BELLlighting 09030V2, 09031V2 Emergency Downlight Installation Guide
- August 27, 2024
- BELLlighting
Table of Contents
BELLlighting 09030V2, 09031V2 Emergency Downlight Installation Guide
Specification
LED3W
Operating environmental temp:
0 to +40°C. Rated Input Voltage: 220-240V AC 50/60Hz
Discharge Current 400mA
Duration 3 Hour
Maximum Ambient Temperature : 30°C
Battery LiFePO4 3.2V 1500mah
Recharge time: 24 hours,
CONNECTION
Important Information
We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.
- All tests should be carried out in accordance to EN 50172:2004.
- BELL will not accept responsibility for any claims arising from a poor installation
- The light source of this luminaire is not replaceable when the light source reaches end of life, the whole luminaire must be replaced.
Important User Advice
- Ambient room temperature should not exceed 30°C.
- Ensure that there is adequate free air ventilation around the fitting
- Always switch off mains supply before installing.
- Leave Fire rated Sheath on driver and battery pack.
Installation Instructions: Emergency Downlight(09030V2/09031V2)
Read these instructions before installation and retain for future reference
NOT Insulation Coverable
Not suitable for covering with insulation material
The instruction of the switch on PCB. On indicates standard mode. indicates self-test mode.
Please make sure that switch position is set before installation.
RECOMMENDED ROUTINE TEST PROCEDURE
The following test are designed to ensure the continued protection of your
premises and occupants, Because of the possibility of a failure of the normal
lighting supply occurring shortly after a period of testing, all tests should,
whenever possible, be undertaken at times of least risk, e.g. during daylight
hours.
ONCE A DAY
Visual inspection of battery charge led
ONCE A MONTH
Each unit should be energized from it’s battery for adequate time to ensure,
by simulation of a failure of the normal lighting supply, the emergency mode
is functioning correctly.
ONCE EACH YEAR
All units should be placed into emergency mode and checked that the duration
provided by the battery meets the specified time period
This product may contain substances that can be hazardous to the environment
if not disposed of properly. Electrical and electronic equipment should never
be disposed of with general household waste but must be separated for its
correct treatment and recovery.
Where possible recycle your packaging.
Self-Test
Self-Test fittings perform a self-commissioning test at first power on. After
charging for 24 hours a full duration test (3 hours) is performed. Initial
function and duration tests are randomly generated. They are then performed in
accordance with standard requirements (every 30 days for function tests and
every 52 weeks for duration tests).
A single bi-colour indicator LED is fitted in all Self-Test products. This LED
is clearly visible for manual inspection. It indicates the module status. The
LED shows permanent green or flashing green when conditions are normal and
flashing red if a fault condition is present
Function test
A function test is a 2 minutes test that simulates a mains failure and checks
the operation of the emergency light source from the battery supply.
The local indicator LED slow flashes green whilst the 2 minutes function test
is in progress.
If there is a failure during a function test the local indicator LED changes
to a flashing red.
Duration test
A duration test simulates a mains failure. It also checks the operation of the
emergency light source from the battery supply for the rated duration of the
module.
The local indicator LED fast flashes green whilst the duration test is in
progress.
If there is a failure during a duration test the local indicator LED either
changes to flashing red. The battery is required to be fully charged before a
duration test can be started.
Please refer to following chart below for more complete description/fault indication:
Test Button | Green LED | Status |
---|---|---|
Green solid | Mains on / No fault | |
Green flash | Stow flash | Function for 2 minutes |
Fast flash, | 3 hour duration test | |
Red flash | 1 Flash cycle | Battery fault |
2 Flash cycle | Lamp fautt | |
3 Flash cycle | Duration test fault |
Conducting additional manual tests of self-test fittings may significantly reduce and flashing red if a fault condition is present battery life
Testing & Commissioning for Emergency Luminaire
- Ensure the Load is connected.
- Connect the battery.
- Switch on the Unswitched Supply Check the Charge LED illuminates.
- Switch on the Maintained Supply – Check the LED illuminates as normal.
- Switch off the Maintained Supply.
- Switch off the Unswitched Supply Check the Charge LED extinguishes and the load LED illuminates at a reduced output.
- Enter the commissioning date on the Battery Pack. Switch on the Unswitched Supply
Tel +44 (0) 1924 893380
www.belllighting.co.uk