INSTALLATION WARNINGS
- “THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND HAZARDS INVOLVED.”
- “WARNING – Risk of fire or electric shock. LED Retrofit kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.”
- “WARNING – Risk of fire or electric shock. Install this kit only in the luminaires that has the construction features and dimensions shown in the photographs and/or drawings and where the input rating of the retrofit kit does not exceed the input rating of the luminaire.”
- “WARNING – To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.”
- “WARNING –Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of LED retrofit kit. Check for enclosed wiring and components.”
- “CAUTION – RISK OF FIRE. CONSULT A QUALIFIED ELECTRICIAN TO ENSURE CORRECT BRANCH CIRCUIT CONDUCTOR.”
- “THE RETROFIT KIT IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION SHALL BE DETERMINED BY THE AUTHORITIES HAVING JURISDICTION.”
- Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation
ORIGINAL LUMINAIRE DIMENSIONS
Original Luminaire
(Lithonia: GT8 1’X4’)
Minimum Luminaire Dimensions
Dimensions are inches (centimeters)
- Remove all the original luminaire parts, hardware, lamp, and ballast in order to begin the retrofit.
- Original luminaire diffuser and original ground wire will need to be kept for this retrofit.
- This Kit can be retrofitted into any luminaire with a similar length/height width greater than or equal to the Minimum Luminaire Dimensions described above.
RETROFIT KIT COMPONENTS
Retrofit kit components will be provided as listed below:
LED Modules
LED Diffuser Lens (Optional)
LED Diffuser End Caps (Optional)
LED Driver
LED Harness
Mounting Hardware
Retrofit Warning Label
RECOMMENDED TOOLS (Not Included)
Power Drill W/ Philips Bit
RETROFIT KIT DESCRIPTION
ITEM | DESCRIPTION | QTY |
---|
A.
| LED Modules| 2
B.
| LED Driver(Varies by model)| 1
C.
| LED Harness: TLC-HN02| 1
D.
| 6-20 X 3/8” Pan Head Self Drilling Screws| 14
E.
| Retrofit Warning Label| 1
F.
| LED Module Lens: TLE-OPT-120-013 (Optional)| 2
G.
| LED Module Lens End Cap: TLE-OPT-120-020 (Optional)| 4
H.
| Name Place Label| 1
Note: Item quantity will vary based on retrofit kit model purchased. Please refer to retrofit kit spec sheet for more details.
ORIGINAL LUMINAIRE DISASSEMBLY
-
Start by removing the Lens from the luminaire. See Picture #1.
-
Remove the lamps and the ballast/driver channel cover from the luminaire. See Picture #2.
-
Remove the original ballast and lamp sockets from the luminaire. See Picture #3.
-
The original ground wire and ballast/driver channel cover will need to be kept for this retrofit.
-
Luminaire should look like Picture #3 in order to begin the retrofit.
RETROFIT KIT ASSEMBLY
-
Start by Placing the LED Modules (A) onto the luminaire as shown on Figure 1.
Note: If kit includes LED Module Lens (F) install the LED Module Lens (F) before placing the LED Module onto the Luminaire. -
Secure the LED Modules to the luminaire using the provided 6-20 x3/8” Pan Head Self Drilling Screws (D). See Figure 1.
-
Affix the Retrofit Warning Label (E) in the area where it can be visible during the LED Driver installation. See Figure 2.
-
Place the LED Driver (B) on the location shown on Figure 2.
-
Secure the LED Driver (B) to the luminaire using the original screw. If the original screw is not available, use provided 6-20 x 3/8” Pan Head Self Drilling Screws (D). See Figure 2.
-
Wire the LED driver output wires to LED module input connectors using the provided LED Harness (C). See Figure 3.
-
Wire the LED driver input wires to the power source. See Figure 3 and refer to the “Connecting Power To The Retrofit Kit” section of Page 7 for appropriate wiring instructions.
RETROFIT KIT ASSEMBLY -
Place the provided Name Plate Label (H) on the luminaire in a readily visible location to anyone attempting to service the luminaire. See Figure 4-A.
-
Replace the ballast/driver channel cover and luminaire lens. See Figure 4-A and Figure 5.
Note: if kit included Module Lens then the completed retrofit should look like Figure 4- B and Figure 5. -
Completed retrofit should look like Figure 5.
Connecting Power to the Retrofit Kit:
- Connect the green wire (Ground) from the luminaire to the Ground that is being fed by the power source. Connect these two wires by using a wire connector with a minimum 18AWG rating.
- Connect the white wire (Neutral) from the LED Driver to the Neutral being fed by the power source. Connect these two wires by using a wire connector with a minimum 18AWG rating.
- Connect the black wire (Line) from LED Driver to the Line being fed by the power source. Connect these two wires by using a wire connector with a minimum 18AWG rating.