IN-SITE Installer Friendly Series Single Phase Simplex Owner’s Manual
- July 29, 2024
- IN-SITE
Table of Contents
IN-SITE Installer Friendly Series Single Phase Simplex
Specifications
- Enclosure base dimensions : 14 x 12 x 6 inches (35.56 x 30.48 x 15.24 cm)
- Enclosure rating: NEMA 4X
- Control panel types: Simplex Timed Dose, Simplex Demand Dose
- Starting device options : 120/208/240V, 120V only
- Pump full load amps options: 0 – 7 FLA, 7 – 15 FLA, 15 – 20 FLA
- Level control applications: Timed Dose, Demand Dose, C-LevelTM Sensor
FAQ
- Q : What is the purpose of the C-LevelTM Sensor?
- A: The C-LevelTM Sensor is used for high water alarm and redundant off floats in pump-down applications.
- Q: How can I set the pump ON/OFF times for timed dose control?
- A: Use the UP and SET push buttons on the touchpad to set the pump ON/OFF times for timed dose control.
- Q: What should I do if a float operates out of sequence?
- A : An alarm will activate if a float operates out of sequence. Check the float and reset it if necessary.
INTRODUCTION
Get In-Site® to your On-Site™ Systems!
- The IFS In-Site® simplex control panel utilizes an innovative circuit board design to control one 120/208/240V single-phase pump in water and sewage applications.
- IFS panels feature an easy-to-use touchpad on the inner door for programming and system monitoring. Quick retrieval of all system events can be done by downloading panel information onto a USB flash drive.
- The panel configuration can be easily converted in the field to either a timed dose or a demand dose. Available with the EZconnex® float system.
- Monitor system events including pump run times, pump cycles, alarm conditions, power outages, service calls, and more! Quick, convenient reports make diagnosing system conditions easy! Plug the flash drive into the USB port located on the inner door of the IFS In-Site® panel to download system events that occurred. No computer is needed at the site!
- Use the flash drive (included with the panel) with any computer to download system information and reports.
- The pre-loaded software on the flash drive formulates system data for you, creating reports quickly in an easy-to-read format so system conditions can be easily identified and corrected. In addition to monitoring system events, the IFS In-Site® panel logs any service calls and changes made to system settings, which helps protect service providers.
- The panel can utilize the C-Level™ sensor for continuous level monitoring. It senses the level in the tank and sends a signal to the panel. Pump activation levels can be
- adjusted by using the panel touchpad. C-Level™ CL40 sensor operating range is 3-39.9 inches (7.6-101.3 cm). C-Level™ CL100 operating range is 3-99.5 inches (7.6-252.7 cm).
- Five-year limited warranty on panel
- Two-year limited warranty on C-Level™ Sensor
TOUCHPAD FEATURES
- A. Level Status indicators illuminate when floats or set points are activated; an alarm will activate if a float operates out of sequence
- B. HOA (Hand-Off-Automatic) buttons with indication control pump mode; Hand mode defaults to Automatic when stop level or redundant off level is reached
- C. Pump Run indicator illuminates when the pump is called to run
- D. LED display for system information including level in inches or centimeters (C-Level™ sensor only), mode, pump elapsed time (hh: mm), events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), pump ON/OFF times
- (timed dose only), and sequence ON/OFF times (timed dose only)
- E. NEXT push button toggles display
- F. UP and SET push buttons used to set pump ON/OFF times (timed dose only), date and hour, activation levels (C-Level™ only)
COMPONENTS
Panel layout may vary with options. Reg. Cdn Pat. & TM Off C-Level™ Sensor US Patent No. 8,336,385; 8,567,242; 8,650,949
- Enclosure base measures 14 x 12 x 6 inches (35.56 x 30.48 x 15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with removable mounting feet for outdoor or indoor use)
- The Red LED beacon provides a 360° visual check of the alarm condition
- The exterior Alarm Test/Normal/Silence switch allows the horn and light to be tested and the horn to be silenced in an alarm condition; the alarm automatically resets once the alarm condition is cleared
- The alarm horn provides audio warning of alarm conditions (83 to 85 decibel rating) (Not shown)
- Circuit breaker (optional) provides pump disconnect and branch circuit protection
- Power relay controls pump by switching electrical lines; definite purpose contactor used when pumping full load amps are above 15
- Float connection terminal block
- Incoming control/alarm terminal block
- Control Power indicator/fuse indicator light illuminates if control power is present in the panel; an alarm will activate if the control fuse is blown
- The alarm Power indicator/fuse indicator light illuminates if alarm power is present in the panel
- Ground lug
- Incoming pump power connections
- RF filter
- Power supply
- Control fuse
- Alarm fuse
- USB port for flash drive to download time-stamped system events
- Manual report switch date and time stamps service calls
Note: Options, voltage, and amp range selected may change enclosure size
and component layout.
Note : Schematic/Wiring Diagram and Pump Specification Label are located
inside the panel.
INSTALLER FRIENDLY SERIES® IN-SITE® SINGLE PHASE SIMPLEX – Demand or timed dose float-controlled system for pump control, system monitoring, event logging and reporting.
CONTROL PANEL| ✓| IF| |
---|---|---|---|---
MODEL TYPE| | 1| Simplex Timed Dose (includes Option 8AC as
standard)| $2,742.00
| 2| Simplex Demand Dose (includes Option 8AC as standard)| $2,774.00
ALARM PACKAGE| ✓| 1| Alarm Package (includes test/normal/silence
switch, fuse, red light, & horn)| Base
ENCLOSURE RATING| ✓| W| Weatherproof, NEMA 4X (engineered
thermoplastic)| Base
STARTING DEVICE| | 1| 120/208/240V| Base
| 9| 120V only| Base
PUMP FULL LOAD AMPS| | 0| 0 – 7 FLA| Base
| 1| 7 – 15 FLA| Base
| 2| 15 – 20 FLA| $106.00
PUMP DISCONNECTS
| | 0| No Pump Disconnect| Base
| 4| Circuit Breaker 120V (select STARTING DEVICE Option 9 above)| $43.00
Circuit Breaker 120/208/240V (select STARTING DEVICE Option 1 above)| $86.00
LEVEL CONTROL APPLICATION
| | H| Floats – Pump Down (select Option 17 below)
Timed dose = timer enable and alarm / Demand dose = stop, start, and alarm
| Base
| E| EZconnex® Float Switch System (select Option 33, 35 or 36 below)| Timed
Dose| – $68.00
Demand Dose| – $102.00
| X| No Floats| Timed Dose| – $68.00
Demand Dose| – $102.00
| C| C-Level™ Sensor (select Option 24 or 29)* Select Option 3E and/ or 4A &
4D for high water alarm and/or redundant off floats| Timed Dose| – $68.00
Demand Dose| – $102.00
NOTE : Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high-level alarm and pump shut off when using the C-Level™ sensor.
| OPTIONS| DESCRIPTION| LIST PRICE
---|---|---|---
| 1J| Duo Alarm Inputs| $34.00
| 3A| Alarm Flasher| $66.00
| 3B| Manual Alarm Reset| $119.00
| 3E| High Water Alarm Float (must also select Option 17)
Only Available with Level Control Application = C
| $34.00
| 4A| Redundant Off
(must also select Option 4D if floats are required)
| Timed Dose| $0.00
Demand Dose| $72.00
| 4D| Redundant Off Float (must also select Option 4A and Option 17)| $34.00
| 6A| Auxiliary Alarm Contact, Form C| $51.00
✓
|
8AC
|
Display Board – Includes: ETM Counter, Events (Cycles) Counter, Alarm Counter, and Override Counter (Timed Dose Only) (included as standard)
|
$0.00
| 10E| Lockable Latch – NEMA 4X| $51.00
| 10F| Lightning Arrestor (select pump circuit breaker, control, and alarm
power combined)| $285.00
| 10K| Anti-condensation Heater (must select if the operating
temperature is colder than 0 degrees F or
-18 degrees C)| $124.00
| 11C| Additional NEMA 1 Remote Alarm Panel (must also select Option 6A)|
$114.00
| 11D| Additional NEMA 4X Remote Alarm Panel (must also select Option 6A)|
$368.00
| 15A| Control/Alarm Circuit Breaker| $112.00
| 16A| 10’ Cord in Lieu of 20’ Cord (per Float)| – $3.00
| 16B| 15’ Cord in Lieu of 20’ Cord (per Float)| – $2.00
| 16C| 30’ Cord in Lieu of 20’ Cord (per Float)| $6.00
| 16D| 40’ Cord in Lieu of 20’ Cord (per Float)| $18.00
| OPTIONS| DESCRIPTION| LIST PRICE
---|---|---|---
| 17C| Sensor Float® / Internally Weighted (per Float) – Mercury| $13.00
| 17D| Sensor Float® / Externally Weighted (per Float) – Mercury| $15.00
| 17G| SJE MilliAmpMaster™ / Pipe Clamp (per Float) – Mechanical| $0.00
| 17H| SJE MilliAmpMaster™ / Externally Weighted (per Float) – Mechanical|
$8.00
| 17J| Sensor Float® / Pipe Clamp (per Float) – Mercury| $6.00
| 18A| Timer Override Float (Timed Dose Float Panel Only)| $34.00
| 24E| C-Level™ CL40 Sensor with 25′ Vented Cable| $380.00
| 24F| C-Level™ CL40 Sensor with 50′ Vented Cable| $425.00
| 24P| C-Level™ CL40 Sensor with 100′ Vented Cable| $515.00
| 24X| No C-Level™ CL40 Sensor| $0.00
| 29A| C-Level™ CL100 Sensor with 25′ Vented Cable| $380.00
| 29B| C-Level™ CL100 Sensor with 50′ Vented Cable| $425.00
| 29C| C-Level™ CL100 Sensor with 100′ Vented Cable| $515.00
| 29X| No C-Level™ CL100 Sensor| $0.00
| 33D ■| EZconnex® 3-Port, 25’, with 10’ Floats (3) / Pipe Clamp| $313.00
| 33E ■| EZconnex® 3-Port, 50’, with 10’ Floats (3) / Pipe Clamp| $355.00
| 33G ■| EZconnex® 3-Port, 25’, with 20’ Floats (3) / Pipe Clamp| $337.00
| 33H ■| EZconnex® 3-Port, 50’, with 20’ Floats (3) / Pipe Clamp| $379.00
| 35D ■| EZconnex® 4-Port, 25’, with 10’ Floats (4) / Pipe Clamp| $442.00
| 35E ■| EZconnex® 4-Port, 50’, with 10’ Floats (4) / Pipe Clamp| $496.00
| 35G ■| EZconnex® 4-Port, 25’, with 20’ Floats (4) / Pipe Clamp| $473.00
| 35H ■| EZconnex® 4-Port, 50’, with 20’ Floats (4) / Pipe Clamp| $526.00
| 36D ■| EZconnex® 3-Port, 25’, with 10’ Floats (2) / Pipe Clamp, Sealing
Plug| $271.00
| 36E ■| EZconnex® 3-Port, 50’, with 10’ Floats (2) / Pipe Clamp, Sealing
Plug| $313.00
| 36G ■| EZconnex® 3-Port, 25’, with 20’ Floats (2) / Pipe Clamp, Sealing
Plug| $286.00
| 36H ■| EZconnex® 3-Port, 50’, with 20’ Floats (2) / Pipe Clamp, Sealing
Plug| $328.00
*C-Level™ Sensor lengths up to 300 ft. available. Call for details.
EZconnex® mechanically-activated, narrow-angle float switches with quick- release connections
California Prop 65 requires the following
WARNING- Cancer and Reproductive Harm – www.P65Warnings.ca.gov