Danfoss AMI 120 NL-1 24V 2-Point Pressure Independent Balancing Control Valves Installation Guide
- July 24, 2024
- Danfoss
Table of Contents
Danfoss AMI 120 NL-1 24V 2-Point Pressure Independent Balancing Control
Valves
Specifications
- Model: AMI 120 NL-1
- Stem Travel: 5 mm
- Travel Speed: 10 (12) s/mm
- Maintenance: 5-95% RH, condensation-free
- Power Supply: AC 24V, 50/60Hz
Product Usage Instructions
Safety Notes
To avoid personal injury and damage to the device or property, follow these
instructions:
- Assembly, start-up, and maintenance work should be done by qualified personnel.
- Do not remove the cover before switching off the power supply.
Mounting Position
The actuator should be mounted with the valve stem in a horizontal position
or pointing upwards.
Wiring
Connect AC 24V via Class 2 (North America) or Safety Extra-Low Voltage
(SELV) (Europe) to avoid equipment damage or personal injury.
Installation
- Check the valve neck to ensure the actuator is in the full up position (factory setting). Reposition if necessary.
- Fix the actuator to the valve body using the ribbed nut; hand tighten only.
Manual Override
Only use the manual override for service purposes and ensure power is
disconnected.
FAQ
-
Q: What is the purpose of control for the AMI 120 NL-1?
A: The purpose of control is an Electrical Actuator. -
Q: How should the actuator be mounted?
A: The actuator should be mounted with the valve stem in a horizontal position or pointing upwards. -
Q: What precautions should be taken during wiring?
A: Switch off the power before wiring the actuator and make all connections according to local regulations.
Operating Guide
AMI 120 NL-1
Safety Notes
To avoid personal injury and damage to the device or other property, it is
necessary to read and follow these instructions carefully.
Assembly, start-up, and maintenance work must be performed by qualified and
authorized personnel.
Comply with the instructions of the system manufacturer or system operator.
Do not remove the cover before the power supply is switched off.
Mounting Position
❶
The actuator should be mounted with the valve stem in either a horizontal position or pointing upwards.
Wiring ❷
AC 24 V
Connect via Class 2 (North America) or Safety Extra-Low Voltage (SELV)
(Europe). Failure to comply can lead to equipment damage or personal injury.
(Europe). Failure to comply can lead to equipment damage or personal injury.
- Make all wiring connections in accordance with local, national, or regional regulations.
- For applications requiring conduit, a field supplied 1/2” trade size electrician’s fitting and lock nut can be mounted in the actuator enclosure. Use flexible metallic tubing or its equivalent with the field supplied fitting.
- Insert wiring material through the removable plug or conduit fitting, and connect to the terminal block using the applicable wiring diagram ❷.
- Optionally, end position feedback is available on terminal 4 and terminal 5, which indicates actuator’s end position travel. Both contacts are normally open.
Jumper position setting B
Jumper Position “A” (Factory Setting)
“On” at terminal block position “1”: Actuator drives up and valve opens,
optional terminal 4 closes.
“Off” at terminal block position “1”: Actuator drives down and valve closes,
optional terminal 5 closes.
Jumper Position “B”
“On” at terminal block position “1”: Actuator drives down and valve closes,
optional terminal 4 closes.
“Off” at terminal block position “1”: Actuator drives up and valve opens,
optional terminal 5 closes.
Do not remove the cover before the power supply is fully switched off.
- The Jumper is factory set in position “A” With the jumper in position “A”, an “ON” command at position 1 of the terminal block will cause the actuator spindle to extend (valve closes). An “OFF” command will cause the spindle to retract (valve opens)
- Moving the jumper to position “B” will reverse the actuator’s action
With the jumper in position “B”, an “ON” command at position 1 of the terminal block will cause the actuator spindle to retract (valve opens). An “OFF” command will cause the spindle to extend (valve closes).
Installation
❸
- Check the valve neck. The actuator should be in the full up position ① (factory setting). If it is not, refer to the manual override instructions and reposition the actuator to its full up position ❸①.
- The actuator is fixed to the valve body by means of a ribbed nut which requires no tools for mounting. The ribbed nut should be hand tightened only.
Manual override ❹
(for service purposes only)
Do not use the manual override if power is connected!
- Remove cover ①
- Press and hold the button (on the bottom side of the actuator) ② during manual override ③
- Replace cover ④
- Install actuator on valve ⑤
Remark
A ‘click’ sound after energizing the actuator indicates that the gear wheel
has jumped into normal position.
Don’t dismount the actuator from the valve when it is in a stem down position!
If dismounted in a stem down position, there is a high risk that the actuator
gets stuck.
The following information is provided on the device or on the instruction manual or datasheet:
- Purpose of control: Electrical Actuator
- Construction of control: Independently Mounted Control
- Method of mounting control
- Type 1 Action
- Pollution Degree 3
- Impulse Voltage: 500V
- Software Class A
- Mechanical and thermal ratings (ref to Ratings section for more details)
- “Use ½ inch flexible metal conduit for connection”
- “Use Listed Flexible Metal Conduit Fitting DWTT/7”
- “Use 60°C/75°C copper (CU) conductor and wire size range (#) AWG, stranded or solid”. “The terminal tightening torque of (#) Lb per In.”
- Torque value for Cover screw: 0,6 +/-0,1 Nm.
Note (#): Values depend by field wiring ratings of terminal block employed on the device construction.
Danfoss A/S
Climate Solutions • danfoss.com • +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.
© Danfoss | DCS-S/SI | 2024.03