IN-SITE Installer Friendly Series Single Phase Duplex Instruction Manual
- July 29, 2024
- IN-SITE
Table of Contents
IN-SITE Installer Friendly Series Single Phase Duplex
Specifications
- Enclosure Base Dimensions: 16 x 14 x 6 inches (40.64 x 35.56 x 15.24 cm)
- Enclosure Rating: NEMA 4X
- Alarm Sound Level: 83 to 85 decibels
- Power Requirements: 120/208/240V or 120V
Product Usage Instructions
- A. Level Status indicators will illuminate when floats or set points are activated. An alarm will activate if a float operates out of sequence.
- B. HOA (Hand-Off-Automatic) buttons control pump mode. Hand mode defaults to Automatic when stop level or redundant off level is reached.
- C. Pump Run indicators will illuminate when pumps are called to run.
- D. LED display shows system information including level in inches or centimeters (C-LevelTM only), mode, pump elapsed time, events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), pump ON/OFF times, and sequence ON/OFF times (timed dose only).
- E. The NEXT button toggles the display.
- F. UP and SET Push Buttons are used to set pump ON/OFF times, pump operation, date and hour, and activation levels (C-LevelTM only).
FAQ
- Q: What are the different options available for the control panel models?
- A: The control panel models include Duplex Timed Dose and Duplex Demand Dose, each with specific features and configurations. The options range from alarm packages, enclosure ratings, starting devices, pump full load amps, pump disconnects, level control applications, and more.
- Q: How can I control the pump operation using the touchpad features?
- A: You can control the pump operation by using the HOA buttons to switch between hand-off and automatic modes. The LED display provides information on pump status, and elapsed time, and allows you to set pump ON/OFF times and activation levels.
Introduction
The IFS In-Site® duplex control panel utilizes an innovative circuit board
design to control two alternating 120/208/240V single-phase pumps in water and
sewage applications. IFS panels feature an easy-to-use touchpad on inner door
for programming and system monitoring. The alternating action equalizes pump
wear. In addition, this system provides override control should either pump
fail. Quick retrieval of all system events can be done by downloading panel
information onto a USB flash drive. The panel configuration can be easily
converted in the field to either a timed dose or a demand dose. Available with
the EZconnex® float system.
Monitor system events including pump run times, pump cycles, alarm conditions,
power outages, service calls and more! Quick, convenient reports make
diagnosing system conditions easy! Plug the flash drive into the USB port
located on the inner door of the IFS In-Site® panel to download system events
that occurred. No computer is needed at the site! Use the flash drive
(included with the panel) with any computer to download system information and
reports. The pre-loaded software on the flash drive formulates system data for
you, creating reports quickly in an easy-to-read format so system conditions
can be easily identified and corrected. In addition to monitoring system
events, the IFS In-Site® panel logs any service calls and changes made to
system settings, which helps protect service providers.
The panel can utilize the C-Level™ sensor for continuous level monitoring. It
senses the level in the tank and sends a signal to the panel. Pump activation
levels can be adjusted by using the panel touchpad. C-Level™ CL40 sensor
operating range is 3-39.9 inches (7.6-101.3 cm). C-Level™ CL100 operating
range is 3-99.5 inches (7.6-252.7 cm).
- Five-year limited warranty on panel
- Two-year limited warranty on C-Level™ Sensor
TOUCH PAD FEATURES
- A. Level Status indicators illuminate when floats or set points are activated; an alarm will activate if a float operates out of sequence
- B. HOA (Hand-Off-Automatic) buttons with indication control pump mode; Hand mode defaults to Automatic when stop level or redundant off level is reached
- C. Pump Run indicators will illuminate when pumps are called to run
- D. LED display for system information including level in inches or centimeters (C-Level™ only), mode, pumps elapsed time (hh:mm), events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), pump ON/OFF times (timed dose only), and sequence ON/OFF times (timed dose only)
- E. NEXT push button toggles display
- F. UP and SET Push Buttons used to set pump ON/OFF times (timed dose only), pump operation (alternate 1-2 and 2-1), date and hour, activation levels (C-Level™ only)
COMPONENTS
- Enclosure base measures 16 x 14 x 6 inches (40.64 x 35.56 x 15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with removable mounting feet for outdoor or indoor use)
- Red LED beacon provides 360° visual check of the alarm condition
- The exterior Alarm Test/Normal/Silence switch allows the horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared
- The alarm horn provides audio warning of alarm conditions (83 to 85 decibel rating)
- Circuit breakers (optional) provide pump disconnect and branch circuit protection
- Power relays control the pump by switching electrical lines; Definite-purpose contactors are used when pump full load amps are above 15
- Float connection terminal block
- Incoming Control/Alarm Terminal Block
- Control Power indicator/fuse indicator light illuminates if control power is present in the panel; alarm activates if control fuse is blown
- Alarm Power indicator/fuse indicator light illuminates if alarm power is present in the panel (Not shown)
- Ground lugs
- Incoming pump power connections
- RF filter
- Power supply
- Control fuse
- Alarm fuse
- USB port for flash drive to download time-stamped system events
- Manual report switch date and time stamps service calls
INSTALLER FRIENDLY SERIES
INSTALLER FRIENDLY SERIES® IN-SITE® SINGLE PHASE DUPLEX – Demand or timed dose float-controlled system for pump control, system monitoring, event logging and reporting.
CONTROL PANEL| ✓| IFI| |
---|---|---|---|---
MODEL TYPE| | 3| Duplex Timed Dose (includes Option 8AC as
standard)| $2,853.00
| 4| Duplex Demand Dose (includes Option 8AC as standard)| $2,885.00
ALARM PACKAGE| ✓| 1| Alarm Package (includes test/normal/silence
switch, fuse, red light, & horn)| Base
ENCLOSURE RATING| ✓| W| Weatherproof, NEMA 4X (engineered
thermoplastic)| Base
STARTING DEVICE| | 1| 120/208/240V| Base
| 9| 120V only| Base
PUMP FULL LOAD AMPS| | 0| 0 – 7 FLA| Base
| 1| 7 – 15 FLA| Base
| 2| 15 – 20 FLA| $129.00
PUMP DISCONNECTS
| | 0| No Pump Disconnect| Base
| 4| Circuit Breaker(s) 120V (select STARTING DEVICE Option 9 above)| $86.00
Circuit Breaker(s) 120/208/240V (select STARTING DEVICE Option 1 above)|
$172.00
LEVEL CONTROL APPLICATION
| | H| Floats – Pump Down (select Option 17 below)
Timed dose = timer enable and alarm / Demand dose = stop, start, and alarm
| Base
| E| EZconnex® Float Switch System (select Option 34 or 35 below)| Timed Dose|
– $68.00
Demand Dose| – $102.00
| X| No Floats| Timed Dose| – $68.00
Demand Dose| – $102.00
| C| C-Level™ Sensor (select Option 24 or 29)* Select Option 3E and/ or 4A &
4D for high water alarm and/or redundant off floats| Timed Dose| – $68.00
Demand Dose| – $102.00
NOTE: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high-level alarm and pump shut off when using the C-Level™ sensor.
| OPTIONS| DESCRIPTION| LIST PRICE
---|---|---|---
| 1J| Duo Alarm Inputs| $34.00
| 3A| Alarm Flasher| $66.00
| 3B| Manual Alarm Reset| $119.00
| 3E| High Water Alarm Float (must also select Option 17)
Only Available with Level Control Application = C
| $34.00
| 4A| Redundant Off
(must also select Option 4D if floats are required)
| Timed Dose| $0.00
Demand Dose| $72.00
| 4D| Redundant Off Float (must also select Option 4A and Option 17)| $34.00
| 6A| Auxiliary Alarm Contact, Form C| $51.00
✓
|
8AC
| Display Board – Includes: ETM Counter, Events (Cycles) Counter, Alarm Counter, Override Counter (Timed Dose Only), and Lead/ Lag Selector (Demand Dose Only) (included as standard)|
$0.00
| 10E| Lockable Latch – NEMA 4X| $51.00
| 10F| Lightning Arrestor (select pump circuit breakers, control, and alarm
power combined)| $285.00
| 10K| Anti-condensation Heater (must select if the operating
temperature is colder than 0 degrees F or
-18 degrees C)| $124.00
| 11C| Additional NEMA 1 Remote Alarm Panel (must also select Option 6A)|
$114.00
| 11D| Additional NEMA 4X Remote Alarm Panel (must also select Option 6A)|
$368.00
| 15A| Control/Alarm Circuit Breaker| $112.00
| 16A| 10’ Cord in Lieu of 20’ Cord (per Float)| – $3.00
| 16B| 15’ Cord in Lieu of 20’ Cord (per Float)| – $2.00
| 16C| 30’ Cord in Lieu of 20’ Cord (per Float)| $6.00
| 16D| 40’ Cord in Lieu of 20’ Cord (per Float)| $18.00
| OPTIONS| DESCRIPTION| LIST PRICE
---|---|---|---
| 17C| Sensor Float® / Internally Weighted (per Float) – Mercury| $13.00
| 17D| Sensor Float® / Externally Weighted (per Float) – Mercury| $15.00
| 17G| SJE MilliAmpMaster™ / Pipe Clamp (per Float) – Mechanical| $0.00
| 17H| SJE MilliAmpMaster™ / Externally Weighted (per Float) – Mechanical|
$8.00
| 17J| Sensor Float® / Pipe Clamp (per Float) – Mercury| $6.00
| 18A| Timer Override Float (Timed Dose Float Panel Only)| $34.00
| 19F| Fourth Float to Separate Alarm Function from Lag (Demand Dose Float
Panel Only)| $34.00
| 24E| C-Level™ CL40 Sensor with 25′ Vented Cable| $380.00
| 24F| C-Level™ CL40 Sensor with 50′ Vented Cable| $425.00
| 24P| C-Level™ CL40 Sensor with 100′ Vented Cable| $515.00
| 24X| No C-Level™ CL40 Sensor| $0.00
| 29A| C-Level™ CL100 Sensor with 25′ Vented Cable| $380.00
| 29B| C-Level™ CL100 Sensor with 50′ Vented Cable| $425.00
| 29C| C-Level™ CL100 Sensor with 100′ Vented Cable| $515.00
| 29X| No C-Level™ CL100 Sensor| $0.00
| 34D ■| EZconnex® 4-Port, 25’, with 10’ Floats (3) / Pipe Clamp, Sealing
Plug| $400.00
| 34E ■| EZconnex® 4-Port, 50’, with 10’ Floats (3) / Pipe Clamp, Sealing
Plug| $454.00
| 34G ■| EZconnex® 4-Port, 25’, with 20’ Floats (3) / Pipe Clamp, Sealing
Plug| $423.00
| 34H ■| EZconnex® 4-Port, 50’, with 20’ Floats (3) / Pipe Clamp, Sealing
Plug| $476.00
| 35D ■| EZconnex® 4-Port, 25’, with 10’ Floats (4) / Pipe Clamp| $442.00
| 35E ■| EZconnex® 4-Port, 50’, with 10’ Floats (4) / Pipe Clamp| $496.00
| 35G ■| EZconnex® 4-Port, 25’, with 20’ Floats (4) / Pipe Clamp| $473.00
| 35H ■| EZconnex® 4-Port, 50’, with 20’ Floats (4) / Pipe Clamp| $526.00
- C-Level™ Sensor lengths up to 300 ft. are available. Call for details.
- EZconnex® mechanically-activated, narrow-angle float switches with quick-release connections