HAYWARD AquaRite Plus Salt Chlorinator Owner’s Manual
- August 9, 2024
- Hayward
Table of Contents
AquaRite Plus Salt Chlorinator
“`html
Specifications:
-
Product Name: AquaRite +
-
Model: AquaRite + Rev. E
-
Intended Use: Control system for swimming pools in accordance
with safety standards -
Power Supply: Must be powered via an isolating transformer or a
residual current device (RCD) with a nominal operating residual
current not exceeding 30 mA -
Compatibility: Used in conjunction with a salt chlorinator for
treating swimming pools
Product Usage Instructions:
Safety Precautions:
Ensure compliance with electrical safety standards and
guidelines for installation.
Keep the device away from openings and moving parts to prevent
accidents.
Wear personal protective equipment when servicing the
device.
Installation:
- Ensure the product is installed in a well-ventilated area.
- Connect the device to the mains using a wall socket.
- Consult a qualified installer for proper installation if
needed.
Operation:
The AquaRite + allows control of the filtration system, pump,
heat pump, lighting, etc.
Consult a professional for installation advice when using
natural stone around the pool.
Avoid using dry acid to adjust pH as it may damage the
chlorinator.
FAQ:
Q: Can I use dry acid to adjust the pH of the pool water?
A: It is not recommended to use dry acid such as sodium
bisulfate as it can damage the chlorinator, especially in arid
regions with significant evaporation.
Q: What should I do if the power cord is damaged?
A: A damaged power cord must be replaced by after-sales service
or qualified personnel to avoid danger.
“`
AquaRite +
OWNER’S MANUAL PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE
HAYWARD POOL EUROPE – 1070 Allée des Chênes – CS 20054 Saint Vulbas – 01154
Lagnieu Cedex – France
WARNING: Electrical hazard.
··
Failure to comply with these instructions can result in serious injuries or death.
THE EQUIPMENT IS INTENDED TO BE USED ONLY IN
SWIMMING POOLS
· WARNING Disconnect the equipment from the mains supply before any intervention.
· WARNING All electrical connections must be carried out by a qualified
approved electrician
in accordance with the standards currently in force in the country of
installation.
F NF C 15-100 D DIN VDE 0100-702 A ÖVE 8001-4-702 E UNE 20460-7-702 1993, REBT ITC-BT-31 2002 IRL IS HD 384-7-702 I CEI 64-8/7 LUX 384-7.702 S2 NL NEN 1010-7-702 P RSIUEE
GB EW H M PL CZ SK SLO TR
BS7671:1992 SIST HD 384-7-702.S2 MSZ 2364-702:1994 / MSZ 10-533 1/1990 MSA HD 384-7-702.S2 TS IEC 60364-7-702 CSN 33 2000 7-702 STN 33 2000-7-702 SIST HD 384-7-702.S2 TS IEC 60364-7-702
· WARNING Check that the device is plugged into a power outlet that is
protected against
short-circuits. The device must also be powered via an isolating transformer
or a residual current device (RCD) with a nominal operating residual current
not exceeding 30 mA.
· WARNING Ensure that children cannot play with the device. Keep your hands
and any foreign
object away from openings and moving parts.
· WARNING Check that the supply voltage required by the product corresponds
to the voltage
of the distribution network and that the power supply cables are suitable for
the product power supply.
· WARNING Chemicals can cause internal and external burns. To avoid death,
serious injury
and/or damage to equipment, wear personal protective equipment (gloves,
goggles, mask, etc.) when servicing or maintaining this device. This device
must be installed in an adequately ventilated place.
· WARNING To reduce the risk of electric shock, do not use an extension
cable to connect the
device to the mains. Use a wall socket.
· WARNING Carefully read the instructions that appear in this
and on the device. Failure to comply with the instructions can cause This
document must be given to every pool user, who should keep it in a safe place.
manual injuries.
· WARNING The appliance can be used by children aged from 8 years and above
and persons
with reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
· WARNING Use only original Hayward parts.
· WARNING If the power supply cable is damaged, it must be replaced by the
manufacturer, the
after-sales service or similarly qualified persons to avoid danger.
· WARNING The device must not be used if the power cord is damaged. An
electric shock
could occur. A damaged power cord must be replaced by the after-sales service
or similarly qualified persons to avoid danger.
USE ONLY GENUINE REPLACEMENT PARTS
Page 2 of 22
AquaRite +
Rev. E
REGISTRATION
Thank you for choosing Hayward. This manual contains important information
regarding the operation and maintenance of your product. Please retain it for
reference.
TO REGISTER YOUR PRODUCT IN OUR DATABASE, GO TO:
www.hayward.fr/en/services/register-your-product
———————————————————————————————————————————————————————————————
For Your Records
Record the following information for your convenience: 1) Purchase
Date 2) Complete Name
____ 3) Address
__ 4) Zip
code__ 5) Email
Address__ 6) Part
number__Serial number__ 7) Pool
Dealer____ 8)
Address__ 9) Zip
code____Country____
Note
———————————————————————————————————————————————————————————————-
Page 3 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
GENERAL
The AquaRite + is a system that controls the equipment and it is used in
conjunction with a salt chlorinator for treating swimming pools.
The AquaRite + allows you to control the filtration system (pump) as well as
the peripheral equipment (heat pump, lighting, etc.).
It can also be used to treat your pool effectively by salt water electrolysis.
For the chlorinator to function, it requires a low concentration of salt
(sodium chloride) in the pool water. The AquaRite + automatically disinfects
your pool by converting the salt into free chlorine which kills the bacteria
and algae in the pool. The chlorine reverts back to sodium chloride. This
continuous cycle means that there is no need to treat your pool manually. The
AquaRite + is suitable for treating most residential swimming pools. The
quantity of chlorine required to treat a swimming pool correctly varies
according to the number of bathers, the rainfall, water temperature and the
cleanliness of the pool…
NOTE: Before installing this product on the filtration system of a pool or spa
with an adjacent natural stone terrace or deck, consult a qualified installer
who will advise you on the type, installation, sealant (if any) and
maintenance of stone that can be laid around a saline pool.
NOTE: The use of dry acid such as sodium bisulfate to adjust the pH of the
swimming pool is not recommended, especially in arid regions where pool water
is subject to significant evaporation and is not commonly diluted with mains
water. Dry acid can cause a build-up of by-products that can damage your
chlorinator.
INSTALLATION
220 mm 300 mm
Øext 63 mm
Øint 63 mm
120 mm
170 mm 130 mm
Page 4 of 22
ELECTRONIC BOX
A Main connection 230 V – 50 Hz B Cell connection C Gas detector connection D
4 A Fuse E 4 A Fuse F pH and Rx connection G ON/OFF switch
CELL
A Electrolysis cell B Connection to unit C Cell housing D Flow/gas detector
(internal)
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Wall-mounted installation
Fix the box and the measuring chamber on the wall (optional). The box must be
installed in the equipment room (dry, temperate, ventilated). Caution, acid
vapours can cause irreversible damage to your device. Position the treatment
product tanks accordingly.
The AquaRite + must be fitted a minimum horizontal distance of 3.5 m (or more,
if required by local regulations) from the pool, within 1 m of a protected
outlet and within 4.5 m of the planned cell location. The box must be placed
vertically on a flat surface, with the cables downwards. As this box is also
used to evacuate heat (heat dissipation from internal components), it is
important that the four sides of the box remain unobstructed. Do not to
install the AquaRite + behind a panel or in an enclosed space.
Before installing the control unit in the intended location, check that the
power cord can reach the protected outlet and that the cell cable can reach
the intended cell location.
Disconnect the pool filtration pump before starting the installation. The
system must be installed in accordance with the standards currently in force
in the country of installation. The control box must be fitted a minimum
horizontal distance of 3.5 m (or more, if required by local regulations) from
the pool, within 1 m of a protected outlet and 4.5 m of the planned cell
location. Install and use the product at an altitude below 2000 m.
The flow switch must be installed on the return pipe directly in line with and
upstream of the cell and the treatment product injection point. Allow a 25 cm
straight section before the flow switch. A hole should previously have been
drilled in the pipe to allow the flow switch to pass through. Screw the flow
switch into the saddle clamp, taking care to seal with Teflon. Then install
the clamp on the pipe. The flow switch must be installed in the direction of
operation to ensure that it is tripped by the flow from the filtration pump.
The device used to inject the treatment products (acid, etc.) must be
installed last on the water return line, after any equipment (heater, cell,
etc.). A hole should previously have been drilled in the pipe to allow the
treatment product to pass through. Install the saddle clamp and screw the
injection valve into the saddle clamp using the adapter provided. Seal with
Teflon. Use the transparent PVC hose for suction (between the acid tank and
the peristaltic pump) and the semi-rigid white polyethylene tube for injection
(between the peristaltic pump and the injection valve).
All the metal components of the swimming pool can be connected to the same
earth as per local regulations
Page 5 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Including in the packaging
pH kit
Temperature probe
Unit installation Cell installation
A Filtration pump timer* B Silex / glass / diatom filter C Recirculation pump
1 Electronic box 2 Electrolysis cell (always vertical) 3 pH probe (optional) 4
Rx probe (optional) 5 Temperature probe (optional) 6 WiFi modul (optional) 7
Acid dosing pump (optional) 8 Acid injector (optional) 9 Sulphuric acid
container (not supplied)
1 – Install the cell in a vertical position. 2 – Install the cell on a by-
pass. 3 – Install the cell at the highest point of the installation. 4 –
Connect the cell and gas detector to the electronic box.
Page 6 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Electrical installation and wiring Connect the AquaRite + to a permanent power
outlet.
· This circuit must be protected by a residual current device (RCD) (residual
current: 30 mA max.).
Cover
FL1 Level
Temperature Probe
AA
BB
CC
DD
EE
110-230 V
FF
max. 3.15 A
GG
11 2 3 4 5 66 7 8 99 1100 1111 1122 1133 1144
HH
I JK
rreeddooXX
ppHH
NL
1
3
A1
2
4
A2
L N
1
3
A1
2
4
A2
L N
1
3
A1
pH
AUX 1 NL
1
3
A1
FILTER PUMP
2
4
A2
LIGHT
2
4
A2
AUX 2
L N
1
3
A1
2
4
A2
AUX 3
FS LP HP
22
TC
12V Controller
Variable speed pump
Remote screen option
Wifi module option
AUX 4
EnergyLine / Easy Temp / EcoPac / PowerLine
OUT3 OUT4 OUT5 AC-N
CN1
BRN BLU Y/G
CN2 12V NET GND
DI01
GND FS DI02
FS GND LP DI03 LP GND HP DI04
HP GND
DI05
GND
DI06
GND
OUT1 OUT2
3 4
3 4
CN19
CN6
+5V
GND
CN16
GND
AI06
AT
GND AI05 AT GND CT
AI04 CT GND OT
AI03 OT GND IT AI02 IT GND SUT AI01 SUT
5K
t
5K
t
5K
t
5K
t
5K
t
Description of outgoing relays
Name pH
Description Peristaltic acid pump 230 V
Aux1
Auxiliary voltage output 230 V
Aux2
Auxiliary voltage output 230 V
Filter Pump Filtration pump control
Light
Lighting control
Aux3
Auxiliary dry contact
Aux4
Auxiliary dry contact (or heating control).
Terminals 1 – 2 3 – 4 5 – 6 7 – 8 9 – 10
11 – 12 13 – 14
Type of output Imax Voltage output 1 A Voltage output 1 A Voltage output 1 A Dry contact Dry contact Dry contact Dry contact
If no heating system is installed on Aux4, it can be used as another auxiliary contact. To do this, contact Hayward technical support.
Page 8 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Connecting a heating system (Aux 4) The AquaRite + is compatible with all
types of pool heaters such as heat pumps, electric heaters or even heat
exchangers.
Connecting to a Hayward heating system fitted with a remote On/Off control
Connect a 2 x 0.75 mm² electric cable (not supplied) across terminals
(13)-(14) of auxiliary contact Aux 4, then connect it across the DI01 and GND
terminals on electronic circuit board PC1001 of the Hayward heat pump or any
other compatible equipment (see the installation instructions). Set the set
point of the heat pump or heating system to maximum. The AquaRite + will use
its own water temperature probe to control the heating set point. Compatible
equipment includes the seasonal Energyline Pro, the All Seasons Energyline
Pro, EasyTemp, EcoPac, PowerLine and other brands with a remote On/Off
control.
Connecting to a Hayward heating system not fitted with a remote On/Off control
In this case, the heating is controlled in series with the flow controller.
Connect a 2 x 0.75 mm² cable in series with the flow control system. Set the
heating system set point to maximum. The AquaRite + will use its own water
temperature probe to control the heating set point.
Connecting inputs:
Name FL1 Cover Level ION
°C / F°
Description Flow switch Closed cover detection Acid container level detection Not used Black wire Yellow wire Red wire
Connect the flow switch supplied to input terminals B and E.
Connecting the cell Connect the cell to the connector beneath the device (B
and C)
Terminals B – E A – E D – E G – H K J I
Type of input Dry contact Dry contact Dry contact
–
The different cells that can be connected to the device are as follows:
AquaRite + ref. AQR-PLUS-SV16ST RC16 AQR-PLUS-SV22ST RC22 AQR-PLUS-SV33ST RC33 AQR-PLUS-SV50ST RC50
Type of cell 16 A (8 V) 20 A (8 V) 16 A (10 V) 20 A (10 V)
Max. Wat. 120 W 160 W 180 W 220 W
Protection 16 A 16 A 16 A 16 A
Page 9 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Characteristics
Power supply Current consumption Power consumption Safety rating
Characteristics of pH and AUX1 relays Dimensions
230 V 50 Hz 0.9 A 200 W IPX4 Imax (pH+Aux1+Aux2) = 3,15A , Pmax (PH+Aux1+Aux2) = 725 W 270 x 220 x 150
Connecting the ORP option (Optional) Insert the ORP probe into the measuring chamber. Connect the BNC connector on the ORP probe to the redox BNC input on the AquaRite +. Remove the two screws from the bottom of the box and unclip the top of the cover to remove it. Fit the electronic card into the AquaRite + box.
ScreVwis
SVicsrew
Page 10 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Connecting a Hayward variable-speed pump with digital inputs
110-230 V
max. 3.15 A
78
1 23C
redoX
pH
L N
1
3
A1
2
4
A2
OFF AUTO
FILTER PUMP (VSTD)
When using a Hayward variable-speed pump fitted with digital inputs, bridge
the common black wire, connected to terminal (C), to terminal (7) and follow
the connection instructions given in the following table. You will have to
strip the digital cable back 15 cm and cut the orange wire.
Brown wire (BRN)
= V1 = 1500 rpm by default
Green wire (G) White wire (WHT) Red wire (R)
= V2 = 2400 rpm by default = V3 = 3000 rpm by default = DI4 = On/Off
Black wire (BLK)
= C = Common
Name V1 V2 V3 C DI4
Description Low pump speed (V1) Average pump speed (V2) High pump speed (V3) Common On/Off
Terminals 1 2 3
C – 7 8
Page 11 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Colour Brown (BRN)
Green (G) White (WHT) Black (BLK)
Red (R)
Rev. E
Assigning speeds Whatever the filtration mode (Manual, Automatic, Smart,
Heating or Intelligent), one of the three operating speeds (V1, V2 or V3) can
be selected, thus providing a high degree of flexibility for setting and
adjusting the water flow according to the equipment. The device will first
have to be configured to take the variable-speed pump into account (see the
section entitled “Setting the pump type”). The speed assigned to the
“antifreeze” mode is V2. Note: We should point out that the speed of all pool
devices requiring a minimum water flow that is appropriate to their correct
operation must be set manually before being stored in the memory and used by
the AquaRite + (heat pump, chlorinator, etc.). See the variable-speed pump
instructions for setting all the parameters related to its operation and
safety. Connecting the Wifi option (Optional) The Wifi module must be
installed in the equipment room (dry, temperate, ventilated) and located
within reach of the wireless network cover to which it will be connected.
Switch off the device before connecting the module. Plug the Wifi module
connector into the RF / WIFI connector on the AquaRite + card.
Installing the screen wall-mounting kit (not supplied) Remove the screen from
the box and unplug it. Plug the extension connector into the DISPLAY connector
on the AquaRite + card. Plug the other end of the extension into the screen
after first passing the cable through the wall bracket. Fit the cover
(supplied) over the front of the AquaRite + to replace the screen.
Page 11 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Preparing the pool water To prepare the pool water to enable the AquaRite + to
function, its chemical composition must be balanced and salt added. This must
be done BEFORE turning on the AquaRite +. Certain adjustments to the chemical
balance of the pool can take several hours. The procedure must therefore be
started well before the AquaRite + is turned on.
Adding salt: Add the salt several hours or, if possible, a day before turning
on the AquaRite +. Ensure that the recommended amount of salt is used. Measure
the salt content 6 to 8 hours after adding the salt to the swimming pool.
NOTE: If the water in the pool is not fresh and/or if it is liable to contain
dissolved metals, use a metal remover, according to the manufacturer’s
instructions. If your water has previously been treated with a product other
than chlorine (bromine, hydrogen peroxide, PHMB, etc.), neutralize this
product or replace all the water in the pool.
Salt concentration Use the following table to determine the quantity of salt
(in kg) needed to reach the recommended concentrations. Use the formulae below
if you do not know the volume of your swimming pool.
Rectangular Round Oval
m3
(pool dimensions, in m)
Length x width x Average depth
Diameter x Diameter x Average depth x 0.785
Length x width x Average depth x 0.893
The ideal salt concentration is between 2.7 and 3.4 g/l, with 3.2 g/l being
the optimum value. If the level is low, determine the volume (m3) of the pool
and add salt in accordance with the following table. A low salt level reduces
the efficiency of the AquaRite + and reduces chlorine production. A high salt
concentration can cause the AquaRite + to fail and make your pool water taste
salty. As the salt in your pool is constantly being recycled, the loss of salt
during the season is minimal. Salt is mainly lost when water has to be added
due to splashing, backwashing or draining (because of rain). Salt is not lost
through evaporation.
Type of salt to use Use only salt intended for chlorinators in conformance
with EN 16401. Use only sodium chloride (NaCl) that is more than 99% pure. Do
not use food-grade salt, iodized salt, salt containing yellow prussiate of
soda or salt containing anti-caking additives.
How to add or remove salt For new pools, let the plaster dry for ten to
fourteen days before adding salt. Start up the filtration pump, then add salt
directly into the intake side of the pool. Make the water circulate to speed
up the dissolution process. Do not allow salt to accumulate at the bottom of
the pool. Run the filtration pump for 24 hours, opening the main drain valve
fully to allow the salt to dissolve evenly throughout the pool.
The only way to lower the salt concentration is to partially empty the pool
and refill it with fresh water.
Always check the stabilizer (cyanuric acid) when checking the salt
concentration. The corresponding concentrations tend to decrease together.
Refer to the following table to determine the quantity of stabilizer to be
added to bring the concentration to 25 ppm. Add stabilizer only if necessary.
Do not add stabilizer to indoor pools.
Page 12 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Current salt
concentration in g/l
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 & +
30
97 91 85 79 73 67 61 55 48 42 36 30 24 18 12 6 Ideal OK Diluted
37.5
121 114 106 98 91 83 76 68 61 53 45 38 30 23 15
8 Ideal OK Diluted
45
145 136 127 118 109 100 91 82 73 64 55 45 36 27 18
9 Ideal OK Diluted
Quantity of salt (kg) required for 3.2 g/l
Volume of water in the pool in m³
52.5
60
67.5
75
82.5
90
97.5 105 112.5 120
170 159 148 138 127 117 106 95 85 74 64 53 42 32 21 11 Ideal OK Diluted
194 182 170 158 145 133 121 109 97 85 73 61 48 36 24 12 Ideal OK Diluted
218 205 191 177 164 150 136 123 109 95 82 68 55 41 27 14 Ideal OK Diluted
242 227 212 197 182 167 152 136 121 106 91 76 61 45 30 15 Ideal OK Diluted
267 250 233 217 200 183 167 150 133 117 100 83 67 50 33 17 Ideal OK Diluted
291 273 255 236 218 200 182 164 145 127 109 91 73 55 36 18 Ideal OK Diluted
315 295 276 256 236 217 197 177 158 138 118 98 79 59 39 20 Ideal OK Diluted
339 318 297 276 255 233 212 191 170 148 127 106 85 64 42 21 Ideal OK Diluted
364 341 318 297 273 250 227 205 182 159 136 114 91 68 45 23 Ideal OK Diluted
388 363 339 317 291 267 243 218 195 169 145 121 98 73 48 24 Ideal OK Diluted
127.5
412 385 360 337 310 283 258 232 207 180 154 129 104 77 51 26 Ideal OK Diluted
135 142.5
436 408 382 358 328 300 274 246 219 190 163 137 110 81 54 27 Ideal OK Diluted
460 430 403 378 346 317 289 259 231 201 172 144 117 86 57 29 Ideal OK Diluted
150
484 453 424 398 364 333 304 263 243 211 181 152 123 90 60 30 Ideal OK Diluted
Current salt concentra-
tion in g/l
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.5 1.6 1.8 2.5 & +
Quantity of salt (kg) required for 1.5 g/l (Low Salt )
Volume of water in the pool in m³
20
25
30
35
40
45
50
55
60
65
70
75
80
30 26 22 18 14 10 6 2 Ideal OK OK Diluted
37.5 32.5 27.5 22.5 17.5 12.5 7.5 2.5 Ideal OK OK Diluted
45 39 33 27 21 15 9 3 Ideal OK OK Diluted
52.5 45.5 38.5 31.5 24.5 17.5 10.5 3.5 Ideal OK OK Diluted
60 52 44 36 28 20 12 4 Ideal OK OK Diluted
67.5 58.5 49.5 40.5 31.5 22.5 13.5 4.5 Ideal OK OK Diluted
75 65 55 45 35 25 15 5 Ideal OK OK Diluted
82.5 71.5 60.5 49.5 38.5 27.5 16.5 5.5 Ideal OK OK Diluted
90 78 66 54 42 30 18 6 Ideal OK OK Diluted
97.5 84.5 71.5 58.5 45.5 32.5 19.5 6.5 Ideal OK OK Diluted
105 91 77 63 49 35 21 7 Ideal OK OK Diluted
112.5 97.5 82.5 67.5 52.5 37.5 22.5 7.5 Ideal OK OK Diluted
120 104 88 72 56 40 24
8 Ideal OK OK Diluted
85
127.5 110.5 93.5 76.5 59.5 42.5 25.5
8.5 Ideal OK OK Diluted
90
135 117 99 81 63 45 27
9 Ideal OK OK Diluted
Quantity of stabilizer (CYANURIC ACID in kg) required for 25 ppm
Current stabilizer
Volume of water in the pool in m³
concentra-
30
37.5
45
52.5
60
67.5
75
82.5
90
97.5 105 112.5 120 127.5 135 142.5 150
tion (ppm)
0 ppm
0.75 0.94 1.13 1.34 1.53 1.69 1.91 2.09 2.28 2.47 2.66 2.84 3.03 3.22 3.41 3.59 3.75
10 ppm
0.45 0.56 0.68 0.81 0.92 1.01 1.14 1.26 1.37 1.48 1.59 1.71 1.82 1.93 2.04 2.16 2.25
20 ppm
0.15 0.19 0.23 0.27 0.31 0.34 0.38 0.42 0.46 0.49 0.53 0.57 0.61 0.64 0.68 0.72 0.75
25 ppm
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Page 13 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Chemical water balance The water must be balanced manually BEFORE the device
is started up.
The following table summarizes the concentrations recommended by Hayward. Your
water should be checked regularly to maintain these concentrations and
minimize surface corrosion or deterioration.
CHEMISTRY Salt Salt (Low salt) Free chlorine pH
Cyanuric acid (Stabilizer)
Total alkalinity Water hardness Metals Saturation index
Recommended CONCENTRATIONS 3.2 g/l 1.5 g/l 1.0 to 3.0 ppm 7.2 to 7.6 20 to 30 ppm max. (Add stabilizer only if necessary) 0 ppm in indoor pool 80 to 120 ppm 200 to 300 ppm 0 ppm -0.2 to 0.2 (preferably 0)
Saturation index The saturation index (Si) gives us information about the calcium content and alkalinity of the water; it is a water balance indicator. Your water is correctly balanced if the Si is 0 ± 0.2. If the Si is below -0.2, the water is corrosive and the coating on the pool walls may be damaged. If the Si is above +0.2, stains may appear. Use the table below to determine the saturation index.
Si = pH + Ti + Ci + Ai – 12.1
°C °F Ti
Hardness (Calcium)
Ci
Total alkalinity
Ai
12 53 0.3 75 1.5 75 1.9
16 60 0.4
100 125
1.6 1.7
100 125
2.0 2.1
19 66 0.5 150 1.8 150 2.2
24 76 0.6
200 250
1.9 2.0
200 250
2.3 2.4
29 84 0.7 300 2.1 300 2.5
34 94 0.8
400 600
2.2 2.4
400 600
2.6 2.8
39 100 0.9 800 2.5 800 2.9
Use: Measure the pH of the pool water, the temperature, water hard-
ness and total alkalinity. Use the table above to determine Ti, Ci and
Ai in the formula shown above. If the Si is equal to 0.2 or more, stains
may appear. If the Si is equal to -0.2 or less, corrosion or deterioration
may occur.
– 0.2
0
0.2
CORROSION
STAIN
{
OK
· WARNING Chemicals can cause internal and external burns. To avoid death, serious injury and/or damage to equipment, wear personal protective equipment (gloves, goggles, mask, etc.) when servicing or maintaining this device. The treatment products must be installed and/or stored in an adequately ventilated place.
Page 14 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
OPERATION
The device is designed to be connected to a protected outlet at all times. The
AquaRite + must not be disconnected unless the pool equipment is undergoing
maintenance or the pool is to be closed (wintering).
Assuming that the chemical balance of the water is within the recommended
ranges, the device can be started up.
Configuration
Heater ON/OFF State of auxiliary relays (On/Off)
Time
Electrolysis Production intensity in gr/h
Automatic measuring pH / redox / salt
Filtration relay state
man Manual aut Automatic hea Heater smt Smart int Intelligent
Communication Red = Communication fault
12:30 1 2 3 4
25º
electrolysis
22 Pol 1 Cover gr/h Low
measures
7.2 pH 7.5 OFF 7.0 OFF
700 Rx 700 OFF mV FL1 TANK
3.2 Sal 15/01/16 g/l 25°C
man
man
off
off
Settings
1
2
3
OK
OK
Water temperature
Pol 1 Polarity 1 Pol 2 Polarity 2 Cover Production automatically reduced
to % selected (20% by default) — Wait time LOW Insufficient salt / cell scaled
up or to be replaced
Flow Filtration stopped or insufficient flow 7.5 Max. pH set point (Acid)
ON/OFF Peristaltic pump operation AL3 Maximum injection time reached ( Alarm
reset) 7.0 Min. pH set point (Base)
ON/OFF Liquid chlorine pump operation (option) FL 1 Insufficient flow 700
Redox set point TANK Empty acid tank detection
Lighting relay state man Manual aut Automatic
15/01/16 Date of the last salinity measurement 25°C Water temperature 3.2 Salt
concentration
3
4
5
OK
6
7
OK
8
9
OK
10
11
OK
12
OK
Page 15 of 22
13
3 Settings: preferred language.
11 Password: Protects access to the user menu by
5 Settings: date and time.
activating a password. To enter your password,
7 Settings: screen lighting intensity (0-100%) and
press a 5-key combination to be memorized by
screen timed On/Off programming.
the system.
9 Sound: Programming the sound transmission
13 System info : Information about the software
system for the following functions: Keyboard
version available on the TFT screen and the
(press a key), Pop-ups (urgent messages),
Power module. The system records the run-time
Alerts (operational alarm), Filtration (start of
count for the different modules and displays it on
filtration).
this screen.
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Setting the salt chlorination
6
7
8
9
10
OK
OK
6 Electrolysis: Electrolysis function programming. 7 Level: Chlorine production (gr/h) required.
Salt concentration
1
2
OK
8 Cover: Closed cover safety activation. Reduction: % of chlorine production
when the cover is closed (20% by default).
9 Boost (Super Chlorination): Filtration and continuous production of chlorine
for 24 hours (maximum production level). Automatic return to the filtration
and production mode programmed after the 24 hours.
Note: the device can only control the operation of the filtration pump if the pump is connected to the “Filter Pump” relay. 10 During the boost period, redox control (option) can be deactivated.
3
4
1 Salt concentration measurement.
2 Enter in the Salinity menu, use Enter to measure
the salt concentration for polarity 1, then for
polarity 2. This measurement can only be done
manually. It will have to be taken periodically.
3 Adjustment: Once the measurement has been
taken, you can adjust the salt level manually.
4 Display: Once the salt concentration has been
measured, it is displayed on the salt chlorination
screen and the main screen.
Setting the pH correction time
1
2
3
4
OK
+ –
5
5 Check that the “Delay” parameter is correctly set to 2 minutes (time delay
after which the peristaltic pump starts up prior to injection).
Set the “Interval” parameter from 0 to 240 minutes according to the size
of your pool and the flow rate of the peristaltic pump (default setting
60 minutes).
Caution: if the interval is too long, your pool may not be protected
against acid overdoses and your equipment may be irreversibly
damaged. Too short an interval may trip unwanted AL3 alarms.
1 Setting the pH correction time. The chemical parameters of the water must be
set manually before the device is started up. If these adjustments are not
made in advance, unwanted AL3 alarms may be tripped.
2 Enter the password: 3 Select the “Dos. pumps” menu. 4 Select the “Pump
times” menu.
Do not change the default values on the “Pump alarm AL3” and “Tank signal”
menus.
Page 16 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Filtration
1
OK
5
+ –
2
- –
6 -
–
3
7
+ –
4
1 Filtration modes.
2 Manual: Allows the filtration process to be turned on
and off manually.
3 Filter cleaning: This mode is used to backwash the
filter.
4 Automatic: In this mode, filtration is turned on
according to the start and end times set in the time
slots. The time slots always operate on a daily basis.
5 Smart*: This mode is based on the automatic mode,
with its three filtration intervals, but the filtration times
are adjusted according to the temperature. This is
done by setting two temperature parameters: the
maximum temperature, above which the filtration
times will be determined by the time slots, and the
minimum temperature, below which filtration will be
reduced to five minutes, the minimum operation period.
Between these two temperatures, the filtration times
will be staggered linearly. The antifreeze mode can be
activated to turn the filtration on if the water temperature
falls below 2°C.
6 Heating : This mode acts in the same way as the automatic mode, but it can also operate via a relay that controls the temperature. The set point temperature is determined in this menu and the system operates with a hysteresis of one degree (for example: if the set point temperature is 23°C, the system will start up when the
temperature falls below 22°C and shut down only when it rises above 23°C).
Heating control OFF: The heating operates only during the filtration periods
configured.
Heating control ON: Keeps the filtration on after
the filtration period has expired if the temperature is below the set point temperature. When the setpoint temperature is reached, the filtration and heating stop and only resume when the next programming period begins.
7 Intelligent*: In this mode, the user has two operating parameters: Select the required water temperature and the minimum filtration time (minimum two hours and maximum 24 hours). The filtration will operate for at least ten minutes every two hours to check the temperature. The minimum filtration time selected is divided into twelve sections that are added to its ten minutes. Example 1: Over twelve hours, the time
Intelligent mode
10 min
is divided between the twelve times a day when the filtration starts up to
check the temperature. Example 2: (12 hours x 60 minutes) / 12 = 60 minutes
every two hours. This is the filtration and heating period every two hours. If
the programmed filtration period ends and the required temperature has not
been reached, the filtration and heating remain on until the required
temperature is reached. To minimize the
T°= 28ºC
number of hours during which filtration operates each day, this additional time will be deducted from the next filtration periods occurring during the rest of the day. (See the chart below).
0h 1h 2h 3h 4h 5h 6h 7h 8h 9h 10h 11h 12h 13h 14h 15h 16h 17h 18h 19h 20h 21h 22h 23h 24h Intelligent mode operation if the temperature is constant
28ºC
28ºC
28ºC
27ºC
27ºC
ON
OFF
10 min
0h 1h 2h 3h 4h 5h 6h 7h 8h 9h 10h 11h 12h 13h 14h 15h 16h 17h 18h 19h 20h 21h
22h 23h 24h
Page 17 of 22
Intelligent mode operation if the temperature varies
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Setting the pump type
1
2
OK
3
4
OK
5
6
OK
6
3 Enter the Service menu from the
6 Select the type of pump.
configuration menu. 4 Enter the password (contact Hayward’s
technical support for the code) 5 Enter the Pump type menu.
The default pump type is “standard” (single-speed). If you are using a
variable-speed pump,
select “Variable speed”.
In this case, one of the 3 speeds (V1,
V2, V3) can be assigned to the heating
and when the cover is closed.
1
2
3
OK
–
4
After connecting a variable speed pump, you can
assign a different speed individually to each filtration
period, as required.
V1: S, V2: M, V3: F
Filter cleaning: To clean the filter with a variablespeed pump, it is best to use the highest speed (V3).
5
6
7
–
–
–
Lighting
1
2
3
4
5
OK
OK
OK
OK
1 Lighting. 2 Manual mode (ON/OFF). 3 Automatic mode: Starts up according to
the
time slots used to set the lighting start and end times. The time slots can be
configured with the following frequencies: daily, every 2 days,
every 3 days, every 4 days, every 5 days, weekly, every 2 weeks, every 3 weeks, every 4 weeks. 4 LED light: If you are using a coloured LED light, go to the menu to configure it.
5 Colour selection: This menu allows you to change the colours manually and, according to the type of LED light, program the pulse length required to cycle through the colours and programs (by default, 0.5 s, maximum 10 s).
Page 18 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Auxiliary relays
1
OK
6
OK
Measures
1
OK
4
OK
2
3
4
5
–
–
–
1 Auxiliary relays. 6 2 A maximum of four additional auxiliary relays
(water features, fountains, garden lighting, etc.) can be controlled. This
menu displays and allows you to configure the relays that remain available on
your equipment. 3 Manual mode (ON/OFF). 4 Automatic mode: Starts up according
to the time slots used to set the start and end times. They can be configured
with the following frequencies: daily, every 2 days, every 3 days, every 4
days, every 5 days, weekly, every 2 weeks, every 3 weeks, every 4 weeks.
5 Timer mode: An operating time can be programmed in minutes. Each time you
press the front panel key associated with the relay, it will be activated for
the programmed time. This function is recommended for timing the operation of
spa blowers.
6 Relay name: It is possible to name the auxiliary relays individually
according to the associated functions. On the keyboard, use the up/down arrows
to move the cursor vertically and the +/- buttons to move the cursor
horizontally. To confirm, press OK.
2
OK
5
OK
3
1 Measures: Adjustment of set points
5 Calibration using buffer solutions
and measuring probes.
(liquids models pH7 / pH10 / neutral).
2 Set points for each measurement.
Follow the on-screen instructions
3 Setting the set points.
(fig. 6).
4 pH probe calibration: Recommended 7 Manual calibration: Allows you to set
once a month during the pool season.
the probes to 1 point (without buffer
solution) recommended only for
adjusting small deviations in readings.
6
7
8
OK
9
OK
14
Page 19 of 22
10
OK
11
12
13 8 Without removing the
OK
probe from the water, use
the + / – keys to adjust the
reading to your reference
value (photometer or other
measuring instrument).
15 9 Redox probe calibration:
recommended only for adjusting
Recommended every two months
small deviations in readings.
during the pool season.
13 Without removing the probe from the
10 Calibration with reference solution
water, use the + / – keys to adjust
465 mV. Follow the on-screen
the reading to your reference value
instructions (fig. 11).
(photometer or other measuring
12 Manual calibration: Allows you to set
instrument).
the probes to 1 point (without solution)
14 Temperature probe calibration: Allows you to set the probes to 1 point.
15 Without removing the probe from the water, use the + / – keys to adjust the
reading to your reference value (thermometer). The same conditions should
apply for measurements.
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
Setting the Wifi module (optional)
1
2
3
4
OK
OK
OK
5
6
OK
7
8 1 Internet: Once the module is
network via the keyboard. Use
change the network parameters
connected, switch on the device.
the up/down arrows to move
in this menu.
A Network menu appears in the
the cursor vertically and the
7 Status: Displays information
Settings menu.
+/- buttons to move the cursor
about your current connection.
2 Wifi: Select the Wifi menu to
horizontally. To confirm, press
8 Test connection: Checks
start an automatic search for
OK.
that your connection has been
available networks.
5 Configuration: If you want
established.
3 Choose the relevant available
to configure your connection
network.
manually or if automatic
4 Enter the password for this
configuration fails, you can
When the module is connected to the Wifi network and the two LEDs are on
continuously (steady), you can register at poolwatch.hayward.fr. Get your ID
Node (see below) and follow the registration process.
Once you have registered, you can monitor all your AquaRite + parameters
remotely with Hayward PoolWatch
9
10
11
12
OK
OK
OK
Setting the redox level (redox kit option)
The redox level tells you the oxidation potential, i.e. the disinfectant
capacity of the water. Setting the redox set point is the last step in setting
the AquaRite +. To find the optimum redox level for your pool, follow the
steps below: 1) Start up the pool filtration system (the salt in the pool must
be evenly dissolved). 2) Add chlorine to the swimming pool until it reaches 1
to 1.5 ppm. This level is achieved with (approximately 1 to 1.5 g/m3 of
water). The pH level must vary between 7.2 and 7.5. 3) After 30 min. Check
whether the level of free chlorine in the pool (manual DPD1 test kit) is
between 0.8 and 1.0 ppm. 4) Look at the redox value on the screen and enter it
as the redox set point. 5) The next day, check the free chlorine levels
(manual DPD1 test kit) and the redox level. Increase / reduce the setting, if
required. Remember to check all your water parameters at regular intervals
(2-3 months) (see table) and adjust the redox set point according to the steps
listed above.
Page 20 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
SERVICING
During the first 10-15 days, your system will require more attention: – Check
that the pH remains at the ideal level (7.2 to 7.4). – If the pH is
exceptionally unstable and uses a lot of acid, check the alkalinity (see
table). If the balance is highly unstable, contact your pool
installer/builder.
REMEMBER that the system needs a certain amount of time to adapt to your pool
and will require additional chemicals during the first 3-5 days.
The pool must be regularly maintained and the skimmer baskets emptied whenever
necessary. Also check that your filter is not clogged.
ADD WATER: It is preferable to add water via the skimmers so that it passes
through the cell before entering the pool. Remember to check the percentage of
salt after adding water.
DOSING PUMPS: Regularly check the acid level to ensure that the pump does not
run dry. The dosing pump must be checked and serviced at regular intervals.
Servicing the probes The probes must be clean and free from oil, chemical
deposits and contamination to function properly. As they are in continuous
contact with the water in the pool, the probes may need to be cleaned weekly
or monthly, depending on the number of bathers and other specific pool
characteristics. A slow response, more frequent pH calibration and
inconsistent readings indicate that the probes need to be cleaned. To clean
the probes, turn off the power to the AquaRite +. Unplug the probe connectors
from the control box, unscrew the probes and carefully remove them from the
chamber. Clean the probe bulb (white ring at the bottom of the body of the
probe) with a soft toothbrush and regular toothpaste. A household washing-up
liquid detergent may also be used to remove any oil. Rinse with fresh water,
replace the Teflon tape on the threads, and reinstall the probes. If the
probes continue to give inconsistent readings or require excessive calibration
after they have been cleaned, they should be replaced.
Servicing and cleaning the AquaRite + cell Turn off the main power supply to
the AquaRite + before removing the cell. Once it has been removed, examine the
inside of the cell for any traces of scale (whitish brittle or flaky deposits)
and debris stuck to the plates. If no deposits are visible, reinstall the
cell. If deposits are visible, try to remove them with a garden hose. If this
method is unsuccessful, use a plastic or wooden tool to remove deposits stuck
to plates (do not use a metal tool as this will damage their coating). A
build-up of deposits on the cell indicates an exceptionally high concentration
of calcium in the pool water. If you cannot find a solution to this situation,
you will have to clean the cell at regular intervals. The best way to avoid
this problem is to maintain the chemical composition of the water at the
recommended concentrations.
Acid washing: This should only be done in severe cases where flushing will not
remove most of the deposits. To acid wash, turn off the main power supply to
the AquaRite +. Remove the cell from the piping. In a clean plastic container,
make up a solution of water and acetic or phosphoric acid (such as that used
to remove scale from a coffee machine). ALWAYS ADD ACID TO WATER – NEVER ADD
WATER TO ACID. Be sure to wear rubber gloves and protective goggles for this
operation. The level of the solution in the container should just reach the
top of the cell, so that the wire harness compartment IS NOT under water. It
may be helpful to coil up the wire before submerging the cell. Allow the cell
to soak for a few minutes, then rinse it with a garden hose. If the deposits
are still visible, soak and rinse again. Put the cell back and examine it from
time to time.
Wintering The AquaRite + cell, the flow switch, probes and pool piping run the
risk of being damaged if the water freezes. In regions that experience long
periods of cold weather, be sure to drain all the water from the pump and
filter and from the supply and return pipes before winter. Do not remove the
control unit.
Probe storage The end of the probes must always be in contact with water or a
solution of KCl. If they are removed from the measuring chamber, they should
be stored in the plastic caps provided (filled with water). If the storage
caps have been mislaid, the probes should be stored separately in small glass
or plastic containers with their ends immersed in water. The probes must
always be in a frost-free environment.
Page 21 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
TROUBLESHOOTING GUIDE
No display Check that the On / Off switch is on. Check the connection cable
between the display and the control box. Check that the external 250 mA fuse
is not defective. Check the power supply: 210-230 V 50 Hz. If the problem
persists, contact your pool installer/builder.
Excessive chlorine Low electrolytic cell current. If your pool has an
automatic redox control system, check the redox setting. Check the redox probe
and calibrate, if necessary.
Electrolysis does not reach maximum intensity Check the concentration of salt
in the water. Check the condition of the cell (it may be dirty or covered in
scale). Clean the cell according to instructions. Check the flow switch and
clean if necessary. Check that the cell is not worn (contact your pool
installer/builder).
Cell scaled up in under a month Very hard water with high pH and total
alkalinity (balance and adjust the pH and total alkalinity of the water).
Check that the system automatically changes polarity (see display)
Impossible to attain a free chlorine level of 0.8 ppm Increase the filtration
time. Increase the chlorination production rate. Check the concentration of
salt in the water. Check the level of isocyanuric acid in the pool (see
table). Check that the reactive agents in your test kit are not out of date.
If the temperature or the number of users increases. If the pH is above 7.8,
it must be adjusted.
Alarm AL3: pH dosing pump stopped The maximum time allowed to attain the pH
set point has been reached. The pH acid dosing pump is stopped to avoid
overdosing and acidifying the water. Please carry out the following checks to
avoid equipment failure: Check that the can of liquid pH is not empty. Check
whether the pH read on the machine corresponds to the pH in the pool (use a pH
analysis kit). Otherwise, please calibrate the pH probe or replace it, if
necessary. Check that the pH pump is running normally. To delete this message
and reset the dosing, press the “Return” key.
Chlorinator display indicates LOW Water lacks conductivity. Check the water
balance and salinity. Check for scale on the cell. See “Electrolysis does not
reach maximum intensity”.
White flakes in the pool This occurs when the water is unbalanced and very
hard. Balance the water, check the cell and clean it, if necessary.
Chlorinator display indicates FLOW Check the flow switch cable.
Page 22 of 22
USE ONLY GENUINE REPLACEMENT PARTS AquaRite +
Rev. E
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>