To optimize your energy efficiency, reduce costs and improve the performance of your electrical systems, the simultaneous power and energy loggers in the PEL 110 Series are ideal tools.
THE PEL 110 SERIES
PEL 112
3 voltage inputs, 3 current inputs. Compact and magnetized with no display,
this model supports negative temperatures and is suitable for use in cold
rooms (-20 °C).
PEL 113
4 voltage inputs, 4 current inputs. With a quadruple backlit digital display.
PEL 115
4 voltage inputs, 4 current inputs. The all-terrain model in an IP67 site-
proof casing.
THE MARKETS
From electricity generators through to consumers, the PEL power loggers are very simple to interface everywhere.
Renewable energies
photovoltaic, wind, hydroelectric, thermal and thermo-dynamic
Process industries
metallurgy, glassmaking, paper, chemicals, agri-food, etc. Building
construction and renovation housing, facilities, etc.
Public services/transport
monitoring where the consumption is occurring (lighting, roads, motorways,
tunnels, rail, etc.)
Datacenter
monitoring and analysis of consumption
APPLICATIONS
ENERGY AUDITS
- Voluntary (ISO 50001, etc.) or mandatory operation aiming to reduce energy consumption: buildings, housing, infrastructure, equipment, etc.
- Implementation of measurement campaigns focused on energy for comprehensive diagnosis of the electrical installation
- Identification of the causes of overconsumption by the equipment or overbilling
PREVENTIVE AND PREDICTIVE MAINTENANCE
- Industrial equipment monitoring
- Analysis of consumption due to the Air-conditioning, Ventilation and Heating systems
- Sizing of a power factor correction cabinet
- Redistribution of the loads on the electrical grid
- + Motor diagnostics: measurement of a motor’s speeds, efficiency and torque without using mechanical sensors.
OUTDOOR USE ON ELECTRICITY POLES
The PEL 115 is integrated in a rugged, waterproof casing ensuring IP67 ingress
protection.
Keep datacenters’ hyperconsumption under control with the PEL110 Series
The vast volume of data requiring constant management places a heavy load on the servers and cooling systems. Consumption monitoring is a key factor for preventing failures and overconsumption. This helps to control costs and make the datacenter more reliable.
MEASUREMENTS & FUNCTIONS
- RMS and DC measurements with 128 samples/cycle simultaneously on each phase
- AC and/or DC voltage measurements up to 1,000 V
- Current up to 10 kA AC, 5 kA DC (depending on the current sensor).
- Active, reactive (N,D,Qf) and apparent power values
- Active energy values
- Fundamental active power values (Pf), balanced active power values (P+) and unbalance active power (Punb)
- Motor measurements and characterization
- Self-powered via the phase
- Extensive measurement range by using voltage and current ratios
- Breakdown of energy losses
- The phase data: cos φ, tan Φ, power factor (PF)
- Crest factor
- THD calculation for currents and voltages
- DC, 50 Hz, 60 Hz and 400 Hz measurements (Naval, etc.)
- Recording of the measurements and calculation results on the SD card
- Automatic recognition of the type of sensor connected
PEL Transfer software
This application software can be used to set up the PEL 110s and process the
energies. A mathematical algorithm applied to the power measurement campaigns
automatically provides a breakdown of all the energy values, highlighting any
losses detected. Users have everything they need to rank the priorities of
their operations. Energy consumption reports can be generated very simply.
- Verification of the connections before starting to record
- Download of the measurements recorded in the PELs
- Display of the results of the various measurements and analyses
Android application
Use the Android application to view your PEL’s connection to the electrical network.
- Useful energy
- Unbalance active energy
- Harmonic active energy
- Non-active energy
- Reactive energy
- Distorting energy
- Apparent energy
NETWORK COMMUNICATION
The PELs are equipped with a wide range of wired and wireless communication possibilities. The free PEL Transfer software interface allows you to monitor the data on a PC in real time.
Ethernet
When possible, the PELs can be connected together via an Ethernet-type wired
link. The PEL Transfer software then takes control of all the instruments
connected. The Ethernet link can be used at the same time as Wifi connections.
WiFi
The PELs offer 2 Wifi operating modes. They can be connected to the company’s
IT network via a server. They can also be addressed directly by a PC or
smartphone.
IRD DataView® Synch
A secure server is provided so that you can view your data from anywhere in
the world.
USB
USB connections can be used to configure or download the data, as well as to
take control of an instrument whatever the circumstances.
ACCESSORIES
Current sensors compatible with the PEL models
Other accessories
- BB196 cables kit (x 5), IP67………………………………………………………….P01295479
- Mains power cable………………………………………………………………………………P01295174
- PEL mains adapter……………………………………………………………………………P01102204B
- Cables/clips kit (x4)……………………………………………………………………………P01295476
- Set of inserts/rings……………………………………………………………………………..P01102080
- 5 A adapter……………………………………………………………………………………………..P01101959
- DataView® Software………………………………………………………………………………..P01102095
- No. 23 Bag………………………………………………………………………………………………P01298078
- Pole mounting kit…………………………………………………………………………………..P01102146
TECHNICAL SPECIFICATIONS
Models | PEL 112 | PEL 113 | PEL 115 |
---|---|---|---|
Display | None | Quadruple digital display | |
Types of installations | Single-phase, split-phase, three-phase |
with or without neutral, and many other specific configurations
Number of channels| 3 voltage inputs, 3 current inputs (neutral
current calculated)| 4 voltage inputs, 4 current inputs
Measurements
Network frequencies| DC, 50 Hz, 60 Hz and 400 Hz
Voltage (measure-ment ranges)| 10.00 -1,000 Vac / 100.00 – 1,000
Vdc
Current (see previous page)| 5 mAac to 10 kAac / 50 mAdc to 5 kAdc
Calculated measurements
Ratio| Up to 650,000 V / up to 25,000 A
Power (P, P f , P + , P unb ,
Q f , N, D, S)| 10 W to 10 GW / 10 var to 10 Gvar /
10 VA to 10 GVA
Energy| Up to 4 EWh / 4 EVAh / 4 Evarh (E = 10 18)
Phase| cos φ, tan Φ, PF
Harmonics| THD
Additional functions
Phase order| Yes
Min / Max| Yes
Alarm| Yes
Mounting| Magnet| Hook (Opt.)
Recording
Acquisition rate / Aggregation period| 5 measurements/s
– 1 min to 60 min
Data storage| SD card, 8 GB (up to 32 GB on SD-HC card)
Communication| USB, Ethernet, Wifi (Access point and Hotspot), IRD
Server DataView® Synch
Power supply| 110 V – 250 V (+10 %, -15 %) at 50-60 Hz & 400 Hz|
Powered by the phase – 1,000 V AC/DC
Safety| IEC 61010 600 V CAT IV and 1000 V CAT III| IEC 61010 1000 V CAT
IV
Mechanical specifications
Dimensions| 256 x 125 x 37 mm without sensor| 245 x 270 x 180 mm without
sensor
Weight| 900 g| 950 g| <3400 g
Casing| IP54| IP67
Operating temperatures| -20°C to +50°C| 0°C to +50°C| -20°C to +50°C
STATE AT DELIVERY
A PEL 112 OR PEL 113 IS DELIVERED WITH:
1 carrying bag, 4 voltage cables, 4 crocodile clips, 1 set of inserts/ rings,
1 SD card, 1 SD Card-USB adapter, 1 USB cable, PEL TRANSFER PC software &
User’s Manual downloadable from our website, 1 Quick Start Guide.
A PEL 115 IS DELIVERED WITH:
1 bag for the accessories, 5 x IP67 voltage cables, 5 lockable crocodile
clips, 1 set of inserts/rings, 1 SD card, 1 SD Card-USB adapter, 1 USB cable,
PEL TRANSFER PC software & User’s Manual downloadable from our website, 1
Quick Start Guide.
REFERENCES TO ORDER:
- PEL 112 without current sensors ……………………………P01157156
- PEL 113 without current sensors ……………………………P01157157
- PEL113 with MA194-350 sensors and adapter……………….P01300003
- PEL 115 without current sensors ……………………………P01157169
INTERNATIONAL Chauvin Arnoux
12-16, rue Sarah Bernhardt
92600 Asnières-sur-Seine
Tél : +33 1 44 85 44 38
Fax : +33 1 46 27 95 59
export@chauvin-arnoux.fr
www.chauvin-arnoux.com
UNITED KINGDOM
Chauvin Arnoux LTD
Unit 1 Nelson Ct, Flagship Sq, Shaw
Cross Business Pk
Dewsbury, West Yorkshire – WF12 7TH
Tel : +44 1924 460 494
Fax : +44 1924 455 328
info@chauvin-arnoux.co.uk
www.chauvin-arnoux.com
MIDDLE EAST
Chauvin Arnoux Middle East
P.O. BOX 60-154
1241 2020 JAL EL DIB – LEBANON
Tel : +961 1 890 425
Fax : +961 1 890 424
camie@chauvin-arnoux.com
www.chauvin-arnoux.com
Documents / Resources
|
CHAUVIN ARNOUX PEL 110 Series Simultaneous Power and Energy
Loggers
[pdf] Owner's Manual
PEL 110 Series, PEL 110 Series Simultaneous Power and Energy Loggers,
Simultaneous Power and Energy Loggers, Power and Energy Loggers, Energy
Loggers, Loggers
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>