SmartGen SGMA800-3200A Series Dual Power Automatic Transfer Switch User Manual

August 2, 2024
SmartGen

SmartGen SGMA800-3200A Series Dual Power Automatic Transfer Switch

FAQ

  • Q: What is the rated voltage of the SGMA800-3200A Series Dual Power Automatic Transfer Switch?
    • A: The rated voltage of the switch is AC400V.
  • Q: In which industries can the SGMA800-3200A Series Dual Power ATS be used?
    • A: The switch can be used in various industries such as high-rise buildings, medical facilities, post and telecommunications, coal mines, ships, rail traffic, military, and fire facilities.

OVERVIEW

SGMA800~3200A series dual power ATS applies to the system which requires AC400V 50/60Hz below, rated working current 800A~3200A. Its structure is motor driven type, and there are three positions for the switch: normal (Ⅰ), spare (Ⅱ) and off (0). It can be used in the occasions where power failure is not allowed, such as high-rise buildings, medical heath, post and telecommunications, coal mine and ships, rail traffic, military and fire facilities.

This series products comply with the standard of GB GB/T 14048.11 ”Low-voltage switchgear and controlgear — part 6-1: Multiple function equipment —-Transfer switching equipment”.

STRUCTURE AND CHARACTERISTICS

SGMA800~3200A series dual power ATS adopts two-in and one-out structure, with electric key lock and mechanical padlock. Electric key lock: control the internal power supply of the switch, when the electric lock is open, the switch acts the automatic and remote operations; when the electric lock is closed, the switch only acts the manual operation. Mechanical padlock: during maintenance, pulling up the mechanical padlock to cut off the internal power supply of the switch, so the electric and manual operations of the switch will be disabled, which ensures the personal safety.

OVERALL DIMENSIONS AND CATEGORY

INSTRUCTION

SGMA800~3200A series dual power ATS can be divided into two types according to their shell frames: SGMA-1600A/4P, SGMA-3200A/4P, three-pole and four-pole switches can be provided by each type, which are suitable for both genset control and ATS control.

The rated current sequence of the switch includes: 800A, 1000A, 1600A, 2000A, 2500A, 3200A. The shapes of the switches are as follows:

Table 2 The Shapes of Switches

SGMA800A-1600A OVERALL DIMENSIONS AND TECHNICAL DATA

Table 3 SGMA800A-1600A Overall Dimensions


Model (SGMA)

| Dimensions

(mm)

| ATS Installation (mm)| Terminals (mm)
---|---|---|---
A| A1| B| B1| C| E| G| J| K| L| M| N| P| R| S| S1| T| U| V| φX| Y| Y1| Y2


800A/3P

| ****

785

| ****

520

| ****

352

| ****

250

| ****

390

| ****

326

| ****

360

| ****

496

| ****

220

| ****

11

| ****

115

| ****

84

| ****

120

| ****

60

| ****

64

| ****

88

| ****

8

| ****

250

| ****

56.5

| ****

13

| ****

109

| ****

254

| ****

254

800A/4P| 1080| 635| 352| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 60| 64| 88| 8| 250| 60.5| 13| 109| 254| 254
1000A/3P| 785| 520| 352| 250| 390| 326| 360| 496| 220| 11| 115| 84| 120| 60| 64| 88| 8| 250| 56.5| 13| 109| 254| 254
1000A/4P| 1080| 635| 352| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 60| 64| 88| 8| 250| 60.5| 13| 109| 254| 254
1250A/3P| 785| 520| 368| 250| 390| 326| 360| 496| 220| 11| 115| 84| 120| 80| 68| 100| 8| 250| 56.5| 13| 109| 254| 254
1250A/4P| 1080| 635| 368| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 80| 68| 100| 8| 250| 60.5| 13| 109| 254| 254
1600A/3P| 785| 520| 376| 250| 390| 326| 360| 496| 220| 11| 115| 84| 120| 80| 68| 108| 10| 250| 56.5| 13| 110| 255| 255
1600A/4P| 1080| 635| 376| 250| 390| 326| 540| 610| 220| 11| 115| 84| 120| 80| 68| 108| 10| 250| 60.5| 13| 110| 255| 255

Table 4  SGMA800A-1600A Technical Parameter

Model| SGMA-800A/XP| SGMA-1000A/XP| SGMA-1250A/XP| SGMA-1600A/XP
---|---|---|---|---
Poles(P)| 3P, 4P| 3P, 4P| 3P, 4P| 3P, 4P
Rated Current| 800A| 1000A| 1250A| 1600A
Rated

Working Volt.

| AC400V
Motor

Working Volt.

| AC220V (175-277)V
Rated Insul. Volt.

Main Circuit

| AC800V
Rated Impulse

Volt. Main Circuit

| 8 kV
Category| AC-33iB
Short-time Withstand

Current

| ****

32 kA/60ms

Rated SC Ability| 67.5 kA
Transfer Time

I-II or II-I

| 1.2s| 1.8s
Mechanical Life| 3000 times
Electrical Life| 500 times
Weight (4P)| 36kg| 36kg| 37kg| 38.6kg

SGMA2000A-3200A OVERALL DIMENSIONS AND TECHNICAL DATA

Table 5 SGMA2000A-3200A Overall Dimensions

Model (SGMA)| Dimensions(mm)| Switch Mounting (mm)| Terminals (mm)
---|---|---|---
A| A1| B| G| J| R| S| T| V| Y1| Y2
2000A/3P| 785| 537| 423| 360| 496| 80| 81| 10| 56| 113| 121
2000A/4P| 1080| 651| 423| 540| 610| 80| 81| 10| 60| 113| 121
2500A/3P| 785| 537| 433| 360| 496| 80| 81| 15| 56| 118| 116
2500A/4P| 1080| 651| 433| 540| 610| 80| 81| 15| 60| 118| 116
3200A/3P| 785| 537| 443| 360| 496| 80| 81| 20| 56| 123| 111
3200A/4P| 1080| 651| 443| 540| 610| 80| 81| 20| 60| 123| 111

Table 6 SGMA2000A-3200A Technical Parameter

Model SGMA-2000A/XP SGMA-2500A/XP SGMA-3200A/XP
Poles(P) 3P, 4P 3P, 4P 3P, 4P
Rated Current 2000A 2500A 3200A

Rated

Working Volt.

| AC400V
Motor

Working Volt.

| AC220V (175-277)V
Rated Insul. Volt.

Main Circuit

| AC800V
Rated Impulse

Volt. Main Circuit

| 8 kV
Category| AC-33iB
Short-time

Withstand Current

| 32 kA/60ms
Rated SC Ability| 67.5kA
Transfer Time

I-II or II-I

| 1.8s| 2.4s
Mechanical Life| 3000 times
Electrical Life| 500 times
Weight (4P)| 55kg| 61kg| 67kg

WIRINGS

Table 7 Terminals and Descriptions

No. Function Remark




Power Terminal

| ****

101

| ****

AC220V Power L Output

| 101 106 are only used as signal to control power supply. 101, 106 cannot be used to mix connected with any

external circuit.

102| I# L-phase LW Input| I# control power AC220V
103| I# N-phase NW Input
104| II# L-phase LW Input| II# control power AC220V
105| II# N-phase NW Input


106

| ****

AC220V Power N Output

| 101 106 are only used as signal to control power supply. 101, 106 cannot be used to mix connected with any

external circuit.





Control Terminal

| ****



201

| ****



Auto      mode     via      short connection with 206

| The automatic mode is controlled by ATS, the normal power is preferred.

Normal power is on, spare power is on, ATS I# is power- on.

Normal power is off, spare power is on, ATS II# is power-on.

Normal power is on, ATS I# is power-on.

202| COM| Closed/Open control common port.
203| I# Normal Power Closed| Close I# by connection with 202.
204| Open| Open by connection with 202.
| 205| II# Spare Power Closed| Close II# by connection with 202.
---|---|---|---




206

| ****



Auto      mode     via      short connection with 201

| The automatic mode is controlled by ATS, the normal power is preferred.

Normal power is on, spare power is on, ATS I# is power- on.

Normal power is off, spare power is on, ATS II# is power-on.

Normal power is on, ATS I# is power-on.






Indication Terminal

| ****

301

| ****

Gen Start Signal Output (NO)

| When detecting I# normal power is power-off, closed with

306. (Start/Stop delay cannot be set, start immediately and stop for 5s delay).

302| Closed/Open          Indication

COM

| ****


Externally connect to AC220V power indicator to display the closed/open status.

303| I# Closed Indication
304| Open Indication
305| II# Closed Indication


306

| ****

Gen Start Signal Output (NO)

| When detecting I# normal power is power-off, closed with

301. (Start/Stop delay cannot be set, start immediately and stop for 5s delay).




Position Auxiliary Terminal

| 401| NC|
402| I# Closed Output (Volts free)| I# closed volts free feedback output, then 402, 403 are

closed.

403| I# Closed Output (Volts free)
404| II#    Closed    Output   (Volts

free)

| ****

II# closed volts free feedback output, then 404, 405 are closed .

405| II#    Closed    Output   (Volts

free)

406| NC| /






Key & Padlock Auxiliary Terminal

| 501| NC| /


502

| Remote        Control/Manual Status     Indication    Output

(Volts free)

| ****

When the key is in Manual position, 502, 503 are closed. When the key is in Remote position, 502, 503 are disconnected.


503

| Remote        Control/Manual Status     Indication    Output

(Volts free)

504| Padlock    Indication  Output

(Volts free)

| When the padlock is pulled up, 504 505 are closed (cut off the internal power of ATS, the ATS cannot act electric and manual operations, then the maintenance is available.

When  the  padlock  is  pulled  down,  504  505  are

disconnected.


505

| ****

Padlock    Indication Output ((Volts free)

506| NC| /

Table 8 Wiring Description

WORKING CONDITION

Table 9 Working Condition

Item Requirements
Working Temperature (-25~+70)ºC
Working Humidity (20~90)%RH
Installation Height ≤2000m
Pollution Degree 3-level

WIRING CONNECTION DIAGRAM

GENSET CONTROLLER APPLICATION DIAGRAM

ATS CONTROLLER APPLICATION DIAGRAM

INSTALLATION AND DEBUGGING

The installation and debugging of ATS should be carried out by professionals and person who knows the switchgear, the related protections and preventive measures must be considered during operating. The wirings of main circuit must be in a way that the leads are not subjected to any pressure or force. Before installation and debugging, firstly check if the switch is damaged or has any harmful effects, meanwhile, check for loose wires may be caused in transportation; clean up the dirt, especially the dirt on the surface of insulation parts, which may be caused by package materials during transportation or storage.

When connecting the primary circuit, pay attention to the phase sequence of the two power supplies that should be consistent, while connecting the secondary circuit, it should be strictly in accordance with the wiring diagram listed on the user manual, at the same time, notice that the voltage level of power supply; switch must be well grounded during installation. Considering in personal safety and the quickness of transferring, the handle is only used for debugging, users should not use the handle to operate with load. During debugging, firstly use handle to operate, then perform the electrical operation by manual button if there is nothing abnormal, finally go to the formal running.

ORDERING MODEL

Table 10 Packing List

No. Item Qty.
4P 3P
1 ATS 1
2 Installation Instructions 1
3 Operating Handle 1
4 Electrical Key 2
5 Nut M12 ****


48

| ****



36

6| Spring Washer M12
7| Flat Washer M12


8

| 800A-1600A| Outer Hexagonal Flat Brain/1240 4.8
2000A| Outer Hexagonal Flat Brain/12
45 4.8
2500A| Outer Hexagonal Flat Brain/1245 4.8
3000A| Outer Hexagonal Flat Brain/12
60 4.8

CONTACT

SmartGen Registered trademark

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.

Table 1 Software Version

Date Version Content
2024-03-07 1.0 Original release.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals