comat RELECO MRS13R Overcurrent Protection Relay Instruction Manual

August 15, 2024
comat RELECO

comat RELECO MRS13R Overcurrent Protection Relay

Product Information

Specifications:

  • Nominal Voltage: 12 – 48 V AC / DC
  • Operating Voltage Range: 10 – 60 V AC / DC
  • Power Consumption AC / DC: 3.2 VA / 1.6 W
  • Power Supply Frequency Range: 0; 16 – 63 Hz
  • Overcurrent Threshold / Saturation Current Threshold: -5 – 5 A
  • Measuring Current Range: -5 – 5 A
  • Short Saturation Current: 50 A for 20 s
  • Minimum Overcurrent Time for Detection: 4.5 ms
  • Minimum Saturation Current Duration for Detection: 3.1 ms
  • Number of Contacts: 1 NO + 1 NC forcibly guided contacts, compliant with IEC 61810-3
  • Rated Voltage (Main Circuit): 240 V AC
  • Rated Current (Main Circuit): 6 A
  • Operating Temperature: 10% – 95%
  • Ingress Protection: IP 20

Product Usage Instructions

Installation:

  1. Ensure the power source voltage is within the specified range of 12 – 48 V AC/DC.
  2. Mount the device in a suitable location following the installation guidelines provided in the manual.

Configuration:

  1. Connect the necessary cables according to the wiring diagram provided.
  2. Adjust any settings or thresholds as required using the configuration interface.

Operation:

  1. Power on the device and monitor the readings on the display or connected interface.
  2. Ensure that the device is functioning within the specified parameters during operation.

Maintenance:

  1. Regularly check for any signs of damage or wear on the device.
  2. Clean the device using a soft, dry cloth to prevent dust buildup.

FAQ:

  • Q: What should I do if the device shows an error code?
    A: Refer to the user manual for troubleshooting steps related to the specific error code displayed.

  • Q: Can I adjust the overcurrent threshold settings?
    A: Yes, you can adjust the overcurrent threshold and other settings through the configuration menu.

  • Q: Is it safe to operate the device in high humidity conditions?
    A: The device is rated for operation in relative humidity conditions of 10% to 95%, ensuring safe use within this range.

Safety instructions

  • WARNING: Read the enclosed instructions carefully before use! Disregarding the instructions may result in damage to equipment and/or serious personal injury.
  • WARNING: The device may only be installed by qualified personnel familiar with the national and international laws, directives and standards that apply to this region.
  • WARNING: This device is not suitable for use in wet areas, or explosive atmospheres (e.g. in areas where the air contains high concentrations of flammable chemicals, vapours or particles such as grain, dust or metal powder).
  • WARNING: Only mount and unmount the device when it is disconnected from the power supply. This applies to the power supply as well as to all inputs and outputs.
  • WARNING: During operation, the electrical connection points of the device carry hazardous voltages! These connection points must not be touched.

Technical Data

Nominal voltage 12 … 48 V AC / DC
Operating voltage range 10 … 60 V AC / DC
Power consumption AC / DC 3.2 VA / 1.6 W
Power supply frequency range 0; 16 … 63 Hz
Overcurrent   threshold/saturation current threshold Ith / Imax
Measuring current range -5 … 5 A
short saturation current 50 A during 20 s
Minimum overcurrent time for detection 4.5 ms
Minimal saturation current duration for detection 3.1 ms
Number of contacts 1 NO + 1 NC forcibly guided, complies with IEC

61810-3
Rated voltage (main circuit)| 240 V AC
Rated current (main circuit)| 6 A
Operating temperature| -40 … 70 ˚C ( Display -20 … 70 ˚C)
Relative humidity, no condensation| 10 – 95 %
Ingress protection| IP 20

Wiring diagrams

A1 / A2 Appliance power
DI1 / DI2 Dia- gnosis input
I+ / I– Current measurement input
11 / 12 Relay
23 / 24 Relay

Functionality

t D1 Overcurrent detection time 4.5 ms
t D2 Saturation current detection time 3.1 ms
t μC Controller processing time 1.3 ms
t Don Switch-on delay configurable
t Doff Switch-off delay configurable
t Op Relay operation time 15 ms
t Rel Relay release time 3 ms
t B NO Relay bouncing time NO contact 2 ms
t B NC Relay bouncing time NC contact 15 ms

Switching state

Menu navigation

  • Increase value / Go to next menu point
  • Decrease value / Go to the previous menu point
    OK Confirm and save value / Select menu point
    OK (long hold) Cancel without saving / Back to the previous menu
    If no key is activated during 20 s, the device returns to the default state without saving the last parameter.

Factory setting includes default parameters:

  • Monitoring: ON
  • Current threshold device Ith: 3 A
  • Current threshold load Ith: 1200 A
  • Hysteresis: 5.0 %
  • On delay tON: 0.0 s
  • Off delay tOFF: 3.0 s

Switching state indicator

Power supply| Load current IL| Diagnostic Input| LED| Relay  | Switching state NC contact| Switching state NO contact
---|---|---|---|---|---|---
Off| Any| Any| does not light up| Off| Closed| Open
On| IL ≤ Ith| 0| does not light up| Off| Closed| Open
On| IL > Ith| 0| lights permanently| On| Open| Closed
On| IL ≤ Ith| 1| lights permanently| On| Open| Closed
On| IL > Ith| 1| lights permanently| On| Open| Closed
On| IL ≤ Ith ➞ IL > Ith| 0| flashes briefly| Off

On

| Closed

Open

| Open

Closed

On| IL > Ith ➞ IL ≤ Ith| 0| flashes briefly | On

Off

| Open

Closed

| Closed

Open

You can find detailed information at www.comatreleco.com in the download area.