victron energy M10 DC Busbars with Integrated Battery Monitor and Main Fuse Holder Owner’s Manual
- August 6, 2024
- victron energy
Table of Contents
victron energy M10 DC Busbars with Integrated Battery Monitor and Main
Fuse Holder
Product Usage Instructions
- Installation:
- Ensure the power supply voltage falls within the range of 9 – 70 Vdc.
- Connect the Lynx Shunt VE. Can to the appropriate system voltage of 12, 24, or 48V.
- Securely fasten the connections using M8 or M10 screws.
- Fuse Installation:
- Purchase a CNN fuse separately.
- Refer to the Fusing section in the Lynx Shunt VE. Can manual for detailed instructions on fuse installation.
- Connection to GX Device:
- Utilize the provided RJ45 VE. Can terminators when connecting to a GX device for communication.
- Ensure proper connection of the VE. Can cables.
FAQs
- Q: What is the purpose of the Lynx Shunt VE? Can?
- A: The Lynx Shunt VE. Can function as a busbar with integrated battery monitoring and a main fuse holder, serving as part of the Lynx Distribution system for efficient power management.
- Q: What is the recommended fuse type for the Lynx Shunt VE? Can?
- A: The Lynx Shunt VE. The can is designed to hold a CNN fuse. This fuse needs to be purchased separately for installation.
Busbar Integrated Battery Monitoring
- The Lynx Shunt VE.Can contain a positive and negative busbar, a battery monitor, and a fuse holder for the main system fuse. It is part of the Lynx Distribution system.
- The Lynx Distributor has a power LED.
- The Lynx Shunt VE.Can can communicate via VE. Can with a GX device.
- The Lynx Shunt VE. Can ship with two RJ45 VE. Can terminators, be used when connecting to a GX device?
- The Lynx Shunt VE. The can is designed to hold a CNN fuse. The fuse needs to be purchased separately. For more info see section Fusing in the Lynx Shunt VE. Can manual.
The Lynx Distribution System
- The Lynx Distribution System is a modular busbar system that incorporates DC connections, distribution, fusing, battery monitoring, and/or Lithium battery management.
- For more information also see the DC Distribution Systems product page.
The Lynx Distribution System consists of the following parts:
- Lynx Power In – A positive and negative busbar with 4 connections for batteries or DC equipment.
- Lynx Distributor – A positive and negative busbar with 4 fused connections for batteries or DC equipment together with fuse monitoring.
- Lynx Shunt VE. Can – A positive busbar with a space for a main system fuse and a negative busbar with a shunt for battery monitoring. It has VE. Can communication for monitoring and setup with a GX device.
- Lynx Smart BMS – For use together with Victron Energy Smart Lithium batteries. It contains a positive busbar with a contactor that is driven by a battery management system (BMS) and a negative busbar with a shunt for battery monitoring. It has Bluetooth communication for monitoring and setup via the VictronConnect App and VE. Can communication for monitoring with a GX device and the VRM portal.
Lynx Shunt VE.Can
Lynx Shunt VE.Can without cover
RJ45 VE. Can terminator
The Lynx modules: Lynx Power In, Lynx Distributor, Lynx Shunt VE.Can and Lynx Smart BMS
SPECIFICATION
Lynx Shunt VE.Can|
---|---
POWER
Supply voltage range| 9 – 70 Vdc
Supported system voltages| 12, 24 or 48V
Reverse polarity protection| No
Current rating| 1000Adc continuous
Power consumption| 60mA @ 12V
33mA @ 24V
20mA @ 48V
Potential free alarm contact| 3A, 30Vdc, 250Vac
CONNECTIONS
Busbar| M8 / M10
Fuse| M8
VE.Can| RJ45 and RJ45 terminator
Power supply connection to Lynx Distributor| RJ10 (an RJ10 cable ships with
each Lynx Distributor)
Temperature sensor| Screw terminal
Relay| Screw terminal
PHYSICAL
Enclosure material| ABS
Enclosure dimensions (h x w x d)| 190 x 180 x 80 mm
Unit weight| 1.4 kg
Busbar material| Tinned copper
Busbar dimensions (hxw)| 8 x 30 mm
ENVIRONMENTAL
Operating temperature range| -40°C to +60°
Storage temperature range| -40°C to +60°
Humidity| Max. 95% (non-condensing)
Protection class| IP22
System Example
System example – Lynx Shunt VE. Can, Lynx Power In, Lynx Distributor, and lead acid batteries
- This system contains the following components:
- Lynx Power In with 4 paralleled 12V lead acid batteries.
- Identical cable lengths for each battery.
- Lynx Shunt VE. Can with the main system fuse and battery monitor.
- Lynx Distributor with fused connections for inverter/charger(s), loads, and chargers. Note that additional modules can be added if more connections are needed.
- Cerbo GX (or other GX device) to read out the battery monitor data.
A system with Lynx Shunt VE.Can, lead acid batteries, a Lynx Shunt VE.Can and a Lynx Distributor