Product Information

Specifications

  • Dimensions: 433 x 677 x 258 mm
  • Weight: 20 Kg
  • Protection Grade: IP30

Technical Specifications

  • Power Supply Voltage: 19-30V
  • Operating Temperature: Varies
  • Consumption @ 27.6V Stand-by Maximum: 1A
  • Maximum Voltage on RS485-REPEATER: 1A @27.6V
  • Maximum Voltage on RS485-BMS: 1A @27.6V

Batteries

  • Maximum Voltage Charge Adapted to Temperature
  • Battery Charger
  • Maximum Internal Resistance of Battery (Ri Max)
  • Battery Shutdown Voltage
  • Operating Temperature: Varies
  • Isolation Class
  • Consumption @ 27.6V Stand-by Maximum:
  • Maximum Voltage on OUT 1:

Product Usage Instructions

Power Supply
Ensure the power supply voltage is within the range of 19-30V for proper functioning of the control panel.

Operating Temperature
Operate the control panel within the specified temperature range to avoid any issues related to overheating or malfunctioning.

Battery Usage
Monitor the battery charge and ensure it is adapted to the temperature for efficient performance. Keep an eye on the battery shutdown voltage to prevent power disruptions.

Frequently Asked Questions (FAQ)

  1. Q: What is the maximum weight capacity of the control panel?
    A: The control panel can support a weight of up to 20 Kg.

  2. Q: What is the recommended power supply voltage range?
    A: The recommended power supply voltage range is between 19-30V for optimal performance.

  3. Q: How should I monitor the battery charge for the control panel?
    A: Monitor the battery charge to ensure it is adapted to the temperature and keep an eye on the battery shutdown voltage to avoid power disruptions.

Technical specifications|
---|---
|
Dimensions| 433 x 677 x 258 mm
Weight| 20 Kg
Protection grade| IP30
Power supply voltage| 19-30V
Operating temperature| -5°C +40°C
Consumption @ 27.6V| stand-by| 130mA
maximum| 140mA
mains fault| 110mA
Maximum voltage on RS485-REPEATER| 1A @27.6V
Maximum voltage on RS485-BMS| 1A @27.6V
Power supply voltage| 230V~ (+10% -15%)
115V~ (+10% -15%)
50/60 Hz
Maximum current draw from mains| 5A @230V~
8.5A @115V~
Nominal output voltage| 26V    ±10%
Maximum output ripple| 200mV pp
Maximum output current of the power group (Imax b according to EN54-4)| 38A @230V~
32A @115V~
Maximum current for external loads
(Imax a according to EN54-4)| 35A @230V~
29A @115V~
Imin| 100mA
Power factor (at full load)| 0.95 @ 230V~
0.99 @ 115V~
Overvoltage protection (% of the declared potential)| 105 / 135
Overvoltage category| CAT II 2500 V
Overload protection| 29 / 33 V
Batteries| 2 x 12V 38Ah, NP38-121
2 x 12 V 24 Ah, NPL24-12I
2 x 12 V 17 Ah, NP 17 -12-FR
Maximum voltage charge adapted to temperature| 28V
Battery charger| 3A
Maximum internal resistance of battery (Ri Max)| 0.1Ohm
Battery shutdown voltage| 19,5V
Operating temperature| -5°C +40°C
Isolation class| I
Consumption @ 27.6V| stand-by| 20mA
maximum| 40mA
mains fault| 30mA
Maximum voltage on OUT 1| 1.5A @27.6V
Maximum voltage on OUT 2| 1.5A @27.6V
Maximum voltage on RELAY| 5A, 30V
Power supply voltage| 20-30 V
---|---
Operating temperature| -5°C +40°C
Maximum number of devices managed by a loop| 240
Consumption @ 27.6V| stand-by| 35mA
maximum| 50mA
Maximum voltage on Loop-A| 0.5A
Maximum voltage on Loop-B| 0.5A

Mains and grounding connection

Batteries connection

Cable entry

Connection of polarized devices (sirens, etc.) to OUT terminals

Connection of non-polarized devices (relays, coils, etc.) to OUT terminals

Relay connection as generic indication

Relay connection as fault signalling
(factory-assigned)

Loop connection

Isolation class I
Terminal type AC INPUT
BATTERY ES1, PS3
RELAY ES1, PS2
OUT1, OUT2 ES1, PS2
RS485-BMS, RS485-REPEATER ES1, PS2
CAN-IN, CAN-OUT ES1, PS2
TAMPER ES1, PS1
USB ES1, PS1
CR2032 (J2) ES1, PS1
RS232 ES1, PS1
LOOP-A, LOOP-B ES1, PS2
ETHERNET ES1, PS1

Regulation (EU) No 305/2011 This product complies with requirements stated by standards listed here below in compliance with Regulation (EU) No. 305/2011.
Directive 2014/53/EU Hereby, INIM Electronics S.r.l. declares that the Previdia Ultra control panels are in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU. This product may be used in all EU Countries.
Documents for the users Declarations of Performance, Declarations of Conformity and Certificates concerning to INIM Electronics S.r.l. products may be downloaded free of charge from the web address www.inim.it, getting access to Extended Access and then selecting “Certifications” or requested to the e-mail address info@inim.it or requested by ordinary mail to the address shown in this manual.
Manuals may be downloaded free of charge from the web address www.inim.it, getting access to Extended Access and then selecting “Manuals”.

0051
INIM Electronics s.r.l.
Via Dei Lavoratori 10 – Fraz. Centobuchi 63076 Monteprandone (AP) – Italy
22
0051-CPR-2826
EN 54-2:1997 + A1:2006
EN 54-4:1997 + A1:2002 + A2:2006 EN 54-21:2006
EN 12094-1:2003
PREVIDIA-ULTRA216
PREVIDIA-ULTRA216R
PREVIDIA-ULTRA216D
Control and signalling panel with power-supply equipment, alarm transmission and fault signalling equipment, automatic electrical device for control and management of switch off and delay for fire detection and signalling in buildings and for gas extinguishing systems installed in buildings as part of a complete operating system.

Essential features Performance
Performance in the event of fire PASS
Power supply performance PASS

Response delay (response time in the event of fire)| PASS
Transmission performance| PASS
Operating reliability| PASS
Durability of operating reliability:| Thermal resistance| PASS
Vibration resistance| PASS
Humidity resistance| PASS
Electrical stability| PASS
Options provided in accordance with EN54- 2| Performance
---|---
7.8 Output to fire alarm devices| PASS
7.9 Output to fire alarm routing equipment| PASS
7.10 Output to fire protection equipment| PASS
7.11 Delay on outputs| PASS
7.12 Co-incidence detection (Type A, B and C)| PASS
7.13 Alarm counter| PASS
8.3 Point fault signal| PASS
8.9 Output to remote fault or warning signalling devices| PASS
9.5 Addressable points out-of-service| PASS
10.0 Test condition| PASS
Options provided in accordance with EN12094- 1| Performance
4.17 Delay of extinguishing signal| PASS
4.18 Signal representing the flow of extinguishing agent| PASS
4.19 Monitoring of the status of components| PASS
4.20 Emergency hold device| PASS
4.21 Control of flooding time| PASS
4.22 Initiation of secondary flooding| PASS
4.24 Triggering signals to equipment within the system| PASS
4.26 Triggering of equipment outside the system| PASS
4.27 Emergency abort device| PASS
4.28 Control of extended discharge| PASS
4.29 Release of the extinguishing media for selected flooding zones| PASS
Additional information according to EN 54- 2
About information required at point 12.2.1, see data contained in this manual.
Additional information according to EN 54- 4
For the information required by point 7.1, see data contained in this manual.
Additional information according to EN 54- 21
For the information required by point 7.2.1, see data contained in this manual.
Additional information according to EN 12094- 1
Environmental class: A
Degree of protection: IP30 Flooding zones: up to 24 Zones from 1 a 24 for CO2, inert gas or halogenated hydrocarbons. Response delay activation condition: max 3s Response delay triggering of outputs: max 1s

This symbol indicates to installer to refer to the instructions manual.

Warranty

Inim Electronics S.r.l.. (Seller, Our, Us) warrants the original purchaser that this product shall be free from defects in materials and workmanship under normal use for a period of 24 months.
As Inim Electronics does not install this product directly, and due to the possibility that it may be used with other equipment not approved by Us;Inim Electronics does not warrant against loss of quality, degradation of performance of this product or actual damage that results from the use of products, parts or other replaceable items (such as consumables) that are neither made nor recommended by Inim Electronics. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller’s option, any product not meeting the specifications. In no event shall Inim Electronics be liable to the purchaser or any other person for any loss or damage whether direct of indirect or consequential or incidental, including without limitation, any damages for lost profits, stolen goods, or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product.
This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover damage arising from improper maintenance or negligence, damage caused by fire, flood, wind or lightning, vandalism, fair wear and tear.
Inim Electronics S.r.l. shall, at its option, repair or replace any defective products. Improper use, that is, use for purposes other than those mentioned in this manual will void the warranty. Contact Our authorized dealer, or visit our website for further information regarding this warranty.

Limited warranty
Inim Electronics S.r.l. shall not be liable to the purchaser or any other person for damage arising from improper storage, handling or use of this product.
Installation of this Product must be carried out by qualified persons appointed by Inim Electronics. Installation of this Product must be carried out in accordance with Our instructions in the product manual.

Copyright
The information contained in this document is the sole property of Inim Electronics S.r.l.. Copying, reprinting or modification of this document, in part or as a whole, is not permitted without prior authorization in writing from Inim Electronics S.r.l.. All rights reserved.

WEEE
Informative notice regarding the disposal of electrical and electronic equipment (applicable in countries with differentiated waste collection systems)
The crossed-out bin symbol on the equipment or on its packaging indicates that the product must be disposed of correctly at the end of its working life and should never be disposed of together with general household waste. The user, therefore, must take the equipment that has reached the end of its working life to the appropriate civic amenities site designated to the differentiated collection of electrical and electronic waste. As an alternative to the autonomous-management of electrical and electronic waste, you can hand over the equipment you wish to dispose of to a dealer when purchasing new equipment of the same type. You are also entitled to convey for disposal small electronic-waste products with dimensions of less than 25cm to the premises of electronic retail outlets with sales areas of at least 400m2, free of charge and without any obligation to buy.
Appropriate differentiated waste collection for the subsequent recycling of the discarded equipment, its treatment and its environmentally compatible disposal helps to avoid possible negative effects on the environment and on health and favours the re-use and/or recycling of the materials it is made of.
Information about disposal of batteries and accumulators (applicable in Countries with separate collection systems)
This marking on batteries and/or their manual and/or their packaging, indicates that batteries of this products, at the end of their working life, should not be disposed of as unsorted municipal waste, but must be object of a separate collection. Where marked, the chemical symbols Hg, Cd o Pb indicate that the battery contains mercury, cadmium or lead above the reference levels of the directive 2006/66/EC. If batteries are not properly disposed of, these substances, together with other ones contained, can cause harm to human health and to the environment. To protect human health and the environment, to facilitate treatment and recycling of materials, separate batteries from other kind of waste and use the collection scheme stated in your area, in accordance to current laws. Before disposing of the above, it’s appropriate to remove them from their holders avoiding to damage them or causing short circuits.

Download

Inim Electronics S.r.l.
ISO 9001 Quality Management certified by BSI with certificate number FM530352
Centobuchi, via Dei Lavoratori 10
63076 Monteprandone (AP), Italy