Carrier R-454B Fan Coil for Puron Advance Refrigerant Instruction Manual

June 26, 2024
Carrier

R-454B Fan Coil for Puron Advance Refrigerant

Specifications

  • Product: FT5, FG5 Fan Coil for Puron AdvanceTM R-454B
    Refrigerant

  • Capacity: 2 thru 5 Ton

  • Refrigerant: Puron AdvanceTM R-454B

  • Designed for: Upflow, horizontal, or downflow applications

  • Nominal Cooling Capacities: 18,000 through 60,000 Btuh

  • Electric Heater Packages: 5 through 30 kW

Product Usage Instructions

Safety Considerations

Before starting the installation, ensure to follow these safety
considerations:

  • Wear safety glasses, protective clothing, and work gloves.
  • Use a quenching cloth for brazing operations.
  • Have a fire extinguisher available.
  • Read and follow all warnings and cautions in the manual.
  • Consult local building codes and electrical codes.

Installation Steps

  1. Unpack the unit and move it to the final location without
    damaging it.

  2. Inspect the equipment for any damage before installation. File
    a claim if necessary.

  3. Locate the unit rating plate for proper installation
    information and check if it matches job specifications.

  4. If the door gasket is damaged or missing, order a gasket kit to
    ensure compliance with standards.

Brazing and Condensate Pan Attention

Due to low leak requirements, special attention is needed in the
condensate pan and drain connection area when brazing tubing.
Follow the manufacturer’s guidelines for brazing operations.

Electric Heater Packages

If applicable, factory-authorized electric heater packages are
available for installation in the unit to meet heating
requirements. Ensure to follow the provided instructions for
installing these packages.

Frequently Asked Questions (FAQ)

Q: What should I do if the unit is damaged during

shipment?

A: If the unit is damaged during shipment, inspect it for damage
before installation and file a claim with the shipping company if
needed.

Q: Can I use a different refrigerant with this unit?

A: No, this unit is designed specifically for Puron AdvanceTM
R-454B refrigerant and should only be used with this refrigerant as
shipped.

FT5, FG5 Fan Coil for Puron AdvanceTM R-454B Refrigerant 2 thru 5 Ton

Installation Instructions

NOTE: Read the entire instruction manual before starting the installation.

Fig. 1 ­ Typical Unit

A02332A

Table of Contents

Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Check Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Mount Fan Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Upflow Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Modular Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Horizontal Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Downflow Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Manufactured and Mobile Home Housing Applications . . . . . . . . 6 Air Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Heat Staging Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Manufactured Housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Refrigerant Tubing Connection and Evacuation . . . . . . . . . . . . . 12 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Leak Dissipation System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Leak Dissipation System Self-Test . . . . . . . . . . . . . . . . . . . . . . . 14 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Unit Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Easy Select Configuration Taps. . . . . . . . . . . . . . . . . . . . . . . . . . 16 Accessory Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Fan Coil Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . 18 Troubleshooting ECM Motor and Controls . . . . . . . . . . . . . . . . . 19 Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Care and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Safety Considerations
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warning or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
! WARNING
PROPERTY OR PERSONAL INJURY HAZARD Risk of fire. Flammable refrigerant used. To be repaired only by trained service personnel. Do not puncture refrigerant tubing. Auxiliary devices which may be ignition sources shall not be installed in the ductwork, other than auxiliary devices listed for use with the specific appliance. See instructions. Dispose of refrigerant properly in accordance with federal or local regulations. Failure to follow proper R-454B mitigation system installation instructions can result in property damage, personal injury, or death. If any fault codes are listed, please troubleshoot to prevent system malfunction.

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
! WARNING
PERSONAL INJURY / PROPERTY DAMAGE HAZARD Failure to follow this warning could result in property damage, personal injury, or death. For continued performance, reliability, and safety, the only approved accessories and replacement parts are those specified by the equipment manufacturer. The use of non-manufacturer approved parts and accessories could invalidate the equipment limited warranty and result in fire risk, equipment malfunction, and failure. Please review manufacturer’s instructions and replacement part catalogs available from your equipment supplier.
! WARNING
ELECTRICAL OPERATION HAZARD Failure to maintain proper clearances could result in personal injury or death. Before installing or servicing unit, always turn off all power to unit. There may be more than 1 disconnect switch. Turn off accessory heater power if applicable.
! CAUTION
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts.
! CAUTION
HOT TUBE WARNING Failure to follow this caution could result in personal injury and/or property damage. Refrigerant lines can reach or exceed 130 °F (54 °C). Avoid contact with the vapor header or vapor line, especially in Heating Mode. Do not service A2L refrigerant fan coils while these components are hot to avoid risk of ignition source.

Introduction
Model FT5, FG5 Fan Coil units are designed for flexibility and can be used for upflow, horizontal, or downflow (kits required on manufactured and mobile home) applications. These units are designed specifically for Puron AdvanceTM refrigerant R-454B refrigerant and must be used only with Puron AdvanceTM refrigerant R-454B refrigerant air conditioners and heat pumps as shipped.
These units leave the factory compliant with low leak requirements of less than 2% cabinet leakage rate at 1.0 inches W.C. and 1.4% cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard. Because of this, the units need special attention in the condensate pan and drain connection area and when brazing tubing.
These units are available for application in systems of 18,000 through 60,000 Btuh nominal cooling capacities. Factory-authorized, field-installed electric heater packages are available in 5 through 30 kW. See Product Data for available accessory kits.
Installation
Check Equipment
Unpack unit and move to final location. Remove carton taking care not to damage unit.
Inspect equipment for damage prior to installation. File claim with shipping company if shipment is damaged or incomplete. Locate unit rating plate which contains proper installation information. Check rating plate to be sure unit matches job specifications.
NOTE: If the door gasket is damaged or missing, the unit may not meet the ASHRAE 193 standard for cabinet air leakage. See the Product Data for this model or contact your supplier to order the gasket kit.
Mount Fan Coil
Unit can stand or lie on floor, or hang from ceiling or wall. Allow space for wiring, piping, and servicing unit.
IMPORTANT: When unit is installed over a finished ceiling and/or living area, building codes may require a field-supplied secondary condensate pan to be installed under the entire unit. Some localities may allow the alternative of running a separate, secondary condensate line. Consult local codes for additional restrictions or precautions.
NOTE: Nuisance sweating may occur if the unit is installed in a high humidity environment with low airflow.
FT5, FG5 Fan Coils can be installed for upflow and horizontal-left applications as factory shipped. Units can be installed for horizontal-right applications with field modifications. Units may be converted for downflow applications using factory-authorized accessory kits.
NOTE: To ensure proper drainage for horizontal installations, unit must be installed so it is within 1/8 in. (3.2mm) level of the length and width of unit.
Upflow Installation
If return air is to be ducted, install duct flush with floor. Set unit on floor over opening. Only use return-air opening provided. All return air must pass through the coil (see Fig. 2).

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 2

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

Fig. 2 ­ Slope Coil Unit in Upflow Application

A07139A

Fig. 3 ­ Slope Coil in Horizontal-Left Application (Factory Ready)

A07140B

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 3

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions A

FACTORY SHIPPED HORIZONTAL LEFT
APPLICATION
B C

DISSIPATION SENSOR CABLE ROUTING

COIL BRACKET
COIL SUPPORT
RAIL

DRAIN PAN SUPPORT BRACKET

DISSIPATION BOARD AIR SEAL ASSEMBLY

HORIZONTAL DRAIN PAN

DISSIPATION SENSOR REFRIGERANT CONNECTIONS

PRIMARY DRAIN SECONDARY DRAIN

Fig. 4 ­ A-Coil in Horizontal-Left Application (Factory Ready)

COIL BRACKET

A240079

Modular Units

Horizontal Installations

Some sizes of the Fan Coils are available in 2-piece modular construction. Modular construction allows installer to disassemble unit into 2 components, coil box and blower box, for ease of installation (refer to Product Data Sheet, and Fig. 5).
To disassemble unit, remove rear corner brackets by removing 2 screws which secure brackets. Remove either 2 screws in each front corner of coil box, or 2 screws in blower box. Do not remove all 4 screws in each corner. Sections may now be separated by lifting top section from lower section.

Be sure installation complies with all applicable building codes that may require installation of a secondary condensate pan.
1. Arrange support for unit by setting it in or above secondary condensate pan.
2. When suspending unit from ceiling dimples in casing indicate proper location of screws for mounting metal support straps (see Fig. 4).
Horizontal-Right Conversion of Units with Slope Coils

To reassemble, reverse above procedure. Be certain to reinstall all fasteners when reassembling.

! CAUTION

2 SCREWS

BLOWER BOX 2 SCREWS

REAR CORNER BRACKET

COIL BOX

2 SCREWS

Fig. 5 ­ Modular Unit Assembly

A95293

PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage. A gasket kit is required for horizontal slope coil conversion to maintain low air leak/low sweat performance. See Product Data or contact your supplier for the kit number.
1. Remove blower and coil access panels and fitting panel (Fig. 6). 2. Disconnect sensor on drain pan and cut wire tie securing sensor
harness to the coil. 3. Undo sensor wire routing and place entire harness in the control
box. 4. Remove coil mounting screw securing coil assembly to right side
casing flange. 5. Remove coil assembly. 6. Lay fan coil on its right side and reinstall coil assembly with
condensate pan down (Fig. 6). 7. Attach coil to casing flange using previously removed coil
mounting screw. 8. Reconnect sensor wire harness by following routing shown (Fig. 6). IMPORTANT: Sensor must be installed with the connector facing down or facing horizontally. Sensor should never be positioned with connector facing upward. Incorrect sensor position could result in premature failure.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 4

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
9. Make sure pan cap in fitting door is properly seated on fitting door to retain low air leak rating of the unit.
10. Add gaskets from kit per kit instructions. See Product Data for kit number.

11. Align holes with tubing connections and condensate pan connections. Reinstall access panels and fitting panel.
12. Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install grommets after brazing.

COIL BRACKET
COIL SUPPORT RAIL
DRAIN PAN SUPPORT BRACKET

Fig. 6 ­ Slope Coil in Horizontal-Right Application
A
REFRIGERANT CONNECTIONS

HORIZONTAL RIGHT
APPLICATION
B C

A230499

AIR SEAL ASSEMBLY

DISSIPATION BOARD

DISSIPATION HORIZONTAL

SENSOR

DRAIN PAN

DISSIPATION SENSOR CABLE ROUTING

PRIMARY DRAIN SECONDARY DRAIN
Fig. 7 ­ A-Coil in Horizontal-Right Application

A240080

Horizontal Right Conversion of Units With A-Coil
1. Remove blower and coil access panels (Fig. 7).
2. Disconnect and remove sensor on delta plate and install on horizontal drain pan clip (Fig. 21).
IMPORTANT: Sensor must be installed with the connector facing down or facing horizontally. Sensor should never be positioned with connector facing upward. Incorrect sensor position could result in premature failure.
3. Undo sensor wire harness routing and place entire harness in the control box.

4. Remove metal clip securing fitting panel to condensate pan. Remove fitting panel.
5. Remove 2 snap-in clips securing A-coil in unit.
6. Slide coil and pan assembly out of unit.
7. Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on coil support rail on right side of unit.
8. Convert air seal assembly for horizontal right. a. Remove air seal assembly from coil by removing 4 screws (Fig. 22).

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 5

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
b. Remove air splitter (B) from coil seal assembly by removing 3 screws (Fig. 7 inset).
c. Remove filler plate (A) and install air splitter (B) in place of filler plate.
d. Install filler plate (A) as shown in horizontal right application. e. Remove condensate troughs (C) and install on opposite tube
sheets. f. Install hose onto plastic spout. 9. Install horizontal pan on right side of coil assembly. 10. Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil support rails. 11. Reinstall 2 snap-in clips to correctly position and secure coil assembly in unit. Be sure clip with large offsets is used on right side of unit to secure horizontal pan. 12. Reconnect the sensor wire harness by following the routing shown in Fig. 7. 13. Remove two oval fitting caps from left side of the coil, access panel, and fitting panel. 14. Remove insulation knockouts on right side of coil access panel. 15. Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel. 16. Install condensate pan fitting caps (from Step 10) in right side of coil door making sure that cap snaps and seats cleanly on back side of the coil door. Make sure no insulation interferes with seating of cap. 17. Reinstall access and fitting panels, aligning holes with tubing connections and condensate pan connections. Be sure to reinstall metal clip between fitting panel and vertical condensate pan. 18. Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
Downflow Installations
! CAUTION
UNIT OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or property damage. The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A-coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.
In this application, field conversion of the evaporator is required using accessory downflow kit along with an accessory base kit. Use fireproof resilient gasket, 1/8- to 1/4-in. (3.2 to 6.4mm) thick, between duct, unit, and floor. NOTE: To convert units for downflow applications, refer to Installation Instructions supplied with kit for proper installation. See the Product Data or contact your supplier for the kit number. Use fireproof resilient gasket, 1/8- to 1/4-in. (3.2 to 6.4mm) thick, between duct, unit, and floor.

! CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage. A gasket kit is required for horizontal slope coil conversion to maintain low air leak/low sweat performance. See Product Data or contact your supplier for the kit number.
Manufactured and Mobile Home Housing Applications
1. Fan coil unit must be secured to the structure using field-supplied hardware.
2. Allow a minimum of 24″ (610 mm) clearance from access panels. 3. Recommended method of securing for typical applications
a. If fan coil is away from wall, attach pipe strap to top of fan coil using No. 10 self tapping screws. Angle strap down and away from back of fan coil, remove all slack, and fasten to wall stud of structure using 5/16-in. (8mm) diameter lag screws. Typical both sides of fan coil.
b. If fan coil is against wall, secure fan coil to wall stud using 1/8-in. (3mm) thick right-angle brackets. Attach brackets to fan coil using No. 10 self tapping screws and to wall stud using 5/16-in. (8mm) diameter lag screws (see Fig. 7).
4″ (102mm) MAX
SECURE FAN COIL TO STRUCTURE UNIT AWAY FROM WALL PIPE STRAP (TYPICAL BOTH SIDES)
OR
UNIT AGAINST WALL .125″ (3mm) MOUNTING BRACKET (TYPICAL BOTH SIDES)

DOWN FLOW BASE KIT (KFACB)
SECURE UNIT TO FLOOR ANGLE BRACKET OR PIPE STRAP

4″ (102mm) MAX
Fig. 8 ­ A-Coil

A07567

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 6

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
Air Ducts
Connect supply-air duct over outside of 3/4-in. (19mm) flange provided on supply-air opening. Secure duct to flange with proper fasteners for type of duct used, and seal duct-to-unit joint. Duct connection flanges are provided on unit air discharge connection. When using Fan Coil units with 20-, 24-, and 30-kW electric heaters, maintain a 1-in. (25mm) clearance from combustible materials to discharge plenum and ductwork for a distance of 36 in. (914mm) from unit. Use accessory downflow base to maintain proper clearance on downflow installations. Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and covered with vapor barrier.
! WARNING
EXPLOSION AND PERSONAL HEALTH HAZARD Failure to follow this warning could result in personal injury, death, and/or unit damage. Ensure to keep any required ventilation openings clear of obstruction. Air ducts connected to the appliance shall not contain a POTENTIAL IGNITION SOURCE. Auxiliary devices which may be a POTENTIAL IGNITION SOURCE shall not be installed in the duct work. Examples of such POTENTIAL IGNITION SOURCES are hot surfaces with a temperature exceeding 1292°F (700°C) and electric switching devices. Ensure only manufacturer approved auxiliary devices are installed.
Ductwork Acoustical Treatment Metal duct systems that do not have a 90° elbow and 10 ft (3m) of main duct to first branch takeoff may require internal acoustical insulation lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with National Fire Protection Association Standards 90A or B as tested by UL Standard 181 for Class 1 air ducts.
Electrical Connections
On units with a factory installed disconnect with pull-out removed, service and maintenance can be safely performed on only the load side of the control package.
! WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Field wires on the line side of the disconnect found in the fan coil unit remain live, even when the pull-out is removed. Service and maintenance to incoming wiring cannot be performed until the main disconnect switch (remote to the unit) is turned off.
Line-Voltage Connections To pair an electric heater with the fan coil, remove and discard power plug from fan coil and connect the heater plug to the plug from unit wiring harness. (See Electric Heater Installation Instructions.) For units without electric heat: 1. Connect 208/230V power leads from field disconnect to yellow and
black stripped leads. 2. Connect ground wire to unit ground lug.

Check all factory wiring per unit wiring diagram and inspect factory wiring connections to be sure none were loosened in transit or installation.
! WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Tag disconnect switch with a suitable warning label. Turn off accessory heater power if applicable.
! CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or property damage. If a disconnect switch is to be mounted on unit, select a location where drill or fastener will not contact electrical or refrigerant components.
NOTE: Before proceeding with electrical connections, make certain that supply voltage, frequency, and phase are as specified on unit rating plate. Be sure that electrical service provided by the utility is sufficient to handle the additional load imposed by this equipment. See unit wiring label for proper field high- and low-voltage wiring. Make all electrical connections in accordance with NEC and any local codes or ordinances that may apply. Use copper wire only. The unit must have a separate branch electric circuit with a field-supplied disconnect switch located within sight from, and readily accessible from the unit. 24V Control System Connections to Unit Printed Circuit Board (PCB) Refer to unit wiring instructions for recommended wiring procedures. Use No. 18 AWG color-coded, insulated (35°C minimum) wires to make low-voltage connections between thermostat and unit. If thermostat is located more than 100 ft (30m) from unit (as measured along the low-voltage wires), use No. 16 AWG color-coded, insulated (35°C minimum) wires. PCB is circuited for single-stage heater operation. When additional heater staging is desired as applicable, remove Jumper J2 on PCB to enable staging. Connect low-voltage leads to thermostat and outdoor unit (see Fig. 13 through Fig. 16). Easy Select Board Jumpers J1 ­ This jumper must be pulled to activate dehumidification mode. The jumper connects R to DH. With the jumper in, the DH terminal is always energized. With the jumper pulled, the DH terminal is de- energized. A control such as the thermidistat must be used to supply the 24V signal when there is no call for dehumidification, and turn off the 24V when there is a call for dehumidification. J2 ­ This jumper activates heat staging. The jumper connects the W1 and W2 terminals together. If either is energized, W2 airflow is delivered. With the jumper pulled, there are separate airflows for W1 and W2. J4 ­ This jumper is for InteliSenseTM operation (FT5). As shipped, Y1 is connected to Y/Y2 by a field-removable jumper J4. With the jumper in place, in single stage operation InteliSenseTM communication is enabled. For 2-stage application, remove jumper J4.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 7

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

A98477A
Fig. 9 ­ FT5 Models, Fan Coil Wiring with 1-Speed Air Conditioner

A98478A
Fig. 10 ­ FT5 Models, Fan Coil Wiring with 2-Speed Air Conditioner

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 8

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

A98475A
Fig. 11 ­ FT5 Models, Fan Coil Wiring with 1-Speed Heat Pump

A02005A
Fig. 12 ­ FT5 Models, Fan Coil Wiring with 2-Speed Heat Pump

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 9

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

Y/Y2 W1 R W2
G
ACC
C

R
(Pin 1)
Common (Pin 8)
YEL Y-IN
(Pin 5)
WHT W-IN
(Pin 3)

Red

SEC-2

Red

24V

BLK

SEC-1

BRN

Common

Jumper Informa J1 IS REMOVED FOR DEHUMIDIFY MODES J2 IS REMOVED FOR HEAT STAGING

DH

J1

R

R

W-OUT
(Pin 7)

WHT/VIO

W1
J2
W2

Y-OUT
(Pin 4)

YEL/VIO

Y1

Y/Y2

Y

G

HUMIDIFIER (24 VAC)

O

C

C

A240275
Fig. 13 ­ FG5 Models, Fan Coil Wiring with 1-Speed Air Conditioner

Y1 W1
R
W2
Y/Y2 G
ACC
C

Pin 1
(24V)
Common (Pin 8)
YEL Y-IN
(Pin 5)
WHT W-IN
(Pin 3)

Red

SEC-2

Red

24V

BLK

SEC-1

BRN

Common

Jumper Information
J1 IS REMOVED FOR DEHUMIDIFY MODES J2 IS REMOVED FOR HEAT STAGING

DH

J1

R

R

W-OUT
(Pin 7)

WHT/VIO

W1
J2
W2

Y-OUT
(Pin 4)

YEL/VIO

Y1

Y1

Y/Y2

Y2

G

HUMIDIFIER (24 VAC)

O

C

C

A240276
Fig. 14 ­ FG5 Models, Fan Coil Wiring with 2-Speed Air Conditioner

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 10

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

Y1 W1
R
W2
G O C
ACC

Pin 1
(24V)
Common (Pin 8)
YEL Y-IN
(Pin 5)
WHT W-IN
(Pin 3)

Red

SEC-2

Red

24V

BLK

SEC-1

BRN

Common

Jumper Information J1 IS REMOVED FOR DEHUMIDIFY MODES J2 IS REMOVED FOR HEAT STAGING

DH

J1

R

R

W-OUT
(Pin 7)

WHT/VIO

W1
J2
W2

Y-OUT
(Pin 4)

YEL/VIO

Y1

Y/Y 2

W2 Y

G

O

O

C

C

HUMIDIFIER (24 VAC)

Y1 W1
R
W2
Y/Y2 G O C
ACC

Pin 1
(24V)
Common (Pin 8)
YEL Y-IN
(Pin 5)
WHT W-IN
(Pin 3)

Red

SEC-2

Red

24V

BLK

SEC-1

BRN

Common

Jumper Information
J1 IS REMOVED FOR DEHUMIDIFY MODES J2 IS REMOVED FOR HEAT STAGING

DH

J1

R

R

W-OUT
(Pin 7)

WHT/VIO

W1
J2
W2

Y-OUT
(Pin 4)

YEL/VIO

Y1

Y/Y2

W1
Y1 Y2

G

O

O

C

C

HUMIDIFIER (24 VAC)

A240277
Fig. 15 ­ FG5 Models, Fan Coil Wiring with 1-Speed Heat Pump

A240278
Fig. 16 ­ FG5 Models, Fan Coil Wiring with 2-Speed Heat Pump

Heat Staging Option

Heat staging of the electric heat package is possible when the Fan Coil is installed as a part of a single speed heat pump system using a corporate 2-speed thermostat or capable zoning control and any one of the following electric heat packages:

Relay Heaters

KFFEH2901N09

KFFEH3001F15

KFFEH3101C15

KFFEH3201F20

KFFEH3301C20

Complete system low-voltage wiring as shown in Fig. 13 thru Fig. 16.
NOTE: Where local codes require thermostat wiring be routed through conduit or raceways, splices can be made inside the fan coil unit. All wiring must be NEC Class l and must be separated from incoming power leads.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 11

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
A factory authorized disconnect kit is available for installation of all single phase 3kW ­ 10kW heaters. When electric heat packages with circuit breakers are installed, the circuit breaker can be used as a disconnect. The factory installed location for the dissipation board interferes with the 24kW, and 30kW heaters. To account for this, an enclosure is included with the heater kit. Follow all Electric Heat Instructions on how to move the dissipation board into the enclosure on the outside of the unit.. Transformer is factory wired for 230V operation. For 208V applications, disconnect black wire from 230V terminal on transformer and connect it to 208V terminal (see Fig. 17).

SECONDARY

BRN RED
PRIMARY
YEL BLK

C 208 230

YEL / GRN TO GROUND LUG

Fig. 17 ­ Transformer Connections

A05182A

The secondary circuit of transformer is protected by a 5-amp fuse

mounted on printed-circuit board.

Manufactured Housing

In manufactured housing applications, the Code of Federal Regulations, Title 24, Chapter XX, Part 3280.714 requires that supplemental electric heat be locked out at outdoor temperatures above 40°F (4°C) except for a heat pump defrost cycle. A corporate thermostat in conjunction with an outdoor sensor can be used to lock out supplemental heat above 40°F (4°C). Refer to thermostat instructions for details. If a non-corporate thermostat is used, an outdoor thermostat may be required.
Ground Connections

! WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. According to NEC, NFPA 70, and local codes, the cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. If conduit connection uses reducing washers, a separate ground wire must be used.

NOTE: Use UL listed conduit and conduit connector to connect supply wire(s) to unit and obtain proper grounding. Grounding may also be accomplished by using grounding lug provided in control box.
Use of dual or multiple supply circuits will require grounding of each circuit to ground lugs provided on unit and heaters.
Refrigerant Tubing Connection and Evacuation
Insulate entire suction tube. Do not use damaged, dirty, or contaminated tubing because it may plug refrigerant flow control device.
Always evacuate coil and field-supplied tubing to 500 microns before opening outdoor unit service valves.

! CAUTION
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product or property damage. A brazing shield MUST be used when tubing sets are being brazed to the unit connections to prevent damage to the unit surface and condensate pan fitting caps.
Units have sweat suction and liquid tube connections. Make suction tube connection first. 1. Cut tubing to correct length. 2. Insert tube into sweat connection on unit until it bottoms. 3. Braze connection using silver bearing or non-silver bearing brazing
materials. Do not use solder (materials which melt below 800°F). Consult local code requirements.
! CAUTION
PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product or property damage. Wrap a wet cloth around rear of fitting to prevent damage to TXV and factory-made joints.
4. Evacuate coil and tubing system to 500 microns using deep vacuum method.
Condensate Drain
To connect drains the cap openings must be removed. Use a knife to start the opening near the tab and using pliers, pull the tab to remove the disk. Clean the edge of the opening if necessary and install the condensate line. Finally caulk around the lines where they exit the fitting to retain the low leak rating of the unit.
! CAUTION
UNIT OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or property damage. The conversion of the fan coil to downflow requires special procedures for the condensate drains on both A-coil and slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the unit.
Units are equipped with primary and secondary 3/4-in. (19mm) FPT drain connections. For proper condensate line installation see Fig. 2, Fig. 4, Fig. 5, Fig. 6, and Fig. 8. To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include properly-sized condensate traps (see Fig. 18 and Fig. 20). Factory- approved condensate traps are available. Be sure to install plastic push-in plugs in unused condensate drain fittings. It is recommended that PVC fittings be used on the plastic condensate pan. Do not over-tighten. Finger-tighten plus 1-1/2 turns. Use pipe dope.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 12

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

UNIT

2″ MIN (51 mm)

2″ MIN (51 mm)

Fig. 18 ­ Recommended Condensate Trap

A03002

! CAUTION

PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or property damage. Shallow running traps are inadequate and DO NOT allow proper condensate drainage (see Fig. 19).

DO NOT USE SHALLOW RUNNING TRAPS!

Fig. 19 ­ Insufficient Condensate Trap

A03013

NOTE: When connecting condensate drain lines avoid blocking filter access panel. Prime both primary and secondary condensate traps after connecting to drain pan.If unit is located in or above a living space where damage may result from condensate overflow, a field-supplied external condensate pan should be installed underneath the entire unit, and a secondary condensate line (with appropriate trap) should be run from the unit into the pan.

Any condensate in this external condensate pan should be drained to a noticeable place. As an alternative to using an external condensate pan, some localities may allow the use of a separate 3/4-in. (19mm) condensate line (with appropriate trap) to a place where the condensate will be noticeable. The owner of the structure must be informed that when condensate flows from the secondary drain or external condensate pan, the unit requires servicing, or water damage will occur.

Install traps in condensate lines as close to the coil as possible (Fig. 20). Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from overflowing the drain pan. Prime all traps, test for leaks, and insulate traps if located above a living area.

PRIMARY TRAP REQUIRED (USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF SUFFICIENT DEPTH.
STANDARD P-TRAPS ARE NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED CONDENSATE TRAP)

FILTER ACCESS PANEL
SECONDARY DRAIN WITH APPROPRIATE TRAP REQUIRED (USE FACTORY KIT OR FIELD- SUPPLIED TRAP)

Fig. 20 ­ Proper Condensate Trap

A03003

Condensate drain lines should be pitched downward at a minimum of 1 in. (25mm) for every 10 ft. (3m) of length. Consult local codes for additional restrictions or precautions.

! CAUTION
UNIT COMPONENT HAZARD Failure to follow this caution may result in product damage. Never operate unit without a filter. Damage to blower motor or coil may result. Factory authorized filter kits must be used when locating the filter inside the unit. For those applications where access to an internal filter is impractical, a field-supplied filter must be installed in the return duct system.

IMPORTANT: Factory authorized filters must be used when locating the filter inside the unit (see Table 1).
Table 1 ­ Filter Kits

FILTER KIT (12 PACK)

PART NUMBER AFAFLTMED12A AFAFLTLRG12A AFAFLTXXL12A

SIZE USED WITH 24
36, 48 60

Leak Dissipation System

! WARNING
PERSONAL INJURY OR PROPERTY DAMAGE HAZARD Failure to follow proper R-454B mitigation system installation instructions can result in property damage, personal injury, or death. If any fault codes are listed, please troubleshoot to prevent system malfunction.
The 24-60 size units come equipped with a factory wired R-454B leak detection and dissipation system to ensure safe operation during a leak. The system consists of a bracket, a PCB, a A2L Detection Sensor, and a drain pan clip. Failure to install this system will result in potentially hazardous conditions and improper equipment operation, and void all system warranties and liabilities. All units are shipped with the A2L Detection Sensor located in the upflow position. For sizes 36, the sensor will always be installed on the drain pan clip.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 13

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
! WARNING
PRODUCT OPERATION / INJURY HAZARD Failure to follow this warning could cause property damage or personal injury. Make sure the sensor is not exposed to significant amounts of dust/dirt contamination. This could clog the sensor and prevent proper functioning. For sensor cleaning instructions, refer to service manual.

A230490
Fig. 21 ­ Dissipation Sensor Mounted on Drain Clip For sizes 24, 48-60, the sensor comes factory installed on the delta plate (Fig. 22, Fig. 23). For horizontal right and left, the sensor will need to be moved to the drain pan clip (Fig. 21, Fig. 5, Fig. 6, Fig. 7). IMPORTANT: Sensor must be installed with the connector facing down or facing horizontally. Sensor should never be positioned with connector facing upward. Incorrect sensor position could result in premature failure.
! WARNING
PRODUCT OPERATION / INJURY HAZARD Failure to follow this warning could cause product damage or personal injury. Make sure the sensor is not exposed to significant amounts of dust/dirt contamination. This could clog the sensor and prevent proper functioning. For sensor cleaning instructions, refer to service manual.

A230502
Fig. 23 ­ Slope Coil Vertical Dissipation Sensor Factory Location
The A2L Detection Sensor is attached to a wiring harness that connects the sensor to the dissipation board. In upflow, the routing of the wire harness is up the right side of the unit behind the wire retainers for the cabinet insulation. At each wire retainers, the harness is attached using two wire ties. When converting unit to horizontal or downflow, follow routing shown in Fig. 5, Fig. 6, or Fig. 7. When converting the unit to any orientation, ensure the sensor wiring harness is disconnected and the wire harness has been placed in the control box before any components are moved.
Refer to Fig. 10 through Fig. 17 for low voltage field connections between the dissipation board and the thermostat. All control wires are labeled with the wire function and landing point.
Leak Dissipation System Self-Test

Power on the unit and verify proper functioning of equipment. The yellow LED on the dissipation board should be steady. If flash codes are present, see (Troubleshooting on p15).
NOTE: Operation of the Test Mode is only possible if no faults exist on the dissipation board.
IMPORTANT: Press the Test button for roughly ONE SECOND to enter Test Mode. Pressing the Test button for a longer periods enables different functions (Table 2).
Press the Test button on the dissipation system control board to ensure proper dissipation system operation under each test condition listed below. After pressing the Test button, system will enter Dissipation Mode for 60 seconds to help verify correct operation.

Table 2 ­ Dissipation Board Test Button Functions

Hold Button Time (sec) 1 – 4 5 – 29 30+
3 rapid presses

Function Dissipation Mode for 60 seconds
Display flash code history Flash code 6
Clear flash code history

Ensure that the fan coil is able to meet the minimum required dissipation mode airflows. These required minimum airflow rates during Dissipation Mode are listed in Table 4. They are based on the total system refrigerant charge quantity.

A230501
Fig. 22 ­ A-Coil Vertical Dissipation Sensor Factory Location

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 14

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

Table 3 ­ Required Operational Checks to Ensure Proper Dissipation System Function

Normal Operation

Test #

T-Stat Call

Compressor Indoor Fan

Electric/Gas Heat

1

None

Off

Off

Off

2

Cool

On

On

Off

3

Heat

Off

On

On

Dissipation Activated

4

None

Off

On

Off

5

Cool

Off

On

Off

6

Heat

Off

On

Off

Table 4 ­ Required Minimum Dissipation Mode Airflows, based on Total System Refrigerant Charge Quantity

Total System Charge (lb)
5 6 7 8 9 10 11 12 13 14 15

Minimum Required Dissipation Airflow
(CFM) 133 160 186 213 239 266 293 319 346 372 399

Total System Charge (lb)
16 17 18 19 20 21 22 23 24 25

Minimum Required Dissipation Airflow
(CFM) 426 452 479 505 532 559 585 612 639 665

Troubleshooting
For all flash codes, first try power cycling the system to remove the code. No Power Verify the wiring to/from pins 1 and 8 on the power harness plug. Check the 24V system wiring from the transformer. Flashing 1 Check for refrigerant leaks using an independent R-454B detector. If no leaks are present, replace the sensor. Flashing 2 Check both ends of the sensor wire harness to ensure proper attachment. Power cycle the system to check whether the flash code has been removed. If the flash code is still present, replace the sensor. Flashing 3 Check for refrigerant leaks using an independent R-454B detector. Flashing 4 If the code does not clear after power cycling the system, replace the dissipation board. Flashing 5 If the code does not clear after power cycling the system, replace the sensor. Flashing 6 Press the test button repeatedly. Power cycle the system. If the button cannot be reset, replace the dissipation board. Flashing 7 Verify wiring of all “Y” and “W” wires in the applicable wiring diagram.

Flashing 8 Verify wiring of all “Y” and “W” wires in the applicable wiring diagram.

Table 5 ­ Flash Code Chart

Yellow LED

Reason

Mode

Solid

Normal Operation

Normal Operation

Flashing 1

Sensor >= 20% LFL

Dissipation

Flashing 2

Sensor Open

Dissipation

Flashing 3 Normal Mitigation after Leak

Dissipation

Flashing 4

No Power to G Output Dissipation with no Blower

Flashing 5 Fault with A2L Digital Sensor

Dissipation

Flashing 6 Test Button Stuck (>30 s)

Dissipation

Flashing 7

Y or W Wiring Inverted

Normal Operation

Flashing 8

Y or W Shorted

Normal Operation

Unit Start-Up
Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 15

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
Easy Select Configuration Taps
Easy Select taps are used by the installer to configure a system. The ECM motor uses the selected taps to modify its operation to a pre-programmed table of airflows (see Table 8 and Table 10). Airflows are based on system size or mode of operation and those airflows are modified in response to other inputs such as the need for de-humidification (see Fig. 24 and Fig. 25 and Table 6).
LOW VOLTAGE TERMINAL BLOCK

A.

B.

A BC D

C.

A BC D

D.

E.

F.

A95276B
Fig. 25 ­ Connection Detail of Printed-Circuit Board (also showing 12-pin cable), applicable to FT5, FG5

MOLEX 12-PIN CONNECTOR

Fig. 24 ­ Detail of Printed-Circuit Board

A95275BB

(bottom part of board is InteliSense for FT5 only)

The Fan Coil must be configured to operate properly with system components with which it is installed. To successfully configure a basic system (see information printed on circuit board label located next to select pins), move the 6 select wires to the pins which match the components used.
A 16×4 motor signal translator is present for the translation of data from the board to the motors and is mounted on the back of the PCB bracket. Ensure that the connections are secure.
Table 6 ­ Airflow Adjustment Table

Unit Size

AUX Heat Range (kW/CFM)

VIO

A

B

C

D

24

0-20 / 1200 0-15 / 1050 0-10 / 750 0-5 / 700

36

0-20 / 1225 0-15 / 1050 0-10 / 750 0-5 / 700

48

0-30 / 1500 0-20 / 1350 0-15 / 1200 0-10 / 1000

60

0-30 / 1750 0-20 / 1350 0-15 / 1250 0-10 / 1200

AC/HP Size

BLU

A

B

C

D

24

036

030

024

018

36

042

036

030

024

48

048

042

036

030

60

060

048

042

036

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 16

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
AUX HEAT KW/CFM – Select Heater Range For Size of Electric Heater Installed
Installer must select the auxiliary heat airflow approved for application with kW size heater installed. If no heater is installed, this step can be skipped. Each select pin is marked with a range of heaters for which airflow, also marked, is approved. For increased comfort select the narrowest kW range matching the heater size, for example, 0-10 for 10-kW heater. This airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe and continuous operation (see Table 11 and Table 12 for airflow delivery and minimum CFM). Note that airflow marked is the airflow which will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. In heat pump heating mode when electric heaters are energized, the ECM motor will run the higher of heat pump heating airflow and electric heater airflow to ensure safe heater operation. The factory selection is the largest heater range approved (see Fig. 24, A as indicated).
AC/HP SIZE – Select System Size Installed
The factory setting for air conditioner or heat pump size is the largest unit meant for application with the model of fan coil purchased. Installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for the size unit installed. This applies to all operational modes with the exception of electric heat modes (see Fig. 24, B as indicated).
SYSTEM TYPE – Select System Type Installed AC or HP
The type of system must be selected:
1. AC – Air conditioner
2. HP-COMFORT – Heat Pump Comfort provides approximately 315 CFM per ton for higher normal heating air delivery temperature. Provides approximately 350 CFM per ton cooling airflow for good humidity removal.
3. HP-EFF – Heat Pump Efficiency provides same airflow for heating and cooling modes to increase overall HP efficiency; approximately 350 CFM per ton. The factory setting is AC. (See Fig. 24, C as indicated.)
AC/HP CFM ADJUST – Select Medium, Low, or High Airflow
To provide airflow at rates described above, the AC/HP ADJUST select is factory set to the nominal (nom) tap. The adjust selections HI/LO will regulate airflow supplied for all operational modes, except non-heat pump heating modes. HI provides 15% airflow over nominal unit size selected and LO provides 10% airflow below nominal unit size selected. Adjust selection options are provided to adjust airflow supplied to meet individual installation needs for such things as noise, comfort, and humidity removal (see Fig. 24, D as indicated).
ON/OFF DELAY – Select Desired Time Delay Profile
NOTE: Delay selections are active in cooling and heat pump heating modes only. Auxiliary heating modes have a 1-minute off-delay and zero on-delay programmed into the ECM motor that cannot be overridden.
Four motor operation delay profiles are provided to customize and enhance system operation (see Fig. 24, E as indicated). Selection options are:
1. The standard 90-second off-delay (Factory setting) at 100% airflow.
2. No-delay option used for servicing unit or when a thermostat is utilized to perform delay functions.
3. A 30-second on-delay with no airflow / 90-second off-delay at 100% airflow profile is used when it is desirable to allow system coils time to heat-up /cool-down in conjunction with the airflow.

4. ENH, enhanced selection, provides a 30-second on-delay with no airflow / plus 150-second at 70% airflow / no off-delay for added comfort. This profile will minimize cold blow in heat pump operation and could enhance system efficiency.
CONTINUOUS FAN – Select Desired Fan Speed When Thermostat is Set on Continuous Fan
NOTE: If installed with a 2-speed outdoor unit, do not select HI speed continuous fan. If HI is selected, low speed compression will also run HI speed possibly resulting in insufficient dehumidification.
1. LO speed – factory setting, 50% cooling mode airflow.
2. MED speed – move connector to MED, 80% cooling mode airflow.
3. HI speed – move connector of HI, 100% cooling mode airflow (see Fig. 24, F as indicated).
Low-Voltage Circuit Fusing and Reference
The low-voltage circuit is fused by a board-mounted 5-amp automotive fuse placed in series with the transformer 24VAC (SEC1 for FT5 and SEC2 for FG5) and the R circuit. The C circuit of the transformer is referenced to chassis ground through a printed circuit run at COM (SEC2 for FT5 and SEC1 for FG5) connected to metal standoff marked with ground symbol. Basic Fan Coil Configuration
The following basic configuration of the fan coil will provide ARI rated performance of the heat pump:
1. AUX HEAT KW/CFM – Select the heater range for the size electric heater installed.
2. AC/HP SIZE – Select system size installed.
3. SYSTEM TYPE – Select system type HP-EFF.
4. AC/HP CFM ADJUST – Select NOM.
5. ON/OFF DELAY – Select 0/90 profile.
6. CONTINUOUS FAN – Select desired fan speed when thermostat is set to continuous fan.
COMFORT OPTIONS – Warmer Heating
The FT5, FG5 Fan Coils provide better than average humidity control and heated air temperature. This configuration will improve the comfort provided by the heat pump system if more humidity removal or if warmer heating air is desired. While providing this improved comfort, the heat pump system will operate efficiently, but not at the published HSPF or ARI SEER efficiency.
The following fan coil configuration is recommended for maximum heating and cooling/dehumidifying comfort (see Fig. 24):
1. AUX HEAT KW/CFM – Select narrowest heater range to match size of electric heater installed (skip this step if no heater is installed).
2. AC/HP SIZE – Select system size installed.
3. SYSTEM TYPE – Select system type HP-COMFORT (for heat pump system) or AC (for air conditioner system).
4. AC/HP CFM ADJUST – Select LO.
5. ON/OFF DELAY – Select ENH profile.
6. CONTINUOUS FAN – Select desired fan speed when thermostat is set to continuous fan.
7. If the fan coil is installed with Heat Staging capable electric heaters, remove jumper J2 (see Fig. 24).
NOTE: If configuring to run warmer heating, do not remove jumper J2 when using 5-, 8-, or 10-kW heaters.
8. Remove jumper J1 to activate dehumidify modes.
9. Wire low voltage connections as shown in Fig. 13 thru Fig. 16.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 17

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

This configuration provides the following comfort enhancements: a. A 30-second blower-on delay with 150 seconds at 70% airflow to allow the indoor coil to warm up or cool down before the blower is asked to deliver 100% airflow reducing the cold blow sensation at start-up in heating and allowing the indoor coil to more quickly reach wet coil operating conditions in cooling. b. No blower off-delay eliminates cold blow which may be associated with running the blower after shut down of the compressor and avoids re-evaporation of condensed moisture after cooling/dehumidifying operation. c. Lower airflow while the compressor is running to reduce draft effects and increase heating air temperature and improved humidity control during cooling operation. d. Staging of the electric heater elements to more closely match heating load requirements and provide more consistent heating air temperatures.
Accessory Installation
Accessory Electric Heaters
Electric heaters may be installed with the Fan Coil per instructions supplied with electric heater package. See unit rating plate for factory-approved electric heater kits.
NOTE: Units installed without electric heat should have a sheet metal block- off plate covering the heater opening. This reduces air leakage and formation of exterior condensation.
Auxiliary Terminals
The AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal, and provide a 24VAC signal whenever the G terminal is energized (see Fig. 24).
Electronic Air Cleaner Connections
The AUX1 and AUX2 terminals are not always energized during blower operation, as described above. When using an electronic air cleaner with the Fan Coil, use Airflow Sensor Part No. KEAAC0101AAA. The airflow sensor turns on electronic air cleaner when the fan coil blower is operating.
Humidifier/Humidistat Connections
Easy Select Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard humidistat (see Fig. 26). These terminals are energized with 24VAC when G thermostat signal is present (see Fig. 27). Alternately, the 24VAC signal may be sourced from the W and C terminal block connections when electric heaters are used as primary heating source.

HUMIDISTAT

HUM 1 (C)
HUM 2 (G)

24-VAC

TO HUMIDIFIER HUMIDIFIER WIRING

Fig. 26 ­ Humidifier Wiring

A95317

Dehumidify Capability with Standard Humidistat Connection

Latent capacities for systems using the Fan Coil are better than average systems. If increased latent capacity is an application requirement, the field wiring terminal block provides connection terminals for use of a standard humidistat. The Fan Coil will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80% of nominal cooling mode airflow. This reduction will increase the system latent capacity until the humidity falls to a level which causes the humidistat to close its contacts. When the contacts close, the airflow will return to 100% of the selected cooling airflow. To activate this mode, remove Jumper J1 and wire in a standard humidistat (see Fig. 27).

EASY SELECT BOARD TERMINAL
BLOCK

J1

DH

REMOVE

R

JUMPER

HUMIDISTAT

Fig. 27 ­ Humidistat Wiring for De-Humidify Mode A95316
Dehumidify Capabilities
This model fan coil is capable of responding to a signal from indoor system control. No special setup or wiring of fan coil is required.
Fan Coil Sequence of Operation
The FT5, FG5 will supply airflow in a range which is more than twice the range of a standard fan coil. It is designed to provide nominal cooling capacities at a 50°F (10°C) evaporator temperature and the required airflow which enables it to match with 4 air conditioner or heat pump system sizes. Table 7 outlines the CFM range for the different Fan Coil sizes.
Continuous Fan · Thermostat closes circuit R to G. · The blower runs at continuous fan airflow.
Cooling Mode – Single Speed · If indoor temperature is above temperature set point and humidity is
below humidity set point, thermostat closes circuits R to G, R to Y/Y2 and R to O. · The fan coil delivers single speed cooling airflow.
Cooling Mode – Dehumidification · If indoor temperature is above temperature set point and humidity is
above humidity set point, thermostat closes circuits R to G, R to O, and R to Y/Y2, and humidistat opens R to DH. · The fan coil delivers airflow which is approximately 80% of the nominal cooling airflow to increase the latent capacity of the system.
Electric Heat Heating Mode · Thermostat closes circuit R to W/W1, or W2. · The fan coil delivers the selected electric heat airflow. Heat Pump Heating Mode – Single Speed · Thermostat closes circuits R to G and R to Y/Y2. · The fan coil delivers single speed heat pump heating airflow.
Heat Pump Heating with Auxiliary Electric Heat · Thermostat closes circuits R to G, R to Y/Y2 and/or R to Y1 with R to
W/W1 or W2 (and R to O in the case of defrost). · In the event that electric heating is called for by the thermostat while
the heat pump is also operating in either heating or defrost modes, the motor will modify its airflow output, if necessary, to provide an airflow which is defined as safe for the operation of the electric heater during heat pump operation. That airflow is the greater of the heat pump heating airflow and the electric heater only airflow.
Leak Dissipation Mode · Thermostat energizes appropriate signals to the dissipation board
based on operation mode. · The dissipation board energizes G output, which energizes the fan
relay on the PCB to complete the circuit to the indoor blower motor. · The dissipation board opens switches for W and Y. This de-energizes
signals going to electric heat and outdoor compressor which opens the electric heat relay(s).

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 18

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
Troubleshooting ECM Motor and Controls
! WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this caution may result in personal injury. High voltage is always present at motor. Disconnect power to unit before removing or replacing connectors or servicing motor. Wait at least 5 min after disconnecting power before opening motor.
The ECM motor used with this product contains two parts: the control module and motor winding section. Do not assume the motor or module is defective if it will not start. Go through the steps described below before replacing control module, Easy Select Board or entire motor. The control module is available as a replacement part. If Motor Turns Slowly: 1. Replace the panel. Motor may appear to run slowly if the access
panel is removed. 2. It is normal operation to run noticeably slower if G terminal is not
energized in cooling or heat-pump modes. If Motor Does Not Run: Turn off power and check the following: 1. Check 5 amp fuse on Easy Select Board. 2. Check for 24VAC on SEC1 and SEC2. If no voltage is present,
check transformer. 3. Check all plugs and receptacles for any deformation which could
cause loose connections. Be sure plugs are fully seated. 4. Verify that approximately 230VAC is present at motor. 5. Verify low-voltage control signals to motor. The motor receives its
control signals through the 12-pin plug (PL-1) on Easy Select Board and 16-pin plug on wiring harness (see Troubleshooting Example). The combinations of pins energized will determine motor speed (see Fig. 27). See Fig. 24for circuit board, low-voltage screw terminals energized and for voltage present at each pin on 12-pin plug (PL-1). See Fig. 24 for pin number on 16-pin plug which should have voltage when Easy Select Board screw terminals have 24VAC. Use Following Procedure To Check Control Signals: THERMOSTAT 1. Remove all thermostat wires from Easy Select Board. 2. Jumper screw terminals (1 at a time): R-G, R-Y/Y2, R-Y1, R-W1. If motor runs in all cases, thermostat is mis- wired, configured incorrectly or defective. If motor runs in some cases, but not others, continue to check wiring harness and circuit board. WIRING HARNESS

  1. Shut off power to unit; wait 5 min. 2. Remove 5-pin plug from motor. 3. Remove 16-pin plug from motor. 4. Remove 4-pin plug from motor. 5. Replace 5-pin plug and turn power on. 6. Check for appropriate voltages on 16-pin connector with screw terminals jumpered. (See Fig. 24 for values and see examples below.) If signals check correctly and motor does not run, inspect wiring harness for loose pins or damaged plastic that could cause poor connections. If connections are good, either control module or motor is defective. If proper signals are not present, check circuit board using procedure below:

12-PIN PLUG (PL-1) ON EASY SELECT BOARD 1. Unplug harness from board. 2. Check for appropriate voltages on pins with Easy Select Board
screw terminals jumpered (see Fig. 24 for values and see example below). If proper signals are not present, replace Easy Select Board. If present at board and not at 16-pin connector, wiring harness is defective.
TROUBLESHOOTING EXAMPLE: Motor is not running on a call for heat-pump heating. System is a single-speed heat pump.
1. After performing checks in Thermostat section, follow steps 1 thru 5 in Wiring Harness section. Then proceed with example.
2. With all thermostat wires removed from Easy Select Board, place a jumper wire between R and Y/Y2 low-voltage screw terminals on the Easy Select board.
3. Check Fig. 24 for pin number on 16-pin connector associated with the Y/Y2 signal. The correct pin is #14. The far right column shows that (-)12vdc should be present between pin #14 and pin #1 (common) on the 16-pin connector.
4. Set meter to read DC voltage. Place meter between pins #1 and #14 and check for (-)12VDC (common side of meter on pin #1). If signal is present, the problem is in the module or motor. If signal is not, problem is either in wiring harness or Easy Select Board.
These steps can be repeated for other modes of operation. To check Easy Select Board: 1. Leave jumper wire in place between R and Y/Y2. 2. Check Fig. 24 under “Wiring Harness Connection to Easy Select
Board” column and row for pin #14 to see pin# on Easy Select Board that should have voltage. The correct pin is #2. The column on far right will show voltage that should be present between pin #2 and #9 (or #10 common). 3. Place meter between pins #2 and #9 on Easy Select Board and check for (-)12VDC. 4. Remove 4-pin plug from the Motor Signal Translator. 5. If voltage is present, the wiring harness is bad; if not, the Easy Select Board is bad. Verify Motor Winding Section:
Before proceeding with module replacement, check the following to ensure motor winding section is functional. With control module removed and unplugged from winding section: 1. The resistance between any 2 motor leads should be similar. 2. The resistance between any motor lead and the unpainted motor end
plate should be greater than 100K ohms. If motor winding section fails one of these tests, it is defective and must be replaced.
Start-Up Procedures
Refer to outdoor unit Installation Instructions for system start-up instructions and refrigerant charging method details.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 19

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions
Care and Maintenance
! WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect all power to unit before servicing field wires or removing control package. The disconnect (when used) on access panel does not disconnect power to the line side of disconnect, but does allow safe service to all other parts of unit. If unit does not have a disconnect, disregard the foregoing. Instead, make sure that a disconnecting means is within sight from, and is readily accessible from, the unit. Disconnect all electrical power to unit before performing any maintenance or service on it.
For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. The only required maintenance that may be performed by the consumer is filter maintenance. The minimum maintenance requirements for this equipment are as follows:

1. Inspect and clean or replace air filter each month or as required. 2. Inspect cooling coil, drain pan, and condensate drain each cooling
season for cleanliness. Clean as necessary. 3. Inspect blower motor and wheel for cleanliness each heating and
cooling season. Clean as necessary. 4. Inspect electrical connections for tightness and controls for proper
operation each heating and cooling season. Service as necessary. Consult Fan Coil Service Manual available from equipment distributor for maintenance procedures.
! CAUTION
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Use the outdoor unit’s Owner’s/User Manual to explain the system operation to the consumer, with particular emphasis on indoor fan coil operation sounds and filter maintenance.

FAN COIL SIZE 24 36 48 60

Table 7 ­ CFM Range
SYSTEM SIZES 24, 30, 36
24, 30, 36, 42 36, 42, 48 42, 48, 60

CFM RANGE 315-1210 315-1410 395-1800 475-2015

UNIT SIZE

OUTDOOR UNIT
CAPACITY

18 24 24 30 36 24 30 36 36 42 30 36 48 42 48 36 42 60 48 60

Table 8 ­ Airflow Delivery (CFM) in Cooling Mode

OPERATING MODE

SINGLE–SPEED APPLICATION

TWO–SPEED APPLICATION

Nominal A/C
Cooling
525 700 875 1050 700 875 1050 1225 875 1050 1225 1400 1050 1225 1400 1750

A/C Cooling Dehumidity
420 560 700 840 560 700 840 980 700 840 980 1120 840 980 1120 1400

High Speed

Nominal A/C
Cooling

A/C Cooling Dehumidity

700

560

1050

840

700

560

1050

840

1050

840

1400

1120

1050

840

1400

1120

1750

1400

Low Speed

Nominal A/C
Cooling

A/C Cooling Dehumidity

560

450

840

670

560

450

840

670

840

670

1120

895

840

670

1120

895

1400

1120

FAN ONLY

Lo

Med

350

420

350

560

435

700

525

840

350

560

435

700

525

840

610

980

434

700

525

840

610

980

700

1120

525

840

610

980

700

1120

875

1400

NOTES: 1.The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM. 2.Air flow can be adjusted +15% or -10% by selecting HI or LO respectively for all modes except fan only. 3.Dry coil at 230 volts and with 10KW heater and filter installed. 4.Airflows shown are at standard air conditions.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 20

High
525 700 875 1050 700 875 1050 1225 875 1050 1225 1400 1050 1225 1400 1750

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

UNIT SIZE
24 36 48 60

OUTDOOR UNIT
CAPACITY
18 24 30 36 24 30 36 42 30 36 42 48 36 42 48 60

Table 9 ­ Cooling Airflow Delivery (CFM) when pairing with 37MU* (2-Speed ODU)

OPERATING MODE

TWO–SPEED APPLICATION

FAN ONLY

High Speed

Low Speed

Nominal

A/C

Nominal

A/C

Lo

A/C

Cooling

A/C

Cooling

Cooling

Dehumidity

Cooling

Dehumidity

525

420

420

350

350

700

560

560

450

350

875

700

700

560

435

1050

840

840

670

525

700

560

560

450

350

875

700

700

560

435

1050

840

840

670

525

1225

980

980

450

610

875

700

700

560

434

1050

840

840

670

525

1225

980

980

785

610

1400

1120

1120

895

700

1050

840

840

670

525

1225

980

980

785

610

1400

1120

1120

895

700

1750

1400

1400

1120

875

Med
420 560 700 840 560 700 840 980 700 840 980 1120 840 980 1120 1400

High
525 700 875 1050 700 875 1050 1225 875 1050 1225 1400 1050 1225 1400 1750

Table 10 ­ Airflow Delivery (CFM) in Heat Pump Only Heating Mode

UNIT SIZE

OUTDOOR UNIT
CAPACITY

SINGLE–SPEED APPLICATION
Heat Pump Heat Pump Comfort Efficiency

18 24 24 30 36 24 30 36 36 42 30 36 48 42 48 36 42 60 48 60

470 630 785 945 630 785 945 1100 787.5 945 1100 1260 945 1100 1260 1575

525 700 875 1050 700 875 1050 1225 875 1050 1225 1400 1050 1225 1400 1750

OPERATING MODE

TWO–SPEED APPLICATION

High Speed

Heat Pump Comfort

Heat Pump Efficiency

630

700

945

1050

630

700

945

1050

945

1050

1260

1400

945

1050

1260

1400

1575

1750

Low Speed

Heat Pump Comfort

Heat Pump Efficiency

505

560

755

840

505

560

755

840

755

840

1010

1120

755

840

1010

1120

1260

1400

NOTES: 1.The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM. 2.Air flow can be adjusted +15% or -10% by selecting HI or LO respectively for all modes except fan only.
3.Dry coil at 230 volts and with 10KW heater and filter installed. 4.Airflows shown are at standard air conditions.

FAN ONLY

Lo

Med

High

350

420

525

350

560

700

435

700

875

525

840

1050

350

560

700

435

700

875

525

840

1050

610

980

1225

435

700

875

525

840

1050

610

980

1225

700

1120

1400

525

840

1050

610

980

1225

700

1120

1400

875

1400

1750

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 21

Fan Coil for Puron AdvanceTM R-454B Refrigerant: Installation Instructions

FAN UNIT SIZE
24
36
FAN UNIT SIZE
48
60

OUTDOOR UNIT
CAPACITY BTUH
18,000 24,000 30,000 36,000 24,000 30,000 36,000 42,000
OUTDOOR UNIT
CAPACITY BTUH
30,000 36,000 42,000 48,000 36,000 42,000 48,000 60,000

Lo 700 700 875 1050 700 875 1050 1225
Lo 1000 1000 1225 1400 1200 1225 1400 1750

0-5 Nom 700 700 875 1050 700 875 1050 1225
0-10 Nom 1000 1000 1225 1400 1200 1225 1400 1750

Table 11 ­ Airflow Delivery (CFM)

ELECTRIC HEATER kW RANGE

0-10

0-15

High 805 805 1006 1208 805 1006 1208 1409

Lo 750 750 875 1050 750 875 1050 1225

Nom 750 750 875 1050 750 875 1050 1225

High 863 863 1006 1208 863 1006 1208 1409

Lo — 1050 1050 1050 1050 1050 1050 1225

Nom —
1050 1050 1050 1050 1050 1050 1225

ELECTRIC HEATER kW RANGE

0-15

0-20

High 1150 1265 1409 1610 1380 1409 1610 2013

Lo 1200 1200 1225 1400 1250 1300 1400 1750

Nom 1200 1200 1225 1400 1250 1300 1400 1750

High 1380 1380 1409 1610 1438 1495 1610 2013

Lo — 1300 1350 1400 1350 1350 1400 1750

Nom —
1300 1350 1400 1350 1350 1400 1750

High —
1208 1208 1208 1208 1208 1208 1409
High —
1495 1553 1610 1553 1553 1610 2013

Lo — — 1200 1200 1225 1225 1208 1225
Lo — — — 1500 — — 1750 1750

NOTE: Lo, NOM, and HI refer to AC, HP CFM ADJUST selection.
— Airflow not recommended for heater/system size.

FAN COIL UNIT SIZE 24
36
48
60

Table 12 ­ Minimum CFM for Electric Heater Application

HEAT PUMP UNIT SIZE
18 24 30 36 24 30 36 42 30 36 42 48 36 42 48 60

5 700 700 875 1050 700 875 1050 1225 — — — — — — — —

8, 9, 10 750 750 875 1050 700 875 1050 1225 1000 1100 1225 1400 1200 1225 1400 1750

CFM HEATER SIZE kW
12, 15 —
1050 1050 1050 1050 1050 1050 1225 1200 1200 1225 1400 1250 1300 1400 1750

18, 20 — —
1200 1200
— — 1208 1409 — 1300 1350 1400 1350 1350 1400 1750

NOTES: These airflows are minimum acceptable airflows as UL listed. Actual airflow delivered will be per airflow delivery chart for Electric Heating Modes.

0-20 Nom
— — 1200 1200 — — 1225 1225

High — —
1380 1380
— — 1409 1409

0-30 Nom
— — — 1500 — — 1750 1750

High — — —
1725 — —
2013 2013

24, 30 — — — — — — — — — — —
1500 — —
1750 1750

© 2024 Carrier. All rights reserved.
A Carrier Company

Edition Date: 06/24

Catalog No: IM-FT5-FG5-01
Replaces: New

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

22

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals