NTI TRX Series ii High Efficiency Gas Instruction Manual
- June 28, 2024
- NTI
Table of Contents
- NTI TRX Series ii High Efficiency Gas
- WARNING
- Part 0. General Safety information
- Part 0. General Safety information
- Breathing Hazard – Carbon Monoxide Gas
- Part 1. Installation and Preset Procedure
- Part 2. Operation Sequence and Gas Line Pressure Check
- Part 3. Combustion Check and Calibration
- Part 4. Document the Conversion
- Specifications:
NTI TRX Series ii High Efficiency Gas
INSTRUCTION MANUAL
Models: TRX085, TRX120, TRX110C, TRX150C
WARNING
This conversion kit shall be installed by a qualified installer, service agency, or the gas supplier in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified installer, service agency, or the gas supplier is responsible for the proper installation of this kit.
THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE
CONVERTED APPLIANCE IS CHECKED AS SPECIFIED IN THE MANUFACTURER’S INSTRUCTIONS
SUPPLIED WITH THE KIT, WHICH
NECESSITATES THE USE OF A CALIBRATED CO2/O2 AND CO COMBUSTION ANALYZER.
Part 0. General Safety information
NTI boilers are factory set to operate with Natural Gas. BEFORE OPERATING WITH
PROPANE the boiler must be converted to Propane using this kit.
Use the procedures outlined in these instructions to fully complete the
Natural Gas to LP conversion for models
TRX085, TRX120,
TRX110C and TRX150C.
IF THE KIT CONTENTS DO NOT MATCH THOSE SPECIFIED FOR YOUR BOILER MODEL (SEE TABLE 1), DO NOT PROCEED WITH INSTALLING THE LP-CONVERSION KIT, AND DO NOT OPERATE THE BOILER – CONTACT NTI FOR ASSISTANCE.
Kit Contents:
– Natural to LP Conversion Instructions nr. 1
– LP Conversion Label nr. 1
– LP-Mixer w. Diaphragm (Table 1) nr. 1
– Gasket for gas pipe nr. 2
Part 0. General Safety information
WARNING
These instructions CANNOT be used to convert NTI appliance models not referenced in these instructions. Contact NTI for the Natural Gas to LP conversion kit and instructions for other models.
Failure to apply these instructions properly may result in dangerous Carbon Monoxide levels, fire or explosion leading to property damage, personal injury or death.
ATTENTION: LIQUEFIED PETROLEUM (LP) PROPANE
Liquefied Petroleum (LP) propane gas is heavier than air; therefore, it is imperative that your boiler is not installed in a pit or similar location that will permit heavier than air gas to collect.
Local Codes may require appliances fueled with LP gas be provided with an approved means of removing unburned gases from the room. Check your local codes for this requirement.
WARNING
Breathing Hazard – Carbon Monoxide Gas
- Do not operate heater if flood damaged.
- Install vent system in accordance with local codes and manufacturers installation instructions.
- Do not obstruct heater air intake or exhaust. Support all vent piping per manufacturers installation instructions.
- Do not place chemical vapor emitting products near unit.
- According to NFPA 720, carbon monoxide detectors should be installed outside each sleeping area.
- Never operate the heater unless it is vented to the outdoors.
- Analyze the entire vent srstem to make sure that condensate wil not become trapped in a section of vent pipe and therefore reduce the open cross sectional area of the vent.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
Part 1. Installation and Preset Procedure
1. Install LP-Mixer with LP-Diaphragm
a. Check that the code of the air / gas mixer and the diameter of the gas
diaphragm are those indicated for the model of boiler to be converted – see
Table 1.
b. Turn the 120VAC power supply OFF to the boiler.
c. Turn the gas supply OFF.
d. Remove the front cover from the unit and rotate the control box.
e. Unhook the electrical connection box.
f. Unscrew the 3 screws to remove the junction box support from the fan and silencer
g. Remove the silencer
h. Unscrew the two nuts and remove the gas pipe.
i. Remove the three bolts securing the NG-mixer to the blower; remove the
NGMixer together with the NG Diaphragm.
Save these parts in-case the boiler needs to be converted back to Natural Gas
at a later date.
NATURAL to PROPANE Conversion instructions
j. Secure the LP-Mixer (with LP Diaphragm) to the blower, reusing the bolts
from the previous step.
NOTICE: Verify the O-ring seal between the mixer and blower is correctly
positioned and in good condition before assembling.
K. Reassemble the gas pipe to the gas valve and mixer.
ATTENTION!! Use the new rubber gaskets provided with the kit.
l . Install the silencer and apply the support bracket.
m. Hook the electrical connection box.
2. Perform preliminary adjustment on gas valve throttle screw 4.
a. TRX085 and TRX120 – Adjust throttle screw 4 counter-clockwise 1.5 turns.
b. TRX110C and TRX150C – Adjust throttle screw 4 counter-clockwise 3 turns.
c. Turn the gas supply on and test for gas leaks in all piping.
d. Perform gas line pressure test and combustion calibration in accordance
with Parts 2 and 3.
Part 2. Operation Sequence and Gas Line Pressure Check
WARNING
Failure to perform the Gas Valve and Burner Setup correctly may result in incorrect operation, component failure, property damage, serious injury or death.
1. Operating Sequence
Prior to commencing the Combustion Check and Calibration, perform the
following operating sequence check:
a. Turn the supply of gas to the boiler off.
b. Set the thermostat to the highest setting.
c. Ensure the combustion fan prepurges for a short time prior to activating
the igniter.
d. Ensure the combustion fan postpurges for at least 5 seconds prior to
reactivating the igniter.
e. Set the thermostat to the lowest setting and continue with the Gas Valve
and Burner Setup procedure outlined below.
2. Gas Line pressure
The boiler gas valve is equipped with a Line Pressure Test Port; see screw 1,
Figure 5.
Use the following procedure to measure the gas line pressure to the boiler to
ensure it falls within the range given in Table 2:
a. Turn the supply of gas to the boiler off.
b. Loosen screw 1 (Torx 10 – Line Pressure Test Port). This port is directly
connected to the gas line feeding the boiler. See screw 1, Figure 5.
c. Connect a gas pressure gauge to the line pressure test port using
applicable tubing.
Ensure both ends of the tubing make a tight connection.
d. Turn the gas supply to the boiler on and check for gas leaks.
e. Observe the line pressure under static conditions and compare it to Table
2.
The pressure will be greatest under static conditions.
f. Observe the line pressure with the boiler running, while checking/adjusting
the CO2 at maximum and minimum gas flow rate (see Part. 3).
Compare it to Table 2. The pressure will be lowest during the maximum flow of
gas.
g. Adjust the gas line pressure to ensure the parameters in Table 2 are
attained under all conditions.
If possible, adjust the line pressure to the “Nominal/Desired” value listed in
Table 2 while the unit is operating at the maximum power.
Continue observing gas line pressure until completing of necessary
Checking/Adjusting of the CO2 (see Part 3), in case adjustments need to be
made.
h. Complete pressure testing. Remove the tubing from the test port and then
return the bleed screw of the Line Pressure Test Port to the closed position.
Check for gas leaks.
DANGER
Failure to close the bleed screw of the Line Pressure Test Port will cause a severe leakage of gas, resulting in a fire or explosion causing property damage, serious injury or death.
NOTICE
The line pressure is a function of the gas supply and is affected solely by
field provided parameters such as line size and regulator settings.
Under no circumstances can the boiler gas valve influence or be used to adjust
the gas line pressure.
Part 3. Combustion Check and Calibration
WARNING
Adjustments to the Gas valve may only be made by a qualified gas technician,
while using a calibrated combustion analyzer capable of measuring CO2 and CO.
Adjustments may only be performed if the gas line pressure is maintained above
minimum levels throughout the duration of the test.
See Table 3. Failure to follow these instructions may result in serious injury
or death.
WARNING
FAILURE TO PERFORM THE FLUE GAS ANALYSIS AND ADJUSTMENT AS DETAILED IN THIS SECTION MAY RESULT IN ERRATIC AND UNRELIABLE BURNER OPERATION, LEADING TO REDUCED EFFICIENCY, INCREASED FUEL CONSUMPTION, REDUCED COMPONENT LIFE, HEAT EXCHANGER COMBUSTION DEPOSITS, AND GENERAL UNSAFE OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN SERIOUS INJURY OR DEATH.
1. Preparing the measuring equipment Remove the flue test port plug as illustrated, and insert a calibrated combustion analyzer (see Fig. 11- next page).
NOTICE
Make sure the analyzer is set to the appropriate fuel.
WARNING
It is required to use a calibrated combustion analyzer to verify final adjustment according to the combustion chart (Table 3). Failure to do so could result in serious personal injury or death.
It is very important that the combustion system be set within the recommended
CO2/CO measurements listed in Table 3. Visually looking at the burner does not
determine combustion quality.
Failure to measure combustion with a calibrated combustion analyzer and set
the throttle within the recommended CO2/CO measurements could result in
property damage, severe personal injury, or death.
2. Checking/Adjusting the CO2 at Max Power (100%)
Set the thermostat at the highest possible setting or draw off the domestic hot water at the maximum water flow rate to create a demand for heat.
Enable Burner Test, access the Main Menu by pressing the Menu button.
Turn the dial to select Test Mode and press ENTER. Press ENTER to activate
Burner Test.
Turn the dial to select MAX Power and press ENTER. The boiler turns on and
ramps to Max Power (100%).
(see Note BURNER TEST)
Wait 1 minute for the boiler to stabilize before carrying out the combustion
analyses.
Read the CO2 value (%) and compare it with the values given in the table
below:
WARNING
WARNING! When the Burner Test Function is activated the temperature of the water coming out of the boiler may exceed 179°F.
Note: BURNER TEST
To activate the BURNER TEST access to the Test Mode Menu.
Press the MENU button.
Turn the dial to select Test Mode and press ENTER.
Press ENTER again to select Burner Test.
Turn the dial to select MAX Power and press ENTER.
The boiler turns on and ramps to Max Power (100%).
Set combustion according to Table 3.
Turn the dial to select MIN Power and press ENTER.
The boiler modulates to Min Power (10%).
Set combustion according to Table 3.
Press ESC to stop the test.
ATTENTION!! VALUES MUST BE OBTAINED WITH THE FRONT COVER INSTALLED.
If the CO2 reading differs from the values given in the table, then adjust the
gas valve following the instructions below.
Otherwise move directly to next operation.
ADJUSTING THE GAS VALVE AT MAX POWER (100%)
Adjust the gas valve by turning setting screw 4 clockwise to increase the CO2
level;
counterclockwise to reduce the CO2 level (1 turn adjusts the CO2 level by
approximately 0.3%). Wait 1 minute after each change in setting for the CO2
value to stabilize.
If the value measured corresponds to the value given in Table 3, max
adjustment is complete.
Otherwise continue the setting procedure.
3. Checking/Adjusting the CO2 at Min Power (10%) From the Burner Test screen, turn the dial to select MIN POWER and press ENTER to operate the boiler at minimum power.
Wait 1 minute for the boiler to stabilize before carrying out the combustion
analyses.
If the CO2 (%) reading at Min Power is outside the range indicated in Table 3,
adjust the gas valve following the instructions in Figure 8.
Otherwise proceed directly to step 4.
NOTE: Min Power calibration must be performed after Max Power calibration.
NOTE: The CO2 at Min Power (10%) must NOT be set higher than the CO2 reading at Max Power (100%); it may be set lower by as much as 0.3%
ADJUSTING THE GAS VALVE AT MIN POWER (10%)
Remove cap and adjust screw 2 by turning counter – clockwise to reduce the CO2
level; clockwise to increase the CO2 level (Note: total adjustment should not
exceed 1/4 of a turn from factory setting).
Wait 1 minute after each adjustment for the CO2 value to stabilize.
WARNING! MIN POWER ADJUSTMENT IS VERY SENSITIVE.
(total adjustment should not exceed 1/4 of a turn from factory setting).
If the value measured corresponds to the value given in Table 3 adjustment is
complete. Otherwise continue the setting procedure.
ATTENTION!! IF THE VALUE OF THE CO2 AT MIN POWER HAS BEEN CHANGED, IT IS NECESSARY TO REPEAT THE ADJUSTING AT MAX POWER.
4. Ending Adjustment
1. Exit Test Mode by pressing RESET.
2. Turn down the thermostat and / or stop the DHW draw-off. For Only Heating
Boiler applications reset all thermostatic valves.
3. Reinstall the combustion test port.
See Figure 6.
4. Check for and repair any leaks of gas.
5. Reinstall the front cover.
WARNING
Carbon Monoxide – Never leave the unit operating while producing Carbon Monoxide (CO) concentrations in excess of the values indicated in Table 3. Failure to follow this warning may result in serious injury or death.
WARNING
Breathing Hazard – Carbon Monoxide Gas
Part 4. Document the Conversion
1. Update rating plate
As the certified installer of the Natural Gas to LP Conversion Kit, you must
indicate on the boiler that it has been converted for use with Propane (LP)
Gas:
a. Update Rating Plate Decal – Locate the rating plate decal on the side of
the appliance. Using a regular ink pen, check the box next to “Field converted
to Propane Gas” and fill in the date.
Press hard enough to permanently mark the decal. See Figure 9.
b. Conversion Decal – Fill out the required information on the Conversion
Decal (included in this kit) and affix it to the boiler cabinet adjacent to
the rating plate decal, in a location where it can be easily seen.
See Figure 10.
NTI Boilers Inc.
30 Stonegate Drive Saint John,
NB E2H 0A4 Canada
Technical Assistance: 1-800-688-2575
Website: www.ntiboilers.com
Fax: 1-506-432-1135
Specifications:
-
Models: TRX085, TRX120, TRX110C, TRX150C
-
Conversion Kit No.: 560000222502, 560000222602, 560000222702
-
Gas Type: Natural Gas (Factory Setting), Propane (after conversion)
-
LP-Mixer Diameter: 6.0 mm (TRX150C), 5.5 mm (TRX120), 5.5 mm (TRX110C), 5.5 mm (TRX085)
-
-
FAQ
Q: What should I do if the kit contents do not match those specified for
my boiler model?
A: If the kit contents do not match, do not proceed with installing the LP-
conversion kit, and do not operate the boiler.
Contact NTI for assistance.
Q: Why is it important to convert the boiler from Natural Gas to Propane
using this kit?
A: Failure to convert properly may result in dangerous Carbon Monoxide levels, fire, or explosion leading to property damage, personal injury, or death. It is crucial to follow the conversion instructions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>