Danfoss ERC 211 Electronic Refrigeration Control Installation Guide
- July 24, 2024
- Danfoss
Table of Contents
- Introduction
- Technical Highlights
- User Interface
- Dimensions (mm) and Mounting
- Electrical Connections
- Quick Configuration At Power Up
- Quick Configuration via “cFg” Menu
- Technical Specifications
- Parameter List
- Safety Standards
- Disposal of the Product
- EU design registration
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Danfoss ERC 211 Electronic Refrigeration Control
Introduction
The ERC 211 is a smart multipurpose
refrigeration controller with temperature and defrost management, available
with 1 relay.
The controller has been designed to fulfill today’s requirements of commercial
refrigeration applications.
Technical Highlights
- Ease of use: Four buttons, easy menu structure, pre installed application solutions ensure superior usability.
- Simple installation: High performance 16 A relay enable direct connection of heavy loads, such as 2 hp compressors, without use of intermediate relays. A wide range of compatible types of sensors and screw connection terminals ensure high flexibility in installation.
- Unit protection: Special software features like compressor protection from fluctuation in power supply or from high condensing temperature ensure the safety operation of the unit.
- Energy efficiency: Defrost on demand and day/night mode ensure energy efficiency
User Interface
Key Function
| Scroll up: Short press (less than 1 second).
Main switch ON/OFF: Press and hold (~ 3 seconds). Factory reset: Press and
hold at Power up.
| Scroll down: Short press (less than 1 sec.) Defrost Start/Stop: Press and
hold (~3 secs.)
| Back function: Short press (less than 1 sec.) Pull down start / stop: Press
and hold (~3 secs.)
| Set point change or OK: Short press (less than 1 sec.) Enter Menu: Press and
hold (~ 3 secs.)
Key Function
| Night mode (Energy saving)
| Compressor running (Flashes in pull-down mode)
| Active alarm
| Defrost
| Unit (°C or °F)
Dimensions (mm) and Mounting
Electrical Connections
Note : 2L and 3L must be connected to the same phase. Power connectors: wire size = 0.5 – 1.5 mm2 , max. tightening torque = 0.4 Nm Low voltage signal connectors: wire size = 0.15 – 1.5 mm2 , max. tightening torque = 0.2 Nm
Quick Configuration At Power Up
- STEP 1: power on
- STEP 2: select the quick configuration menu Within 30 seconds of power on, press “<” BACK for 3 seconds. The main switch “r12” is automatically set to OFF.
- STEP 3: select pre-installed application o61 The display automatically shows the application selection parameter “o61”. Press SET to select the pre-installed application. The display shows the default value (eg. “AP0” flashing). Choose the application type by pressing UP/DOWN and press SET to confirm. The controller presets parameter values according to the selected application and does not hide relevant parameters. Tip: you can easily move from AP0 to AP5, and thus select the simplified list of parameters, by pressing the UP key (circular list).
- STEP 4: select sensor type “o06 The display automatically shows sensor selection parameter “o06”. Press SET to select the sensor type. The display shows the default value (eg. “n10” flashing).
Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm.
Note : All sensors must be the same type.
APP Description Temp. range Defrost end DO1 AI1 DI1 (1)
AP0| Fully Configurable Standard Application (Cooling / Heating)
AP1| MT, No defrost| 4 – 20 °C| NA| | Sair| DI1
AP2| MT, Natural defrost| 2 – 6 °C| Time| | Sair| DI1
AP3| MT, Natural defrost, defrost stop by Sair| 2 – 6 °C| Sair temp| | Sair|
DI1
AP4| Heating Thermostat| 30 – 70 °C| NA| | Sair| DI1
AP5| Fully configurable simplified application (Cooling / Heating)
APP| Description| Temp. range| Defrost end| DO1| AI1| DI1(1)
---|---|---|---|---|---|---
AP0| Fully Configurable Standard Application (Cooling / Heating)
AP1| MT, No defrost| 4 – 20 °C| NA| | Sair| DI1
AP2| MT, Natural defrost| 2 – 6 °C| Time| | Sair| DI1
AP3| MT, Natural defrost, defrost stop by Sair| 2 – 6 °C| Sair temp| | Sair|
DI1
AP4| Heating Thermostat| 30 – 70 °C| NA| | Sair| DI1
AP5| Fully configurable simplified application (Cooling / Heating)
(1) The digital inputs DI1 can be configured for multiple functions (refer parameter “o02”).
Quick Configuration via “cFg” Menu
- Press “SET” button for 3 seconds to access the parameter menu (display will show “cFg”).
- Enter “CFg” menu by pressing “SET” button (diaplay will show first parameter “r12” main switch.
- Select “r12” by pressing “SET” button again and set the main switch to “oFF” (r12=0).
- Press back button (<) to come back to ‘CFg” menu.
- Press DOWN button to scroll through the “cFg” menu parameter list.
- Open the “o61 application mode” and select needed application mode (Press SET).
- Open the “o07 Cooling/Heating” and select needed function and press”SET” (applicable only for AP0 and AP5).
- Open the “o06 Sensor type” and select the temperature sensor type used (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000)- (Press “SET”).
- Open the “o02 DI1 Configuration” and select the function associated to digital input 1 (Press “SET”).
- Navigate back to parameter “r12 Main switch” and set it in “ON” position to start control.
- Go through other parameters default settings and change wherever needed.
Technical Specifications
Features | Description |
---|---|
Purpose of control | Operating temperature sensing control suitable for |
incorporation into commercial air- conditioning and refrigeration applications
Construction of control| Incorporated control
Power supply| 115 V AC / 230 V AC 50/60 Hz, galvanic isolated low voltage
regulated power supply
Rated power| Less than 0.7 W
Inputs| Sensor inputs, Digital inputs, Programming key Connected to SELV
limited energy <15 W
Allowed sensors types| NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C –
EKS 211)
NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C – EKS 221)
PTC 990 Ohm at 25 °C, (EKS 111)
Pt1000, (AKS 11, AKS 12, AKS 21)
Sensors included in Kit Solution| NTC 10000 Ohm at 25 °C, cable length: 1.5 m
Accuracy| Measuring range:
-40 – 105 °C (-40 – 221 °F)
Controller accuracy:
±1 K below -35 °C, ±0.5 K between -35 – 25 °C
±1 K above 25 °C
Type of action| 1B (relay)
Output| DO1 Compressor relay: 16 A, 16 (16) A, EN 60730
10 FLA/60 LRA at 230 V, UL60730
16 FLA/72 LRA at 115 V, UL60730
Display| LED display, 3 digits, decimal point and multi- function icons, °C +
°F scale
Operating conditions| -10 – +55 °C (14 – 131 °F), 90% Rh
Storage conditions| -40 – +70 °C (-40 – +158 °F), 90% Rh
Protection| Front: IP65 (Gasket integrated) Rear: IP00
Environmental| Pollution degree II, non-condensing
Overvoltage category| II – 230 V supply version – (CE, UL recognized) III –
115 V supply version – (UL recognized)
Resistance to heat and fire| UL94-V0
Temperature for ball pressure test statement According to Annex G (EN 60730-1)
EMC category| Emission: IEC/EN 61000 6-3
Immunity: IEC/EN 61000 6-2
Approvals| UL recognition (US & Canada) (UL 60730-1) CQC
CE (LVD & EMC Directive) EAC
NSF ROHS2.0
HACCP temperature monitoring in compliance with EN13485 Class I, when used with AKS 12 sensor
Parameter List
Function | Code | Min | Max | AP0 | AP1 | AP2 | AP3 | AP4 | AP5 |
---|---|---|---|---|---|---|---|---|---|
Configuration | cFg | ||||||||
Main switch ( -1=Service 0=OFF, 1=ON,) | r12 | -1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Predefined applications | o612 | AP0 | AP5 | AP0 | AP1 | AP2 | AP3 | AP4 | AP5 |
Cooling/Heating (rE=Cooling, Ht= Heating) | o072 | rE | Ht | rE | rE1 | rE1 | rE1 | ||
Ht1 | rE | ||||||||
Sensor type selection (n5=NTC 5K, n10=NTC10K, ptc=PTC, pt1=PT1000) | o062 | n5 | |||||||
ptc | n10 | n10 | n10 | n10 | n10 | n10 | |||
Reference | r– | ||||||||
Setpoint (unit: °C) | r00 | -100 | 200 | 2 | 8 | 4 | 4 | 50 | 2 |
Differential (unit: K) | r01 | 0.1 | 20 | 2 | 2 | 2 | 2 | 2 | 2 |
Maximum set point limitation (unit: °C) | r02 | -100 | 200 | 50 | 20 | 6 | 6 | 70 | 50 |
Minimum set point limitation (unit: °C) | r03 | -100 | 200 | -35 | 4 | 2 | 2 | 30 | -35 |
Display offset (unit: K) | r04 | -10 | 10 | 0 | 0 | 0 | 0 | 0 | 0 |
Display Unit (°C/ °F) | r05 | -C | -F | -C | -C | -C | -C | -C | -C |
Calibration of Sair (unit: K) | r09 | -20 | 20 | 0 | 0 | 0 | 0 | 0 | – |
Main switch (-1=Service, 0=OFF, 1=ON,) | r12 | -1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Night Set back (unit: K) | r13 | -50 | 50 | 0 | 0 | 0 | 0 | 0 | 0 |
Reference displacement offset temperature (unit: °C) | r40 | -50 | 20 | 0 | 0 | 0 | |||
0 | 0 | – | |||||||
Pull down duration (unit: min) | r96 | 0 | 960 | 0 | – | 0 | 0 | – | – |
Pull down limit temperature (unit: °C) | r97 | -100 | 200 | 0 | – | 0 | 0 | – | – |
Alarm | A– | ||||||||
Delay for temp alarm during normal conditions (unit: min) | A03 | 0 | 240 | 30 | |||||
45 | 45 | 45 | 10 | 30 | |||||
Delay for temp alarm during pull- down/start up/ defrost (unit: min) | A12 | 0 | |||||||
240 | 60 | 60 | 90 | 90 | NA | 60 |
- This option is a default setting in the controller and cannot be changed.
- This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0.
Function| Code| Min| Max| AP0| AP1| AP2|
AP3| AP4| AP5
---|---|---|---|---|---|---|---|---|---
High temp. alarm limit (unit: °C)| A13| -100| 200| 8| 16| 10| 10| 80| 8
Low temp. alarm limit (unit: °C)| A14| -100| 200| -30| 0| 0| 0| 10| -30
DI1 delay (Time delay for selected DI1 function)
(unit: min)
| A27| 0| 240| 30| 30| 30| 30| 30| 30
Condenser High alarm limit (unit: °C)| A37| 0| 200| 80| 80| 80| 80| –| –
Condenser High block limit (unit: °C)| A54| 0| 200| 85| 85| 85| 85| –| –
Voltage protection enable| A72| no| YES| no| no| no| no| no| no
Minimum cut-in voltage (unit: V)| A73| 0| 270| 0| 0| 0| 0| 0| 0
Minimum cut-out voltage (unit: V)| A74| 0| 270| 0| 0| 0| 0| 0| 0
Maximum voltage (unit: V)| A75| 0| 270| 270| 270| 270| 270| 270| 270
Defrost| d–|
Defrost Method (no=no defrost, nAt=Natural)| d01| no| nAt| nAt| no| nAt| nAt|
no| no
Defrost stop temperature (unit: °C)| d02| 0.0| 50.0| 6.0| –| –| 8.0| –| 6.0
Defrost Interval (unit: hour)| d03| 0| 240| 8.0| –| 6.0| 6.0| –| 8.0
Max defrost Time (unit: min)| d04| 0| 480| 30| –| 45| 60| –| 30
Defrost delay at power up (or DI signal) (unit: min)| d05| 0| 240| 0| –| 0| 0|
–| –
Drip delay (unit: min)| d06| 0| 60| 0| –| 0| 0| –| –
Defrost stop sensor non=None (Time),
Air = Sair temp. Sensor
| d10| non| Air| non| –| non1| Air1| –| non
- This option is a default setting in the controller and cannot be changed.
Function| Code| Min| Max| AP0| AP1| AP2|
AP3| AP4| AP5
---|---|---|---|---|---|---|---|---|---
Accumulated Compressor runtime to start defrost (0=OFF)
(unit: hour)
| d18| 0| 96| 0| –| 0| 0| –| –
Defrost delay after pull down cycle (unit: min)| d30| 0| 960| 0| –| 0| 0| –| –
Compressor| c–|
Compressor minimum ON time (unit: min)| C01| 0| 30| 0.0| 0.0| 0.0| 0.0| 0.0|
0.0
Compressor minimum OFF time (unit: min)| C02| 0| 30| 2.0| 2.0| 2.0| 2.0| 2.0|
2.0
Compressor OFF delay at open door (unit: sec)| C04| 0| 900| 900.0| 900.0|
900.0| 900.0| 900.0| 60.0
Zero crossing selection (YES / no)| C70| no| YES| YES| YES| YES| YES| YES|
YES1
Others| o–|
Delay of outputs at startup (unit: sec)| o01| 0| 600| 10| 10| 10| 10| 10| 101
DI1 configuration| o02| oFF| Sc| oFF| oFF| oFF| oFF| oFF| oFF
Serial address (unit: No)| o03| 0| 247| 0| 0| 0| 0| 0| –
Password (unit: No)| o05| 0| 999| 0| 0| 0| 0| 0| 0
Sensor type selection (n5=NTC 5K, n10=NTC10K, ptc=PTC, pt1=PT1000)| o062| n5|
ptc| n10| n10| n10| n10| n10| n10
Cooling/Heating (rE=Cooling, Ht= Heating)| o072| rE| Ht| rE| rE1| rE1| rE1|
Ht1| rE
Display Resolution| o15| 0.1| 1.0| 0.1| 0.1| 0.1| 0.1| 0.1| 0.11
Predefined applications| o612| AP0| AP5| AP0| AP1| AP2| AP3| AP4| AP5
Save settings as factory
WARNING: The earlier factory settings are overwritten
| o67| no| YES| no| no| no| no| no| –
Display during defrost Air=actual air temperature, FrE=freezed temperature,
-d-=”-d-” is displayed
| o91| -d-| Air| -d-| –| -d-| -d-| –| -d-1
- This option is a default setting in the controller and cannot be changed.
- This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0.
Function | Code | Min | Max | AP0 | AP1 | AP2 | AP3 | AP4 | AP5 |
---|---|---|---|---|---|---|---|---|---|
Polarity | P- |
DI1 input polarity (nc / no) no = normally open,
nc = normally closed
| P73| no| nc| no| no| no| no| no| no
Key board lock
(no / yes)(0=no, 1=yes)
| P76| no| YES| no| no| no| no| no| –
Note : DI1 configuration list as follows –
nC= Not configured; Sdc = Status display output, doo = Door alarm with
resumption,
doA = Door alarm without resumption, SCH = Main switch, nig = Day/ Night mode,
rFd = Reference displasement, EAL = External alarm, dEF = Defrost, Pud = Pull
down;
Sc = Condensor Sensor
Code | Alarms | Description |
---|---|---|
E29 | Sair sensor error | Air temperature sensor error |
E27 | Def sensor error | S5 Evaporator sensor is defect or electrical connection |
is lost
E30| Sc sensor error| Sc Condenser sensor is defect or electrical connection
is lost
A01| High temp alarm| Air temperature in cabinet is too high
A02| Low temp alarm| Air temperature in cabinet is too low
A99| High Volt alarm| Supply voltage is too high (compressor protection)
AA1| Low Volt alarm| Supply voltage is too low (compressor protection)
A61| Condenser alarm| Condenser temp. too high – check air flow
A80| Cond. block alarm| Condenser temp. too high – manual reset of alarm
required1)
A04| Door alarm| Door has been open for too long
A15| DI Alarm| External alarm from DI input
A45| Standby Alarm| Control has been stopped by “r12 Main switch”
- The condenser block alarm can be reset by setting r12 Main switch OFF and ON again or by powering down the controller.
Safety Standards
Check if the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: Use the controller only within the
operating limits avoiding sudden temperature changes with high atmospheric
humidity to prevent the formation of condensation.
Disposal of the Product
The appliance (or the product) must be disposed in accordance with the local waste disposal legislation.
EU design registration
002566703-0001
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, on line or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/5 or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All
rights reserved.