutdown when oil pressure lower than
this value. Detecting only after safety 103
delay is over. The delay value (default: 3s)
can be set.
Warn when oil pressure higher than this
value. Detecting only after safety delay is 124
over. The delay value (default: 5s) and
return value (default: 138) can be set.
Setting curves according to sensors’ performance.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 37 of 70
No.
Items
Fuel Level Sensor
1
Curve Type
2
Open
Circuit
Action
Parameters (0~15) (0~2)
Low
Level
3
(0~300)%
Warning
4
Custom Curve
Flexible Sensor 1
Flexible Sensor 1 1
Setting
Flexible Sensor 2
Flexible Sensor 2 1
Setting
Digital Inputs
Digital Input Port 1
1
Contents Setting
(0~3) (0~3) (0~50)
2
Active Type
(0~1)
Digital Input Port 2
1
Contents Setting (0~50)
2
Active Type
(0~1)
Digital Input Port 3
1
Contents Setting (0~50)
2
Active Type
(0~1)
Digital Input Port 4
1
Contents Setting (0~50)
2
Active Type
(0~1)
3
Arming
(0~3)
4
Active Actions
(0~4)
5
Active Delay
Digital Input Port 5
1
Contents Setting
2
Active Type
(0~20.0)s
(0~50) (0~1)
Defaults
Description
4
SGH. See Table 16.
0
0: Warning; 1: Shutdown;
2: No action
Warn when level lower than this value. It
is detecting all the time. The delay value 10
(default: 5s) and return value (default: 15)
can be set.
Setting curves according to sensors’
performance.
0: None; 1: Temperature sensor; 2: 0
Pressure sensor; 3: Fuel Level sensor
0: None; 1: Temperature sensor; 2: 0
Pressure sensor; 3: Fuel Level sensor
28
Remote start on load. See Table 15.
0: Closed to active 0
1: Open to active
High temperature shutdown. See Table 26
15. 0: Closed to active 0 1: Open to active
27
Low oil pressure shutdown. See Table 15.
0: Closed to active 0
1: Open to active
0
User defined. See Table 15.
0: Closed to active 0
1: Open to active
0: From safety on 1: From starting 2: 2
Always 3: Never
0: Warning; 1: Shutdown; 2: Trip and stop 0
3: Trip 4: Indication
2.0
Time from detecting active to confirm
0
User defined. See Table 15.
0
0: Closed to active
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 38 of 70
No.
Items
Parameters
3
Arming
(0~3)
4
Active Actions
(0~4)
5
Active Delay
Digital Input Port 6
1
Contents Setting
(0~20.0)s (0~50)
2
Active Type
(0~1)
3
Arming
(0~3)
4
Active Actions
(0~4)
5
Active Delay
Digital Input Port 7
1
Contents Setting
(0~20.0)s (0~50)
2
Active Type
(0~1)
Digital Input Port 8
1
Contents Setting (0~50)
2
Active Type
(0~1)
3
Arming
(0~3)
4
Active Actions
(0~4)
5
Active Delay
Relay Outputs
Relay Output Port 1
(0~20.0)s
1
Contents Setting (0~299)
2
Active Type
(0~1)
Flexible Output Port 2
1
Contents Setting (0~299)
2
Active Type
(0~1)
Flexible Output Port 3
1
Contents Setting (0~299)
2
Active Type
(0~1)
Defaults
2 1 2.0
Description 1: Open to active 0: From safety on 1: From starting 2: Always 3: Never 0: Warning; 1: Shutdown; 2: Trip and stop 3: Trip 4: Indication Time from detecting active to confirm
0
User defined. See Table 15.
0: Closed to active 0
1: Open to active
0: From safety on 1: From starting 2: 2
Always 3: Never
0: Warning; 1: Shutdown; 2: Trip and stop 2
3: Trip 4: Indication
2.0
Time from detecting active to confirm
5
Lamp test. See Table 15.
0: Closed to active 0
1: Open to active
0
User defined. See Table 15.
0: Closed to active 0
1: Open to active
0: From safety on 1: From starting 2: 0
Always 3: Never
0: Warn; 1: Shutdown; 2: Trip and stop 3: 0
Trip 4: Indication
2.0
Time from detecting active to confirm
User defined period output1(default 1
output is in preheating). See Table 14. 0: Normally open; 0 1: Normally close
35
Idle control output. See Table 14.
0: Normally open;
0
1: Normally close
29
Generator closed output. See Table 14.
0: Normally open; 0
1: Normally close
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 39 of 70
No.
Items
Flexible Output Port 4
1
Contents Setting
Parameters (0~299)
2
Active Type
(0~1)
Flexible Output Port 5
1
Contents Setting (0~299)
2
Active Type
(0~1)
Flexible Output Port 6
1
Contents Setting (0~299)
2
Active Type
(0~1)
Defaults
Description
31
Mains closed output. See Table 14.
0
0: Normally open;
1: Normally close
38
ETS solenoid hold. See Table 14.
0: Normally open; 0
1: Normally close
48
Common alarm. See Table 14.
0: Normally open; 0
1: Normally close
NOTE 1: Master-standby running condition: The gensets are in the auto mode, the master-standby running is enabled, the input of Remote Start Demand is configured and active, and the input of First Priority in one genset is configured and active. The master one of two gensets will start first. If the master-standby role of two gensets is changed, the running genset will stop, and another one will start. When it is in the master-standby running mode, if abnormal conditions of shutdown, non-auto mode and inactive Remote Start Demand input occurs in one normal running genset, it will stop and another one will start. NOTE 2: Balanced running condition: The gensets are in the auto mode, the balanced running is enabled, the master-standby running is disabled, the input of Remote Start Demand is configured and active, and the input of First Priority in one genset is configured and active. When it is in the balanced running mode, according to the accumulated time B of each genset, the fewer one will start first. After it runs for the preset time of Balanced Running Time, it will stop and another one will start and run for the same preset time. Two gensets will run in this mode to keep the running time of each one equal. If abnormal conditions of shutdown, non-auto mode and inactive Remote Start Demand input occurs in one normal running genset, it will stop and another one will start.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 40 of 70
8.2 DEFINED CONTENTS OF OUTPUT PORTS
8.2.1 DEFINED CONTENTS TABLE OF OUTPUT PORTS
Table 14 Defined Contents of Output Ports
No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13
Type Not Used Custom Period 1 Custom Period 2 Custom Period 3 Custom Period 4 Custom Period 5 Custom Period 6 Custom Combined 1 Custom Combined 2 Custom Combined 3 Custom Combined 4 Custom Combined 5 Custom Combined 6 Reserved
14
Engine Oil Pump
15
Gas Choke On
16
Gas Ignition
17
Air Flap Control
18
Audible Alarm
19
Louver Control
20
Fuel Pump Control
21
Heater Control
22
Cooler Control
23
Oil Pre-supply
24
Generator Excite
25
Pre-Lubricate
Description
Details of function description please see the following.
It is active when the engine type is YUCHAI-LMB, and the output is enabled;
When it is on standby, it outputs once per 30 minutes; When it is preheating,
it outputs continuously. Action while cranking. Action time is as pre-set.
Action when genset starting, and disconnect when engine stopped. Action when
over speed shutdown and emergence stop. It can close the air inflow to stop
the engine as soon as possible. Action when warning, shutdown, trips. Can be
connected annunciator externally. When “alarm mute” configurable input port is
active, it can remove the alarm. Action when genset is cranking and disconnect
when genset stopped completely. It is controlled by fuel pump of level
sensor’s limited threshold. It is controlled by heating of temperature
sensor’s limited threshold. It is controlled by cooler of temperature sensor’s
limited threshold. Action from “crank on” to “safety on”. Output in start
period. If there is no generator frequency during normal running, it outputs
for 2 seconds again. Actions in period of pre-heating to safety run.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 41 of 70
No.
Type
26
Remote Control Output
27
GSM Power Supply
28
Reserved
29
Close Generator
30
Open Breaker
31
Close Mains
32
Reserved
33
Crank Relay
34
Fuel Relay
35
Idle Control
36
Speed Raise Relay
37
Speed Drop Relay
38
Energize to Stop
39
Speed Drop Pulse
40
ECU Stop
41
ECU Power Supply
42
Speed Raise Pulse
43
Crank Success
44
Generator OK
45
Generator Load Available
46
Mains OK
47
Reserved
48
Common Alarm
49
Common Trip and Stop
50
Common Shutdown
51
Common Trip
52
Common Warning
53
Reserved
54
Battery Over Voltage
55
Battery Under Voltage
56
Charge Alternator Fail
57
Reserved
Description This port is controlled by communication (PC). Power for GSM
module (GSM module is reset when GSM communication failed).
Control generator to take load. Control off-load. Control mains to take load.
Action when genset is cranking and disconnect when cranking success. Action
when genset is cranking and disconnect when stopped completely. Used for
engine which has idles. Close before starting and open in warming up delay;
Close during stopping idle mode and open when stop is completed. Action in
warming up delay. Action between the period from “stop idle” to “failed to
stop”. Used for engines with ETS electromagnet. Close when stop idle is over
and open when pre-set “ETS delay” is over. Active 0.1s when controller enters
into stop idle, used for control part of ECU dropping to idle speed. Used for
ECU engine and control its stop. Used for ECU engine and control its power.
Active 0.1s when controller enters into warming up delay; used for control
part of ECU raising to normal speed. Close when detects a successful start
signal. Action when generator is normal. Action in period of generator is
normal running to hi-speed cooling. Action when mains are normal.
Action when genset common warning, common shutdown, common trips alarm. Action
when common trip and stop alarm. Action when common shutdown alarm. Action
when common trips alarm. Action in common warning alarm.
Action when battery’s over voltage warning alarm. Action when battery’s low
voltage warning alarm. Action when charge failure warning alarms.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 42 of 70
No. 58 59 60 61
62
63 64 65 66 67 68 69 70 71 72 73 74 75 76 77~ 80 81 82 83 84 85 86 87 88 89 90
91 92 93 94 95 96 97 98 99 100
Type
Reserved
ECU Key Switch
ECU Warning
ECU Shutdown
ECU
Communication
Failure
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Aux Input 1 Active
Aux Input 2 Active
Aux Input 3 Active
Aux Input 4 Active
Aux Input 5 Active
Aux Input 6 Active
Aux Input 7 Active
Aux Input 8 Active
Description
Action after fuel relay outputs for 3s. Indicate ECU sends a warning signal.
Indicate ECU sends a shutdown signal. Indicate controller not communicates
with ECU.
Action when input port 1 is active Action when input port 2 is active Action
when input port 3 is active Action when input port 4 is active Action when
input port 5 is active Action when input port 6 is active Action when input
port 7 is active Action when input port 8 is active
Reserved
Exp. Digital Input 1 Active Exp. Digital Input 2 Active Exp. Digital Input 3 Active Exp. Digital Input 4 Active Exp. Digital Input 5 Active Exp. Digital Input 6 Active Exp. Digital Input 7 Active Exp. Digital Input 8 Active Exp. Digital Input 9 Active Exp. Digital Input 10 Active Exp. Digital Input 11 Active Exp. Digital Input 12 Active Exp. Digital Input 13 Active Exp. Digital Input 14 Active Exp. Digital Input 15 Active Exp. Digital Input 16 Active Reserved Reserved Emergency Stop Fail To Start
Action when expand digital input port 1 is active Action when expand digital
input port 2 is active Action when expand digital input port 3 is active
Action when expand digital input port 4 is active Action when expand digital
input port 5 is active Action when expand digital input port 6 is active
Action when expand digital input port 7 is active Action when expand digital
input port 8 is active Action when expand digital input port 9 is active
Action when expand digital input port 10 is active Action when expand digital
input port 11 is active Action when expand digital input port 12 is active
Action when expand digital input port 13 is active Action when expand digital
input port14is active Action when expand digital input port 15 is active
Action when expand digital input port 16 is active
Action when emergency stop alarm. Action when failed start alarm.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 43 of 70
No. 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118
119 120 121 122 123 124 125 126 127 128 129
130
131 132~ 138 139 140 141 142 143 144
145
Type Fail To Stop Under Speed Warning Under Speed Shutdown Over Speed Warning Over Speed Shutdown Reserved Reserved Reserved Gen Over Freq. Warning Gen Over Freq. Shutdown Gen Over Volt Warning Gen Over Volt Shutdown Gen Under Freq. Warning Gen Under Freq. Shutdown Gen Under Volt. Warning Gen Under Volt. Shutdown Gen Loss of Phase Gen Reverse Phase Reserved Over Power Alarm Reserved Reverse Power Alarm Over Current Alarm Reserved Mains Inactive Mains Over Freq Mains Over Volt Mains Under Freq Mains Under Volt Mains Phase Sequence Wrong Mains Loss of Phase
Description Action when failed stop alarm. Action when under speed alarm.
Action when under speed shuts down. Action when over speed warns. Action when
over speed shutdown alarm.
Action when generator over frequency warns. Action when generator over
frequency shutdown alarm. Action when generator over voltage warns. Action
when generator over voltage shutdown. Action when generator low frequency
warns. Action when generator low frequency shutdown. Action when generator low
voltage warns. Action when generator low voltage shutdown. Action when
generator loss phase. Action when generator reverse phase.
Action when controller detects generator have over power.
Action when controller detects generator have reverse power. Action when over
current.
Reserved
High Temperature Warning Low Temperature Warning High Temp. Shutdown Reserved Low Oil Pressure Warning Low Oil Pressure Shutdown Oil Pressure Sensor Open Circuit
Action when hi-temperature warns. Action when low temperature warns. Action
when hi-temperature shutdown alarm.
Action when low oil pressure warns. Action when low oil pressure shutdown.
Action when oil pressure sensor is open circuit.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 44 of 70
No. 146 147 148 149 150 151
152
153
154 155
156
157
158~ 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178
179 180 181 182 183 184 185
Type Reserved Low Fuel Level Reserved Reserved Flexible Sensor 1 High Warn Flexible Sensor 1 Low Warn Flexible Sensor 1 High Shutdown Flexible Sensor 1 Low Shutdown Flexible Sensor 2 High Warn Flexible Sensor 2 Low Warn Flexible Sensor 2 High Shutdown Flexible Sensor 2 Low Shutdown
Description Action when controller has low oil level alarm.
Reserved
Exp. 1 Ch.15 High Shut Exp. 1 Ch.15 High Warn Exp. 1 Ch.15 Low Shut Exp. 1 Ch.15 Low Warn Exp. 1 Ch.16 High Shut Exp. 1 Ch.16 High Warn Exp. 1 Ch.16 Low Shut Exp. 1 Ch.16 Low Warn Exp. 1 Ch.17 High Shut Exp. 1 Ch.17 High Warn Exp. 1 Ch.17 Low Shut Exp. 1 Ch.17 Low Warn Exp. 1 Ch.18 High Shut Exp. 1 Ch.18 High Warn Exp. 1 Ch.18 Low Shut Exp. 1 Ch.18 Low Warn Exp. 1 Ch.19 High Shut Exp. 1 Ch.19 High Warn Exp. 1 Ch.19 Low Shut Exp. 1 Ch.19 Low Warn Exp. 1 Ch.20 High Shut Exp. 1 Ch.20 High Warn Exp. 1 Ch.20 Low Shut Exp. 1 Ch.20 Low Warn
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 45 of 70
No. 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202229 230 231 232 233 234 235 236 237 238 239 240279 280299
Type Exp. 1 Ch.21 High Shut Exp. 1 Ch.21 High Warn Exp. 1 Ch.21 Low Shut Exp.
1 Ch.21 Low Warn Exp. 1 Ch.22 High Shut Exp. 1 Ch.22 High Warn Exp. 1 Ch.22
Low Shut Exp. 1 Ch.22 Low Warn Exp. 1 Ch.23 High Shut Exp. 1 Ch.23 High Warn
Exp. 1 Ch.23 Low Shut Exp. 1 Ch.23 Low Warn Exp. 1 Ch.24 High Shut Exp. 1
Ch.24 High Warn Exp. 1 Ch.24 Low Shut Exp. 1 Ch.24 Low Warn
Reserved
Stop Mode Manual Mode Reserved Auto Mode Generator Load Mains Load Reserved
Reserved Reserved Reserved
PLC Flag1-40
Reserved
8.2.2 CUSTOM PERIOD OUTPUT
Description
Action in stop mode. Action in Manual mode. Action in Auto mode.
Defined Period output is composed by 2 parts, period output S1 and condition output S2.
While S1 and S2 are TRUE synchronously, OUTPUT;
While S1 or S2 is FALSE, NOT OUTPUT.
Period output S1, can set generator’s one or more period output freely, can set the delayed time and output
time after enter into period.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 46 of 70
Condition output S2; can set as any conditions in output ports.
NOTE: when delay time and output time both are 0 in period output S1, it is
TRUE in this period. Example, Output period: start Delay output time: 2s
Output time: 3s Condition output contents: input port 1 is active Close when
condition output active/inactive: close when active (disconnect when
inactive); Output port 1 active, after enter “starts time” and delay 2s, this
defined period output is outputting, after 3s, stop outputting; Output port 1
inactive, defined output period is not outputting.
8.2.3 CUSTOM COMBINED OUTPUT
Defined combination output is composed by 3 parts, or condition output S1, S2,
and condition output S3.
S1 or S2 is TRUE, while S3 is TRUE, defined combination output is outputting;
S1 and S2 are FALSE, or S3 is FALSE, defined combination output is not
outputting.
NOTE: S1, S2, S3 can be set as any contents except for “defined combination
output” in the output setting. NOTE: 3 parts of defined combination output
(S1, S2, and S3) couldn’t include or recursively include themselves. Example,
Contents of probably condition output S1: input port 1 is active; Close when
probably condition output S1 is active /inactive: close when active
(disconnect when inactive); Contents of probably condition output S2, input
port 2 is active; Close when probably condition output S2 is active /inactive:
close when active (disconnect when inactive); Contents of probably condition
output S3: input port 3 is active; Close when probably condition output S3 is
active /inactive: close when active (disconnect when inactive); When input
port 1 active or input port 2 active, if input port 3 is active, defined
combination output is outputting; If input port 3 inactive, defined
combination output is not outputting; When input port 1 inactive and input
port 2 inactive, whatever input port 3 is active or not, defined combination
output is not outputting.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 47 of 70
8.3 DEFINED CONTENTS OF DIGITAL INPUT PORTS (ALL GND (B-) ACTIVE)
Table 15 Defined Contents of Digital Input Ports
No.
Type
0
Users Configured
1
Balanced Running Test
2
Alarm Mute
3
Alarm Reset
4
60Hz Active
5
Lamp Test
Description Including following functions, Indication: indicate only, not warning or shutdown. Warning: warn only, not shutdown. Shutdown: alarm and shutdown immediately Trip and stop: alarm, generator unloads and shutdown after hi-speed cooling Trip: alarm, generator unloads but not shutdown. Never: input inactive. Always: input is active all the time. From crank: detecting as soon as start. From safety on: detecting after safety on run delay. It can be used only when commissioning; When it is active, one minute is equivalent to one hour, that is, the accumulated time B of balanced running will increase by one hour per minute. Can prohibit “Audible Alarm” output when input is active. Can reset shutdown alarm and trip alarm when input is active. Use for CANBUS engine and it is 60Hz when input is active. All LED indicators are illuminating when input is active. All buttons in panel is inactive except
6
Panel Lock
7
Speed Raise Pulse
8
Idle Control Active
9
Auto Stop Inhibit
10
Auto Start Inhibit
11
Scheduled Run Inhibit
12
Speed Drop Pulse
13
Generator Closed Auxiliary
14
Generator Load Inhibit
15
Mains Closed Auxiliary
and there is in the right of
first row in LCD when input is active. When it is active, the genset will
raise the speed gradually. (It is suitable for TSC1 engines) Under
voltage/frequency/speed protection is inactive. In Auto mode, during generator
normal running, when input is active, inhibit generator shutdown
automatically. In Auto mode, inhibit generator start automatically when input
is active. In Auto mode, inhibit scheduled run genset when input is active.
When it is active, the genset will drop the speed gradually. (It is suitable
for TSC1 engines) Connect generator loading switch’s Aux. Point. Prohibit
genset switch on when input is active. Connect mains loading switch’s Aux.
Point.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 48 of 70
No.
Type
16
Mains Load Inhibit
Description Prohibit mains switch on when input is active. When input is active, controller enters into Auto mode; all
17
Auto Mode Lock
the keys except
are
inactive.
When input is active, controller won’t work under Auto
18
Auto Mode Inhibit
19
Controller LCD Backlit
20
Controller Buzzer
21
Battle Mode
22
Aux Instrument Mode
23
Reset Maintenance 1
24
Reset Maintenance 2
25
Reset Maintenance 3
mode.
key and simulate auto key input does not
work. The LCD backlight will illuminate when the input is active. Controller buzzer will peal when the input is active. All shutdown alarms are prohibited except emergency stop. All outputs are prohibited in this mode. Controller will set maintenance time and date 1 as default when input is active. Controller will set maintenance time and date 2 as default when input is active. Controller will set maintenance time and date 3 as default when input is active.
26
High Temperature Shutdown
Connected sensor digital input.
27
Low Oil Pressure Shutdown
Connected sensor digital input.
In Auto mode, when input active, genset can be started
28
Remote Start On Load
automatically and take load after genset normal running;
when input inactive, genset will stop automatically.
In Auto mode, when input is active, genset can be started
29
Remote Start Off Load
automatically and NOT take load after genset normal running; when input is inactive, genset will stop
automatically.
In Manual mode, when input active, genset will start
30
Manual Start Auxiliary
automatically; when input inactive, genset will stop
automatically
31
Remote Start Demand
When it is active, it will send regeneration inhibition
Aftertreatment Regeneration
32
command to the ECU that supports aftertreatment
Inhibit
regeneration.
33
Simulate Stop Key
An external button can be connected and pressed as
34
Simulate Manual Key
simulate panel.
Manual Aftertreatment 35
Regeneration
When it is active, it will send regeneration command to the ECU that supports aftertreatment regeneration.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 49 of 70
No.
Type
Description
36
Simulate Auto Key
An external button can be connected and pressed as
37
Simulate Start Key
simulate panel.
38
Simulate Generator Load Key This is simulate G-close key when HGM9310MPU(CAN)
controller is applied.
39
Simulate Mains Load Key
This is simulating G-open key when HGM9310MPU (CAN) controller is applied.
40
Low Coolant Level
Connect with water level sensor digital input port.
41
Detonation Shutdown
Connect with detection module warn input port.
42
Intermediate Speed Input
Specific ECU speed control.
43
Rated Speed Input
Specific ECU speed control.
Selection for which genset has the highest priority. When
44
First Priority
it is master-standby running mode or balanced running mode, one of the gensets should be set as the master
one.
45
Auxiliary Mains OK
In Auto mode, mains are normal when input is active.
46
Auxiliary Mains Fail
In Auto mode, mains are abnormal when input is active.
47
Alternative Configuration 1
Alternative configuration is active when the input is
48
Alternative Configuration 2
active. Users can set different parameters to make it
49
Alternative Configuration 3
easy to select current configuration via input port.
50
Gas Leak Shutdown
Connect with detection module warn input port.
8.4 SELECTION OF SENSORS
Table 16 Sensors Selection
No.
Description
0 Not used
1 User Configured (Resistance)
2 User Configured (4-20mA)
3 VDO
4 CURTIS
5 VOLVO-EC
6 DATCON
1
Temperature Sensor
7 SGX
8 SGD
9 SGH
10 PT100
11 SUSUKI
12 PRO
13~15 Reserved
0 Not used
2
Pressure Sensor
1 User Configured (Resistance) 2 User Configured (4-20mA)
3 VDO 10Bar
Remark
Defined resistance’s range is (0~6)K, default is SGX sensor.
Defined resistance’s range is (0~6)K, default is SGX sensor.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 50 of 70
No.
3
Fuel Level Sensor
Description 4 CURTIS 5 VOLVO-EC 6 DATCON 10Bar 7 SGX 8 SGD 9 SGH 10 VDO 5Bar 11 DATCON 5Bar 12 DATCON 7Bar 13 SUSUKI 14 PRO 15 Reserved 0 Not used 1 User Configured (Resistance) 2 User Configured (4-20mA) 3 SGD 4 SGH 5~15 Reserved
Remark
Defined resistance’s range is (0~6)K, default is SGH sensor.
NOTE: User should make special declare when order controller if your genset equip with sensor of 4~20mA.
8.5 CONDITIONS OF CRANK DISCONNECT SELECTION
Table 17 Crank Disconnect Conditions Selection
No.
Setting description
0
Gen frequency
1
Engine Speed
2
Engine Speed + Gen frequency
3
Oil pressure
4
Oil pressure + Gen frequency
5
Oil pressure + Engine Speed
6
Oil pressure + Engine Speed + Gen frequency
NOTE:
a) There are 3 conditions to make starter disconnected with engine (engine
speed, generator frequency and engine oil
pressure). They all can be used separately. We recommend that engine oil
pressure should be using with speed and generator frequency together, in order
to make the starter motor is separated with engine immediately and can check
crank disconnect exactly.
b) Speed sensor is the magnetic equipment which be installed in starter for
detecting flywheel teeth. c) When set as speed sensor, must ensure that the
number of flywheel teeth is as same as setting, otherwise, “over speed
shutdown” or “under speed shutdown” may be caused.
d) If genset without speed sensor, please don’t select corresponding items,
otherwise, “start fail” or “loss speed signal”
maybe caused.
e) If genset without oil pressure sensor, please don’t select corresponding
items. f) If not select generator frequency in crank disconnect setting,
controller will not collect and display the relative power
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 51 of 70
quantity (can be used in water pump set); if not select speed sensor in crank
disconnect setting, the speed displayed in controller is calculated by
generator frequency and number of poles.
9 PARAMETERS SETTING
CAUTION: Please change the controller parameters when generator is in standby
mode only (e. g., setting auxiliary input, auxiliary output, various delays),
otherwise, shutdown and other abnormal conditions may happen.
NOTE: Maximum set value must over minimum set value in case that the condition
of too high as well as too low will happen.
NOTE: When setting the warning alarm, please set the correct return value;
otherwise, maybe there is abnormal alarm. When setting the maximum value, the
return value must less than set value; when setting the minimum value, the
return value must over set value.
NOTE: Auxiliary input could not be set as same items; otherwise, there are
abnormal functions. However, the auxiliary output can be set as same items.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 52 of 70
10 SENSORS SETTING
a) When reselect sensors, the sensor curve will be transferred into the
standard value. For example, if temperature sensor is SGX (120°C resistor
type), its sensor curve is SGX (120°C resistor type); if select the SGD (120°C
resistor type), the temperature sensor curve is SGD curve.
b) When there is difference between standard sensor curves and using sensor,
user can adjust it in “curve type”.
c) When input the sensor curve, X value (resistor) must be input from small to
large, otherwise, mistake occurs.
d) If select sensor type as “None”, sensor curve is not working. e) If
corresponding sensor has alarm switch only, user must set this sensor as
“None”, otherwise, maybe
there is shutdown or warning. f) The headmost or backmost values in the
vertical coordinates can be set as same as below,
1Pa 1kgf/cm2
1bar 1psi
Fig.4 Curve Diagram
Table 18 Normal Pressure Unit Conversion
pa 1 9.8×104 1×105 6.89×103
kgf/cm2 1.02×105
1 1.02 7.03×102
bar 1×105
0.98 1
6.89×102
psi 1.45×104
14.2 14.5
1
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 53 of 70
11 COMMISSIONING
Please make the under procedures checking before commissioning, a) Ensure all
the connections are correct and wires diameter is suitable. b) Ensure that the
controller DC power has fuse, controller`s positive and negative connected to
starting
battery are correct. c) Emergence stop must be connected with positive of
start battery via scram button’s normal close
point and fuse. d) Take proper action to prevent engine to crank disconnect
(e. g. Remove the connection wire of fuel
valve). If checking is OK, make the start battery power on; choose manual mode
and controller will executive routine. e) Set controller under manual mode,
press “start” button, genset will start. After the setting times as setting,
controller will send signal of Start Fail; then press “stop” to reset
controller. f) Recover the action of stop engine start (e. g. Connect wire of
fuel valve), press start button again, genset will start. If everything goes
well, genset will normal run after idle running (if idle run be set). During
this time, please watch for engine’s running situations and AC generator’s
voltage and frequency. If abnormal, stop genset running and check all wires
connection according to this manual. g) If there is any other question, please
contact SmartGen’s service.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 54 of 70
12 TYPICAL APPLICATION Fig.5 HGM9310MPU(CAN) Typical Application Diagram
Fig.6 HGM9320MPU(CAN) Typical Application Diagram
NOTE: Fuse F1: min. 2A; max. 20A. Fuse F2: max. 32A. Users should select
suitable fuse depend on practical application.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 55 of 70
13 INSTALLATION
Controller is panel built-in design; it is fixed by clips when installed. The
controller’s overall dimensions and cutout dimensions for panel, please refers
to as following,
Fig.7 Overall and Cutout Dimensions
Battery Voltage Input
HGM93XXMPU(CAN) series controller can suit for widely range of battery voltage
DC(8~35)V. Negative of battery must be connected with the engine shell. The
diameter of wire which from power supply to battery must be over 2.5mm2. If
floating charge configured, please firstly connect output wires of charger to
battery’s positive and negative directly, then, connect wires from battery’s
positive and negative to controller’s positive and negative input ports in
order to prevent charge disturbing the controller’s normal working.
Speed Sensor Input
Speed sensor is the magnetic equipment which be installed in starter and for
detecting flywheel teeth. Its connection wires to controller should apply for
2 cores shielding line. The shielding layer should connect to No. 16 terminal
in controller while another side is hanging in air. The else two signal wires
are connected to No.17 and No.18 terminals in controller. The output voltage
of speed sensor should be within AC (1~24) V (effective value) during the full
speed. AC12V is recommended (in rated speed). When install the speed sensor,
let the sensor is spun to contacting flywheel first, then, port out 1/3 lap,
and lock the nuts of sensor at last.
Output and Expand Relays
All outputs of controller are relay contact output type. If need to expand the
relays, please add freewheel diode to both ends of expand relay’s coils (when
coils of relay have DC current) or, increase resistance-capacitance return
circuit (when coils of relay have AC current), in order to prevent disturbance
to controller or others equipment.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 56 of 70
AC Input
Current input of controller must be connected to outside current transformer.
And the current transformer’s secondary side current must be 5A. At the same
time, the phases of current transformer and input voltage must correct.
Otherwise, the current of collecting and active power maybe not correct.
Withstand Voltage Test
When controller had been installed in control panel, if need the high voltage
test, please disconnect controller’s all terminal connections, in order to
prevent high voltage into controller and damage it.
NOTE: ICOM port must be connected to negative pole of battery.
WARNING! When there is load current, transformer’s secondary side prohibit
open circuit.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 57 of 70
14 GSM SHORT MESSAGE ALARM AND REMOTE CONTROL 14.1 GSM SHORT MESSAGE ALARM
When controller detects alarm, it will send short message to phone
automatically.
NOTE: All alarms about shutdown, trip and stop and trip will be sent to the
pre-set phone. Warnings are sent to the phone according to the pre-set.
14.2 GSM SHORT MESSAGE REMOTE CONTROL
Users send order message to GSM module, then controller will make actions according to this SMS order and pass back corresponding operations information. Controllers only sent the message to the pre-set phone number.
Table 19 Detail Orders
No.
SMS Orders
Pass back Information
Description
GENSET ALARM
When genset is shutdown alarm
SYSTEM IN STOP MODE
At rest status in stop
GENSET AT REST
mode
SYSTEM IN MANUAL MODE At rest status in manual
GENSET AT REST
mode
1 SMS GENSET
SYSTEM IN AUTO MODE GENSET AT REST
At rest status in auto Get status of
mode
genset
SYSTEM IN STOP MODE
Running status in stop
GENSET IS RUNNING
mode
SYSTEM IN MANUAL MODE Running status in
GENSET IS RUNNING
manual mode
SYSTEM IN AUTO MODE
Running status in auto
GENSET AT RUNNING
mode
GENSET ALARM
Generator is shutdown alarm or trip alarm
2 SMS START
STOP MODE NOT START
Cannot start in stop
mode
Start genset
SMS START OK
Start in manual mode
AUTO MODE NOT START
Cannot start in auto mode
SMS 3
MODE
STOP SMS STOP OK
Set as stop mode
SMS MANUAL
4
SMS MANUAL MODE OK
MODE
Set as manual mode
SMS 5
MODE
AUTO SMS AUTO MODE OK
Set as auto mode
6 SMS DETAIL
Pass back information can Gets details information of genset.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 58 of 70
No.
SMS Orders
Pass back Information
Description
be set via controller software.
SMS INHIBIT
7
INHIBIT START OK
START
Generator start will be inhibited.
SMS PERMIT
8
PERMIT START OK
START
Discharge the inhibit start signal.
NOTE: Its national and area’s cods must be added. E.g. China: 8613666666666.
NOTE: When sending orders, users need to follow SMS orders in above form and all the letters must be capital.
NOTE: Pass back information from SMS DETAIL including: working mode, mains voltage, generator voltage, load current,
mains frequency, generator frequency, active power, apparent power, power factor, battery voltage, D+ voltage, water
temperature, oil pressure, oil level, engine speed, total running time, genset status, and alarm status.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 59 of 70
15 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE
15.1 CUMMINS ISB/ISBE
Table 20 Connector B
Terminals of controller Fuel relay output Start relay output
Auxiliary output 1
Connector B 39 Expand 30A relay, battery voltage of 01, 07, 12, 13 is supplied by relay
Remark
Connect with starter coil directly. ECU power; Set Auxiliary output 1 as “ECU
power”.
Table 21 9-pin Connector
Terminals of controller
9 pins connector
CAN GND
SAE J1939 shield
CAN(H)
SAE J1939 signal
CAN(L)
SAE J1939 return
Engine type: Cummins ISB.
Remark CAN communication shielding line (connect with ECU terminal only). Impedance 120 connecting line is recommended. Impedance 120 connecting line is recommended.
15.2 CUMMINS QSL9
Suitable for CM850 engine control module.
Table 22 50-pin Connector
Terminals of controller
50 pins connector
Fuel relay output
39
Start relay output
–
Remark Connect to starter coil directly
Table 23 9-pin Connector
Terminals of controller
9 pins connector
CAN GND
SAE J1939 shield-E
CAN(H)
SAE J1939 signal-C
CAN(L)
SAE J1939 return-D
Engine type: Cummins-CM850.
Remark
CAN
communication
shielding
line(connect with ECU terminal only)
Impedance 120 connecting line is recommended.
Impedance 120 connecting line is
recommended.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 60 of 70
15.3 CUMMINS QSM11 (IMPORT)
It is suitable for CM570 engine control module. Engine type is QSM11 G1, QSM11 G2.
Table 24 C1 Connector
Terminals of controller
C1 connector
Fuel relay output
5&8
Start relay output
–
Remark Outside expand relay, when fuel output, making port 5 and port 8 of C1 be connected. Connect to starter coil directly.
Table 25 3-pin Data Link Connector
Terminals of controller 3 pins data link connector
CAN GND
C
CAN(H)
A
CAN(L)
B
Engine type: Cummins ISB.
Remark CAN communication shielding line (connect with ECU terminal only). Impedance 120 connecting line is recommended. Impedance 120 connecting line is recommended.
15.4 CUMMINS QSX15-CM570
It is suitable for CM570 engine control module. Engine type is QSX15.
Table 26 50-pin Connector
Terminals of controller
50 pins connector
Fuel relay output
38
Start relay output
–
Remark Oil spout switch . Connect to starter coil directly.
Table 27 9-pin Connector
Terminals of controller
9 pins connector
CAN GND
SAE J1939 shield-E
CAN(H)
SAE J1939 signal-C
CAN(L)
SAE J1939 return-D
Engine type: Cummins QSX15-CM570.
Remark
CAN
communication
shielding
line(connect with ECU terminal only)
Impedance 120 connecting line is
recommended.
Impedance 120 connecting line is
recommended.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 61 of 70
15.5 CUMMINS GCS-MODBUS
It is suitable for GCS engine control module. Use RS485-MODBUS to read information of engine. Engine types are QSX15, QST30, QSK23/45/60/78 and so on.
Table 28 D-SUB Connector 06
Terminals of controller
D-SUB connector 06
Fuel relay output
5&8
Start relay output
–
Remark Outside expand relay, when fuel output, making port 05 and 08 of the connector 06 be connected. Connect to starter coil directly.
Table 29 D-SUB Connector 06
Terminals of controller
D-SUB connector 06
RS485 GND
20
RS485+
21
RS485-
18
Remark CAN communication shielding line (connect with ECU terminal only). Impedance 120 connecting line is recommended. Impedance 120 connecting line is recommended.
Engine type: Cummins QSK-MODBUS, Cummins QST-MODBUS, Cummins QSX-MODBUS.
15.6 CUMMINS QSM11
Table 30 Engine OEM Connector
Terminals of controller Fuel relay output Start relay output
OEM connector of engine 38 –
CAN GND
–
CAN(H)
46
CAN(L)
37
Engine type: Common J1939.
Remark
Connect with starter coil directly. CAN communication shielding line (connect
with controller’s this terminal only). Impedance 120 connecting line is
recommended. Impedance 120 connecting line is recommended.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 62 of 70
15.7 CUMMINS QSZ13
Table 31 Engine OEM Connector
Terminals of controller Fuel relay output Start relay output
OEM connector of engine 45 –
Auxiliary output 1
16&41
Auxiliary output 2
19&41
CAN GND
–
CAN(H)
1
CAN(L)
21
Engine type: Common J1939
Remark
Connect to starter coil directly Setting to idle speed control; normally close
output. Making 16 connect to 41 during high-speed running of controller via
external expansion relay. Setting to pulse raise speed control; normally open
output. Making 19 connect with 41 for 0.1s during high-speed warming of
controller via external expansion relay. CAN communication shielding line
(connect with controller’s this terminal only) Impedance 120 connecting line
is recommended. Impedance 120 connecting line is recommended.
15.8 DETROIT DIESEL DDEC III / IV
Table 32 Engine CAN Port
Terminals of controller Fuel relay output Start relay output CAN GND CAN(H) CAN(L)
CAN port of engine Expand 30A relay; battery voltage of ECU is supplied by
relay. –
CAN(H)
CAN(L)
Remark
Connect to starter coil directly. CAN communication shielding line (connect
with controller’s terminal only). Impedance 120 connecting line is
recommended. Impedance 120 connecting line is recommended.
Engine type: Common J1939.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 63 of 70
15.9 DEUTZ EMR2
Table 33 Engine OEM Connector
Terminals of controller
Fuel relay output
Start relay output CAN GND CAN(H) CAN(L) Engine type: VolvoEDC4.
F connector Expand 30A relay; battery voltage of terminal 14 is supplied by
relay. Fuse is 16A. 1
–
12
13
Remark
Connect to starter coil directly. Connect to battery negative pole. CAN
communication shielding line (connect with controller’s terminal only).
Impedance 120 connecting line is recommended. Impedance 120 connecting line is
recommended.
15.10 JOHN DEERE
Table 34 21-pin Connector
Terminals of controller Fuel relay output Start relay output
21 pins connector G, J D
CAN GND
–
CAN(H)
V
CAN(L)
U
Engine type: John Deere.
Remark
CAN communication shielding line (connect with controller’s terminal only).
Impedance 120 connecting line is recommended. Impedance 120 connecting line is
recommended.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 64 of 70
15.11 MTU MDEC
Suitable for MTU engines, 2000 series, 4000series.
Table 35 X1 Connector
Terminals of controller
Fuel relay output
BE1
Start relay output
BE9
CAN GND
E
X1 connector
CAN(H)
G
CAN(L)
F
Engine type: MTU-MDEC-303.
Remark
CAN communication shielding line (connect with one terminal only). Impedance
120 connecting line is recommended. Impedance 120 connecting line is
recommended.
15.12 MTU ADEC (SMART MODULE)
It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Table 36 ADEC (X1 Port)
Terminals of controller
ADEC (X1 port)
Fuel relay output
X1 10
Start relay output
X1 34
Remark X1 Terminal 9 Connected to negative of battery. X1 Terminal 33 Connected to negative of battery.
Table 37 SMART (X4 Port)
Terminals of controller
SMART (X4 port)
CAN GND
X4 3
CAN(H)
X4 1
CAN(L)
X4 2
Engine type: MTU-ADEC.
Remark CAN communication shielding line (connect to controller’s this terminal only) Impedance 120 connecting line is recommended. Impedance 120 connecting line is recommended.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 65 of 70
15.13 MTU ADEC (SAM MODULE)
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Table 38 ADEC (X1 Port)
Terminals of controller
ADEC (X1 port)
Fuel relay output
X1 43
Start relay output
X1 37
Remark X1 Terminal 28 Connected to negative of battery. X1 Terminal 22 Connected to negative of battery.
Table 39 SAM (X23 Port)
Terminals of controller
SAM (X23 port)
CAN GND
X23 3
CAN(H)
X23 2
CAN(L)
X23 1
Engine type: Common J1939.
Remark CAN communication shielding line (connect with controller’s this terminal only). Impedance 120 connecting line is recommended. Impedance 120 connecting line is recommended.
15.14 PERKINS
It is suitable for ADEM3/ ADEM4 engine control module. Engine type is 2306, 2506, 1106, and 2806.
Table 40 Connector
Terminals of controller Fuel relay output Start relay output
Connector 1, 10, 15, 33, 34 –
CAN GND
–
CAN(H)
31
CAN(L)
32
Engine type: Perkins.
Remark
Connect to starter coil directly. CAN communication shielding line (connect
with controller’s terminal only). Impedance 120 connecting line is
recommended. Impedance 120 connecting line is recommended.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 66 of 70
15.15 SCANIA
It is suitable for S6 engine control module. Engine type is DC9, DC12, and DC16.
Table 41 B1 Connector
Terminals of controller
Fuel relay output
3
Start relay output
–
CAN GND
–
B1 connector
CAN(H)
9
CAN(L)
10
Engine type: Scania.
Remark
Connect to starter coil directly. CAN communication shielding line (connect
with controller’s terminal only). Impedance 120 connecting line is
recommended. Impedance 120 connecting line is recommended.
15.16 VOLVO EDC3
Suitable engine control mode is TAD1240, TAD1241, and TAD1242.
Table 42 “Stand alone” Connector
Terminals of controller Fuel relay output Start relay output
“Stand alone” connector H E
Auxiliary output 1
P
Remark
ECU power; Set Auxiliary output 1 as “ECU power”.
Table 43 “Data bus” Connector
Terminals of controller
“Data bus” connector
CAN GND
–
CAN(H)
1
CAN(L)
2
Remark CAN communication shielding line (connect with controller’s terminal only). Impedance 120 connecting line is recommended. Impedance 120 connecting line is recommended.
Engine type: Volvo.
NOTE: When this engine type is selected, preheating time should be set to at least 3 seconds.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 67 of 70
15.17 VOLVO EDC4
Suitable engine types are TD520, TAD520 (optional), TD720, TAD720 (optional), TAD721, TAD722, and TAD732.
Table 44 Connector
Terminals of controller Fuel relay output Start relay output CAN GND CAN(H) CAN(L) Engine type: VolvoEDC4.
Connector
Remark
Expand 30A relay; battery
voltage of terminal 14 is
supplied by relay. Fuse is
16A.
–
Connect to starter coil directly.
1
Connected to negative of battery.
CAN communication shielding line –
(connect with controller’s terminal only).
Impedance 120 connecting line is 12
recommended.
13
Impedance 120 connecting line is
recommended.
15.18 VOLVO-EMS2
Volvo Engine types are TAD734, TAD940, TAD941, TAD1640, TAD1641, and TAD1642.
Table 45 Engine CAN Port
Terminals of controller
Auxiliary output 1
6
Engine’s CAN port
Auxiliary output 2
5
3 4
CAN GND
–
CAN(H)
1(Hi)
CAN(L)
2(Lo)
Remark ECU stop; Set Auxiliary output 1 as “ECU Stop”. ECU power; Set Auxiliary output 2 as “ECU power”. Negative power. Positive power. CAN communication shielding line (connect with controller’s terminal only). Impedance 120 connecting line is recommended. Impedance 120 connecting line is recommended.
Engine type: Volvo-EMS2.
NOTE: When this engine type is selected, preheating time should be set to at least 3 seconds.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 68 of 70
15.19 YUCHAI
It is suitable for BOSCH common rail electronic-controlled engine.
Table 46 Engine 42-pin Port
Terminals of controller Fuel relay output Start relay output
Engine 42 pins port 1.40 –
CAN GND
–
CAN(H)
1.35
CAN(L)
1.34
Remark
Connect to engine ignition lock
Connect to starter coil directly
CAN
communication
shielding
line(connect with controller’s this
terminal only)
Impedance 120 connecting line is
recommended.
Impedance 120 connecting line is
recommended.
Table 47 Engine 2-pin Port
Battery Battery negative Battery positive
Engine type: BOSCH.
Engine 2 pins 1 2
Remark Wire diameter 2.5mm2. Wire diameter 2.5mm2.
15.20 WEICHAI
It is suitable for Weichai BOSCH common rail electronic-controlled engine.
Table 48 Engine Port
Terminals of controller
Fuel relay output
1.40
Start relay output
1.61
CAN GND
–
CAN(H)
1.35
Engine port
CAN(L)
1.34
Remark Connect to engine ignition lock.
CAN communication shielding line (connect to the controller at this end only).
Impedance 120 connecting line is recommended. Impedance 120 connecting line is
recommended.
Engine type: GTSC1.
NOTE: If there is any question of connection between controller and ECU communication, please feel free to contact
SmartGen’s service.
HGM9300MPU(CAN) Series Genset Controller User Manual
Page 69 of 70
16 FAULT FINDING
Table 49 Fault Finding
Symptoms Controller no response with power. Genset shutdown
Controller emergency stop Low oil pressure alarm after crank disconnect High
water temp. alarm after crank disconnect Shutdown alarm in running
Fail to start
Starter no response Genset running while ATS not transfer RS485 communication
is abnormal
ECU communication failed
ECU warning or shutdown
Possible Solutions Check starting batteries; Check controller connection
wirings; Check DC fuse. Check the water/cylinder temperature is too high or
not; Check the genset AC voltage; Check DC fuse. Check emergence stop button
is correct or not; Check whether the starting battery positive is connected
with the emergency stop input; Check whether the circuit is open.
Check the oil pressure sensor and its connections.
Check the temperature sensor and its connections.
Check related switch and its connections according to the information on LCD; Check auxiliary input ports. Check fuel oil circuit and its connections; Check starting batteries; Check speed sensor and its connections; Refer to engine manual. Check starter connections; Check starting batteries. Check ATS; Check the connections between ATS and controllers. Check connections; Check COM port setting is correct or not; Check RS485’s connections of A and B is reverse connect or not; Check RS485 transfer module whether damage or not; Check communication port of PC whether damage or not. Check connections of CAN high and low polarity; Check if correctly connected of 120 resister; Check if type of engine correct; Check if connections from controller to engine and output ports setting are correct. Get information from LCD of alarm page; If there is detailed alarm, check engine according to description. If not, please refer to engine manual according to SPN alarm code.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>