Product Information
Specifications
- Dimensions: 433 x 677 x 258 mm
- Weight: 20 Kg
- Protection Grade: IP30
Technical Specifications
- Power Supply Voltage: 19-30V
- Operating Temperature: Varies
- Consumption @ 27.6V Stand-by Maximum: 1A
- Maximum Voltage on RS485-REPEATER: 1A @27.6V
- Maximum Voltage on RS485-BMS: 1A @27.6V
Batteries
- Maximum Voltage Charge Adapted to Temperature
- Battery Charger
- Maximum Internal Resistance of Battery (Ri Max)
- Battery Shutdown Voltage
- Operating Temperature: Varies
- Isolation Class
- Consumption @ 27.6V Stand-by Maximum:
- Maximum Voltage on OUT 1:
Product Usage Instructions
Power Supply
Ensure the power supply voltage is within the range of 19-30V for proper
functioning of the control panel.
Operating Temperature
Operate the control panel within the specified temperature range to avoid
any issues related to overheating or malfunctioning.
Battery Usage
Monitor the battery charge and ensure it is adapted to the temperature for
efficient performance. Keep an eye on the battery shutdown voltage to prevent
power disruptions.
Frequently Asked Questions (FAQ)
-
Q: What is the maximum weight capacity of the control panel?
A: The control panel can support a weight of up to 20 Kg. -
Q: What is the recommended power supply voltage range?
A: The recommended power supply voltage range is between 19-30V for optimal performance. -
Q: How should I monitor the battery charge for the control panel?
A: Monitor the battery charge to ensure it is adapted to the temperature and keep an eye on the battery shutdown voltage to avoid power disruptions.
Technical specifications|
---|---
|
Dimensions| 433 x 677 x 258 mm
Weight| 20 Kg
Protection grade| IP30
Power supply voltage| 19-30V
Operating temperature| -5°C +40°C
Consumption @ 27.6V| stand-by| 130mA
maximum| 140mA
mains fault| 110mA
Maximum voltage on RS485-REPEATER| 1A @27.6V
Maximum voltage on RS485-BMS| 1A @27.6V
Power supply voltage| 230V~ (+10% -15%)
115V~ (+10% -15%)
50/60 Hz
Maximum current draw from mains| 5A @230V~
8.5A @115V~
Nominal output voltage| 26V ±10%
Maximum output ripple| 200mV pp
Maximum output current of the power group (Imax b according to EN54-4)| 38A
@230V~
32A @115V~
Maximum current for external loads
(Imax a according to EN54-4)| 35A @230V~
29A @115V~
Imin| 100mA
Power factor (at full load)| 0.95 @ 230V~
0.99 @ 115V~
Overvoltage protection (% of the declared potential)| 105 / 135
Overvoltage category| CAT II 2500 V
Overload protection| 29 / 33 V
Batteries| 2 x 12V 38Ah, NP38-121
2 x 12 V 24 Ah, NPL24-12I
2 x 12 V 17 Ah, NP 17 -12-FR
Maximum voltage charge adapted to temperature| 28V
Battery charger| 3A
Maximum internal resistance of battery (Ri Max)| 0.1Ohm
Battery shutdown voltage| 19,5V
Operating temperature| -5°C +40°C
Isolation class| I
Consumption @ 27.6V| stand-by| 20mA
maximum| 40mA
mains fault| 30mA
Maximum voltage on OUT 1| 1.5A @27.6V
Maximum voltage on OUT 2| 1.5A @27.6V
Maximum voltage on RELAY| 5A, 30V
Power supply voltage| 20-30 V
---|---
Operating temperature| -5°C +40°C
Maximum number of devices managed by a loop| 240
Consumption @ 27.6V| stand-by| 35mA
maximum| 50mA
Maximum voltage on Loop-A| 0.5A
Maximum voltage on Loop-B| 0.5A
Mains and grounding connection
Batteries connection
Cable entry
Connection of polarized devices (sirens, etc.) to OUT terminals
Connection of non-polarized devices (relays, coils, etc.) to OUT terminals
Relay connection as generic indication
Relay connection as fault signalling
(factory-assigned)
Loop connection
Isolation class | I |
---|---|
Terminal type | AC INPUT |
BATTERY | ES1, PS3 |
RELAY | ES1, PS2 |
OUT1, OUT2 | ES1, PS2 |
RS485-BMS, RS485-REPEATER | ES1, PS2 |
CAN-IN, CAN-OUT | ES1, PS2 |
TAMPER | ES1, PS1 |
USB | ES1, PS1 |
CR2032 (J2) | ES1, PS1 |
RS232 | ES1, PS1 |
LOOP-A, LOOP-B | ES1, PS2 |
ETHERNET | ES1, PS1 |
Regulation (EU) No 305/2011 This product complies with requirements
stated by standards listed here below in compliance with Regulation (EU) No.
305/2011.
Directive 2014/53/EU Hereby, INIM Electronics S.r.l. declares that the
Previdia Ultra control panels are in compliance with the essential
requirements and other relevant provisions of Directive 2014/53/EU. This
product may be used in all EU Countries.
Documents for the users Declarations of Performance, Declarations of
Conformity and Certificates concerning to INIM Electronics S.r.l. products may
be downloaded free of charge from the web address
www.inim.it, getting access to Extended Access and then
selecting “Certifications” or requested to the e-mail address
info@inim.it or requested by ordinary mail to the
address shown in this manual.
Manuals may be downloaded free of charge from the web address
www.inim.it, getting access to Extended Access and then
selecting “Manuals”.
0051
INIM Electronics s.r.l.
Via Dei Lavoratori 10 – Fraz. Centobuchi 63076 Monteprandone (AP) – Italy
22
0051-CPR-2826
EN 54-2:1997 + A1:2006
EN 54-4:1997 + A1:2002 + A2:2006 EN 54-21:2006
EN 12094-1:2003
PREVIDIA-ULTRA216
PREVIDIA-ULTRA216R
PREVIDIA-ULTRA216D
Control and signalling panel with power-supply equipment, alarm transmission
and fault signalling equipment, automatic electrical device for control and
management of switch off and delay for fire detection and signalling in
buildings and for gas extinguishing systems installed in buildings as part of
a complete operating system.
Essential features | Performance |
---|---|
Performance in the event of fire | PASS |
Power supply performance | PASS |
Response delay (response time in the event of
fire)| PASS
Transmission performance| PASS
Operating reliability| PASS
Durability of operating reliability:| Thermal
resistance| PASS
Vibration resistance| PASS
Humidity resistance| PASS
Electrical stability| PASS
Options provided in accordance with EN54- 2|
Performance
---|---
7.8 Output to fire alarm devices| PASS
7.9 Output to fire alarm routing equipment|
PASS
7.10 Output to fire protection equipment| PASS
7.11 Delay on outputs| PASS
7.12 Co-incidence detection (Type A, B and
C)| PASS
7.13 Alarm counter| PASS
8.3 Point fault signal| PASS
8.9 Output to remote fault or warning
signalling devices| PASS
9.5 Addressable points out-of-service| PASS
10.0 Test condition| PASS
Options provided in accordance with EN12094- 1|
Performance
4.17 Delay of extinguishing signal| PASS
4.18 Signal representing the flow of
extinguishing agent| PASS
4.19 Monitoring of the status of components|
PASS
4.20 Emergency hold device| PASS
4.21 Control of flooding time| PASS
4.22 Initiation of secondary flooding| PASS
4.24 Triggering signals to equipment within the
system| PASS
4.26 Triggering of equipment outside the system|
PASS
4.27 Emergency abort device| PASS
4.28 Control of extended discharge| PASS
4.29 Release of the extinguishing media for
selected flooding zones| PASS
Additional information according to EN 54- 2
About information required at point 12.2.1, see
data contained in this manual.
Additional information according to EN 54- 4
For the information required by point 7.1,
see data contained in this manual.
Additional information according to EN 54- 21
For the information required by point 7.2.1,
see data contained in this manual.
Additional information according to EN 12094- 1
Environmental class: A
Degree of protection: IP30 Flooding zones: up
to 24 Zones from 1 a 24 for CO2, inert
gas or halogenated hydrocarbons. Response delay
activation condition: max 3s Response delay
triggering of outputs: max 1s
This symbol indicates to installer to refer to the instructions manual.
Warranty
Inim Electronics S.r.l.. (Seller, Our, Us) warrants the original purchaser
that this product shall be free from defects in materials and workmanship
under normal use for a period of 24 months.
As Inim Electronics does not install this product directly, and due to the
possibility that it may be used with other equipment not approved by Us;Inim
Electronics does not warrant against loss of quality, degradation of
performance of this product or actual damage that results from the use of
products, parts or other replaceable items (such as consumables) that are
neither made nor recommended by Inim Electronics. Seller obligation and
liability under this warranty is expressly limited to repairing or replacing,
at Seller’s option, any product not meeting the specifications. In no event
shall Inim Electronics be liable to the purchaser or any other person for any
loss or damage whether direct of indirect or consequential or incidental,
including without limitation, any damages for lost profits, stolen goods, or
claims by any other party caused by defective products or otherwise arising
from the incorrect or otherwise improper installation or use of this product.
This warranty applies only to defects in parts and workmanship relating to
normal use. It does not cover damage arising from improper maintenance or
negligence, damage caused by fire, flood, wind or lightning, vandalism, fair
wear and tear.
Inim Electronics S.r.l. shall, at its option, repair or replace any defective
products. Improper use, that is, use for purposes other than those mentioned
in this manual will void the warranty. Contact Our authorized dealer, or visit
our website for further information regarding this warranty.
Limited warranty
Inim Electronics S.r.l. shall not be liable to the purchaser or any other
person for damage arising from improper storage, handling or use of this
product.
Installation of this Product must be carried out by qualified persons
appointed by Inim Electronics. Installation of this Product must be carried
out in accordance with Our instructions in the product manual.
Copyright
The information contained in this document is the sole property of Inim
Electronics S.r.l.. Copying, reprinting or modification of this document, in
part or as a whole, is not permitted without prior authorization in writing
from Inim Electronics S.r.l.. All rights reserved.
WEEE
Informative notice regarding the disposal of electrical and electronic
equipment (applicable in countries with differentiated waste collection
systems)
The crossed-out bin symbol on the equipment or on its packaging indicates that
the product must be disposed of correctly at the end of its working life and
should never be disposed of together with general household waste. The user,
therefore, must take the equipment that has reached the end of its working
life to the appropriate civic amenities site designated to the differentiated
collection of electrical and electronic waste. As an alternative to the
autonomous-management of electrical and electronic waste, you can hand over
the equipment you wish to dispose of to a dealer when purchasing new equipment
of the same type. You are also entitled to convey for disposal small
electronic-waste products with dimensions of less than 25cm to the premises of
electronic retail outlets with sales areas of at least 400m2, free of charge
and without any obligation to buy.
Appropriate differentiated waste collection for the subsequent recycling of
the discarded equipment, its treatment and its environmentally compatible
disposal helps to avoid possible negative effects on the environment and on
health and favours the re-use and/or recycling of the materials it is made of.
Information about disposal of batteries and accumulators (applicable in
Countries with separate collection systems)
This marking on batteries and/or their manual and/or their packaging,
indicates that batteries of this products, at the end of their working life,
should not be disposed of as unsorted municipal waste, but must be object of a
separate collection. Where marked, the chemical symbols Hg, Cd o Pb indicate
that the battery contains mercury, cadmium or lead above the reference levels
of the directive 2006/66/EC. If batteries are not properly disposed of, these
substances, together with other ones contained, can cause harm to human health
and to the environment. To protect human health and the environment, to
facilitate treatment and recycling of materials, separate batteries from other
kind of waste and use the collection scheme stated in your area, in accordance
to current laws. Before disposing of the above, it’s appropriate to remove
them from their holders avoiding to damage them or causing short circuits.
Download
Inim Electronics S.r.l.
ISO 9001 Quality Management certified by BSI with certificate number FM530352
Centobuchi, via Dei Lavoratori 10
63076 Monteprandone (AP), Italy
Tel. +39 0735 705007 Fax +39 0735 704912
info@inim.it www.inim.it
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>