zeta ALARMS ZT-CP4 Addressable Fyreye II Resettable Call Point Instruction Manual

June 12, 2024
zeta ALARMS

ZT-CP4/AD Addressable Fyreye II
Resettable Call Point, Surface Mount
Instruction Manual

GENERAL

The ZT-CP4/AD models are designed for use as components of a compatible fire control system using appropriate analogue addressable devices.
MODEL ZT-CP4/AD
This model provides both signalling of alarm to the monitoring control panel, and local led indication of activation. This MCP also includes on board isolation, providing short circuit protection of the loop.
LED STATUS (TRI COLOUR)
The LED status is controlled by Fire Panel commands and can be set to pulse Green each time the device is polled, or continuous Red to indicate Fire. Yellow color is used to indicate isolator status. See Short Circuit Isolator Specification document GLT-315-6-2 for details.

MOUNTING ARRANGEMENTS

The ZT-CP4/AD can be supplied as either a flush, surface or both mounted device in a normal internal environment. It is not intended for use in an externally exposed or hazardous location (refer to your supplier for product recommendations should these applications be involved).
Important Notes: please do not over tighten fixing screws. The use of lubricants, cleaning solvents or petroleum based products should be avoided.
INSTALLATION DETAILS – Please read carefully
Do not connect circuit wiring to this call point, other field devices or the control panel, or apply power to any portion of the system until all necessary wiring polarity, continuity and insulation tests have been performed. All wiring must conform to applicable local and national regulations and codes of practice.

  1. Terminate field wiring in the Push Fit Terminal Connector as shown taking care to maintain continuity of any shielding provided.
    Positive (+) communication loop: Terminals 2 & 4
    Negative (-) communication loop: Terminals 1 & 3

  2. Set the call point address according to the designated project drawings by using a flat bladed screwdriver to turn the two rotary switches, selecting the desired number between 1 and 250 (See table below).

  3. Plug the Terminal connector onto the rear of the call point as shown.

  4. Fix call point to mounting box taking care that all cables are secure and have sufficient clearance. Locate glass or flexible element in the front of the call point and close cover as shown.zeta ALARMS ZT-CP4 Addressable Fyreye II Resettable Call Point - fig 1

Reset Instructions

zeta ALARMS ZT-CP4 Addressable Fyreye II Resettable Call Point - fig
2

Dimensions (mm)

zeta ALARMS ZT-CP4 Addressable Fyreye II Resettable Call Point - fig
3

Surface Mounting

Fix the surface back box to a flat vertical surface using at least two of the four mounting holes provided. The back box may be drilled to allow cable access as required and a 1,8mm hole is already provided at the rear.

Technical Specifications

Input Voltage 17-28V
Quiescent Current 600µA Maximum
Alarm Current 2.5mA Maximum
Cable Termination 0,5 – 2,5 mm2
Operating Temperature -20 / 60 °C
Max Humidity 95%RH Non-Condensing
IP rating 21
Material ABS/Policarbonate/PA6+glass fiber
ADDRESS S W 1
--- ---
0
1 OFF
2 ON
3 OFF
4 ON
5 OFF
6 ON
7 OFF
8 ON
9 OFF
10 ON
11 OFF
12 ON
13 OFF
14 ON
15 OFF
16 ON
17 OFF
18 ON
19 OFF
20 ON
21 OFF
22 OFF
23 OFF
24 ON
25 OFF
26 ON
27 OFF
28 ON
29 OFF
30 ON
31 OFF
32 ON
33 OFF
34 ON
35 OFF
36 ON
37 OFF
38 ON
39 OFF
40 ON
41 OFF
42 ON
43 OFF
44 ON
45 OFF
46 ON
47 OFF
48 ON
49 OFF
50 ON
51 OFF
52 ON
53 OFF
54 ON
55 OFF
56 ON
57 OFF
58 ON
59 OFF
60 ON
61 OFF
62 ON
63 OFF
ADDRESS S W 1
--- ---
64 ON
65 OFF
66 ON
67 OFF
68 ON
69 OFF
70 ON
71 OFF
72 ON
73 OFF
74 ON
75 OFF
76 ON
77 OFF
78 ON
79 OFF
80 ON
81 OFF
82 ON
83 OFF
84 ON
85 OFF
86 OFF
87 OFF
88 ON
89 OFF
90 ON
91 OFF
92 ON
93 OFF
94 ON
95 OFF
96 ON
97 OFF
98 ON
99 OFF
100 ON
101 OFF
102 ON
103 OFF
104 ON
105 OFF
106 ON
107 OFF
108 ON
109 OFF
110 ON
111 OFF
112 ON
113 OFF
114 ON
115 OFF
116 ON
117 OFF
118 ON
119 OFF
120 ON
121 OFF
122 ON
123 OFF
124 ON
125 OFF
126 ON
127 OFF
ADDRESS S W 1
--- ---
128 ON
129 OFF
130 ON
131 OFF
132 ON
133 OFF
134 ON
135 OFF
136 ON
137 OFF
138 ON
139 OFF
140 ON
141 OFF
142 ON
143 OFF
144 ON
145 OFF
146 ON
147 OFF
148 ON
149 OFF
150 OFF
151 OFF
152 ON
153 OFF
154 ON
155 OFF
156 ON
157 OFF
158 ON
159 OFF
160 ON
161 OFF
162 ON
163 OFF
164 ON
165 OFF
166 ON
167 OFF
168 ON
169 OFF
170 ON
171 OFF
172 ON
173 OFF
174 ON
175 OFF
176 ON
177 OFF
178 ON
179 OFF
180 ON
181 OFF
182 ON
183 OFF
184 ON
185 OFF
186 ON
187 OFF
188 ON
189 OFF
190 ON
191 OFF
ADDRESS S W 1
--- ---
192 ON
193 OFF
194 ON
195 OFF
196 ON
197 OFF
198 ON
199 OFF
200 ON
201 OFF
202 ON
203 OFF
204 ON
205 OFF
206 ON
207 OFF
208 ON
209 OFF
210 ON
211 OFF
212 ON
213 OFF
214 OFF
215 OFF
216 ON
217 OFF
218 ON
219 OFF
220 ON
221 OFF
222 ON
223 OFF
224 ON
225 OFF
226 ON
227 OFF
228 ON
229 OFF
230 ON
231 OFF
232 ON
233 OFF
234 ON
235 OFF
236 ON
237 OFF
238 ON
239 OFF
240 ON
241 OFF
242 ON
243 OFF
244 ON
245 OFF
246 ON
247 OFF
248 ON
249 OFF
250 ON
251
252
253
254
255

Zeta Alarms Limited
Detection House, 72-78 Morfa Road Swansea, SA1 2EN
Telephone: +44 (0)1792 455 175
Email: info@zetaalarmsystems.com
22
2831-CPR-F4782
22
0832-UKCA-CPR-F1455
EN 54-11:2001+ A1:2005
EN 54-17:2005
Zeta CP4/AD
Addressable Fyreye II
Resettable Call Point,
Indoor
Red series only
TSD-ZT-CP4-AD-00A – Rev.
date: 2022-09-06 16:34:58

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals