SmartGen SGMA800-3200A Series Dual Power Automatic Transfer Switch User Manual
- August 2, 2024
- SmartGen
Table of Contents
- SmartGen SGMA800-3200A Series Dual Power Automatic Transfer Switch
- FAQ
- OVERVIEW
- STRUCTURE AND CHARACTERISTICS
- OVERALL DIMENSIONS AND CATEGORY
- WIRINGS
- WORKING CONDITION
- WIRING CONNECTION DIAGRAM
- INSTALLATION AND DEBUGGING
- ORDERING MODEL
- CONTACT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SmartGen SGMA800-3200A Series Dual Power Automatic Transfer Switch
FAQ
- Q: What is the rated voltage of the SGMA800-3200A Series Dual Power Automatic Transfer Switch?
- A: The rated voltage of the switch is AC400V.
- Q: In which industries can the SGMA800-3200A Series Dual Power ATS be used?
- A: The switch can be used in various industries such as high-rise buildings, medical facilities, post and telecommunications, coal mines, ships, rail traffic, military, and fire facilities.
OVERVIEW
SGMA800~3200A series dual power ATS applies to the system which requires AC400V 50/60Hz below, rated working current 800A~3200A. Its structure is motor driven type, and there are three positions for the switch: normal (Ⅰ), spare (Ⅱ) and off (0). It can be used in the occasions where power failure is not allowed, such as high-rise buildings, medical heath, post and telecommunications, coal mine and ships, rail traffic, military and fire facilities.
This series products comply with the standard of GB GB/T 14048.11 ”Low-voltage switchgear and controlgear — part 6-1: Multiple function equipment —-Transfer switching equipment”.
STRUCTURE AND CHARACTERISTICS
SGMA800~3200A series dual power ATS adopts two-in and one-out structure, with electric key lock and mechanical padlock. Electric key lock: control the internal power supply of the switch, when the electric lock is open, the switch acts the automatic and remote operations; when the electric lock is closed, the switch only acts the manual operation. Mechanical padlock: during maintenance, pulling up the mechanical padlock to cut off the internal power supply of the switch, so the electric and manual operations of the switch will be disabled, which ensures the personal safety.
OVERALL DIMENSIONS AND CATEGORY
INSTRUCTION
SGMA800~3200A series dual power ATS can be divided into two types according to their shell frames: SGMA-1600A/4P, SGMA-3200A/4P, three-pole and four-pole switches can be provided by each type, which are suitable for both genset control and ATS control.
The rated current sequence of the switch includes: 800A, 1000A, 1600A, 2000A, 2500A, 3200A. The shapes of the switches are as follows:
Table 2 The Shapes of Switches
SGMA800A-1600A OVERALL DIMENSIONS AND TECHNICAL DATA
Table 3 SGMA800A-1600A Overall Dimensions
Model (SGMA)
| Dimensions
(mm)
| ATS Installation (mm)| Terminals (mm)
---|---|---|---
A| A1| B| B1| C| E| G| J| K| L| M| N| P| R| S| S1| T| U| V| φX| Y| Y1| Y2
800A/3P
| ****
785
| ****
520
| ****
352
| ****
250
| ****
390
| ****
326
| ****
360
| ****
496
| ****
220
| ****
11
| ****
115
| ****
84
| ****
120
| ****
60
| ****
64
| ****
88
| ****
8
| ****
250
| ****
56.5
| ****
13
| ****
109
| ****
254
| ****
254
800A/4P| 1080| 635| 352| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 60|
64| 88| 8| 250| 60.5| 13| 109| 254| 254
1000A/3P| 785| 520| 352| 250| 390| 326| 360| 496| 220| 11| 115| 84| 120| 60|
64| 88| 8| 250| 56.5| 13| 109| 254| 254
1000A/4P| 1080| 635| 352| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 60|
64| 88| 8| 250| 60.5| 13| 109| 254| 254
1250A/3P| 785| 520| 368| 250| 390| 326| 360| 496| 220| 11| 115| 84| 120| 80|
68| 100| 8| 250| 56.5| 13| 109| 254| 254
1250A/4P| 1080| 635| 368| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 80|
68| 100| 8| 250| 60.5| 13| 109| 254| 254
1600A/3P| 785| 520| 376| 250| 390| 326| 360| 496| 220| 11| 115| 84| 120| 80|
68| 108| 10| 250| 56.5| 13| 110| 255| 255
1600A/4P| 1080| 635| 376| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 80|
68| 108| 10| 250| 60.5| 13| 110| 255| 255
Table 4 SGMA800A-1600A Technical Parameter
Model| SGMA-800A/XP| SGMA-1000A/XP| SGMA-1250A/XP|
SGMA-1600A/XP
---|---|---|---|---
Poles(P)| 3P, 4P| 3P, 4P| 3P, 4P| 3P, 4P
Rated Current| 800A| 1000A| 1250A| 1600A
Rated
Working Volt.
| AC400V
Motor
Working Volt.
| AC220V (175-277)V
Rated Insul. Volt.
Main Circuit
| AC800V
Rated Impulse
Volt. Main Circuit
| 8 kV
Category| AC-33iB
Short-time Withstand
Current
| ****
32 kA/60ms
Rated SC Ability| 67.5 kA
Transfer Time
I-II or II-I
| 1.2s| 1.8s
Mechanical Life| 3000 times
Electrical Life| 500 times
Weight (4P)| 36kg| 36kg| 37kg| 38.6kg
SGMA2000A-3200A OVERALL DIMENSIONS AND TECHNICAL DATA
Table 5 SGMA2000A-3200A Overall Dimensions
Model (SGMA)| Dimensions(mm)| Switch Mounting (mm)|
Terminals (mm)
---|---|---|---
A| A1| B| G| J| R| S| T| V| Y1| Y2
2000A/3P| 785| 537| 423| 360| 496| 80| 81| 10| 56| 113| 121
2000A/4P| 1080| 651| 423| 540| 610| 80| 81| 10| 60| 113| 121
2500A/3P| 785| 537| 433| 360| 496| 80| 81| 15| 56| 118| 116
2500A/4P| 1080| 651| 433| 540| 610| 80| 81| 15| 60| 118| 116
3200A/3P| 785| 537| 443| 360| 496| 80| 81| 20| 56| 123| 111
3200A/4P| 1080| 651| 443| 540| 610| 80| 81| 20| 60| 123| 111
Table 6 SGMA2000A-3200A Technical Parameter
Model | SGMA-2000A/XP | SGMA-2500A/XP | SGMA-3200A/XP |
---|---|---|---|
Poles(P) | 3P, 4P | 3P, 4P | 3P, 4P |
Rated Current | 2000A | 2500A | 3200A |
Rated
Working Volt.
| AC400V
Motor
Working Volt.
| AC220V (175-277)V
Rated Insul. Volt.
Main Circuit
| AC800V
Rated Impulse
Volt. Main Circuit
| 8 kV
Category| AC-33iB
Short-time
Withstand Current
| 32 kA/60ms
Rated SC Ability| 67.5kA
Transfer Time
I-II or II-I
| 1.8s| 2.4s
Mechanical Life| 3000 times
Electrical Life| 500 times
Weight (4P)| 55kg| 61kg| 67kg
WIRINGS
Table 7 Terminals and Descriptions
No. | Function | Remark |
---|
Power Terminal
| ****
101
| ****
AC220V Power L Output
| 101 106 are only used as signal to control power supply. 101, 106 cannot be used to mix connected with any
external circuit.
102| I# L-phase LW Input| I# control power AC220V
103| I# N-phase NW Input
104| II# L-phase LW Input| II# control power AC220V
105| II# N-phase NW Input
106
| ****
AC220V Power N Output
| 101 106 are only used as signal to control power supply. 101, 106 cannot be used to mix connected with any
external circuit.
Control Terminal
| ****
201
| ****
Auto mode via short connection with 206
| The automatic mode is controlled by ATS, the normal power is preferred.
Normal power is on, spare power is on, ATS I# is power- on.
Normal power is off, spare power is on, ATS II# is power-on.
Normal power is on, ATS I# is power-on.
202| COM| Closed/Open control common port.
203| I# Normal Power Closed| Close I# by connection with 202.
204| Open| Open by connection with 202.
| 205| II# Spare Power Closed| Close II# by connection with 202.
---|---|---|---
206
| ****
Auto mode via short connection with 201
| The automatic mode is controlled by ATS, the normal power is preferred.
Normal power is on, spare power is on, ATS I# is power- on.
Normal power is off, spare power is on, ATS II# is power-on.
Normal power is on, ATS I# is power-on.
Indication Terminal
| ****
301
| ****
Gen Start Signal Output (NO)
| When detecting I# normal power is power-off, closed with
306. (Start/Stop delay cannot be set, start immediately and stop for 5s delay).
302| Closed/Open Indication
COM
| ****
Externally connect to AC220V power indicator to display the closed/open status.
303| I# Closed Indication
304| Open Indication
305| II# Closed Indication
306
| ****
Gen Start Signal Output (NO)
| When detecting I# normal power is power-off, closed with
301. (Start/Stop delay cannot be set, start immediately and stop for 5s delay).
Position Auxiliary Terminal
| 401| NC|
402| I# Closed Output (Volts free)| I# closed volts free feedback output, then
402, 403 are
closed.
403| I# Closed Output (Volts free)
404| II# Closed Output (Volts
free)
| ****
II# closed volts free feedback output, then 404, 405 are closed .
405| II# Closed Output (Volts
free)
406| NC| /
Key & Padlock Auxiliary Terminal
| 501| NC| /
502
| Remote Control/Manual Status Indication Output
(Volts free)
| ****
When the key is in Manual position, 502, 503 are closed. When the key is in Remote position, 502, 503 are disconnected.
503
| Remote Control/Manual Status Indication Output
(Volts free)
504| Padlock Indication Output
(Volts free)
| When the padlock is pulled up, 504 505 are closed (cut off the internal power of ATS, the ATS cannot act electric and manual operations, then the maintenance is available.
When the padlock is pulled down, 504 505 are
disconnected.
505
| ****
Padlock Indication Output ((Volts free)
506| NC| /
Table 8 Wiring Description
WORKING CONDITION
Table 9 Working Condition
Item | Requirements |
---|---|
Working Temperature | (-25~+70)ºC |
Working Humidity | (20~90)%RH |
Installation Height | ≤2000m |
Pollution Degree | 3-level |
WIRING CONNECTION DIAGRAM
GENSET CONTROLLER APPLICATION DIAGRAM
ATS CONTROLLER APPLICATION DIAGRAM
INSTALLATION AND DEBUGGING
The installation and debugging of ATS should be carried out by professionals and person who knows the switchgear, the related protections and preventive measures must be considered during operating. The wirings of main circuit must be in a way that the leads are not subjected to any pressure or force. Before installation and debugging, firstly check if the switch is damaged or has any harmful effects, meanwhile, check for loose wires may be caused in transportation; clean up the dirt, especially the dirt on the surface of insulation parts, which may be caused by package materials during transportation or storage.
When connecting the primary circuit, pay attention to the phase sequence of the two power supplies that should be consistent, while connecting the secondary circuit, it should be strictly in accordance with the wiring diagram listed on the user manual, at the same time, notice that the voltage level of power supply; switch must be well grounded during installation. Considering in personal safety and the quickness of transferring, the handle is only used for debugging, users should not use the handle to operate with load. During debugging, firstly use handle to operate, then perform the electrical operation by manual button if there is nothing abnormal, finally go to the formal running.
ORDERING MODEL
Table 10 Packing List
No. | Item | Qty. |
---|---|---|
4P | 3P | |
1 | ATS | 1 |
2 | Installation Instructions | 1 |
3 | Operating Handle | 1 |
4 | Electrical Key | 2 |
5 | Nut M12 | **** |
48
| ****
36
6| Spring Washer M12
7| Flat Washer M12
8
| 800A-1600A| Outer Hexagonal Flat Brain/1240 4.8
2000A| Outer Hexagonal Flat Brain/1245 4.8
2500A| Outer Hexagonal Flat Brain/1245 4.8
3000A| Outer Hexagonal Flat Brain/1260 4.8
CONTACT
SmartGen Registered trademark
- No. 28 Xuemei Street, Zhengzhou, Henan, China
- Tel: +86-371-67988888/67981888/67992951
- +86-371-67981000(overseas)
- Fax: +86-371-67992952
- Web: www.smartgen.com.cn
- Email: sales@smartgen.cn
All rights reserved. No part of this publication may be reproduced in any
material form (including photocopying or storing in any medium by electronic
means or other) without the written permission of the copyright holder.
SmartGen reserves the right to change the contents of this document without
prior notice.
Table 1 Software Version
Date | Version | Content |
---|---|---|
2024-03-07 | 1.0 | Original release. |