DoorKing 1625 Wedge Barrier Instruction Manual
- June 23, 2024
- DOORKING
Table of Contents
1625 Wedge Barrier
“`html
Specifications
- Model: 1625 Wedge Barrier
- Phase: Single
- Frequency: 60 Hz
- Voltage: As specified
- Manufacturer: DoorKing, Inc.
- Location: Inglewood, CA
Product Information
The 1625 Wedge Barrier is a surface mount vehicular wedge
barrier accessory designed to be used with circuit board 1601-010
Revision W or higher. It is crash rated to the ASTM F2656-23
Standard with a PU-30 (P1,P2) rating, ideal for controlling
passenger vehicles and light duty trucks.
IMPORTANT: Installation of Traffic Light,
Photocell, and Octagon Arm with LED Edge is required for proper
operation.
Warning: Installation and use of the wedge
barrier in areas subject to freezing weather with potential for
snow and ice accumulation is not recommended.
Note: This product should only be installed and
serviced by a trained gate/door systems technician.
Product Usage Instructions
Installation
1. Ensure all required accessories (Traffic Light, Photocell,
Octagon Arm with LED Edge) are installed.
2. Mount the wedge barrier securely following the provided
layout.
3. Connect the barrier to a compatible Barrier Gate Operator
(1602-590) as per the operator’s manual.
Maintenance
1. Regularly inspect the wedge barrier for any signs of wear or
damage.
2. Keep the barrier clean and free of debris that may hinder its
operation.
3. Follow the maintenance schedule outlined in the user manual
for optimal performance.
Operation
1. Use the provided controls or automation system to operate the
wedge barrier as needed.
2. Ensure proper communication between the barrier and any
connected devices for seamless operation.
Frequently Asked Questions
Q: Can the wedge barrier be used without the Barrier Gate
Operator?
A: No, the 1625 Wedge Barrier must be used with a compatible
Barrier Gate Operator (1602-590) for proper functionality.
Q: Is it safe for pedestrians to be near the wedge
barrier?
A: Pedestrians should be provided with separate access as the
moving gate can cause serious injury or death. The entrance is for
vehicles only.
Q: What should I do if I encounter freezing weather
conditions?
A: It is recommended not to use the wedge barrier in areas
subject to freezing weather with potential for snow and ice
accumulation. Contact a professional technician for further
guidance.
“`
Installation Manual
1625 Wedge Barrier
Surface Mount Vehicular Wedge Barrier Accessory
Use this manual for circuit board 1601-010 Revision W or higher.
1625-065-B-6-23
IMPORTANT: Installation of Traffic Light, Photocell and Octagon Arm with LED Edge is REQUIRED.
NOT A WALKWAY
WARsMSacNNeatTIOruANOaiVsYlo:GlPBMeIuNCteisivocGLmdetyiEeonhcAeAsrjlisRcuecRt.ryrlMsioeycaflcndoeaasarsrnmmdeaagteh,.
53382
CAONNSFIO/URLM-3S2T5O
VEHICCUALNA/CRCSEGARTACIT2FE2IE.DO2 PNTOOER. 2A4T7OR
HP
CLASS
MODEL
PHASE
SERIAL
60 Hz
VOLTS
AMMAPXSDGoAoTrEKiLnOg,AIDnc., Inglewood, CA
SMeorvioinugs GInajuteryCoarnDCeaauthse PTiDKwnheEoittidhhEsneoePoesutngttCrltaiepraLtatrenEincosAachrermRiweld!iauasr.serGfntnoiaunrotsgevpe.eemhsraieactpyleeamstrhaooetvneeglyeaa.nttetraaonnrycpetlia.mye
D
A
N
G
E
R W
A
L
K
W
A
Y
NOT A
WARNING pre-stressed concrete may be used in multi-level parking garages.
Cutting a tensioned cable, or tendon, can endanger the contractor and
compromise the structural integrity of the floor. Contact the building
structural engineer for specific instructions and information BEFORE drilling
or saw cutting into the floor.
INSTALLATION AND USE OF THE WEDGE BARRIER IN AREAS SUBJECT TO FREEZING WEATHER
WITH POTENTIAL FOR SNOW AND ICE ACCUMULATION IS NOT RECOMMENDED.
THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE/DOOR SYSTEMS
TECHNICIAN ONLY. Visit www.doorking.com/dealer-locator to find a professional
installing and servicing dealer in your area.
Copyright 2023 DoorKing®, Inc. All rights reserved.
The 1625 wedge barrier is not a stand-alone product. It must be used with a
1602-590 Barrier Gate Operator (sold separately). The 1625 is crash rated to
the ASTM F2656-23 Standard and is certified with a PU-30 (P1,P2) rating. The
1625 is ideally used to control passenger vehicles and light duty trucks.
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION
Wedge Barrier One-Way Operation Wedge Barrier and 1602-590 Operator Overview
Wedge Barrier Models Layout Wedge, Support Post and Counterbalance
Installation Operator Connection Wedge Covers and Maintenance Install
Reverse/LED Edge on Octagon Arm Install Octagon Arm with Reverse/LED Edge
Install Traffic Light (Required) Install Photocell (Required) Entry Lane Only
In-Ground Loop Options Manual Release Operation ALL Components Wiring
Schematic
Wedge Components
2-3 4 5 6
7-8 9 10 11 12
13-14 15-16
17 18 19 20
Octagon Reversing/LED Edge Arm
Choose
14 Ft 1-Piece Octagon Arm Only P/N 1601-555 14 Ft 2-Piece Octagon Arm Only P/N 1601-567
Octagon Arm Hardware Kit (Required) P/N 1601-235
Choose Reversing Edge P/N 8080-080 Reverse Edge + Red/Green LED P/N 8080-096
RetrDoo-RoreKIfnlienccglut8idv0ee8dP0h-0ot5o7cell
1625-065-B-6-23 1
DLInEoDcolTruKrdaienfdfgic16Li0g3h-t223 BDaorroireKriGnagt1e6O0p2e-5ra9t0or
DoorKing Safety for Wdge Barrier
· DKS Wedge Barrier System is NOT crash rated. It is intended to provide a formidable barrier to help prevent passenger vehicles and light-duty trucks from driving through a controlled traffic lane.
· Wedge barrier MUST have reverse/LED edge on arm, traffic light and
photoelectric cell functioning or remove wedge barrier from service until
repairs have been made.
· Make sure all warning signs are on operator and arm. They MUST be easily
visible.
· Do not install the operator in such a way that the arms moves within 16
inches of a rigid object or 10 feet from high voltage power wires with arm in
the raised position.
· Speed limit through barrier area is 5 MPH. Install speed bumps, warning
signs and hazard stripes where visible in the area of the wedge barrier gate,
failure to do so may result in injury, damage to operator and vehicle.
· Users should be familiar with proper use of operator, these include;
hardware operation, reversing functions and testing, reversing loops, inherent
reversing system, electric edges, photoelectric cells related external devices
and possible hazards.
· Keep adults, children and objects away from operator and HAZARD ZONES.
· Automotive ONE-WAY traffic only – No bicycles or motorcycles.
Pedestrians MUST be provided with separate access.
· All electrical connections should be made in accordance with local
electrical codes.
Moving Gate Can Cause Serious Injury or Death
KEEP CLEAR! Gate may move at any time without prior warning. Do not let
children operate the gate or play in the gate area. This entrance is for
vehicles only. Pedestrians must use separate entrance.
IMPORTANT: A wedge barrier gate operator installed WITHOUT any external safety
sensors CANNOT sense a person under the raised arm and can strike them while
the arm is lowering.
This scenario is VERY DANGEROUS and MUST
NEVER OCCUR!!
· Security features should be installed to avoid unauthorized use.
· Controls intended for user activation must be located at least six feet (6′) away from any moving part of the barrier gate and where the user is prevented from reaching over, under or around the wedge barrier gate to operate the controls. Emergency access controls only accessible by authorized personnel (e.g., fire, police, EMS) may be placed at any location in the line-of-sight of the wedge barrier gate.
· When manually operating the gate operator arms, the user MUST make sure that the gate area is clear BEFORE operating the controls. Any activity in the traffic lane should be monitored to ensure a safe operation when opening or closing the wedge barrier gate. The motion of the barrier arms must be directly observable by the person operating the wedge barrier. While barrier arm is in motion NO pedestrian and NO vehicle shall be in the immediate vicinity of the wedge barrier area.
· When removing the operator from service, move the arms to the full open position and shut off power at the service panel.
· Operators and components should be properly installed and maintained following the
Photo Sensor
recommended service schedule, test the operator monthly. Keep all debris from underneath
When the photo
wedge plate and from operator housing vents and off of arms. Contact your service
beam gets interrupted by a
dealer for any maintenance or repairs.
pedestrian, a lowering arm
· Vehicular wedge barrier gate operator can produce high levels of force, it is important that you are aware and eliminate possible HAZARDS; Pinch Points, Entrapment Areas, Overhead Power Wires, Absence of Controlled Pedestrian Access, Traffic Backup.
will reverse and raise.
WARcsMSaNaetNTOuraIAiOsNloVYleu:tIGsivNCPBMmeieiGLnhocedjEiytsucoeAc.AlrrsleRyceRtrysdMoicoaarlfnecmdasasearnamgteh,.
CAONNSFIO/URLM-3S2T5O CAN/CSEARTCI2F2IE.D2 NTO. 247
VEHICULAR GATE OPERATOR CLASS MODEL SERIAL VOLTS
AMPS
MAX
GATE LOAD DoorKing,
Inc.,
Inglewood,
CA
53382
HP PHASE 60 Hz
MSeorvioinugs GInajuteryCoarnDCeaauthse iTPKwDnheEiottidhhEsneoePoesutgnttCrlateiprLatatreEnincosAachrreRmiwled!iauasre.srGnftnoaiunrotsgevpe.eemhsraaiectypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam. ye
NOT A WALKWAY
IMPORTANT: ALL debris and trash needs to be kept from underneath wedge plate.
1625-065-B-6-23
D N
A O
N T
GE A
R W
A
L
K
W
A
Y
2
Safety and Traffic Management for Wedge Barrier System
Vehicular wedge barrier gate operator can produce high levels of force. It is
important that you are aware and eliminate possible HAZARDS; Pinch Points,
Entrapment Areas, Overhead Power Wires, Absence of Controlled Pedestrian
Access, and Traffic Management.
Pedestrians MUST be provided with separate access.
A Separate Pedestrian Entrance: Located so pedestrians CANNOT come in contact
with the wedge barrier system.
B Warning Signs: Permanently mounted on operator and arm and easily visible.
C Non-Contact Sensor: (photocell) Minimizes the potential of the arms lowering
on vehicular or other traffic that loops cannot sense. Located directly under
arm.
D Hazard Stripes: NO stopping or standing “Hazard Stripes”. Permanently
painted WHITE on pavement on both sides of arm.
E Pedestrian Alert Warning: “NOT A WALKWAY” pavement marking facing both
directions, permanently painted WHITE on pavement.
F In-Ground Loops: Minimizes the potential of the gate closing when a vehicle
is present.
Arm Red/Green LED Lights: Helps with arm’s visibility and position. Helps
control traffic.
TIP: The stripes and letters can be painted on cement BEFORE installation of wedge begins. Painting the word “DANGER” underneath wedge plate is recommended. See next page and cover for example.
OTrNaEff-icWDAOiYrNecLtYion
F
Contact Sensor: (reverse edge) Minimizes the potential of the arms lowering on
vehicular or other traffic that loops cannot sense. Located directly on arm.
LAErDms RtuArInOSPGEESRNEIaNEnGNd:
tuTrrOnasfPfiEGcNRLIEiNgEGhNt:
Entrance
A
B
Traffic Red/Green Light: Helps control traffic.
C
WARscMSaNaetNTOruaIAiOsNloVYleu:tIGsivNCPMBmeieiGLnhocedjEiytsuceoAc.ArlsrleRyceRtrysdMoicoaarlfnemcdasasearnamgteh,.
CAONNSFIO/URLM-3S2T5O CAN/CSEARTCI2F2IE.D2 NTO. 247
VEHICULAR GATE OPERATOR CLASS MODEL SERIAL VOLTS
AMPS
MAX
GATE LOAD DoorKing,
Inc.,
Inglewood,
CA
53382
HP PHASE 60 Hz
MSeorvioinugs GInajuteryCoarnDCeaauthse DiwPTKnheEoittihdhEsnoeePoeustgnttCrlateiprLatatreEnincosAachrreRmiwled!iauasre.srGnftnoaiunrotsgevpe.eemhsraaiectypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam. ye
B
NOT A WALKWAY
IMPORTANT: ALL debris and trash needs to be kept from underneath wedge plate.
1625-065-B-6-23
D
A
N G E R WedOgPeELNOINWG:ERS W
A
L
K
W
A
Y
A
D NOT E
3
NOT A WALKWAY
WALKWAY NOT A
Wedge Barrier One-Way Operation
Wedge Barrier in secure position.
TrafficisLRigEhDt
WARcaMSsNaetNTOuraIAiOsNloVYleu:tIGsivNCPBMmeieiGLnhocedjEiytsucoeAc.AlrrsleRyceRtrysdMoicoaarlfnemcdasasearnamgteh,.
CAONNSFIO/URLM-3S2T5O CAN/CSEARTCI2F2IE.D2 NTO. 247
VEHICULAR GATE OPERATOR CLASS MODEL SERIAL VOLTS
AMPS
MAX
GATE LOAD DoorKing,
Inc.,
Inglewood,
CA
53382
HP PHASE 60 Hz
MSeorvioinugs GInajuteryCoarnDCeaauthse PKwDiTnheEiottihdhEsnoeePoeustgnttCrlatpieraLtartenEinocsAachrremRiweld!iauasre.srGnftnoiaunrotsgevpe.eemhsraaiectypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam. ye
OArpmtioDnoawl LnE,Ds are RED
Wedge Up
D
A
N
G
E
R W
A
L
K
W
A
Y
A
NOT
Optional LAErDms RtuArInSGESREaEnNd
After access control device has approved entry . . . .
TraffiGc RtLuEigrEnhNst
WARaMScsNeatNTOruaIAiOsNloVYleu:tIGsivNCMBPmeiieGLnhocedjEiytsuceoAc.AlrsrleRyceRtrysdMoicoaarlfnemcdasasearnamgteh,.
CAONSFIO/URLM-3S2T5O CAN/CSEARTCI2F2IE.D2 NTO. 247
VEHICULAR GATE OPERATOR CLASS MODEL SERIAL VOLTS
AMPS
MAX
GATE LOAD DoorKing,
Inc.,
Inglewood,
CA
53382
HP PHASE 60 Hz
SMeorvioinugs GInajuteryCoarnDCeaauthse wDPiTKnheEiottidhhEsneoePoesutgnttCrlateiprLatatreEnincosAachrerRmiwled!iauasre.srGnftnoaiunrotsgevpe.eemhsraaiectypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam. ye
1625-065-B-6-23
D A N G E RW Wedge Lowers A L K W A Y A
NOT
4
Wedge Barrier and 1602-590 Operator Overview
OTrNaEff-icWDAOiYrNecLtYion
Layout page 7-8 Operation page 4
Operator Connection page 9
Traffic Light pages 15, 16
Loop Detectors page 18
Left Cover
Concrete Pad page 8
WALKWAY NOT A
Right Cover Right Wedge
WARscaMSNNaetTIOurANOaiVsYlo:GlBMPeIuNCtiesivocGLmdeytiEoenhceAArsjlisRcuecRt.ryrlMsioeycaflcndoeaasarsrnmmdeaagteh,.
53382
CAONNSFIO/URLM-3S2T5O VEHICUCALNA/RCCSEGARATCTI2FE2IE.OD2PNTEOOR. A24T7OR
CLASS
MODEL
HP PHASE
SERIAL
60 Hz
VOLTS
MAMAXPSDGoAoTrEKiLnOg,AIDnc., Inglewood, CA
SMeorvioinugs GInajuteryCoarnDCeaauthse KTwDPinheEoittihdEhsnoeePoeustngttCrltapeirLatarteEninocsAachrerRmiwled!iuaasrse.rGfntnoaiunrotsgevpe.eemhsraaeictypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam. ye
Arm pages 12, 13
Photocell page 17
Left Wedge
DANG NOT
ER A
W
A
L
K
W
A
Y
Wedge Barrier Safety pages 2, 3
Wedge Connection page 9
Covers page 11
Safety Stripes page 3
Use this manual for the Model 1602 operators with circuit board 1601-010 Rev W or higher ONLY.
Class of Operation Model 1602 – UL 325 Class II, III, IV ETL Listed
Type of Gate Traffic Lane Vehicular Barrier Gate Only
1602 Housing
15.75″
15.26″
Arm Types Octagon Aluminum with reverse edge
Gate Cycles
Type of wiring to be used on ALL external devices: A) Type CL2, CL2P, CL2R, or CL2X. B) Other cable with equivalent or better electrical, mechanical, and flammability ratings.
Low Cycle
Pedestrian Protection Inherent entrapment sensing system (Type A) Provision
for connection of a non-contact sensor (Type B1) and/or contact sensor (Type
B2)
CONFORMS TO ANSI/UL-325
CERTIFIED TO CAN/CSA C22.2 NO. 247
53382
VEHICULAR GATE OPERATOR
CLASS
HP
MODEL
SERIAL
VOLTS
PHASE
AMPS MAX GATE LOAD
60 Hz
DoorKing, Inc., Inglewood, CA
Model #
Convenience Open
Horsepower – Volts
Amp
Max Arm Length
Speed 90°
1602-590 No
1 HP – 115 VAC 9.7 14 Ft. 3.5 Sec
Note: 208/230/460/575 VAC input voltage can be connected to the operator by installing an “Optional” High Voltage Kit (P/N 2600-266).
34.5″
39.6″ 13″
SSeeMMrriioooouuvvssiinnIIggnnjjGGuurraayytteeoorrCCDDaaeennaaCCtthhaauussee PPeeTTddeehhssiiiissnnttrreettiiDDaahhnnnneeoottrrwwssaaggnniimmnnaaoottKKhhccttttuueeooEEeellsseeuuEEaattiittttssrrPPuuccppeeffsshhrraaooCCeeiiiioo..rrllLLddrrssvvEErreeeewweeAApphhnnaaRRaaiirrccoorrnn!!llaappeeiinntteeGGsseeggrraaooaa..eettnnttnneeeellttyyrrmmtt..aahhaanneeyyccggeemmaa.. ttooeevvooeerraappttllaaaayynnyy
time time
2 Warning Signs (Included) MUST be mounted on EACH side of gated area and easily visible.
1625-065-B-6-23 5
Wedge Barrier Models
Prior to beginning the installation of the wedge barrier, we suggest that you
become familiar with the instructions, illustrations, and wiring guide-lines
in this manual. This will help insure that your installation is performed in
an efficient and professional manner.
Barrier operator 1602-590 can be located on either end of wedge plates P/N:
1625-612
12 FT LANE
Left Wedge Plate
Right Wedge Plate
P/N: 1625-714
14 FT LANE
1602-590
Left Wedge Plate
Right Wedge Plate
1602-590
CONCRETE PAD · 4000 psi reinforced concrete – minimum depth five (5) inches.
GENERAL NOTES · Automated vehicular gates shall be designed and installed to
be in strict compliance with the UL 325 Safety Standard and the ASTM F2200
Construction Standard. · Automated vehicular gates that do not meet the
requirements of these standards shall not be allowed. · This drawing is for
the sole purpose of general gate operator foot-print and location, photo beam
coverage and placement, and vehicular loop dimensions and placement. Drawings
are not all inclusive or guaranteed to scale. · No considerations have been
made for grade, existing public utilities, landscape, drainage, site
peculiarities, or requirements by the authority having jurisdiction, ie; Fire
Marshall, Building Inspector, Street and Alley Departments. · Warning Signs
must be installed and must be highly visible upon both entry and exit of the
property, and must remain in place for the life of the gate operating system.
· Proper lane identification and vehicular direction signs should be highly
visible upon entry onto the property. · Gate dimensions, posts, guide rollers,
photo beams, reversing edges, hinges, and other gate hardware may vary in
size, dimension, and placement and should not be used as an exact reference. ·
All loop sizing and placement dimensions indicated are solely intended for
reference only, and not intended to be the final criterion for determining the
loop sizing and placement on any automated vehicular gate project. DoorKing,
Inc does not assume responsibility or liability for any installation with
regard to equipment/system malfunction, vehicle detector loop sizing and
placement, or consequent damages or injuries caused thereby. · DoorKing, Inc.
does not assume responsibility or liability for the installation and
unauthorized changes to the design and operation of equipment, or alterations
to the final site plan.
WARNING for Precast Concrete Drilling into precast concrete is NOT recommended
without professional advice or assistance. If you don’t know where the
prestressed wire strands are located, you risk damaging the structural
integrity of the precast concrete and the drilling equipment you use. If you
need to drill into precast concrete to anchor the wedge barrier to it, you
must contact the building engineer before proceeding.
1625-065-B-6-23 6
Layout
WARNING for Precast Concrete
Drilling into precast concrete is NOT recommended without professional advice or assistance. If you don’t know where the
prestressed wire strands are located, you risk damaging the structural integrity of the precast concrete and the drilling equipment
you use. If you need to drill into precast concrete to anchor the wedge barrier to it, you must contact the building engineer before
proceeding.
18′ 6″ (12 ft wedge) 20′ 6″ (14 ft wedge)
Note: Shown without counterweight baskets to better clarify installation of support posts.
9.5″ CRITICAL!
9.5″ CRITICAL!
Concrete Pad
58.8″ Support Post Support Post
IMPORTANT: Bolt plates together BEFORE positioning plates on concrete)
Left Wedge Plate
Right Wedge Plate
15.5″
Wedge Plate Width: 12′ (12 ft wedge) 14′ (14 ft wedge)
See 12″ Below
12″
Actual Lane Width: 11′ 7 3/4″ (12 ft wedge) 13′ 7 3/4″ (14 ft wedge)
12″
12″
2.63″
2.63″
CRITICAL!
CRITICAL!
Barrier operator can be installed on EITHER end of wedge plates
Install Barrier Operator FIRST and then install support posts and wedge plates to operator.
7″ CRITICAL!
1.5″ CRITICAL!
7′
Left Wedge Plate
5″ Minimum Depth
Right Wedge Plate 34.5″
conduit
Right Wedge Plate
Support Post 12″
CRITICAL! 7″
Operator Detail 3/4″ Conduit Options:
– AC Power
– Low Voltage Accessories
– Earth Ground
– Vehicle Loops
10.25″
– Spare (Optional)
15″
Conduit
3.5″
Location
Access Door
2.63″ CRITICAL!
1.5″
CRITICAL! 13.5″
12″ 19.5″ 12″
1625-065-B-6-23 7
Layout Cont
3″ Min 3″
Rebar Mat
Rebar / Concrete Pad Detail
Heating Element should be considered for areas with freezing temperatures.
Concrete Pad
7′
18′ 6″ (12 ft wedge) 20′ 6″ (14 ft wedge)
Rebar Mat
5″ Minimum Depth
· Concrete Pad 4,000 PSI.
conduit
· Soil compression under and around the foundation shall be compacted to a soil density of 95% of standard ASTM-698.
· Add gravel where necessary to insure a solid base. Soil must be stable and able to support the weight of the concrete pad.
· The 1625 Wedge must be installed on a flat and level surface on grade with the roadway surface.
· Place one layer rebar mat at eight (8) inch on-center. Use #5 (5/8 inch) Grade 40 or better.
· Cure concrete properties 4000 psi (minimum) with smooth finish and proper drainage.
· Heating element should be considered for areas with freezing temperatures.
Anchor Detail
16 Anchors
22 Anchors
Concrete Pad 16 Anchors
Support Post Support Post
Grade 8 Steel Washer 0.812 ID 2.00 OD 0.122 0.177 Thickness
McMaster-Carr 98026A036 or equivalent
316 Stainless Steel Wedge Anchor Length Thread Pull Out Shear Torque 5.5 inch
3/4 – 10 Anchor 2200 lbs 2800 lbs 175 ft/lbs
McMaster-Carr 98026A036 or equivalent 4,000 PSI Concrete
1625-065-B-6-23
6 Anchors
IMPORTANT · Position the operator, post and wedge on the concrete slab per the
CRITICAL measurements on the
previous pages and mark the mounting holes. · Drill ¾ inch holes (54) to
anchor posts and wedge, minimum of six (6) anchor holes for the operator. ·
Use a ¼” bit to drill pilot holes if necessary. · Minimum depth engagement for
the wedge anchors is 3.75 inch. · Use a 2″ O.D. Grade 8 washer with the wedge
anchors. · Torque wedge anchors bolts to 175 Ft Lb.
8
Wedge, Support Post and Counterbalance Installation
Install Barrier Operator BEFORE installing support posts and wedge plates.
Wedge Activator Arm (Reverse order to connect other end)
Counterbalance Basket Load weights in baskets and secure with bolt through center. (11 plates for each side)
Wedge
Cut off excess threads flush with top of nut on the anchors that will come in contact with tires.
Wedge Activator Arm
1625-065-B-6-23
Counterbalance Basket
Wedge Down
9
Support Post
Wedge Up
Operator Connection
Install Barrier Operator BEFORE installing wedge plate to it.
Wedge Activator Arm see previous page for connection.
Hub 3 Bolts
Hub Operation
Operator Bracket
Note: Shown with out support post to better clairify operator connection to
wedge.
Test hub UP and DOWN position BEFORE installing operator bracket.
Hub
Wedge Wedge Up, Arm Down
1625-065-B-6-23 10
Wedge Wedge Down, Arm Up
Wedge Covers and Maintenance
Outside of Left Cover
Protective Cover Cap: Only one. Install on the outside of the cover as shown, on the opposite cover from the operator side. Use 4 self-tapping screws. Helps potect against debris and trash getting inside the cover and interfering with the moving parts of the wedge.
Installed Protective Cover Cap
Cotter Pin Note: Covers have a LEFT and RIGHT side. They are NOT
interchangeable
Protective Cover Cap (on outside)
L(ienfstiCdeo)ver
Cotter Pin
Right Cover
Right Wedge Plate
Left Wedge Plate
Regular Maintenance of Wedge System
Regular inspection and removal of trash, debris, gravel, and rock is required
in order to keep wedge barrier functioning properly. Neglecting to regularly
clean trash and debris UNDERNEATH WEDGE PLATE is the number one cause of
breakage and malfunctions. Make sure all moving parts are functioning
normally. If they are NOT, remove wedge barrier from service immediately until
it can be repaired.
1625-065-B-6-23 11
Install Reverse/LED Edge on Octagon Arm
Install on a 14 ft aluminum octagon arm. Note: DO NOT operate arm with a
malfunctioning reverse edge.
DoorKing Part Numbers
8080-080
Reverse Edge
8080-096
Reverse Edge + Red/Green LED
2 Slide on Spacer
Tip: Liquid soap will help spacer slide on easier.
5″ Rubber Spacer
1 Remove End Cap
Push a screwdriver through hole in bottom of end cap to release spring while
pulling cap off.
Octagon Arm
Spacer MUST be used or edge will slide in slot.
Reverse/LED Edge
Spacer
Cover
3 Slide on Edge
Tip: Liquid soap will help reverse edge slide on easier.
Spacer Reverse/LED Edge
4 Reinstall End Cap
Push a screwdriver through the hole in cap to release spring while pushing cap
on. Keep pushing cap on until a “CLICK” is heard which locks it in place.
1625-065-B-6-23
Spacer MUST be used or edge will slide in slot.
Drawings NOT to scale. 12
Install Octagon Arm with Reverse/LED Edge
Drawings NOT to scale.
Install End Cap
Push a screwdriver through the hole in the bottom of cap to release spring
while pushing cap on. Keep pushing cap on until a “CLICK” is heard, locking it
in place.
1 Install Arm & Reverse Edge (REQUIRED)
SSleiedeneRxetvpearsgee.Edge on Arm
Allow arm to protrude about 1″ past the end of arm bracket. Make sure arm cover fits over arm.
Test hub UP and DOWN position before installing arm bracket.
Hub
Octagon
Arm
Tip: Liquid soap will
Spacer
help reverse edge
slide on easier.
Reverse Edge
2 Connect Wire Harness to Arm
Arm Bracket
Install Arm Cover IMPORTANT: Wire harness MUST remain clear of the rotating arm and the arm cover to avoid wire chaffing.
Note: Spacer MUST be in position when installing a reverse edge. See previous page.
IMPORTANT: Choose which side of the operator the arm is mounted on, remove knock-out and run wire harness accordingly as shown.
OpNSteiiodaner
Use supplied adhesive zip tie to secure harness to bottom of bracket.
WiretoHTaornpFeAosRfsICnsSaciedbluceiundoreeeptddZtfiAoioprdnhTeiessive
Knock-Out
FOapr tSioidne
CGarbiple CGarbiple
Knock-Out
IMPORTANT: Allow slack in the wire harness between the cable grips of at least 13″ or more for the rotating arm.
CGarbiple
Plug in reverse edge. Red/Blue plugs NOT used. Use bottom hole on arm bracket
to secure cable grip. IMPORTANT: Allow slack in the wire harness between the
cable grips of at least 13″ or more for the rotating arm. 1625-065-B-6-23
13
Wiring: See next page.
Wiring
Octagon Reverse/LED Edge Arm
UP LOOP
TIME DELAY
1601 Standard Bracket
Red
Plugs
Breakaway Sensor Red Connector
C7 L8
Black
NOT Used
Breakaway Sensor
Red Connector
C6 L7
Blue
Breakaway Sensor
Blue Plugs Blue Connector Battery Backup C8 L9 Pink
NOT
Breakaway Sensor
Used
Blue Connector Battery BackUp C9 L10 Yellow
ON 12345678
NOT Used
L16
110VAC HOT L14
Main PCB
Terminal 2
ON 12345678
SW 1
1601-010 POWER
SW 2
DOWN LOOP
REVERSE SENSITIVITY
Arm Relay Contacts
C NC NO
Common NC Main PCB
1 2 3 4 5 6 7 8 9 10 11 12 13 14
N-Open Main PCB Green Light C2 L2 Green N-Close Main PCB Red Light C1 L1 Red
Common Main PCB LED Light C10 L11 White
110VAC HOT
Solid State Relay
White
Black
Terminal 9 Main PCB Reverse Edge C5 L5
Terminal 14
Main PCB
Reverse Edge C4 L4
Grey
Grey/Pink
White
Circuit Board
Terminal 1 – Neutral
Terminal 2 – Hot Circuit Board L19
L20
SUPPLY GROUND
Ground Panel Stud
L24
Required
Green
L – Line Transformer 8.5 amp
L21
N – Neutral Transformer 8.5 amp
L22
Ground Transformer 8.5 amp
L23
Red NOT Used
12V Positive (+) Solid State Relay
C3 L3
VTransformer 8.5 amp
L18
-V 12V Transformer
V- V+
LN
Traffic Light – Black (to V+ Power Supply)
1601-426 Power Supply 8.5A
V+ Transformer 8.5 amp
L17
Make sure ANY unused wires are properly terminated and do NOT
Black
have exposed bare wires or metal
connectors that could cause
the operator to malfunction.
1625-065-B-6-23
Red/Blue
Blue NOT Used Pink NOT Used Yellow NOT Used
14
12V Negative (-) Solid State Relay
C6 L6
Terminal 2 Battery Backup PCB Breakaway Sensor NC
C8 L13
Terminal 1 Battery Backup PCB Breakaway Sensor NC
C9 L15
Cable Grip
1601-356 Harness
ElecStridoeniocfBox
1
2
1N1E5UV 1H1O5TV
3 4 5 6 7 8
9
10 11
GSRUOPUPNLYD
12 13
14
ON
OFF
ON
UP
OFF
AC POWER DC POWER AUTO
Terminal
DOWN
Power Supply
NOTE: Power supply MUST removed BEFORE terminal can be accessed.
Install Traffic Light (REQUIRED)
1 Assemble Support Post
Traffic Light
2 Mount Support Post on OPPOSITE Side of Access Door
Access Door
Support Post
Use 2″ conduit nuts to secure traffic light to support post.
Support Post
Route traffic light cable through support post.
2″ conduit nut to secure elbow. 2″ Elbow
6AtpfhtpRrcohroaououbgxltelhee.18″ SMeorvioinugs GInajuteryCoarnDCeaauthse iTPwKDnheEiottihdEhsnoeePoeustngttCrltaepirLatarteEninocsAachrerRmiwled!iuaasrse.rGnftnoaiunrotsgevpe.eemhsraaiectypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam.ye
bscUuriraspccetpukoboeietrxrmtabtibscooptokuaoinelrntstdgstt.
SBurPapocpskotertt
CDceo(fSinroNAelperobninpidecpmlodltprurpuewai7rlrlirettolet/heeot8xodde3r”ium/htwh4choooa”hhoputleeelecseorsloiywefnnoi1gdtph8ue”ictrEdoanlbotniopowdrpwu)nl.iet nut.
UCl-aBmolpt UCl-aBmoplt
Arm Up
Make sure traffic light stays clear of raising arm.
Arm Down
BCroacvkeert
1625-065-B-6-23
Top View
15
See next page to wire traffic light.
Install Traffic Light (Continued)
3 Wire Traffic Light Cable from Operator to Traffic Light
LED Traffic Light Kit
UP LOOP
TIME DELAY
Red/ Brown
White White
Traffic Light Terminal
Black Green Red
ON 12345678
SW 1
1601-010 POWER
SW 2
ON 12345678
Traffic Light Cable
DOWN LOOP
REVERSE SENSITIVITY
NC – Close – Red NO – Open – Green
Arm Relay Contacts
C NC NO
NC
ElecStridoeniocfBox
Common Main PCB
1 2 3 4 5 6 7 8 9 10 11 12 13 14
White
1
2
1N1E5UV 1H1O5TV
3 4 5 6 7 8
9
10 11
GSRUOPUPNLYD
12 13
14
ON
OFF
ON
UP
OFF
AC POWER DC POWER AUTO
Black
-V 12V Transformer
Terminal 2 – Hot
Circuit Board
L19
Terminal
DOWN
Traffic Light – Black (to V+ Power Supply)
1601-426 Power Supply 8.5A
Power Supply
White
L20
Circuit Board
Terminal 1 – Neutral
SUPPLY GROUND
Ground Panel Stud
L24
Required
Green
L – Line Transformer 8.5 amp
L21
N – Neutral Transformer 8.5 amp
L22
Ground Transformer 8.5 amp
L23
LN
NOTE: Power supply MUST removed BEFORE terminal can be accessed.
V- V+
Keep wire clear of all moving parts.
1625-065-B-6-23 16
45678
Install Photocell (REQUIRED) SW 1
ON 12345678
Mount photocell directly below the octagon arm on separate posts as shown,
mounting brackets not supplied.
1601 POWER
Type of wiring to be used on ALL external devices:
A) Type CL2, CL2P, CL2R, or CL2X.
SW 2
B) Other cable with equivalent or better electrical,
mechanical, and flammability ratings.
24 VAC – 250 mA max Reverse Input Low Voltage Common
Terminal #5 Note: ExceDeOdWinN g 250 mA of poLwOOePr from this terminal may cause the circuit board transformer to overheat, causing intermittent problems.
1601-010 REVERSE
SENSITIVITY NC NO
Main Terminal
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Power Relay
S6 AC10-25V NO NC COM DC12-30V
DIP-Switch
Relay (NO) Power
DoorKing Retro-Reflective Photocell (P/N 8080-057)
If using other photocells refer to the manufacturer’s manual for wiring
installation.
Fine Tune Photocell After photocell has
been mounted, spring mounted beam sensors can be
precisely adjusted “Fine tuned” using the 3 screws to help keep the GREEN LED
ON if
necessary.
Green LED Beam Sensors
S6 AC10-25V NO NC COM DC12-30V
Wiring Note: See page 20 for complete wiring.
ON 12345678
SW 2, Switch 5 is ON. The lowering arm will instantly reverse when photocell
gets blocked.
SW 2
IMPORTANT: DO NOT mount photocell to the operator cabinet. Cabinet can flex or vibrate during operation which may cause misalignment of the beam.
NOT A WALKWAY
Reflector Position reflector directly across from mounted and wired photocell.
Green LED on photocell will remain lit Mounting Post when reflector is in
correct position. Permanently mount reflector making sure LED remains lit.
“Fine Tune” photocell alignment if necessary, see above.
1625-065-B-6-23
WARcMSasNaetNTOuraIAiOsNloVYleu:tIGsivNCPBMmeieiGLnhocedjEitysuceoAc.AlrsrleRyceRtrysdMoicoaarlfnemcdasasearnamgteh,.
CAONNSFIO/URLM-3S2T5O CAN/CSEARTCI2F2IE.D2 NTO. 247
VEHICULAR GATE OPERATOR CLASS MODEL SERIAL VOLTS
AMPS
MAX
GATE LOAD DoorKing,
Inc.,
Inglewood,
CA
53382
HP PHASE 60 Hz
MSeorvioinugs GInajuteryCoarnDCeaauthse KPTDiwnhEeoittihdhEsnoeePoeustgnttCrlatiepraLtatrenEincosAachrermRiweld!iauasre.srGnftnoiaunrotsgevpe.eemhsraiaectypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam. ye
Mounting Post
D
A
N
G
E
R W
A
L
K
W
A
Y
Photocell
A
NOT
17
Entry Lane Only In-Ground Loop Options
OFF OFF OFF
OFF OFF
OFF
A
OFF OFF OFF OFF
OFF OFF OFF
ON 12345678
ON 12345678
Typical DIP-Switch Settings
Switch 4 is ON.
SW 1
Switch 7 is OFF (Timer). The arm will rotate down after the vehicle clears the down loop. See timer note below.
Switch 5 is ON. The lowering arm will instantly reverse when photo sensor gets
blocked.
SW 2
Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a licensed electrical contractor perform this work.
Loop detector wiring shown is for DoorKing model 9409 Dual Channel plug-In loop detector only. If using other loop detectors refer to their Loop Information Manual for installation instructions, loops/preformed loops and wiring diagrams. All inputs to the main terminal are NORMALLY OPEN.
Type of wiring to be used on ALL external devices: A) Type CL2, CL2P, CL2R, or CL2X. B) Other cable with equivalent or better electrical, mechanical, and flammability ratings.
DoorKing offers a free “Loop and Loop-Detectors Information Manual” PDF located at DoorKing’s web site for more information. www.doorking.com
TIME DELAY
UP LOOP
ON 12345678
NOT A WALKWAY
12 Ft.
NO Com
Down Loop DOWN Port
LOOP
A SW 1 DIP Switches
1601-010 POWER
SW 2
REVERSE SENSITIVITY
ON 12345678
UP Input Reverse Input Low Voltage Common
NC NO
9409
Dual Channel
If the ARMING LOOP is
Main Terminal 1 2 3 4 5 6 7 8 9 10 11 12 13 14
not used, then a single
channel loop detector
can be used (9410) in the down loop port.
Connect the down loop to loop 1 on this
detector. Connect the access control device
directly to main terminal 6 and 14.
Photocell See page 16.
Reverse
Down Loop
1 Ft. Minimum Distance
NOT A WALKWAY
NO
Com
Arming Loop Note: The arming loop only allows the access control device to
function when a vehicle is on the loop, otherwise it will not function. This
prevents pedestrians from gaining access through the vehicular gate.
Timer Note: The timer can be used with a down loop. When timer is ON with a
down loop, it will start countdown when the arm has fully raised. Activation
of the down loop will cancel timer countdown. Useful when an access control
device OR ticket spitter has been activated but vehicle does not move forward
to activate the down loop. The arm will remain UP. Timer will time out and
lower the arm without the down loop being activated.
Access Control Device
OR Ticket Spitter
1625-065-B-6-23 18
Arming Loop
for Access Control Device (Optional) OR
Ticket Eject Loop
for Ticket Spitter (Required)
Manual Release Operation
1. Unlock and remove access door. 2. Remove crank tool from inside access
door. 3. Flip interlock assembly door up, power will be disabled from
operator. 4. Insert crank tool into motor pulley as shown. 5. Rotate crank
tool to manually move operator arms up or down.
Access Door CraSntkorTaogoel
AIsnsteemrDloobcolkyr
2
1 +3
-4
WARMScasNaetNTOuraIAiOsNloVYleu:ItGsivNCPBMmeieiGLnhocedjEiytsucoeAc.AlrrsleRyceRtrysdMoiocaarlfncemdasaseranmagteh,.
53382
CAONNSFIO/URLM-3S2T5O VEHCIACNU/CCLSEAARRTCI2GF2IAE.D2TENTOOO.P2E4R7 ATHOPR
CLASS
MODEL
PHASE
SERIAL
60 Hz
VOLTS
MAMAXPDSGooArTKEinLgO, AInDc., Inglewood, CA
MSeorvioinugs GInajuteryCoarnDCeaauthse PDiTKwnheEoittihdhEsnoeePoeustngttCrltaieprLatatrenEinocsAachrerRmiwled!iuaasres.rGnftnoiaunrotsgevpe.eemhsraaeictypleeamstrhaooetvneeglyeaa.nttetraaonnrycpetliam. ye
1625-065-B-6-23 19
ALL Components Wiring Schematic
Type of wiring to be used on ALL external devices: A) Type CL2, CL2P, CL2R, or CL2X. B) Other cable with equivalent or better electrical, mechanical, and flammability ratings.
Octagon Reverse/LED Edge Arm
1601 Standard Bracket
UP LOOP
DoorKing Retro-Reflective Photocell (P/N 8080-057)
See Page 14
Wiring Required
Up Limit Magnet
TIME DELAY
Magnetic Limit Sensor
Down Limit Magnet (White Dot)
Red
Plugs
Breakaway Sensor Red Connector
C7 L8
Black
NOT Used
Breakaway Sensor
Red Connector
C6 L7
Blue
Breakaway Sensor
Blue Plugs Blue Connector
Battery Backup C8 L9 Pink
NOT
Breakaway Sensor
Used
Blue Connector Battery BackUp C9 L10 Yellow
LED Traffic Light
ON 12345678
Power Relay
S6 AC10-25V NO NC COM DC12-30V
See Page 16
Wiring Required
Manual Release Assembly
ON 12345678
DoorKing Plug-In Dual Channel Loop Detector (P/N 4909)
NO Com
SW 1
1601-010 POWER
SW 2
DOWN LOOP
REVERSE SENSITIVITY
LooDpown
9409
Arm Relay Contacts
C NC NO
Common NC Main PCB
1 2 3 4 5 6 7 8 9 10 11 12 13 14
LoAorpming
Red/ Brown
Traffic Light Terminal
White White
Black Green Red
See Page 15
Wiring Required
Traffic Light Cable
N-Open Main PCB Green Light C2 L2 Green
N-Close Main PCB Red Light C1 L1 Red
NC – Close – Red NO – Open – Green
Interlock Cut-Off Switch
Com N.O.
Power
Neutral 115 VAC Open Outlets
1602 1 HP Single Phase
Ground Orange
Yellow
White Blue Red
To #14 To #9
To #14
Access Control Device OR Ticket Spitter
To #5
Circuit Board
Terminal 1 – Neutral
NEU HOT
115 VAC
SUPPLY GROUND
Green
Ground Panel Stud
L24
Red NOT Used
12V Positive (+) Solid State Relay
C3 L3
L20
White
Common Main PCB LED Light C10 L11 White
Terminal 9 Main PCB Reverse Edge C5 L5
Terminal 14
Main PCB
Reverse Edge C4 L4
Grey
Grey/Pink
-V 12V Transformer White
Black
Terminal 2 – Hot
Circuit Board
L19
L – Line Transformer 8.5 amp
L21
Traffic Light – Black (to V+ Power Supply)
1601-426 Power Supply 8.5A
LN
N – Neutral Transformer 8.5 amp
L22
Ground Transformer 8.5 amp
L23
VTransformer 8.5 amp
L18
V- V+
Black
Red/Blue
12V Negative (-) Solid State Relay
C6 L6
Black Black Purple Blue Red
V+ Transformer 8.5 amp
L17
AC Power
UP/Auto/Down
Blue NOT Used Pink NOT Used Yellow NOT Used
Terminal 2 Battery Backup PCB Breakaway Sensor NC
C8 L13
Terminal 1 Battery Backup PCB Breakaway Sensor NC
C9 L15
Cable Grip
1601-356 Harness
1625-065-B-6-23 20
1625-065-B-6-23 21
Installation Manual
1625 Wedge Barrier
Surface Mount Vehicular Wedge Barrier Accessory
Use this manual for circuit board 1601-010 Revision W or higher.
1625-065-B-6-23
IMPORTANT: Installation of Traffic Light, Photocell and Octagon Arm with LED Edge is REQUIRED.
WARNING pre-stressed concrete may be used in multi-level parking garages.
Cutting a tensioned cable, or tendon, can endanger the contractor and
compromise the structural integrity of the floor. Contact the building
structural engineer for specific instructions and information BEFORE drilling
or saw cutting into the floor.
INSTALLATION AND USE OF THE WEDGE BARRIER IN AREAS SUBJECT TO FREEZING WEATHER
WITH POTENTIAL FOR SNOW AND ICE ACCUMULATION IS NOT RECOMMENDED.
THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE/DOOR SYSTEMS
TECHNICIAN ONLY. Visit www.doorking.com/dealer-locator to find a professional
installing and servicing dealer in your area.
www.doorking.com
The 1625 wedge barrier is not a stand-alone product. It must be used with a
1602-590 Barrier Gate Operator (sold separately). The 1625 is not crash rated.
It is intended to provide a more formidable barrier in conjunction with a
standard barrier arm operator system. The 1625 is ideally used to control
passenger vehicles and lightduty trucks.
DoorKing, Inc. 120 S. Glasgow Avenue Inglewood, California 90301
U.S.A.
Phone: 310-645-0023 Fax:
310-641-1586