Amico MD1U Cleanroom Universal Installation Guide
- August 6, 2024
- Amico
Table of Contents
Amico MD1U Cleanroom Universal
Product Information
The Amico Cleanroom Universal is designed for installation in hard-ceiling environments. It comes with swing-out support brackets and requires a ceiling cut-out for mounting.
Specifications:
- Brand: Amico
- Model: Cleanroom Universal
- Installation: Hard Ceiling Flange
Product Usage Instructions
Hard Ceiling Flange Installation:
- Disconnect electrical power intended for the luminaire.
- Locate and cut the required opening in the ceiling based on the provided dimensions.
- Install and secure the necessary support structure ensuring it aligns with the ceiling cut-out dimensions.
- Remove the lens and door assembly by unscrewing all twelve self-sealing screws from the luminaire.
- Insert the luminaire into the ceiling and extend the swing-out brackets above the support structure. Tighten all swing-out brackets securely.
- Make electrical connections to the power supply following safety precautions. Do not use a different power cord fitting than the one provided.
- Replace the ballast cover and install suitable lamps (not included).
- Reattach the lens and door assembly using the original self-sealing screws. Tighten to a maximum torque of 10 in-lbs.
- Ensure the door gasket forms a continuous seal with the ceiling surface before applying power.
FAQ:
Q: Can this product be used with a T-Bar ceiling?
A: No, this product is not compatible with T-Bar ceilings. It is specifically
designed for hard ceiling installations.
Introduction
- Installation should be completed by an individual familiar with the construction and operation of the luminaire.
- Installation of luminaire must be by nation and local building and electrical codes.
- Carefully read and follow all warnings and instructions before installing or servicing the luminaire.
- Instructions do not cover all details and all possible product configurations
- Do not restrict luminaire ventilation.
- Ensure the LED luminaire is not covered with material that will prevent convection or conduction cooling.
- Do not exceed the luminaire’s maximum ambient temperature.
- Ensure the LED luminaire has the correct polarity before installation.
- Based on maximum voltage restrictions for class 2 circuits in the Canadian Electrical Code, the output cannot be accessible. This product has accessible output terminals. This product complies with this requirement since the installation instruction requires installation in a Restricted Access Area.
Warnings
ELECTRIC SHOCK
- Disconnect or turn off the power before installing or servicing the luminaire.
- All electrical wiring is to be completed by a qualified licensed electrician according to local and National/Canadian Electrical Code.
- Ensure the supply voltage corresponds with the correct ballast/driver voltage.
- Avoid exposing wiring to metal edges and sharp objects.
- Ensure that the luminaire is properly grounded to prevent electric hazards.
FIRE
- Keep flammable and combustible materials away from the light source and/or lens.
- Use correctly rated supply conductors as indicated by product labeling.
BURN
- Allow the luminaire to cool before handling the luminaire.
- Use correctly rated supply conductors as indicated by product labeling.
PERSONAL INJURY
- Wear safety glasses and gloves when handling the luminaire to avoid physical injury.
- Avoid direct eye contact with the light source.
- Always support the weight of the luminaire. Use correctly rated supply conductors as indicated by product labeling.
Hard Ceiling Flange
- Use 1-5/8 Unistrut (not included) or equivalent support beams on all four sides above the opening edge. The support structure should be suitably rigid and secured to support the weight of the luminaire. (Minimum thickness of ceiling and framing is 1 1/2”, maximum is 2 3/4”).
- Only qualified electricians should make the electrical connections and should ensure that all Building and Safety code requirements are observed. CRU & MD1U when supplied with white + red or white + green LEDs, are to be separately switched externally. Also, they are NOT to be operated simultaneously.
NOTE:
The models requires an accurate cutout of the luminaire opening. It is
essential that the opening room side edge be flat to ensure the integrity of
the seal.
Mounting:
- Disconnect electrical power intended to be connected to the luminaire.
- Locate and cut the required opening in the ceiling.
- Install and secure the required support structure.
- Remove the lens and door assembly by removing all twelve self-sealing screws from the luminaire.
- Insert the luminaire into the ceiling then extend the swing-out brackets above the support structure.
- Tighten all swingout brackets to ensure a tight and continuous seal on the room side of the opening.
- Remove the cover and make the electrical connections to the power supply. Do not remove or use a different power
- cord fitting than the one supplied.
- Replace the cover and install suitable lamps (not supplied).
- Replace the lens and door assembly with the original self-sealing screws. Tighten to a maximum torque of 10 in-lbs.
- Ensure that the door gasket makes a continuous seal to the ceiling surface.
- Apply power.
Installation
Hard Ceiling Flange Installation
Recessed Grid (T-Bar)
- The fixture is designed for use with 1”/1 ½” T-bar grid systems with vertical grid T thickness of less than 1/4” with a maximum height of 1 ½”. Grid systems can be installed with standard 12, 24, or 48” centerline spacing of the grid.
- Fixture housing lays into the grid. Ensure four (4) swing arms are in the stowed position as shown. If securing the fixture to the superstructure with hanger wire (by others) loop wire through holes on the swing arm and attach the bracket. Position the door frame into the housing opening and start all screws by hand. Tighten all screws to seal the door frame to the fixture.
Ceiling Cut-out Dimensions
Size | Width | Length |
---|---|---|
1 x 2 | 10-7/8″ | 22-7/8″ |
1 x 3 | 10-7/8″ | 34-7/8″ |
1 x 4 | 10-7/8″ | 46-7/8″ |
2 x 2 | 22-7/8″ | 22-7/8″ |
2 x 4 | 22-7/8″ | 46-7/8″ |
SAF – Model – Not for use with T-Bar ceiling
- NOTE: The SAF model requires an accurate cutout of the luminaire opening. The opening room side edge must be flat +/- 1/32 inch to ensure the integrity of the seal.
- Use 1-5/8 Unistrut (not included) or equivalent support beams on all four sides above the opening edge. The support structure should be suitably rigid and secured to support the weight of the luminaire.
- Only qualified electricians should make the electrical connections and should ensure that all Building and Safety code requirements are observed.
Mounting:
- Disconnect electrical power intended to be connected to the luminaire.
- Locate and cut the required opening in the ceiling.
- Install and secure the required support structure.
- Remove the lens and door assembly by removing all twelve self-sealing screws from the luminaire.
- Insert the luminaire into the ceiling then extend the swing-out brackets above the support structure. Tighten all swing-out brackets to ensure a tight and continuous seal on the room side of the opening.
- Remove the ballast cover and make the electrical connections to the power supply. Do not remove or use a different power cord fitting than the one supplied.
- Replace the ballast cover and install suitable lamps (not supplied).
- Replace the lens and door assembly with the original self-sealing screws. Tighten to a maximum torque of 10 in-lbs. Ensure that the door gasket makes a continuous seal to the ceiling surface.
- Apply power.
SAF – Model – Not for use with T-Bar ceiling
Ceiling Cut-out Dimensions
Size | Width | Length |
---|---|---|
1 x 2 | 10-7/8″ | 22-7/8″ |
1 x 3 | 10-7/8″ | 34-7/8″ |
1 x 4 | 10-7/8″ | 46-7/8″ |
2 x 2 | 22-7/8″ | 22-7/8″ |
2 x 4 | 22-7/8″ | 46-7/8″ |
Amico Lights Corporation
- 122-B East Beaver Creek Road, Richmond Hill, ON L4B 1G6, Canada.
- Toll-Free Phone: 1.877.462.6426
- Toll Free Fax: 1.866.440.4986
- Tel: 905.764.0800
- Fax: 905.764.0862
- Email: alt-sales@amico.com.
- Website: www.amico.com.
References
Read User Manual Online (PDF format)