Amico RGB LED Illuminated Image Wall Fixture Installation Guide
- August 6, 2024
- Amico
Table of Contents
Amico RGB LED Illuminated Image Wall Fixture
Product Information
- Product: RGB LED Illuminated Image Wall Fixture
- MRI Compatible
- For dry locations only.
Product Usage Instructions
Installation
- Turn off the power supply.
- Create a rough opening in the intended mounting location. The rough opening should be 4 1/2 inches from the finished floor for a standard 4″ toe kick. Refer to Table 1 for the correct rough-in dimensions.
- Remove the removable frame assembly by lifting it up and off of the latch clips. Set the assembly aside in a safe place.
- Remove the Phillips head screws securing the mounting frame and secondary lens to the wall box. Ensure safety when removing these parts and set them aside safely.
Mounting
- Secure the luminaire to the intended mounting surface with screw or bolt-type fasteners through the 6 mounting holes located on the rear surface of the luminaire housing. Ensure screws do not penetrate the shielding material.
- If mounting through the sides of the luminaire housing is necessary, appropriately sized holes may be drilled through the side walls, and the luminaire housing may be secured to the mounting surface with screw or bolt-type fasteners. A minimum of 6 fasteners is recommended.
FAQ
Q: Can this product be installed in wet locations?
A: No, this product is designed for dry locations only.
Q: How far should insulation be kept away from this luminaire during installation?
A: Do not install insulation within 76 mm (3 inches) of any part of this luminaire.
Q: Is professional installation recommended for this product?
A: It is recommended to consult a professional for installation to ensure proper setup and safety.
Important Safety Instructions
When using electrical equipment, basic safety precautions should always be followed including the below:
Read And Follow All Safety Instructions
- Warning: This luminaire must be installed by the NEC or your local electrical code. If you are not familiar with these codes and requirements, consult a qualified electrician.
- Warning: This equipment is not for use in hazardous combustible atmospheres as defined by the National Electrical Code.
- Danger: Risk of shock – Disconnect power before installation.
- Do not install insulation within 76 mm (3 in) of any part of this luminaire.
- Dry locations only.
- Access behind the wall is required.
- Inherently protected.
- This luminaire must be mounted or supported independently of an outlet box.
Save These Instructions For Future Reference.
Installation
Table 1 – Dimensions
Part Number | Rough-in Dimensions | Cutout Dimensions |
---|---|---|
Width (inches) | Height (inches) | |
1-07-000013 | See Diagram 1 | 47″ |
1-07-000140 | See Diagram 1 | 47″ |
1-07-000141 | See Diagram 1 | 47″ |
1-07-000142 | See Diagram 1 | 47″ |
1-07-000143 | See Diagram 2 | 23″ |
1-07-000144 | See Diagram 2 | 23″ |
1-07-000145 | See Diagram 2 | 23″ |
1-07-000150 | See Diagram 2 | 23″ |
-
Step 1:
Turn off the power supply. -
Step 2:
Create a rough opening in the intended mounting location. The rough opening should be 4 1/2″ from the finished floor for a standard 4″ toe kick. Reference to the table determines the correct rough in Table 1. -
Step 3:
Remove the removable frame assembly by lifting it up and off of the 8 latch clips. Refer to Diagram 3. Set the assembly aside in a safe and clean place. -
Step 4:
Remove the 22 Phillips head screws securing the mounting frame and secondary lens to the wall box.- NOTE: Ensure safety when removing the mounting frame and secondary lens. Refer to Diagram 4. Set the mounting frame and secondary lens aside in a safe and clean place.
-
Step 5:
Secure the luminaire to the intended mounting surface with screw or bolt-type fasteners through the 6 mounting holes located on the rear surface of the luminaire housing. Screws should be sized to NOT penetrate the shielding material.- NOTE: If mounting through the sides of the luminaire housing is necessary, appropriately sized holes may be drilled through the side walls and the Luminaire housing may be secured to the intended mounting surface with screw or bolt-type fasteners. A minimum of 6 fasteners is recommended.
-
Step 6:
Remove the Junction box cover located within the mounting frame. -
Step 7:
Wire the luminaire per the Electrical Connections section. -
Step 8:
Replace the Junction box cover removed in Step 6. -
Step 9:
Replace the mounting frame and secondary lens removed in Step 4 ensuring all of the 22 screws are replaced. -
Step 10:
Replace the decorative lens assembly removed in Step 3. -
Step 11:
Turn on the power supply.
Electrical Connections
-
Step 1:
Using customer supplied UL Listed conduit, bring the minimum 12 Awg supply wire to the junction box located at the top of the luminaire housing -
Step 2:
Using 90°C minimum-rated wire connectors, terminate the supply wiring in the Junction Box.
RGB LED Illuminated Wall Fixture – Diagrams 5 and 6
- Connect + 12V supply lead to the Black lead.
- Connect – 208A Red supply lead to the Red negative lead.
- Connect – 209A Green supply lead to the Green negative lead.
- Connect – 210A Blue supply lead to the Blue negative lead.
Note:
If using the Linear RGB Controller, be sure to wire to a site-specific wiring
diagram for proper current balancing.
Directive 2012/19/EU (WEEE – Waste Electrical and Electronic Equipment):
Information for Users
This product complies with EU Directive 2012/19/EU. The crossed-out wheeled
bin symbol on the article means that at the end of its useful lifespan, this
product must not be disposed of with your other household or municipal waste.
This product has required the extraction and use of natural resources for its
production. It may contain hazardous substances that could impact health and
the environment if not properly disposed of. To avoid the dissemination of
those substances in our environment and to diminish the pressure on natural
resources, the user is responsible for delivering the appliance to an
appropriate collection facility at the end of its useful lifespan. The
separate collection and recycling of your waste equipment at the time of
disposal will help conserve natural resources and ensure that it is recycled
in a manner that protects human health and the environment. For more
information on available collection facilities contact your local waste
collection service or the place of purchase.
Amico Lights Corporation
- 122-B East Beaver Creek Road, Richmond Hill, ON L4B 1G6, Canada
- Website: www.amico.com.
- Toll Free Tel: 1.877.462.6426
- Toll Free Fax: 1.866.440.4986
- Tel: 905.764.0800
- Fax: 905.764.0862