Century AMP24S1A SE Series Multi Position Air Handler Owner’s Manual

July 3, 2024
CENTURY

MULTI-POSITION
AIR HANDLER
PSC Motor
Cooling Capacity: 24 – 60 kBTU/h

FEATURES

  • Available for cooling and heat pump applications
  • All-aluminum tubes & fins
  • Factory-sealed cabinet certified to achieve 2% or less leakage rate at 1.0 inch water column
  • Multi-position Installation
  • Horizontal and vertical condensate drain pans standard
  • Blower and coil slide out for ease of maintenance
  • Field Installed heater kits are optional: 5/7.5/10/15/20kW
  • AHRI Listed & ETL Cer tified

MODEL NUMBER GUIDE

A M P 24 S 1 A
Air Handler Multi- Position PSC/Piston Capacity
BTUH x 1000 SE Series **Power
1 = 208/230-1-60** Revision Level

SPECIFICATIONS

AMP24S1A AMP36S1A AMP48S1A AMP60S1A

NOMINAL RATING
Cooling (BTU/h)| 24,000| 36,000| 48,000| 60,000
ELECTRICAL DATA
Voltage / Phase(60Hz)| 208/230/1| 208/230/1| 208/230/1| 208/230/1
Min. / Max. Voltage| 187/253| 187/253| 187/253| 187/253
Min. Circuit Amps| 2.9| 3.3| 4.2| 5.7
Max. Overcurrent Protection| 15| 15| 15| 15
FAN MOTOR
Motor Type| PSC| PSC| PSC| PSC
Capacitor (uF)| 10| 10| 20| 20
Horsepower (HP)| 1/4| 1/2| 1/2| 3/4
Rated RPM| 903| 865| 925| 990
Full Load Amps (FLA)| 2.3| 2.6| 3.3| 4.5
FAN BLOWER
Material| Metal| Metal| Metal| Metal
Type| Centrifugal| Centrifugal| Centrifugal| Centrifugal
Diameter(in.)| 13| 13| 13| 13
Height(in.)| 10-5/8| 10-5/8| 10-5/8| 10-5/8
EVAPORATOR COIL
Type| Tube & Fin| Tube & Fin| Tube & Fin| Tube & Fin
Tube Material| Aluminum| Aluminum| Aluminum| Aluminum
Tube Size(in.)| 9/32| 9/32| 9/32| 9/32
REFRIGERANT CONNECTION SIZE
Liquid Line Size (O.D.)| 3/8| 3/8| 3/8| 3/8
Suction Line Size (O.D.)| 3/4| 3/4| 7/8| 7/8

TXV KITS

| Part#| Description| Used On
---|---|---|---
**** TXV Kit| TR6-3TONNB| 18-36K| MAA18(36,42)S1A, MAA3042S1A, MAA36(42,48,60)S1A, AMP36S1A, AMC24S1A, AMC36S1A, AMP48S1A
TR6-4TON| 42-48K| MAA(18,30)42S1A, MAA36(48,60)S1A, MAA4260S1A, AMP48S1A, AMC36S1A, AMC60S1A
TR6-5TON| 60K| MAA3660S1A, MAA4260S1A, AMP60S1A, AMC60S1A

NOTE: 25” CLEARANCE IS REQUIRED IN THE FRONT OF THE UNIT FOR FILTER AND COIL MAINTENANCE. UPFLOW CONFIGURATIONS SHOWN; MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT.

| AMP24S1A| AMP36S1A| AMP48S1A| AMP60S1A
---|---|---|---|---
DIMENSIONS AND WEIGHTS
Height (in.)| 46-1/2| 46-1/2| 54-1/2| 54-1/2
Width (in.)| 19-5/8| 19-5/8| 22| 22
Depth (in.)| 21-5/8| 21-5/8| 24| 24
Weight (lbs.)| 128| 128| 159| 161

AIR FLOW DATA

NOTE: Shaded boxes represent airflow outside the required 300-450 cfm/ton, which are not recommended.

NOTE: Shaded boxes represent airflow outside the required 300-450 cfm/ton, which are not recommended.
ELECTRIC HEATER KITS

NO. Kit Description Ref.Air Handler Use
1 EHK- 05A(UL) 5kW Heat Strip 24/36/48/60
2 EHK- 08A(UL) 7.5kW Heat Strip 24/36/48/60
3 EHK- 10A(UL) 10kW Heat Strip 24/36/48/60
4 EHK- 15B(UL) 15kW Heat Strip, double Breaker panel 36/48/60
5 EHK- 20B(UL) 20kW Heat Strip, double Breaker panel 36/48/60

HEATER KITS

**Model| ****Air Handler Capacity (kBTU/h)| ****Electric Heat(kW)| ****Min. Circuit Ampacity| Max. Fuse or Breaker (HACR) Ampacity| ****Blower Speed
---|---|---|---|---|---
240V| 208V| 240V| 208V| 1| 2| 3
AMP24S1A
EHK- 05A(UL)| ** 24| 5| 29| 25.5| 30| 30| x| •| •
EHK- 08A(UL)| 7.5| 42| 36.8| 45| 40| •| •| •
EHK- 10A(UL)| 10| 55| 48.1| 60| 50| x| •| •
AMP36S1A
EHK- 05A(UL)| ** 36| 5| 29.4| 25.9| 30| 30| •| •| •
EHK- 08A(UL)| 7.5| 42.4| 37.2| 45| 40| •| •| •
EHK- 10A(UL)| 10| 55.4| 48.5| 60| 50| •| •| •
EHK- 15B(UL)| 15| 55.4/26.1| 48.5/22.6| 60/30| 50/25| •| •| •
EHK- 20B(UL)| 20| 55.4/52.1| 48.5/45.2| 60/60| 60/50| •| •| •
AMP48S1A
EHK- 05A(UL)| ** 48| 5| 30.3| 26.8| 35| 30| x| x| •
EHK- 08A(UL)| 7.5| 43.3| 38.1| 45| 40| x| x| •
EHK- 10A(UL)| 10| 56.3| 49.4| 60| 50| x| x| •
EHK- 15B(UL)| 15| 56.3/26.1| 49.4/22.6| 60/30| 50/25| x| x| •
EHK- 20B(UL)| 20| 56.3/52.1| 49.4/45.2| 60/60| 50/50| x| x| •
AMP60S1A
EHK- 05A(UL)| ** 60| 5| 31.8| 28.3| 35| 30| •| •| •
EHK- 08A(UL)| 7.5| 44.8| 39.6| 45| 40| •| •| •
EHK- 10A(UL)| 10| 57.8| 50.9| 60| 60| •| •| •
EHK- 15B(UL)| 15| 57.8/26.1| 50.9/22.6| 60/30| 60/25| •| •| •
EHK- 20B(UL)**| 20| 57.8/52.1| 50.9/45.2| 60/60| 60/50| •| •| •

NOTE: Heat kit suitable for AHU 4-way position installation.
Ampacities for MCA and Fuse/breaker including the blower motor.
Due to ongoing product improvements, specifications and dimensions are subject to change and correction without notice or incurring obligations. Determining the application and suitability for use of any product is the responsibility of the installer. Additionally, the installer is responsible for verifying dimensional data on  the actual product prior to beginning any installation preparations.
Third party incentive and rebate programs have precise requirements as to product performance and certification. All products meet applicable regulations in effect on date of manufacture; however, certifications are not necessarily granted for the life of a product. Therefore, it is the responsibility of the applicant to determine whether a specific model qualifies for these incentive/rebate programs.
“This product complies with all California product labeling laws including, but not limited to, the Safe Drinking Water and To xic Enforcement Act of 1986, more commonly known as Proposition 65.”

Limited Warranty
5 years on unit parts. Unit cost replacement if heat exchanger, condenser coil,
evaporator coil (packaged systems only), or compressor fails in the first year.
With registration, 10 years on compressor and 20 years on heat exchanger.
(Limitations apply, see actual warranty for complete details.)
www.century-hvac.com