BELLlighting 09030V2, 09031V2 Emergency Downlight Installation Guide

August 27, 2024
BELLlighting

BELLlighting 09030V2, 09031V2 Emergency Downlight Installation Guide

Specification

LED3W
Operating environmental temp:
0 to +40°C. Rated Input Voltage: 220-240V AC 50/60Hz
Discharge Current 400mA
Duration 3 Hour
Maximum Ambient Temperature : 30°C
Battery LiFePO4 3.2V 1500mah
Recharge time: 24 hours,

CONNECTION

Important Information

We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.

  • All tests should be carried out in accordance to EN 50172:2004.
  • BELL will not accept responsibility for any claims arising from a poor installation
  • The light source of this luminaire is not replaceable when the light source reaches end of life, the whole luminaire must be replaced.

Important User Advice

  • Ambient room temperature should not exceed 30°C.
  • Ensure that there is adequate free air ventilation around the fitting
  • Always switch off mains supply before installing.
  • Leave Fire rated Sheath on driver and battery pack.

Installation Instructions: Emergency Downlight(09030V2/09031V2)

Read these instructions before installation and retain for future reference

NOT Insulation Coverable
Not suitable for covering with insulation material

The instruction of the switch on PCB. On indicates standard mode. indicates self-test mode.

Please make sure that switch position is set before installation.

RECOMMENDED ROUTINE TEST PROCEDURE
The following test are designed to ensure the continued protection of your premises and occupants, Because of the possibility of a failure of the normal lighting supply occurring shortly after a period of testing, all tests should, whenever possible, be undertaken at times of least risk, e.g. during daylight hours.

ONCE A DAY
Visual inspection of battery charge led

ONCE A MONTH
Each unit should be energized from it’s battery for adequate time to ensure, by simulation of a failure of the normal lighting supply, the emergency mode is functioning correctly.

ONCE EACH YEAR
All units should be placed into emergency mode and checked that the duration provided by the battery meets the specified time period

This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of with general household waste but must be separated for its correct treatment and recovery.
Where possible recycle your packaging.

Self-Test
Self-Test fittings perform a self-commissioning test at first power on. After charging for 24 hours a full duration test (3 hours) is performed. Initial function and duration tests are randomly generated. They are then performed in accordance with standard requirements (every 30 days for function tests and every 52 weeks for duration tests).
A single bi-colour indicator LED is fitted in all Self-Test products. This LED is clearly visible for manual inspection. It indicates the module status. The LED shows permanent green or flashing green when conditions are normal and flashing red if a fault condition is present

Function test
A function test is a 2 minutes test that simulates a mains failure and checks the operation of the emergency light source from the battery supply.
The local indicator LED slow flashes green whilst the 2 minutes function test is in progress.
If there is a failure during a function test the local indicator LED changes to a flashing red.

Duration test
A duration test simulates a mains failure. It also checks the operation of the emergency light source from the battery supply for the rated duration of the module.
The local indicator LED fast flashes green whilst the duration test is in progress.
If there is a failure during a duration test the local indicator LED either changes to flashing red. The battery is required to be fully charged before a duration test can be started.

Please refer to following chart below for more complete description/fault indication:

Test Button Green LED Status
Green solid Mains on / No fault
Green flash Stow flash Function for 2 minutes
Fast flash, 3 hour duration test
Red flash 1 Flash cycle Battery fault
2 Flash cycle Lamp fautt
3 Flash cycle Duration test fault

Conducting additional manual tests of self-test fittings may significantly reduce and flashing red if a fault condition is present battery life

Testing & Commissioning for Emergency Luminaire

  • Ensure the Load is connected.
  • Connect the battery.
  • Switch on the Unswitched Supply Check the Charge LED illuminates.
  • Switch on the Maintained Supply – Check the LED illuminates as normal.
  • Switch off the Maintained Supply.
  • Switch off the Unswitched Supply Check the Charge LED extinguishes and the load LED illuminates at a reduced output.
  • Enter the commissioning date on the Battery Pack. Switch on the Unswitched Supply

Tel +44 (0) 1924 893380
www.belllighting.co.uk
Email sales@belllighting.co.uk

British Electric Lamps Ltd
BELL House, Oxbridge Way, Norman ton Industrial Estate Norman ton, West Yorkshire. WF6 1TN UK

T +44 (011924 893380 F:
+44 (0)1924 894320
E: sales@belllighting.co.uk
www.belllighting.co.uk

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals