EPEVER IPB Series Pure Sine Wave Inverter
USER MANUAL
MODEL: IPB500-12; IPB1000-12; IPB1500-12; IPB2000-12; IPB3000-12
Important Safety Instructions
Please reserve this manual for future review.
This manual contains instructions on the safety, installation, and operation
of the IPB series pure sine wave inverter (“inverter” as referred to in this
manual).
1. Explanation of symbols
Please read related literature accompanying the following symbols to enable
users to use the product efficiently and ensure personal and property safety.
Please read the literature accompanying the following symbols.
Symbols | Definition |
---|---|
TIP | Indicates any practical advice for reference |
IMPORTANT: Indicates a critical tip during the operation, if ignored, may |
cause the device to run in error.
| CAUTION: Indicates potential hazards. If not avoided, it may cause the
device to be damaged.
| WARNING: Indicates the danger of electric shock. If not avoided,
it would cause casualties.
| WARNING HOT SURFACE: Indicates the risk of high temperature, if not
avoided, would cause scalds.
| Read the user manual carefully before any operation.
|
WARNING| The entire system should be installed by professional and
technical personnel.
2. Requirements for professional and technical personnel
- Professionally trained;
- Familiar with related safety specifications for the electrical system;
- Read this manual carefully and master related safety cautions.
3. Professional and technical personnel is allowed to do
- Install the inverter to a specified location.
- Conduct trial operations for the inverter.
- Operate and maintain the inverter.
4. Safety cautions before installation
IMPORTANT
| When you receive the inverter, check whether there is any
damage in transportation. Contact the transportation company, our
local distributor, or our company for any problem.
---|---
CAUTION
|
- When placing or moving the inverter, follow the instructions in the manual.
- When installing the inverter, evaluate whether the operation area exists arc danger.
- The inverter needs to be connected to a battery. The battery’s minimum capacity (Ah) is recommended to be five times the current that equals the inverter’s rated output power divided by the battery’s voltage.
WARNING
|
- Keep the inverter out of the reach of children.
- This inverter is an off-grid type. It is strictly prohibited to connect the inverter to the grid. Otherwise, the inverter will be damaged.
- This inverter is only allowed for stand-alone operation. It is prohibited to connect multiple units in parallel or series. Otherwise, the inverter will be damaged.
5. Safety cautions for mechanical installation
WARNING
- Before installation, ensure the inverter has no electrical connection.
- Confirm enough heat dissipation space for the inverter before installation. Do not install the inverter in a harsh environment such as humid, salt spray, corrosion, greasy, flammable, explosive, or dust accumulation.
6. Safety cautions for electrical connection
CAUTION
-
Check whether wiring connections are tight to avoid the danger of heat accumulation due to loose connections.
-
The protective grounding is connected to the ground. The cross-section of the wire should not be less than 4mm2.
-
The DC input voltage must strictly follow the parameter table. Too high or too low
DC input voltage will affect the inverter’s normal operation and damage it. -
It is recommended that the connection length between the battery and the inverter be less than 3 meters. If greater than 3 meters, please reduce the current density of the connection wire.
-
A fast-acting fuse or breaker should be used between battery and Inverter; the fast-acting fuse or breaker’s rated current should be twice the inverter rated input current.
-
DO NOT install the inverter close to the flooded lead-acid battery because the terminals’ sparkle may ignite the hydrogen released by the battery.
WARNING
- The AC output terminal is only for the load connection. Do NOT connect it to another power source or utility. Otherwise, the inverter will be damaged. Turn off the inverter when connecting loads.
- It is strictly forbidden to connect a transformer or a load with a surge power (VA) exceeding the overload power at the AC output port. Otherwise, the damage will be caused to the inverter.
- Do not connect battery chargers or other similar products to the input terminal of the inverter. Otherwise, the inverter will be damaged.
7. Safety cautions for controller operation
WARNING HOT SURFACE
When the inverter is working, the cover temperature is very high because of the accumulated heat; please do not touch it.
CAUTION
When the inverter is running, please do not open the cabinet.
WARNING
The inverter’s AC output is of high voltage, do not touch the wiring connection to avoid electric shock
8. Dangerous operations which would cause an electric arc, fire, or explosion
- Touch the wire end that hasn’t been insulation treated and may be electriferous.
- Touch the wiring copper row, terminals, or internal inverter modules that may be electriferous.
- The connection of the power cable is loose.
- Screw or other spare parts inadvertently falls into the inverter.
- Improper operations by untrained non-professional or technical personnel.
WARNING
Once an accident occurs, it must be handled by professional and technical personnel. Improper operations would cause more serious accidents.
9. Safety cautions for stopping the inverter
- The internal conductive modules could be touched after the inverter stopped running for five minutes.
- The inverter is allowed to restart after removing the faults, which affects the safety performance.
- There are no serviceable parts inside. If any maintenance service is required, please contact our local distributor or the service personnel.
WARNING
Do NOT touch or open the shell after the inverter is powered off within ten minutes.
10. Safety cautions for inverter maintenance
- It is recommended to check the inverter with testing equipment to ensure no voltage and current.
- When conducting electrical connection and maintenance, post a temporary warning sign or put up barriers to prevent the unrelated personnel from entering the electrical connection or maintenance area.
- An improper operation of the inverter may cause personal injury or equipment damage.
- It is recommended to wear an antistatic wrist strap or avoid unnecessary contact with the circuit board.
1. Overview
The IPB series, a high-frequency sine wave inverter, adopts a fully digital intelligent design and voltage-current dual closed-loop control algorithm. It is designed with the Utility bypass function (when the Utility is normal, the inverter output will automatically switch to the Utility bypass, i.e. utility priority). Featured with fast response, high conversion efficiency, low Total Harmonic Distortion(THD), and high reliability running, the IPB series can be widely used in the DC-AC off-grid systems (such as vehicle systems, security monitoring systems, emergency lighting systems, household power systems, field power systems, and other systems requiring higher power quality).
Features:
- Pure sine wave output
- Input to output electrical isolation
- Output power factor up to 1
- Input Protection: Low-voltage, Over-voltage
- Output Protection: Overload, Short circuit, Overheating
- RS485 com. port to realize remote monitoring①
- Utility bypass automatic switching function (utility supplies load when the utility is normal)
- External switch design, matched with EPEVER products, to expand inverter control function and reduce power consumption
- Diversified AC output sockets
① For inverters with 12V input voltage, there is no communication isolation design for the RS485/RJ11 port.
2. Appearance
connected to the product, equipped with a fast-acting fuse terminal, cannot exceed the marked value.
⑤ The DC input terminals vary with different products. Please refer to the real product.
Cooling fan
3. Naming Rule
4. Connection Diagram
IPB1000-12/IPB1500-12/IPB2000-12
The connection diagram is the same for IPB1000-12, IPB1500-12, and IPB2000-12,
the following takes
IPB1000-12 as an example to introduce the system connection.
5. Installation
5.1 Attentions
-
Read all the installation instructions carefully in the manual before installation.
-
Be very careful when installing the batteries. When installing the open-type lead-acid battery, please wear eye protection and rinse with clean water for battery acid contact.
-
Keep the battery away from any metal objects, which may cause a short circuit of the battery.
-
Loose power connectors and corroded wires may result in high heat, melt wire insulation, burn surrounding materials, or cause a fire. Ensure tight connections and secure cables with cable clamps to prevent them from swaying in moving applications.
-
The DC input voltage must strictly follow the parameter table. Too high or too low DC input voltage affects the normal operation and may damage the inverter. DC input 12V: Surge voltage < 20V.
-
Select the system cables according to 3.5A/mm2 or less current density.
-
Avoid direct sunlight and rain infiltration when installing it outdoor.
-
After turning off the power switch, do not open or touch the internal component immediately.
Performing related operations after 10 minutes is recommended. -
Do not install the inverter in a harsh environment such as humid, salt spray, corrosion, greasy, flammable, explosive, or dust accumulation.
-
The AC output is of high voltage, do not touch the wiring connection to avoid electric shock.
-
To prevent injury, do not touch the fan while it is working.
5.2 Wire Size and Circuit Breaker
The wiring and installation methods conform to the national and local electrical code requirements.
- Wire, terminals, and circuit breaker selection for battery
5.3 Mounting
Installation procedures:
Step1: Professional personnel reads this manual carefully.
Step 2: Determine the installation location and heat-dissipation space The
inverter shall be installed in a place with sufficient airflow through the
dissipation pad of the inverter.
And a minimum clearance of 150mm from the upper and lower edges of the
inverter is recommended to ensure natural thermal convection. The following
takes IPB2000-12 as an example.
2. Battery connection
CAUTION
A fast-acting fuse must be installed on the battery side, conformed to the
following requirements:
1. Fast-acting fuse voltage is 1.5 to 2 times the inverter’s rated voltage.
2. Fast-acting fuse current is 2 to 2.5 times the inverter’s rated current.
3. Distance between the fast-acting fuse and the battery cannot be farther
than 150mm.
3. AC load connection
WARNING
-
The AC loads shall be determined by the continuous output power of the inverter.
The surge power of the AC load must be lower than the instantaneous surge power of the inverter, or the inverter will be damaged. -
The N pole of the AC output port cannot be grounded.
4. Connect the Utility
WARNING
-
Risk of electric shock! The Utility input can generate dangerous high-voltage!
Disconnect the circuit breaker or fast-acting fuse before wiring, and ensure that the poles’ leads are connected correctly. -
After the Utility is connected, the battery cannot be grounded. In contrast, the inverter cover must be grounded reliably (to shield the outside electromagnetic interference effectively and prevent the cover from causing electric shock to the human body).
5. Optional accessories connection
- RS485 communication port
6. (Reserved) Remote switch connection
Step 4:Power on the inverter
⑴ Connect the breaker at the inverter input terminal or the fast-acting fuse
at the battery terminal.
⑵ Turn on the inverter switch, and the green indicator will be lighted on,
which states a normal AC output.
⑶ Connect the breaker at the AC load terminal, turn on the AC loads, and check
the system working status.
CAUTION
When supplying power for different loads, it is recommended to first turn on
the load with a large impulse current. And then turn on the load with a
smaller impulse current after the load output is stable.
⑷ If the FAULT indicator flashes red and the buzzer alarms after powering the
inverter, please immediately turn off the load and the inverter. Clear the
faults according to chapter 8 Troubleshooting. After clearing the faults,
please operate the inverter again by following the above steps.
6. Parameters Setting
IPB parameters such as power saving mode, baud rate, output voltage class, and
output frequency class can be set by the remote meter (optional, you need to
purchase it additional), phone APP, or PC software.
The following chapters take parameters setting on the remote meter as an
example (for connection of the remote meter, please refer to chapter 5.3
Mounting).
6.1 Power Saving Mode
Users can enable the power saving mode and set the PSI/PSO value by the remote
meter (The minimum power step is 1VA).
When the actual load power is lower than the PSI (the power to enter the power
saving mode), the system will automatically switch to the power saving mode.
And then, the device output is turned on for 1s and turned off for 5s.
When the actual load power exceeds the PSO (the power to exit the power saving
mode), the inverter will automatically exit the power saving mode and resume
work.
- Enable power saving mode (PSE)
7. Protections
- Input voltage protection
- The following rules must be followed when modifying the battery’s input voltage parameters:
A. Over voltage limiting voltage (16.2) ≥ Over voltage disconnect voltage ≥
Over voltage
reconnect voltage +1V.
B. Over voltage reconnect voltage ≥ Low voltage reconnect voltage.
C. Low voltage reconnect voltage ≥ Low voltage disconnect voltage +1V.
D. Low voltage disconnect voltage ≥ Low voltage limiting voltage (10.5).
- Detailed status is shown as the following when the input voltage protection occurs.
5) Inverter over temperature protection
8. Troubleshooting
9. Maintenance
The following inspections and maintenance tasks are recommended at least two times per year for good performance.
- Make sure no block on airflow around the inverter. Clear up any dirt and fragments on the heat sink.
- Check all the naked wires to ensure insulation is not damaged by sun exposure, frictional wear, dryness, insects or rats, etc.
- Verify the indicator display is consistent with the actual operation.
- Confirm that terminals have no corrosion, insulation damage, high temperature, burnt/discolored sign, and tighten terminal screws to the suggested torque.
- Clear up dirt, nesting insects, and corrosion in time.
- Check and confirm that the lightning arrester is in good condition. Replace a new one in time to avoid damaging the inverter and other equipment.
WARNING
Risk of electric shock! Confirm all the power is turned off and all the
capacitor’s energy has been discharged before performing the above operations.
10. Specifications
Appendix 1 Disclaimers
The warranty does not apply to the following conditions:
- Damage is caused by improper use or an inappropriate environment (humid, salt spray, corrosion, greasy, flammable, explosive, dust accumulative, or other severe environments).
- The actual current/voltage/power exceeds the limit value of the inverter.
- Damage caused by working temperature exceeds the rated range.
- Arc, fire, explosion, and other accidents are caused by failure to follow the inverter stickers or manual instructions.
- Disassemble and repair the inverter without authorization.
- Damage caused by force majeure.
- Damage occurred during transportation or handling.
- Before using precise instruments, such as a medical instrument, end-users must read the manual carefully and ensure the inverter’s output power/output voltage is suitable. We are not responsible for the instrument damage caused by improper use.
Specifications
-
Model Numbers: IPB500-12, IPB1000-12, IPB1500-12, IPB2000-12,
IPB3000-12 -
Waveform: Pure Sine Wave
-
Power Saving Mode: Yes
-
Installation Type: Off-grid, Stand-alone operation only
-
Professional Installation Required: Yes
-
Minimum Battery Capacity: Recommended to be 5 times the current that equals the inverter’s rated output power divided by the battery’s voltage
HUIZHOU EPEVER TECHNOLOGY CO., LTD.
Tel: +86-752-3889706
E-mail: info@epever.com
Website: www.epever.com
Frequently Asked Questions (FAQ)
Q: Can I connect multiple units of the inverter in parallel or series?
A: No, it is strictly prohibited to connect multiple units of the inverter in parallel or series as it may damage the inverter.
Q: What type of waveform does the inverter produce?
A: The inverter produces a pure sine wave, ensuring compatibility with sensitive electronic devices.
Q: What should be the minimum battery capacity for connecting to the
inverter?
A: It is recommended that the battery’s minimum capacity (Ah) be five times the current that equals the inverter’s rated output power divided by the battery’s voltage for optimal performance.