neptronic CMMB106 Remote I and O Communication Module Instruction Manual
- July 20, 2024
- neptronic
Table of Contents
neptronic CMMB106 Remote I and O Communication Module
Specifications
- Model: CMMB106
- Input Voltage: 24 Vac or 27-33 Vdc
- Consumption: 5VA (331mA @ 24 Vac)
- Universal Inputs: 8 [0.00-10.00Vdc, 10K/20K/30K, on/off (dry contact), 4.00-20.00mA]
- Digital Inputs: 2 [normally open/closed or direct/reverse]
- Universal Outputs: 2 [0-10Vdc, pulsed signal (20mA drive), on/off, 4-20mA]
- Analog Outputs: 2 [0-10Vdc]
- Digital Relay Outputs: 4
- BACnet and Modbus Communication
- Operational Temperature: A = 6.30 / 160 mm, B = 5.00 / 126 mm, C = 2.25 / 57 mm
Product Usage Instructions
Connections and Configurations
Please follow the below instructions for setting up the connections and
configurations of the CMMB106:
- MAC Address (DS2): Set the DIP switches to calculate the MAC address.
- End of Line (JP3/JP4): Set to 120 Ohms.
- Network Port (TB10): A+: BACnet/Modbus A+, B-: BACnet/Modbus B-.
- Universal Inputs (TB12-15): Selectable inputs from AI1 to AI8.
- Digital Inputs (TB16): Configurable inputs DI1 and DI2.
- Voltage Input (TB17): COM: Common, 24V: 24 Vac or 27-33 Vdc.
FAQ
How do I configure the MAC address?
To configure the MAC address, set the DIP switches representing binary logic
to calculate the MAC address. The default setting is all switches OFF.
Models
CMMB106
Description
The CMMB extends your BACnet or Modbus network when your application requires
additional inputs and outputs on a physical controller. Combining the 20
inputs and outputs of the CMMB with your Building Automation System provides
simple expansion of a new or existing controller and reduces unnecessary costs
of additional components.
Features
Power & Communication
- 24Vac or 30Vdc supply
- BACnet® MS/TP or Modbus communication port (selectable)
Inputs & Outputs
- 8 universal inputs
- 2 digital inputs
- 2 universal outputs (supervised)
- 2 analog outputs (supervised)
- 6 digital outputs (supervised)
Installation
- 10 override switches to manually control each output
- LED status indication of each input and output
- DIN rail mounting
- Removable, non-strip, raising clamp terminals
Network Communication
- BACnet® MS/TP or Modbus communication port (selectable via DIP switch)
- Select MAC address via DIP switch or via network BACnet®
- MS/TP @ 9600, 19200, 38400 or 76800 bps
- Automatic baud rate detection
- Automatic device instance configuration
- Copy & broadcast configuration to other CMMB modules
Modbus
- Modbus @ 9600, 19200, 38400 or 57600 bps
- RTU Slave, 8 bits (configurable parity and stop bits)
- Connects to any Modbus master
Technical Specifications
Connections and Configurations
Specifications | CMMB106 |
---|---|
Input Voltage | 24 Vac or 27-33 Vdc |
Consumption | 5VA (331mA @ 24 Vac) |
Universal Inputs | 8 [0.00-10.00Vdc, 10KΩ/20KΩ/30KΩ, on/off (dry contact), |
4.00-20.00mA] / 12b hardware resolution with oversampling
Digital Inputs| 2 [normally open/closed or direct/reverse]
Universal Outputs| 2 [0-10Vdc, pulsed signal (20mA drive), on/off,
4-20mA] / 1mV resolution
Analog Outputs| 2 [0-10Vdc] / 1mV resolution
Digital Relay Outputs| 6 [normally open/closed, independent common per
relay, 5A resistive]
BACnet| BACnet® MS/TP @ 9600, 19200, 38400 or 76800 bps (BAS-C)
Modbus| Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and
stop bit configuration:
- No parity, 2 stop bit
- Even parity, 1 stop bit
- Odd parity, 1 stop bit
Communication Connections| 24 AWG twisted-shield cable (Belden 9841 or
equivalent)
Electrical Connections| 0.8 mm2 [18 AWG] minimum
Operational Temperature| 0ºC to 50ºC [32ºF to 122ºF]
Storage Temperature| -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity| 5 to 95% non condensed
Weight| 0.4 kg [0.9 lb]
Dimensions| | | |
A = 6.30” / 160 mm| | | |
B = 5.00” / 126 mm| | | |
C = 2.25” / 57 mm| | | __**__**|
Please note that all jumper settings must also be set to the same value through BACnet. Some additional configurations are only available through BACnet (see Network Conditions on page 4).
MAC Address DIP Switch
(DS2)
MAC address for BACnet and Modbus communication, are selectable by DIP switch
DS2 using binary logic. BACnet
- Highest MAC address is 254.
- Default is all switches OFF = MAC address 0
- If you do not change device instance in program mode, it will be automatically modified according to the MAC address.
MAC Address| DS.1 = 1| DS.2 = 2| DS.3 = 4| DS.4 = 8|
DS.5 = 16| DS.6 = 32| DS.7 = 64| DS.8 = 128| Default
Device Instance
---|---|---|---|---|---|---|---|---|---
0| OFF| OFF| OFF| OFF| OFF| OFF| OFF| OFF| 153000
1| ON| OFF| OFF| OFF| OFF| OFF| OFF| OFF| 153001
2| OFF| ON| OFF| OFF| OFF| OFF| OFF| OFF| 153002
3| ON| ON| OFF| OFF| OFF| OFF| OFF| OFF| 153003
4| OFF| OFF| ON| OFF| OFF| OFF| OFF| OFF| 153004
…| …| …| …| …| …| …| …| …| …
126| OFF| ON| ON| ON| ON| ON| ON| OFF| 153126
…| …| …| …| …| …| …| …| …| …
254| OFF| ON| ON| ON| ON| ON| ON| ON| 153254
Modbus
- Highest MAC address is 247.
- Default is all switches OFF = MAC address 1
- MAC address is binary value +1
- There is no device instance for Modbus.
MAC Address| DS.1 = 1| DS.2 = 2| DS.3 = 4| DS.4 = 8|
DS.5 = 16| DS.6 = 32| DS.7 = 64| DS.8 = 128
---|---|---|---|---|---|---|---|---
0+1 = 1| OFF| OFF| OFF| OFF| OFF| OFF| OFF| OFF
1+1 = 2| ON| OFF| OFF| OFF| OFF| OFF| OFF| OFF
2+1 = 3| OFF| ON| OFF| OFF| OFF| OFF| OFF| OFF
3+1 = 4| ON| ON| OFF| OFF| OFF| OFF| OFF| OFF
4+1 = 5| OFF| OFF| ON| OFF| OFF| OFF| OFF| OFF
…| …| …| …| …| …| …| …| …
126+1 = 127| OFF| ON| ON| ON| ON| ON| ON| OFF
…| …| …| …| …| …| …| …| …
246+1 = 247| OFF| ON| ON| OFF| ON| ON| ON| ON
LEDs
- Power
- On = Input voltage normal
- Off = No power
Status
- Flashing = Normal operation (watchdog)
RX/TX (BACnet)
- Flashing = Receiving (RX) and/or transmitting (TX) data.
RX/TX (Modbus)
- Flashing = Receiving (RX) and/or transmitting (TX) data.
Input Status
- On = Input on
- Off = Input off
- Flashing = Input not connected (thermistor setting only)
- Analog = When Universal Inputs are set to analog values (Vdc, mA, or 10KΩ); the LED intensity corresponds to the input value.
- For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off.
Output Status
- On = Activated
- Off = Deactivated
- Flashing = Output pulsed
- Analog = When Universal and Analog outputs are set to analog values (Vdc or mA); the LED intensity corresponds to the output value. For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off.
Network Conditions
Please note that all jumper settings must also be set to the same value
through BACnet or Modbus. The following is a list of conditions and additional
BACnet or Modbus objects.
Universal Inputs (AI1-AI8)
- When the jumper is set to Thermistor, you can select either °C or °F or you can set the input as a digital on/off input.
- If the universal input is set as a digital on/off input, you can also set the polarity to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal.
- When the jumper is set to 0-10 Vdc, you can also set the range to 0-5 Vdc.
Digital Inputs (DI1-DI2)
- You can set the polarity to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal.
Universal/Analog Outputs (AO1-AO4)
- You can set the polarity to direct or reverse. For example, in reverse the output range would be 10-0 Vdc instead of 0-10 Vdc.
The polarity applies to all settings 0-10Vdc, 4-20mA, on/off and pulsed.
- You can also set the outputs to pulsed or digital on/off.
- A fixed output value can only be modified via BACnet when the override switch is in the “Automatic” position.
Digital Outputs (DO1-DO6)
- A fixed output (open/closed) can only be modified via BACnet when the override switch is in the “Automatic” position.
- The displayed text can be set to either Open/Closed, On/Off, or Alarm/Normal (BACnet only).
Supervised Outputs
- All outputs are fully supervised via BACnet. This provides the actual state of the output including any manual overrides done using the on-board switches.
Pulse Counting Feature
The pulse counting feature enables counting the number of pulses detected by
the universal or digital inputs.
- When an active edge is detected, the Pulse Count is incremented by 1 up to the Prescaler value. When the Prescaler value is reached, the Accumulator is incremented by 1 and the Pulse Count is reset to 0.
- For digital inputs, there is a 1ms debouncing for the detection of the edge.
- For universal inputs, a value that is higher than 80% of the input’s saturation confirms a high level. A value that is lower than 20% of the input’s saturation confirms a low level.
- On both types of inputs, the maximum frequency is 100Hz and the minimum pulse length is 5ms/50%D.C.
BACnet Objects Table
ID 1| Name| Description| Writable?| *Notes ( = default)**
( † = only when UniversalInputxFunction is set to _10KType3/G )
---|---|---|---|---
AI.1
| ****
UniversalInput1
| ****
Universal input 1
mode selected by MSV.1
| ****
Out of service
| 0 to 10Volt or -40 to 100ºC (150ºC) † or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
**AI.2| ** UniversalInput2| **** Universal input 2
mode selected by MSV.12
| ** Out of service| 0 to 10Volt or -40 to 100ºC (150ºC) †** or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
**AI.3| ** UniversalInput3| **** Universal input 3
mode selected by MSV.15
| ** Out of service| 0 to 10Volt or -40 to 100ºC (150ºC) †** or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
**AI.4| ** UniversalInput4| **** Universal input 4
mode selected by MSV.48
| ** Out of service| 0 to 10Volt or -40 to 100ºC (150ºC) †** or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
**AI.5| ** UniversaInput5| **** Universal input 5
mode selected by MSV.57
| ** Out of service| 0 to 10Volt or -40 to 100ºC (150ºC) †** or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
**AI.6| ** UniversalInput6| **** Universal input 6
mode selected by MSV.58
| ** Out of service| 0 to 10Volt or -40 to 100ºC (150ºC) †** or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
**AI.7| ** UniversalInput7| **** Universal input 7
mode selected by MSV.59
| ** Out of service| 0 to 10Volt or -40 to 100ºC (150ºC) †** or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
**AI.8| ** UniversalInput8| **** Universal input 8
mode selected by MSV.60
| ** Out of service| 0 to 10Volt or -40 to 100ºC (150ºC) †** or
-40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1
AV.1| UI1PulseCount| Universal input 1 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.2| UI2PulseCount| Universal input 2 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.3| UI3PulseCount| Universal input 3 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.4| UI4PulseCount| Universal input 4 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.5| UI5PulseCount| Universal input 5 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.6| UI6PulseCount| Universal input 6 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.7| UI7PulseCount| Universal input 7 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.8| UI8PulseCount| Universal input 8 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.9| DI1PulseCount| Digital input 1 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.10| DI2PulseCount| Digital input 2 pulse count.| Present Value| 0 to
16777216, Resolution: 1
AV.11| UI1Accumulator| Universal input 1 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.12| UI2Accumulator| Universal input 2 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.13| UI3Accumulator| Universal input 3 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.14| UI4Accumulator| Universal input 4 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.15| UI5Accumulator| Universal input 5 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.16| UI6Accumulator| Universal input 6 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.17| UI7Accumulator| Universal input 7 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.18| UI8Accumulator| Universal input 8 pulse counter rollovers.|
Present Value| 0 to 16777216, Resolution: 1
AV.19| DI1Accumulator| Digital input 1 pulse counter rollovers.| Present
Value| 0 to 16777216, Resolution: 1
AV.20| DI2Accumulator| Digital input 2 pulse counter rollovers.| Present
Value| 0 to 16777216, Resolution: 1
ID 1| Name| Description| Writable?| *Notes ( =
default)**
( † = only when UniversalInputxFunction is set to _10KType3/G )
---|---|---|---|---
AV.52| AnalogOutput1Min| Min. voltage of analog output 1| Present Value|
0 Volt to AV.54 | Resolution 0.1 Volt
AV.53| AnalogOutput2Min| Min. voltage of analog output 2| Present Value|
0 Volt to AV.55 | Resolution 0.1 Volt
AV.54| AnalogOutput1Max| Max. voltage of analog output 1| Present Value|
AV.52 to 10.0 Volt | Resolution 0.1 Volt
AV.55| AnalogOutput2Max| Max. voltage of analog output 2| Present Value|
AV.53 to 10.0 Volt | Resolution 0.1 Volt
AV.72| AnalogOutput1| Analog output 1 value| Present Value| 0-100% |
Resolution 0.1%
AV.73| AnalogOutput2| Analog output 2 value| Present Value| 0-100% |
Resolution 0.1%
AV.118| AnalogOutput3Min| Min. voltage of analog output 3| Present
Value| 0 Volt to AV.120 | Resolution 0.1 Volt
AV.119| AnalogOutput4Min| Min. voltage of analog output 4| Present
Value| 0 Volt to AV.121 | Resolution 0.1 Volt
AV.120| AnalogOutput3Max| Max. voltage of analog output 3| Present
Value| AV.118 to 10.0 Volt | Resolution 0.1 Volt
AV.121| AnalogOutput4Max| Max. voltage of analog output 4| Present
Value| AV.119 to 10.0 Volt | Resolution 0.1 Volt
AV.124| AnalogOutput3| Analog output 3 value| Present Value| 0-100% |
Resolution 1%
AV.125| AnalogOutput4| Analog output 4 value| Present Value| 0-100% |
Resolution 1%
AV.226| UniversalInput1Offset| Universal input 1 offset| Present Value|
-5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.227| UniversalInput2Offset| Universal input 2 offset| Present Value| -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.228| UniversalInput3Offset| Universal input 3 offset| Present Value| -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.229| UniversalInput4Offset| Universal input 4 offset| Present Value| -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.230| UniversalInput5Offset| Universal input 5 offset| Present Value| -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.231| UniversalInput6Offset| Universal input 6 offset| Present Value| -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.232| UniversalInput7Offset| Universal input 7 offset| Present Value| -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.233| UniversalInput8Offset| Universal input 8 offset| Present Value| -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*)
Resolution: 0.01 ºC/ºF/Volt/mA
AV.468| CopyCfgStartAdd| Copy configuration start address| Present Value| 0-254 Address of first CMMB to copy Available only if BV.101 is set to No
AV.469
|
CopyCfgEndAdd
|
Copy configuration end address
|
Present Value
| AV.468 – (AV.468 + 64)
Address of last CMMB to copy Available only if BV.101 is set to No
AV.470| CopyCfgResult 2| Copy configuration result| Present Value| AV.468 – AV.469
Result of copy is available on Description property and is available only if BV.101 is set to Yes. Results: Succeed, Prog_Error, Type_Error, Model_Error, FW_Error, Mem_Error, Size_Error, Comm_Error, SlaveDevice, InProgress, AllSucceed
AV.500| U1_MinInputValue| Universal input 1 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.501| U1_MaxInputValue| Universal input 1 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.502| U1_MinValue| Universal input 1 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.503| U1_MaxValue| Universal input 1 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.504| U2_MinInputValue| Universal input 2 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.505| U2_MaxInputValue| Universal input 2 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.506| U2_MinValue| Universal input 2 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.507| U2_MaxValue| Universal input 2 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.508| U3_MinInputValue| Universal input 3 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.509| U3_MaxInputValue| Universal input 3 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.510| U3_MinValue| Universal input 3 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
Write 526address in present value, result will be available in description.
ID 1| Name| Description| Writable?| *Notes ( = default)**
( † = only when UniversalInputxFunction is set to _10KType3/G )
---|---|---|---|---
AV.511| U3_MaxValue| Universal input 3 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.512| U4_MinInputValue| Universal input 4 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.513| U4_MaxInputValue| Universal input 4 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.514| U4_MinValue| Universal input 4 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.515| U4_MaxValue| Universal input 4 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.516| U5_MinInputValue| Universal input 5 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.517| U5_MaxInputValue| Universal input 5 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.518| U5_MinValue| Universal input 5 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.519| U5_MaxValue| Universal input 5 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.520| U6_MinInputValue| Universal input 6 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.521| U6_MaxInputValue| Universal input 6 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.522| U6_MinValue| Universal input 6 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.523| U6_MaxValue| Universal input 6 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.524| U7_MinInputValue| Universal input 7 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.525| U7_MaxInputValue| Universal input 7 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.526| U7_MinValue| Universal input 7 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.527| U7_MaxValue| Universal input 7 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.528| U8_MinInputValue| Universal input 8 minimum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.529| U8_MaxInputValue| Universal input 8 maximum input value| Present
Value| 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA
AV.530| U8_MinValue| Universal input 8 minimum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.531| U8_MaxValue| Universal input 8 maximum scaled value| Present
Value| -32768 to 32767, Resolution: 0.01
AV.532| AO1FailsafePreset| Analog output 1 failsafe preset value|
Present Value| 0 to 100%, Resolution: 0.1%
AV.533| AO2FailsafePreset| Analog output 2 failsafe preset value|
Present Value| 0 to 100%, Resolution: 0.1%
AV.534| AO3FailsafePreset| Analog output 3 failsafe preset value|
Present Value| 0 to 100%, Resolution: 0.1%
AV.535| AO4FailsafePreset| Analog output 4 failsafe preset value|
Present Value| 0 to 100%, Resolution: 0.1%
AV.536| TimeoutValue| Network Timeout value| Present Value| 5 to 600
sec, Resolution: 5 sec
AV.537| UI1_PulsePrescaler| Universal input 1 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.538| UI2_PulsePrescaler| Universal input 2 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.539| UI3_PulsePrescaler| Universal input 3 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.540| UI4_PulsePrescaler| Universal input 4 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.541| UI5_PulsePrescaler| Universal input 5 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.542| UI6_PulsePrescaler| Universal input 6 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
ID 1| Name| Description| Writable?| *Notes ( =
default)**
( † = only when UniversalInputxFunction is set to _10KType3/G )
---|---|---|---|---
AV.543| UI7_PulsePrescaler| Universal input 7 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.544| UI8_PulsePrescaler| Universal input 8 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.545| DI1_PulsePrescaler| Digital input 1 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
AV.546| DI2_PulsePrescaler| Digital input 2 pulse counter rollover
threshold.| Present Value| 0 to 16777216, Resolution: 1
BI.1
|
DigitalInput1
|
Digital input 1 status
|
Out of service
| 0= Open / Ouvert * 1= Close / Fermé
Text depends of selection in MSV.76
BI.2
|
DigitalInput2
|
Digital input 2 status
|
Out of service
| 0= Open / Ouvert * 1= Close / Fermé
Text depends of selection in MSV.77
BV.22
|
ContactOutput1
|
Digital output 1 status
|
Present Value
| 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.66
BV.23
|
ContactOutput2
|
Digital output 2 status
|
Present Value
| 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.67
BV.24
|
ContactOutput3
|
Digital output 3 status
|
Present Value
| 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.68
BV.25
|
ContactOutput4
|
Digital output 4 status
|
Present Value
| 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.69
BV.26
|
ContactOutput5
|
Digital output 5 status
|
Present Value
| 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.70
BV.27
|
ContactOutput6
|
Digital output 6 status
|
Present Value
| 0= Open / Ouvert / Off / Arret / Normal 1= Close / Fermé / On / Marche /
Alarm Text depends of selection in MSV.71
BV.33| DigitalInput1Polarity| Polarity of digital input 1| Present
Value| 0= Direct
1= Reverse
BV.34| DigitalInput2Polarity| Polarity of digital input 2| Present Value| 0= Direct *
1= Reverse
BV.66| AnalogOutput1Direction| Polarity of analog output 1| Present Value| 0= Direct *
1= Reverse
BV.67| AnalogOutput2Direction| Polarity of analog output 2| Present Value| 0= Direct *
1= Reverse
BV.68| AnalogOutput3Direction| Polarity of analog output 3| Present Value| 0= Direct *
1= Reverse
BV.69| AnalogOutput4Direction| Polarity of analog output 4| Present Value| 0= Direct *
1= Reverse
BV.93| UI1_DI_Polarity| Polarity of universal input 1 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.94| UI2_DI_Polarity| Polarity of universal input 2 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.95| UI3_DI_Polarity| Polarity of universal input 3 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.96| UI4_DI_Polarity| Polarity of universal input 4 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.97| UI5_DI_Polarity| Polarity of universal input 5 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.98| UI6_DI_Polarity| Polarity of universal input 6 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.99| UI7_DI_Polarity| Polarity of universal input 7 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.100| UI8_DI_Polarity| Polarity of universal input 8 when used in digital input mode| Present Value| 0= Direct *
1= Reverse
BV.101| CopyCfgExecute| Start or stop copy configuration|
Present Value
| 0= No *
1= Yes
Start copy and give results, must be reset by user.
BV.102| SystemUnit| Select the unit system to use on the device| Present Value| 0= Celsius *
1= Fahrenheit
D 1| Name| Description| Writable?| *Notes ( = default)**
( † = only when UniversalInputxFunction is set to _10KType3/G )
---|---|---|---|---
BV.103| Inhibit Output Override| Inhibit the override of the outputs|
Present Value| 0= Off *
1= On
BV.104| TimeoutStatus| Network timeout status| | 0= Inactive *
1= Active
MSV.1| UniversalInput1Function| Selected analog input 1 mode| Present Value| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
MSV.12
|
UniversalInput2Function
|
Selected analog input 2 mode
|
Present Value
| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
MSV.15| UniversalInput3Function| Selected analog input 3 mode|
Present Value
| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
MSV.48| UniversalInput4Function| Selected analog input 4 mode| Present Value| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
MSV.54| AnalogOutput1Mode| Select analog output 1 mode| Present Value| 1= Analog *
2= On_Off
3= Pulsing
MSV.55| AnalogOutput2Mode| Select analog output 2 mode| Present Value| 1= Analog *
2= On_Off
3= Pulsing
MSV.57| UniversalInput5Function| Selected analog input 5 mode| Present Value| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
ID 1| Name| Description| Writable?| *Notes ( = default)**
( † = only when UniversalInputxFunction is set to _10KType3/G )
---|---|---|---|---
MSV.58
|
UniversalInput6unction
| Selected analog input 6 mode|
Present Value
| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
MSV.59
|
UniversalInput7Function
|
Selected analog input 7 mode
|
Present Value
| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
MSV.60
|
UniversalInput8Function
|
Selected analog input 8 mode
|
Present Value
| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
9= DigitalInput
10= ScaledValue_Volt
11= ScaledValue_mA
12= 10K_NTC_Carel
MSV.66
|
ContactOutput1Text
|
Contact output 1 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
3= On_Off
4= Marche_Arret
5= Alarm_Normal
MSV.67
|
ContactOutput2Text
|
Contact output 2 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
3= On_Off
4= Marche_Arret
5= Alarm_Normal
MSV.68
|
ContactOutput3Text
|
Contact output 3 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
3= On_Off
4= Marche_Arret
5= Alarm_Normal
MSV.69
|
ContactOutput4Text
|
Contact output 4 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
3= On_Off
4= Marche_Arret
5= Alarm_Normal
MSV.70
|
ContactOutput5Text
|
Contact output 5 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
3= On_Off
4= Marche_Arret
5= Alarm_Normal
MSV.71
|
ContactOutput6Text
|
Contact output 6 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
3= On_Off
4= Marche_Arret
5= Alarm_Normal
MSV.76
|
DigitalInput1Text
|
Digital input 1 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
ID 1| Name| Description| Writable?| *Notes ( = default)**
( † = only when UniversalInputxFunction is set to _10KType3/G )
---|---|---|---|---
MSV.77
|
DigitalInput2Text
|
Digital input 2 inactive & active text
|
Present Value
| 1= Open_Close *
2= Ouvert_Fermé
MSV.81
|
AnalogOutput3Mode
|
Select analog output 3 mode
|
Present Value
| 1= Analog *
2= On_Off
3= Pulsing
4= 4_20mA
MSV.82
|
AnalogOutput4Mode
|
Select analog output 4 mode
|
Present Value
| 1= Analog *
2= On_Off
3= Pulsing
4= 4_20mA
MSV.83
|
CfgBO1FailsafeMode
| Configuration of the binary output 1 failsafe mode|
Present Value
| 1= LastState *
2= Open
3= Close
MSV.84
|
CfgBO2FailsafeMode
| Configuration of the binary output 2 failsafe mode|
Present Value
| 1= LastState *
2= Open
3= Close
MSV.85
|
CfgBO3FailsafeMode
| Configuration of the binary output 3 failsafe mode|
Present Value
| 1= LastState *
2= Open
3= Close
MSV.86
|
CfgBO4FailsafeMode
| Configuration of the binary output 4 failsafe mode|
Present Value
| 1= LastState *
2= Open
3= Close
MSV.87
|
CfgBO5FailsafeMode
| Configuration of the binary output 5 failsafe mode|
Present Value
| 1= LastState *
2= Open
3= Close
MSV.88
|
CfgBO6FailsafeMode
| Configuration of the binary output 6 failsafe mode|
Present Value
| 1= LastState *
2= Open
3= Close
MSV.89
|
CfgAO1FailsafeMode
| Configuration of the analog output 1 failsafe mode|
Present Value
| 1= LastState *
2= Preset
MSV.90
|
CfgAO2FailsafeMode
| Configuration of the analog output 2 failsafe mode|
Present Value
| 1= LastState *
2= Preset
MSV.91
|
CfgAO3FailsafeMode
| Configuration of the analog output 3 failsafe mode|
Present Value
| 1= LastState *
2= Preset
MSV.92
|
CfgAO4FailsafeMode
| Configuration of the analog output 4 failsafe mode|
Present Value
| 1= LastState *
2= Preset
Modbus Registers
-
Register address
- As per protocol base (base 0); for PLC add 1 to protocol base.
- As per holding register (base 40001)
-
Functions :
- 03 Read Holding Register
- 06 Write Single Register
- 16 Write Multiple Registers
-
Error Codes :
- 02 Illegal Data Address
- 03 Illegal Value
- 06 Slave Device Busy
-
W = Writable register, [blank] = read only.
No Real number in modbus register, use scale to calculate real number. Register = Real number * Scale => Real number = Register / Scale. Scale could be 1, 10 or 100
Attention when writing a register that contains a bit string. If bit is writable (conditional or not), the write will always be accepted. If bit is reserved or not writable, the write will be ignored and will keep its actual state. -
Use READ-MODIFY-WRITE sequence.
Protocol Base|
Holding Register
| Description| Data Type| MSB/LSB| Units/Values|
Writable| Default Value
---|---|---|---|---|---|---|---
MB| LB
0| 40001| MSB = Neptronic Device ID LSB = MAC Address| Unsigned| 105 (69h)|
[1..247]
(1h- F7h)
| MAC address is writable if all DIP switches of DS2 are OFF.| W| 69h| 1h
1
|
40002
|
Device Baud Rate
|
Unsigned Scale 0.01
| [96] [192] [384] [576]| 9,600
19,200
38,400
57,600
| |
96
2
|
40003
| COM Port Configuration
IMPORTANT : The default value is “no parity, 2 stop bits”. To change the value, you must set DIP switch DS1-3 to OFF. If set to ON, it will always remain at the default value. Refer to Connections and
Configurations on page 2.
|
Unsigned
| [0..2]| 0 = no parity, 2 stop bits 1 = even parity, 1 stop bit 2 = odd parity, 1 stop bit|
W
|
0
3| 40004| Product Name (characters 8 & 7)| 2 x ASCII| char 8| char 7| Valid
ASCII character: 32 (20h) – 122 (7ah), Empty = 0| W| 43h [C]| 40h [M]
4| 40005| Product Name (characters 6 & 5)| 2 x ASCII| char 6| char 5| Valid
ASCII character: 32 (20h) – 122 (7ah), Empty = 0| W| 40h [M]| 42h [B]
5| 40006| Product Name (characters 4 & 3)| 2 x ASCII| char 4| char 3| Valid
ASCII character: 32 (20h) – 122 (7ah), Empty = 0| W| 31h [1]| 30h [0]
6| 40007| Product Name (characters 2 & 1)| 2 x ASCII| char 2| char 1| Valid
ASCII character: 32 (20h) – 122 (7ah), Empty = 0| W| 36h [6]| 20h [ ]
7| 40008| Firmware Version| Unsigned Scale 100| 115| 1.15| | 115
8| 40009| Application Version| Unsigned Scale 100| 103| 1.03| | 103
Protocol Base|
Holding Register
| Description| Data Type| MSB/LSB| Units/Values|
Writable| Default Value
---|---|---|---|---|---|---|---
MB| LB
9
|
40010
|
System Status 1
|
Bit String
| [B0..B15]| 0 = Normal
1 = Fault
– – – – – – – – – – – – – – – – – – –
B0 = System operation
| |
0000, 0001, 1111, 1110b
10| 40011| System Status 2| Bit String| [B0..B15]| Always 0| | 0000, 0000,
0000, 0000b
11| 40012| Analog Input 1| 0-10V: Type: Unsigned, Scale:100, Unit:
Volt, Range: 0.00-10.00V,
Resolution: 0.01 4-20mA: Type: Unsigned, Scale:100, Unit: mA, Range:
4.00-20.00 mA, Resolution: 0.01 10K Type 3A1, 10K Type 4AI, 10K Type 2, 20K
Type 6AI, 30K Type 6AI:
Type: Signed, Scale:100, Unit: ºC, Range: -40.00 – 100.00 ºC, Resolution: 0.01 Type: Signed, Scale:100, Unit: ºF, Range: -40.00 – 212.00 ºF, Resolution: 0.02
10K Type 3/G:
Type: Signed, Scale:100, Unit: ºC, Range: -40.00 – 150.00 ºC, Resolution: 0.01 Type: Signed, Scale:100, Unit: ºF, Range: -40.00 – 302.00 ºF, Resolution: 0.02
DI: Type: Unsigned, Scale:1, No Unit, Range: 0-1, Resolution: 1 Scaled Input (Volt), Scaled Input (mA):
Type: Unsigned, Scale:1 , No Unit, Range: Ux_MinValue – Ux_MaxValue, Resolution: 1
| | 32767
12| 40013| Analog Input 2| 32767
13| 40014| Analog Input 3| 32767
14| 40015| Analog Input 4| 32767
15| 40016| Analog Input 5| 32767
16| 40017| Analog Input 6| 32767
17| 40018| Analog Input 7| 32767
18| 40019| Analog Input 8| 32767
19| 40020| Digital Input| Bit String| [B0..B1]| B0 = DI1 B1 = DI2| | 0000,
0000, 0000, 0000b
20| 40021| Analog Output 1|
Unsigned Scale 10
|
[0..1000]|
Unit: %, Range: 0-100.0%, Resolution: 0.1
|
W
| 0
21| 40022| Analog Output 2| 0
22| 40023| Analog Output 3| 0
23| 40024| Analog Output 4| 0
24
|
40025
|
Relay Output
|
Bit String
| [B0..B5]| B0 = Relay 1 B1 = Relay 2
B2 = Relay 3 B3 = Relay 4 B4 = Relay 5 B5 = Relay 6
|
W
|
0000, 0000, 0000, 0000b
25
|
40026
|
Output Overwrite Status
Indicates that the output is overridden by the hardware switch (SW5-SW10).
|
Bit String
|
[B0..B9]| B0 = Relay 1 B1 = Relay 2 B2 = Relay 3 B3 = Relay 4 B4 = Relay 5 B5 = Relay 6 B6 = AO1 B7 = AO2
B8 = AO3 B9 = AO4
| |
0000, 0000, 0000, 0000b
26| 40027| Universal Input 1 Function|
Unsigned
|
[1..12]| 1= 0_10Volt
2= 4_20mA
3= 10K_Type3/G *
4= 10K_Type3A1
5= 10K_Type4A1
6= 10K_Type2
7= 20K_Type6A1
8= 30K_Type6A1
|
W
| 3
27| 40028| Universal Input 2 Function| 3
28| 40029| Universal Input 3 Function| 3
29| 40030| Universal Input 4 Function| 3
30| 40031| Universal Input 5 Function| 3
Protocol Base
|
Holding Register
| Description| Data Type| MSB/LSB| Units/Values|
Writable| Default Value
---|---|---|---|---|---|---|---
MB| LB
4
|
40055
| System Options
* = digital input mode only
| it String|
[B0..B15]| 0 = Direct 0 = Off
1 = Reverse 1 = On
– – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
B0 = AO1 polarity B14 = Inhibit Output Override B1 = AO2 polarity – – – – – – – – – – – – – – – – – – –
B2 = AO3 polarity 0 = Celsius
B3 = AO4 polarity 1 = Fahrenheit
B4 = AI1 polarity * – – – – – – – – – – – – – – – – – – –
B5 = AI2 polarity B15 = System Unit B6 = AI3 polarity
B7 = AI4 polarity B8 = AI5 polarity B9 = AI6 polarity * B10 = AI7 polarity
- B11 = AI8 polarity * B12 = DI1 polarity
B13 = DI2 polarity
|
W
|
0000, 0000, 0000, 0000b
55| 40056| Universal Input 1 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 56, Resolution: 0.01 Unit: mA,
Range: 4.00 mA – Register 56, Resolution: 0.01| W| 0
56| 40057| Universal Input 1 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 55 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 55 – 20.00 mA, Resolution: 0.01| W| 1000
57| 40058| Universal Input 1 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 58, Resolution: 0.01| W| 0
58| 40059| Universal Input 1 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 57 – 32767, Resolution: 0.01| W| 1000
59| 40060| Universal Input 2 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 60, Resolution: 0.01 Unit: mA,
Range: 4.00 mA – Register 60, Resolution: 0.01| W| 0
60| 40061| Universal Input 2 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 59 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 59 – 20.00 mA, Resolution: 0.01| W| 1000
61| 40062| Universal Input 2 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 62, Resolution: 0.01| W| 0
62| 40063| Universal Input 2 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 61 – 32767, Resolution: 0.01| W| 1000
63| 40064| Universal Input 3 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 64, Resolution: 0.01 Unit: mA,
Range: 4.00 mA – Register 64, Resolution: 0.01| W| 0
64| 40065| Universal Input 3 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 63 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 63 – 20.00 mA, Resolution: 0.01| W| 1000
65| 40066| Universal Input 3 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 66, Resolution: 0.01| W| 0
66| 40067| Universal Input 3 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 65 – 32767, Resolution: 0.01| W| 1000
67| 40068| Universal Input 4 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 68, Resolution: 0.01 Unit: mA,
Range: 4.00 mA – Register 68, Resolution: 0.01| W| 0
Protocol Base| Holding Register| Description| Data Type|
MSB/LSB| Units/Values| Writable| Default Value
---|---|---|---|---|---|---|---
MB| LB
68| 40069| Universal Input 4 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 67 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 67 – 20.00 mA, Resolution: 0.01| W| 1000
69| 40070| Universal Input 4 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 70, Resolution: 0.01| W| 0
70| 40071| Universal Input 4 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 69 – 32767, Resolution: 0.01| W| 1000
71| 40072| Universal Input 5 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 72, Resolution: 0.01 Unit: mA,
Range: 4.00 mA – Register 72, Resolution: 0.01| W| 0
72| 40073| Universal Input 5 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 71 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 71 – 20.00 mA, Resolution: 0.01| W| 1000
73| 40074| Universal Input 5 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 66, Resolution: 0.01| W| 0
74| 40075| Universal Input 5 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 65 – 32767, Resolution: 0.01| W| 1000
75| 40076| Universal Input 6 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 64, Resolution: 0.01 Unit: mA,
Range : 4.00 mA – Register 64, Resolution: 0.01| W| 0
76| 40077| Universal Input 6 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 63 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 63 – 20.00 mA, Resolution: 0.01| W| 1000
77| 40078| Universal Input 6 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 78, Resolution: 0.01| W| 0
78| 40079| Universal Input 6 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 77 – 32767, Resolution: 0.01| W| 1000
79| 40080| Universal Input 7 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 80, Resolution: 0.01 Unit: mA,
Range: 4.00 mA – Register 80, Resolution: 0.01| W| 0
80| 40081| Universal Input 7 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 79 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 79 – 20.00 mA, Resolution: 0.01| W| 1000
81| 40082| Universal Input 7 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 82, Resolution: 0.01| W| 0
82| 40083| Universal Input 7 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 81 – 32767, Resolution: 0.01| W| 1000
83| 40084| Universal Input 8 Minimum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: 0.00 V – Register 84, Resolution: 0.01 Unit: mA,
Range: 4.00 mA – Register 84, Resolution: 0.01| W| 0
84| 40085| Universal Input 8 Maximum Input Value| Unsigned Scale 100|
[0..100]| Unit: Volt, Range: Register 83 – 10.00 V, Resolution: 0.01 Unit: mA,
Range: Register 83 – 20.00 mA, Resolution: 0.01| W| 1000
85| 40086| Universal Input 8 Minimum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: -32768 – Register 86, Resolution: 0.01| W| 0
86| 40087| Universal Input 8 Maximum Value| Signed Scale 1| [-32768…32767]| No
Unit, Range: Register 85 – 32767, Resolution: 0.01| W| 1000
87
|
40088
|
Binary Output 1 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
Protocol Base
|
Holding Register
| Description| Data Type| MSB/LSB| Units/Values|
Writable| Default Value
---|---|---|---|---|---|---|---
MB| LB
88
|
40089
|
Binary Output 2 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
89
|
40090
|
Binary Output 3 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
90
|
40091
|
Binary Output 4 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
91
|
40092
|
Binary Output 5 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
92
|
40093
|
Binary Output 6 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
93| 40094| Analog Output 1 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
94| 40095| Analog Output 1 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
95| 40096| Analog Output 2 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
96| 40097| Analog Output 2 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
97| 40098| Analog Output 3 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
98| 40099| Analog Output 3 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
99| 40100| Analog Output 4 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
100| 40101| Analog Output 4 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
101| 40102| Timeout Status| Unsigned| [0,1]| 0= Inactive
1= Active
| | 0
102| 40103| Network Timeout Value| Unsigned Scale 1| [5..600]| Unit: Seconds
(sec), Range: 5 – 600 sec, Resolution: 5 sec| W| 30
103| 40104| UI1 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
104| 40105| UI1 Pulse Prescaler (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
105| 40106| UI2 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
106| 40107| UI2 Pulse Prescaler (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
107| 40108| UI3 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
108| 40109| UI3 Pulse Prescaler (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
109| 40110| UI4 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
Protocol Base
|
Holding Register
| Description|
Data Type
|
MSB/LSB
|
Units/Values
|
Writable
| Default Value
---|---|---|---|---|---|---|---
MB| LB
88
|
40089
|
Binary Output 2 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
89
|
40090
|
Binary Output 3 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
90
|
40091
|
Binary Output 4 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
91
|
40092
|
Binary Output 5 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
92
|
40093
|
Binary Output 6 Fail Safe Mode
|
Unsigned
| [1..3]| 1= LastState
2= Open
3= Close
|
W
|
1
93| 40094| Analog Output 1 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
94| 40095| Analog Output 1 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
95| 40096| Analog Output 2 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
96| 40097| Analog Output 2 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
97| 40098| Analog Output 3 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
98| 40099| Analog Output 3 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
99| 40100| Analog Output 4 Fail Safe Mode| Unsigned| [1,2]| 1= LastState
2= Preset
| W| 1
100| 40101| Analog Output 4 Fail Safe Preset Value| Unsigned Scale 10|
[0..1000]| Unit: %, Range: 0 – 100.00 %, Resolution: 0.1| W| 100
101| 40102| Timeout Status| Unsigned| [0,1]| 0= Inactive
1= Active
| | 0
102| 40103| Network Timeout Value| Unsigned Scale 1| [5..600]| Unit: Seconds
(sec), Range: 5 – 600 sec, Resolution: 5 sec| W| 30
103| 40104| UI1 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
104| 40105| UI1 Pulse Prescaler (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
105| 40106| UI2 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
106| 40107| UI2 Pulse Prescaler (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
107| 40108| UI3 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
108| 40109| UI3 Pulse Prescaler (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
109| 40110| UI4 Pulse Prescaler (0)| Unsigned Scale 1| [0…16777216]| Range: 0
to 16777216, Resolution: 1| W| 0
Protocol Base| Holding Register| Description| Data Type|
MSB/LSB| Units/Values| Writable| Default Value
---|---|---|---|---|---|---|---
MB| LB
139| 40140| DI1 Pulse Count (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
140| 40141| DI1 Pulse Count (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
141| 40142| DI2 Pulse Count (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
142| 40143| DI1 Pulse Count (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
143| 40144| UI1 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
144| 40145| UI1 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
145| 40146| UI2 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
146| 40147| UI2 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
147| 40148| UI3 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
148| 40149| UI3 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
149| 40150| UI4 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
150| 40151| UI4 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
151| 40152| UI5 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
152| 40153| UI5 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
153| 40154| UI6 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
154| 40155| UI6 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
155| 40156| UI7 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
156| 40157| UI7 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
157| 40158| UI8 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
158| 40159| UI8 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
159| 40160| DI1 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
160| 40161| DI1 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
161| 40162| DI2 Accumulator (0)| Unsigned Scale 1| [0…16777216]| Range: 0 to
16777216, Resolution: 1| W| 0
162| 40163| DI2 Accumulator (1)| | [0…16777216]| Range: 0 to 16777216,
Resolution: 1| |
Recycling at end of life: please return this product to your Neptronic local
distributor for recycling. If you need to find the nearest Neptronic
authorized distributor, please consult
www.neptronic.com.
400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com
Toll free in North America:
1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday: 8:00am to 5:00pm (Eastern time)