Pulsar HPSG3-LCD Series Switch Mode Power Supply Units User Manual
- June 16, 2024
- Pulsar
Table of Contents
- Pulsar HPSG3-LCD Series Switch Mode Power Supply Units
- GENERAL SAFETY RULES
- Features
- Technical description
- Installation
- Functions
- Reserve power supply circuit.
- Graphic LCD – preview
- graphic LCD display – PSU settings
- Remote monitoring (option: Ethernet, RS485).
- Specifications
- Technical inspections and maintenance.
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Pulsar HPSG3-LCD Series Switch Mode Power Supply Units
GENERAL SAFETY RULES
- Before installation, read the instruction manual to avoid errors that can damage the device and give you an electric shock.
- Before installation, cut off voltage in the 230 V power-supply circuit.
- To switch power off, use an external switch, in which the distance between contacts of all poles in disconnection state is not less than 3mm.
- The shock protection circuit shall be done with particular care: the yellow and green wire coat of the power cable should be connected to the terminal marked with the grounding symbol on the PSU enclosure. Operation of the PSU without the properly made and fully operational shock protection circuit is UNACCEPTABLE! It can cause damage to the equipment or an electric shock.
- The device should be transported without batteries. This has a direct impact on the safety of the user and device.
- Installing and connecting the power supply must be carried out without batteries.
- When connecting batteries to a power supply, pay particular attention to correct polarity. If necessary, it is possible to permanently disconnect the battery from power supply systems by removing the FBAT fuse.
- The power supply is adapted to be connected to a power distribution network with an effectively earthed neutral conductor.
- Ensure a free, convection airflow around the enclosure. Do not cover ventilation openings.
Features
- compliance with norm EN50131-6:2017 in grade 1, 2, 3 and II environmental class
- compliance with norm EN60839-11-2:2015+AC:2015 and I environmental class
- supply voltage ~200-240 V
- DC 13,8 V or 27,6 V uninterruptible power supply
- powered by 17Ah – 65Ah batteries
- high efficiency (up to 86%)
- available versions with current efficiencies 13,8V: 3A, 5A, 10A 27,6V 2A, 5A
- ow ripple voltage
- microprocessor-based automation system
- measurement of resistance of battery circuit
- automatic temperature-compensated charging
- automatic battery test
- output voltage control
- battery circuit continuity control
- battery voltage control
- battery charging and maintenance control
- deep discharge battery protection (UVP)
- battery overcharge protection
- battery output protection against short circuits and reverse connection
- function START allows running PSU from battery power
- optical indication
- technical outputs OC type (open collector)
- collective failure input EXT IN
- EPS technical output indicating AC power loss
- PSU technical output indicating PSU failure
- APS technical output indicating battery failure
- protections:
- SCP short circuit protection
- OLP overload protection
- OVP overvoltage protection
- surge protection
- optional equipment (AWZ642)
- optical indication – LCD panel
- electrical parameters’ readings, e.g. voltage, current
- failure indication
- PSU settings adjusted from the panel’s level
- 3 levels of access, password-protected
- operation memory of PSU
- failure memory
- real-time clock, battery-backed
- the internal memory of PSU operating status
- remote monitoring
- ethernet or RS485 communication (options)
- embedded PowerSecurity web application
- preview of the operating parameters: voltages, currents, temperature and resistance of the battery circuit
- PSU work history chart from a period of more than 100 days: voltages, currents and resistance of the battery circuit
- battery operating temperature readings from periods up to 5 years
- event log of up to 2048 power supply failures
- remote battery test
- SERIAL” communication port with implemented MODBUS RTU protocol
- remote monitoring (options: Ethernet, RS485)
- remote battery test (additional modules required)
- convectional cooling
- warranty – 3 years from production date
Technical description
General description.
Buffer power supplies have been designed under requirements of the (I&HAS)
EN50131-6:2017 grade 1-3 and II environmental class and (KD)
EN60839-11-2:2015+AC:2015 standard and I environmental class. Power supply
units are intended for an uninterrupted supply of alarm system devices
requiring a stabilized voltage of 12 or 24 V DC (±15%). Depending on the
required protection level of the alarm system in the installation place, the
PSU efficiency and the battery charging current should be set as follows:
Power supply model| Battery/charging current| Output current [A] depending on the application PSU
(according to EN50131-6)
---|---|---
Grade 1, 2 – standby
time 12 h
| * Grade 3 – standby
time 30 h
| ** Grade 3 – standby
time 60 h
HPSG3-12V3A-C-LCD| 17Ah /0,8 A| 1,39 A| 0,54 A| 0,25 A
HPSG3-12V5A-C-LCD| 17Ah /0,8 A| 1,39 A| 0,54 A| 0,25 A
HPSG3-12V5A-D-LCD| 40Ah/1,8 A| 3,3 A| 1,30 A| 0,64 A
HPSG3-12V10A-E-LCD| 65Ah/2,6 A| 5,4 A| 2,1 A| 1,0 A
HPSG3-24V2A-C-LCD| 17Ah (x2)/0,8 A| 1,4 A| 0,5 A| 0,24 A
HPSG3-24V5A-D-LCD| 40Ah (x2)/1,8 A| 3,3 A| 1,3 A| 0,63 A
- if faults of the primary source are reported to the ARC alarm receiving centre (by 9.2 EN50131-6)
- if faults of the primary source are not reported to the ARC alarm receiving centre (by 9.2 EN50131-6)
In case of a lack of main power, a battery backup is activated immediately. A metallic enclosure with PSU (colour RAL 7016 – grey) can accommodate battery/batteries. It is equipped with a tamper switch signalling door opening and detaching from the surface.
Block diagram.
PSU has been manufactured based on a high-efficiency system of AC/DC
converter. The applied microprocessor circuit is responsible for full
diagnostics of PSU parameters and batterie.
Description of components and power supply terminals.
Table 1. Elements of PSU PCB (Fig. 2).
Element
no.
| Description
---|---
1| 230 V supply connector with a terminal for connection of a protective
conductor
2| START – button (launching from battery)
3| Battery temperature sensor
4
| START – button (launching from battery) Terminals:
+AUX, -AUX – AUX power supply output ( – AUX=GND, +AUX= power supply output) EPS – technical output of AC network absence indication – OC type
Open = AC power failure Close = AC supply – O.K.
APS – technical output of battery failure Open = battery failure
Close = battery O.K.
PSU – technical output of PSU failure – OC type Open = failure
Close = O.K.
EXTi – input of external failure.
Closed input = no indication Open input = failure
+BAT- – terminals for connecting the battery
TAMPER – antisabotage protection microswitch connector TEMP – input of battery temperature sensor
5| Battery connectors ; positive: +BAT = red, negative: – BAT = black
6| PANEL – connector to external LED indicators
7| LEDs – optical indication:
230V AC – indicates ~230 V power CHARGE – battery charging indication ALARM – collective fault indication
8| F BAT – fuse in the battery circuit
9| LCD connector
10| Communication interface connector
Table 2. Elements of PSU (see Fig. 3).
Element no. | Description |
---|---|
1 | PSU module (Tab. 1, Fig. 2) |
2 | Battery temperature sensor |
3 | Battery connectors; positive: BAT = red, negative: – BAT = black |
4 | A place for the installation of additional communications modules |
5 | TAMPER; microswitch (contacts) of antisabotage protection (NC) |
6 | Fitting battery |
7 | Battery blocking plate |
8 | Screen module |
Installation
Requirements
Power supply units are to be mounted by a qualified installer, holding
relevant permits and licenses (required in installation country) to connect
(interfere) with ~230 V mains supply. Because power supply units is designed
for the continuous operation and is not equipped with ON/OFF switch, the power
supply circuit should have the appropriate overload protection. Moreover, the
user shall be informed about the method of unplugging (most frequently through
separating and assigning an appropriate fuse in the fuse-box). The electrical
system shall follow valid standards and regulations. The PSU shall work in a
vertical position that guarantees sufficient convectional air-flow through
ventilating holes of the enclosure. As PSU cyclically runs a periodic battery
test, during which resistance in battery circuit is measured, pay attention to
proper connection of cables to terminals. Installation cables should be firmly
connected to battery side terminals and to power supply connector. If
necessary, it is possible to permanently disconnect battery from power supply
systems by removing FBAT fuse. PSU is protected from access to configuration
menu by two-level access passwords. If, during installation, modification of
factory settings is required then access must be unlocked by entering the
installer password – Table 9 and section 7.1.
Installation procedure.
CAUTION!
Before installation, cut off voltage in ~230 V power-supply circuit. To switch
power off, use an external switch, in which the distance between contacts of
all poles in disconnection state is not less than 3mm.
It is required to install in the supply circuits, in addition to the power supply, a circuit breaker with 6 A nominal current.
-
Mount the PSU in a selected location.
-
Connect power cables ~230 V to L-N clips of PSU. Connect the ground wire to clip marked by earth symbol .
- Use a three-core cable (with a yellow and green protection wire ) to make the connection. Wires should be desolated to a length of 7mm.
Shock protection circuit shall be done with a particular care: yellow and green wire coat of power cable should be connected to terminal marked with grounding symbol on PSU enclosure. Operation of PSU without properly made and fully operational shock protection circuit is UNACCEPTABLE! It can cause damage to equipment or an electric shock.
- Use a three-core cable (with a yellow and green protection wire ) to make the connection. Wires should be desolated to a length of 7mm.
-
Connect receivers’ cables to AUX output terminals.
-
If needed, connect cables from devices to technical inputs and outputs: – APS; technical output of battery failure – EPS; technical output indication of 230 V power collapse (alarm control panel, controller, indicator, etc.).
- PSU; the technical output of the collective failure of PSU – EXTi; input of external failure
- TAMPER; contacts of antisabotage protection
-
Install battery/batteries in a designated area of the enclosure. Connect batteries with PSU paying special attention to correct polarity and type of connections (Fig. 4):
-
Fig. 4. Connecting batteries depending on voltage version of power supply: a) power supplies 12V version, b) power supplies 24V version
-
Screw terminals of temperature sensor to “Temp” terminals of PSU (figure 2, point 3). Attach sensor to the battery, e.g. with adhesive tape. For the 27.6V version, it is recommended to place the sensor between batteries.
-
Switch on ~230 V supply. The corresponding LEDs on the power supply PCB should be ON: green 230 V AC and above AUX connectors.
-
Check the current consumption of receivers, taking into account battery charging current, so as not to exceed the total current efficiency of the PSU (see section 2.1).
-
Once the tests and control operation have been completed, close the enclosure.
-
Close the power supply cover after testing and operation control.
Procedure for checking power supply module on installation site.
- Check indication displayed on printed circuit board of power supply:
- 230 V AC LED should remain lit to indicate the presence of mains supply voltage.
- LED above AUX connectors lights up to indicate the presence of output voltage.
- Check output voltage after 230 V power failure.
- Simulate lack of 230 V mains voltage by disconnecting the main circuit breaker.
- 230 V LED should go out.
- LED above AUX connectors lights up to indicate the presence of output voltage.
- LED ALARM LED will start blinking.
- EPS technical outputs will change status into opposite after time 11 s.
- Turn on 230 V mains voltage again. Indication should return to the initial status from point 1 after about 11 seconds.
- Check whether lack of continuity in battery circuit is properly indicated.
- During normal PSU operation (230 V mains voltage on), disconnect battery circuit by disconnecting FBAT fuse.
- Within 5 minutes PSU will start signalling a failure in battery circuit.
- LED ALARM LED will start blinking. APS technical output will change status into the opposite.
- FBAT fuse in battery circuit again.
- Power supply should return to normal operation, indicating initial status, within 5 minutes after battery test is completed.
Functions
Technical outputs
PSU module is equipped with indication outputs OC type changing status after a
specified event:
EPS – output indicating 230 V power loss.
The output indicates 230 V power loss. Under normal status – with 230 V supply
on, output is closed. In case of power failure, PSU will switch output into
open position after a time about 11 seconds.
APS – output indicating battery failure.
The output indicates the PSU failure. Under normal status (during correct
operation) the output is closed. In case of failure, the PSU will switch the
output into the open position. Failure can be triggered by the following
events:
- defective or low battery
- battery voltage below 23 V or 11,5 V (depending on the voltage version of the power supply) during battery operation
- battery fuse failure
- no continuity in the battery circuit
PSU – output indicating PSU failure.
The output indicates the PSU failure. Under normal status (during correct
operation) the output is closed. In case of PSU failure, it will switch into
the open position. PSU failure can be caused by the following events:
- low UAUX output voltage, less than 23 or 13 V – depending on the voltage version of the power supply
- high UAUX output voltage, higher than 28,4 or 14,2 V – depending on the voltage version of power supply
- exceeding power supply output current
- battery charging circuit failure
- internal damage of PSU
- activation of the EXT IN input
- to high battery temperature (> 65°C)
- temperature sensor failure, t < -20°C or t > 80°C
The power supply technical outputs are open collector (OC) type, as shown schematically below.
If it is necessary to use technical relay outputs, the AWZ642 relay module should be used.
Collective failure input EXT IN.
EXT IN (external input) technical input indicating collective failure is
intended for additional, external devices that generate failure signal. The
voltage appearing at the EXT IN input will trigger PSU failure, storing the
information about the event in the internal memory and sending the signal
about the failure to the PSU output.
The connection of external devices to the EXT IN input is shown in the
electrical diagram below. OC outputs (open collector) or relay outputs can be
used as the source of the signal.
The EXT IN input has been adjusted to work with fuse modules generating a failure signal in case of blown fuse in any of output sections (e.g. AWZ536). To guarantee a correct cooperation between the fuse module and the EXT IN input, the connections shall be made as presented in the diagram below .
Optical indication.
PSU is equipped with LEDs on PCB indicating PSU operation status:
ALARM LED flashes specified number of times to indicate failure code according to table below. If PSU has several failures at the same time, they are all indicated consecutively.
Table 3. Coding of PSU failure by number of ALARM LED flashes on PCB of PSU.
Failure description | Number of flashes |
---|---|
F01 – AC power loss | 1 |
F04 – Output overload | 2 |
F05 – Undercharged battery | 3 |
F06 – High AUX1 voltage | 4 |
F08 – Charging circuit failure | 5 |
F09 – Low AUX1 voltage | 6 |
F10 – Low battery voltage | 7 |
F12 – External input EXTi | 8 |
F14 – Temperature sensor failure | 9 |
F15 – High battery temperature | 10 |
F16 – No battery | 11 |
F17 – Battery fail | 12 |
F30 – PSU overload | 13 |
F51 – Service code | 14 |
F52 F70 – Service codes | 15 |
Failures are also indicated on the LCD panel (see section 6.4.3.)
Indication opening enclosure – TAMPER.
PSU is fitted with tamper microswitches indicating enclosure opening and
detaching from the surface. The contacts of microswitches are normally closed,
and their wires must be connected to input of control panel, etc.
PSU overload.
PSU is equipped with an output overload protection circuit. If a rated current
of PSU is exceeded, the microprocessor will switch to a specially implemented
procedure and signal failure on PSU output and ALARM LED on PCB. Depending on
duration and level of PSU overload, microprocessor may put PSU into battery
operation mode. After overload has stopped, PSU will resume correct operation.
An overload status of the PSU is indicated by changing status of PSU technical
output and blinking of ALARM LED on the PCB.
Reserve power supply circuit.
PSU is fitted with circuits: charging and battery control whose main task is to monitor the state of the battery and connections in its circuit. If the controller detects a power failure in battery circuit, appropriate indication and change of APS technical output.
Running PSU on battery backup.
PSU has been fitted with a button on PCB to enable activate battery operation
of PSU if required. Activation of PSU from battery: to do that, press and hold
the START button on the unit board for 1 second.
Deep discharge battery protection UVP.
PSU is fitted with a disconnection system and battery discharge indication.
During battery operation, lowering voltage below 10 V +/-0.2 V (20 V±0.2 in
27.6 V version) will disconnect battery within a few seconds. Batteries are
reconnected to power supply unit automatically once ~230 V mains supply is
restored.
Battery test.
The PSU runs a dynamic battery test every 5 minutes, temporarily switching the
receivers to the battery operation mode. During testing, the control unit of
the PSU measures the electrical parameters according to the implemented
measuring method. Negative test result will occur as soon as continuity of
battery circuit is broken, or if the voltage drops below 12 V or 24 V
(depending on the version of the PSU). The battery test function will also be
automatically blocked if the PSU is in a working mode in which running of the
battery test would not be possible. This condition occurs, for example, during
battery operation or when PSU is overloaded.
Measurement of resistance of battery circuit.
PSU is checking resistance in the battery circuit. During measurement, the PSU
driver takes into account key parameters in circuit, and once limit value of
300m ohms is exceeded for 13,8 V version or 350 mΩ for 27,6 V version, a
failure is indicated. A failure may indicate considerable wear or loose cables
connecting batteries.
Battery operating temperature readings.
Temperature measurement and compensation of battery charging voltage can
extend life of batteries. PSU has a temperature sensor to monitor the
temperature parameters of installed batteries. Attach sensor to battery, e.g.
with adhesive tape. For the 27.6V version, it is recommended to place sensor
between batteries. Be careful not to damage the sensor when moving batteries.
Standby time.
Battery-assisted operating depends on battery capacity, charging level and
load current. To maintain an appropriate standby time, current drawn from the
PSU in battery mode should be limited.
Power supply model
|
Battery/charging current
| Output current [A] depending on application PSU
(according to EN50131-6)
---|---|---
Grade 1, 2 –
standby time 12 h
| * Grade 3 standby
time 30 h
| ** Grade 3 standby
time 60 h
HPSG3-12V3A-C-LCD| 17Ah / 0,8 A| 1,39 A| 0,54 A| 0,25 A
HPSG3-12V5A-C-LCD| 17Ah / 0,8 A| 1,39 A| 0,54 A| 0,25 A
HPSG3-12V5A-D-LCD| 40Ah / 1,8 A| 3,3 A| 1,30 A| 0,64 A
HPSG3-12V10A-E-LCD| 65Ah / 2,6 A| 5,4 A| 2,1 A| 1,0 A
HPSG3-24V2A-C-LCD| 17Ah(x2) / 0,8 A| 1,4 A| 0,5 A| 0,24 A
HPSG3-24V5A-D-LCD| 40Ah(x2) / 1,8 A| 3,3 A| 1,3 A| 0,63 A
- if faults of primary source are reported to the ARC alarm receiving centre (under 9.2 EN50131-6)
- if faults of primary source are not reported to the ARC alarm receiving centre (under 9.2 EN50131-6)
Depending on a required protection level of the alarm system in the installation place, the PSU efficiency and the battery charging current should be set as follows:
- Output current PSU an be calculated from formula:
where:
- QAKU – minimum battery capacity [Ah]
- IZ – PSU current consumption (including optional modules) [A] (Table 4)
- T- standby time (12, 30 or 60 h)
Graphic LCD – preview
Control Panel.
The PSU features a panel with buttons and LCD display, enabling reading of all
the available electrical parameters. The panel buttons are used to select and
confirm the parameters, which should be displayed.
Table 4. Description of buttons and LEDs of LCD panel.
First run of PSU – language selection screen.
One time, during the first run of the PSU, language selection screen will be
displayed. Use „<” or „>” buttons to select available languages. After
selecting the appropriate language, confirm by pressing the “SET” button. The
main screen will be displayed.
If language selection is not done, the language selection screen will be displayed on the next start-up. If a choice has already been made, language selection can be done as explained in section 7.3.1. To facilitate the user’s selection of the language of messages, the PSU enables calling up a menu on the main screen, displaying all available languages. To this end, press the arrow keys “<” and “>” on the front panel of the PSU simultaneously and hold them for a minimum of 5 seconds.
Main screen of LCD.
Main screen of LCDs basic electrical parameters and indicates the current
status of the power supply.
The resolution of voltage and current measurement is 0.1 V and 0.1 A, respectively. The displayed values of voltages and currents should be treated with caution; if a greater accuracy is required, use a multi-meter.
Table 5. Description of main screen symbols.
Information displayed on LCD panel.
Preview menu.
Pressing „ESC” button at bottom of display starts preview menu, allowing to
choose one of four available PSU screens. Use „<” or „>” buttons to choose a
proper screen and press „SET” button to confirm.
LCD screen – current parameters
To set a screen, press the „ESC” button, use „<” or „>” buttons to choose an
icon and press the „SET” button to confirm. The screen displays electrical
parameters and the status of technical outputs during operation. The
illumination of an element informs about activation and reflects the status of
LEDs on the PCB of the PSU (Table 1, [4]).
Table 6. Description of screen symbols – current parameters of PSU.
LCD screen – current failures
In case of abnormal electrical parameters during the operation, the PSU will
indicate a failure by displaying a message on the LCD, turning on the red LED
ALARM on the panel and changing the status of a dedicated technical output
.
At a given time, multiple failures can occur. To check which faults are indicated, choose current failures of PSU screen. To do that, press „ESC” button, use „<” or „>” buttons to choose icon and press „SET” button to confirm.
Screen displays codes and descriptions of failures. Display order of failures is arranged by priority of importance. First failures in display order are of highest priority.
LCD screen – history of parameters
If any incorrect electrical parameters occur during operation, PSU will start
failure indication by displaying an appropriate message, cyclically blinking
LCD display backlight, illuminating ALARM LED on panel and activating
anacoustic indication (if it has not been switched off). The relevant
technical outputs are also activated. To choose history of events screen,
press „ESC” button, use „<” or „>” buttons to choose icon ****and press „SET”
button to confirm.
History of events screen enables overviewing events recorded by internal diagnostic system. Internal memory can store up to 2048 events, carrying information about fault type, time of occurrence and the values of other electrical parameters. In addition, the diagnostic system assigns the failure code for a particular event on the basis of the stored parameters. In order to preview history of events, use „<” or „>” buttons. It can be done in two modes: short mode (date, time, code, fault description) or full mode – with additional information about electrical parameters and status of inputs and outputs. To switch between modes, press „SET” button.
Section 5.4.6 lists all codes that may occur during the operation of PSU. Individual codes are accompanied by appropriate optical indication on panel, acoustic indication and activation of a dedicated technical output. Memory of new power supply remembers events that are result of efficiency tests carried out at production stage.
List of failure codes and information messages.
PSU indicates operation status with appropriate code. Codes are divided into
two groups, marked with the initial letters „F” or „I”. Codes beginning with
letter „F” indicate a failure. Codes that begin with letter „I” indicate
correct operation of PSU or repaired fault, involving, for example, fuse
replacement: „I03 – BAT fuse replaced”.
Table 7. List of failure codes of power supply unit.
Failure code| ****
Information
| Technical
output activation
| Additional information
---|---|---|---
F01| AC power fail| EPS| – No AC mains supply
– Burnt main fuse FMAINS
F04| Output overload| PSU| – PSU overload
F05| Undercharged battery| APS| – Worn out battery
– Undercharged batteries
F06| High AUX voltage| PSU| – Output voltage over 14,2 or 28.4V
F08| Charging circuit failure| PSU| – Battery charging circuit failure
F09| Low AUX voltage| PSU| – Output voltage below 13/26V
F10| Low battery voltage| APS| – The battery voltage has dropped below
11,5/ 23V (during battery operation)
F11| Low battery voltage – off| APS| – The battery voltage has dropped
below 20V (during battery operation)
F12| External input EXTi| PSU| – Activation of the input of collective
failure: EXTi
---|---|---|---
F14| temperature sensor failure| PSU| – Temperature sensor damaged
– Temperature sensor disconnected
F15
| High battery temperature| PSU| – The ambient temperature of the PSU is too hot
– Batteries overloaded
– Batteries damaged
F16
| No battery| APS| – Batteries disconnected
– Battery fuse damaged
– Interruption on battery circuit
F17| Battery fail| APS| – Used battery
– High inside resistance of battery
F30| PSU overload| PSU| – PSU overload
F64| Clock failure| | – Check tdate and system time setting
F65| Access unlocked| | – Access to PSU settings has been unlocked
F71| Low battery voltage RTC| | – Discharged battery of LCD panel
F51- F74| Service codes| PSU| – Service codes
Table 8. List of PSU message codes.
Message code | Incident number | Description |
---|---|---|
I00 | 254 | Power supply start-up |
I01 | 253 | AC power back |
I05 | 249 | Battery OK |
I06 | 248 | Battery temperature correct |
I10 | 244 | Battery test – start |
I29 | 225 | Power supply current exceeded |
I30 | 224 | Power supply current correct |
I31 | 223 | Charging |
graphic LCD display – PSU settings
PSU has a configuration menu, allowing to configure PSU settings by changing or activating certain parameters. To enter setting mode, press „SET” button from main screen’s level.
Password.
PSU supports two levels of access to configuration, which limit possibility of
changing PSU’s settings from LCD panel. Both levels are protected by a
separate password.
- Service password – full access to PSU’s settings
- User’s password – locked access to „PSU” settings menu
Table 9. Access ranges.
PASSWORD
| Access range
---|---
„Control panel” settings| PSU settings
INSTALLER’S| ·| ·
USER’S| ·| –
Pre-set passwords
- User’s password – 1111
- Service password – 1234
Entering the password.
If access to configuration of the power supply has been blocked by activation
of service or user password, perform the following steps to unlock the PSU
configuration:
- use „<” or „>” buttons to display menu Password (enter/change)
- press „SET” button, another window with available levels of passwords will be displayed
- use „<” or „>” buttons to choose right level of password
- confirm by pressing „SET” button
- use „<” or „>” buttons to enter first digit
- confirm by pressing „SET” button
- use „<” or „>” buttons to enter second digit
- confirm by pressing „SET” button
- use „<” or „>” buttons to enter third digit
- confirm by pressing „SET” button
- use „<” or „>” buttons to enter fourth digit
- confirm by pressing „SET” button
If entered password is wrong, following message will be displayed:
After entering correct password, it is possible to access settings. If no buttons are pressed within 5 minutes, PSU settings will be locked automatically.
Changing password.
After entering correct password, it is possible to change it. To do this,
choose a password that will be changed (user’s password or service password)
and enter new one.
Disabling the password.
If password is not required, it can be turned off. Access to settings will not
be locked after 5 minutes of inactivity. To disable password, type „0000” as a
new password. User password „0000” unlocks access from user level. Service
password „0000” unlocks access from installer level.
Resetting passwords.
If the passwords are lost for any reason, a procedure may be performed to
enable the reassignment of the factory default passwords. In order to perform
this procedure, one should access the interior of the PSU casing. Locate the
JP jumper in the rear part of the PCB of the LCD; it is used in the password-
unlocking procedure.
Password unlocking procedure.
- Switch off the PSU completely for a minimum of 10 s. Disconnect the PSU both from the 230 V network and from the batteries.
- Place the JP jumper.
- Connect the batteries and switch on the 230 V network supply.
- Within 5 s from switching the PSU on, remove the JP jumper.
- The message „Access unlocked”, will appear on the display; confirm by pressing „SET”.
- Go to the menu „Settings -> Password” and replace the passwords with new ones.
Keyboard lock.
The PSU enables setting a key lock of the LCD panel.
- use „<” or „>” buttons to display the Keyboard lock menu
- use the „<” or „>” buttons to set the delay time
- use „<” or „>” buttons to select
- YES – keyboard lock ON
- NO – keyboard lock OFF
- confirm by pressing „SET” button When on, keyboard will be locked automatically if no buttons are pressed within 5 minutes. After this time, pressing any button on control panel will display a window with keyboard password request. Enter password using „<” or „>” buttons as explained above. The key lock function may only be selected if the installer password has been set. If the installer password is permanently unlocked with the „0000” code, the key lock option will not be available.
Entering correct user’s password unlocks access to settings from user level, while entering correct service password unlocks access to settings from the installer level
- full access. If no buttons are pressed within 5 minutes, PSU settings will be locked automatically.
PSU menu.
„PSU” menu is only available after entering the correct service password.
Selecting „PSU” in settings menu will display another menu, allowing full
configuration of PSU: zał/wył testu accumulator, ON/OFF battery protection,
setting delay time for EPS output, communication parameters setting. After
entering right settings, they are stored in internal non-volatile memory,
which protects PSU against data loss in case of a failure or power failure
.
Table 10. Description of „PSU” screen.
Position| Description| Additional
information
---|---|---
Battery test| START – manual activation of battery test| See
section 7.2.1
Acoustic indication| 1…247 PSU address required during communication
with computer
1 – factory settings
| See section 7.2.2
Transmission| Defines speed and protocol of communication
9.6k 8E1 (factory settings)
38.4k 8E1
115.2k 8E1
| See section 7.2.3
Performing battery test.
The function enables testing of the batteries (see section 5.3) connected to the PSU. If the test result is negative, this will be signalled on the display by an appropriate message and change of the output status to ALARM.
- use the „<” or „>” buttons to display Battery test menu
- use the „<” or „>” buttons to set the delay time
- confirm by pressing „SET” button (the battery test takes place immediately upon confirmation)
- During the test, the WAIT message appears on the screen
The PSU has a software protection against too frequent testing of batteries, which could cause them to undercharge. The protection consists in blocking the option of performance of the test for 60 s since it has last been enabled. In such situation, the “WAIT” message appears on the LCD in the Settings -> PSU -> Battery Test menu.
The temporary blockade option may be disabled through placing the JP jumper on the PCB panel of the display.
The battery test function will also be automatically blocked if the PSU is in a working mode in which running of the battery test would not be possible. Such a condition occurs e.g. during battery-mode operation. In such situation, the LCD shows the message „PROHIBITED” in the Settings -> PSU -> Battery Test menu.
Setting communication address.
All power supplies are factory-set to address 1.
- use „<” or „>” buttons to display Communication address menu
- use the „<” or „>” buttons to set the delay time
- use „<” or „>” buttons to set communication address 1…247 – PSU address during communication with computer
- confirm by pressing „SET” button
Setting transmission parameters.
Power supply has set transmission parameters of 9600 bps 8E1. However, if it
is to be connected to a network with differently defined parameters, its
configuration must be changed accordingly.
- use „<” or „>” buttons to display the Transmission menu
- use the „<” or „>” buttons to set the delay time
- use „<” or „>” buttons to set the transmission speed
- 9.6k 8E1 (factory settings)
- 38.4k 8E1
- 115.2k 8E1
- confirm by pressing the „SET” button
Control Panel menu.
Menu is only available after entering correct user’s or service password. The
„control panel” menu enables configuration of the settings directly related to
the user interface. It is possible to set the display language, date, time,
intensity of the backlight and blinking light indicating failure. Setting the
correct date and time is important for keeping chronology of events stored in
the internal memory. Setting the backlight mode and contrast guarantees the
quality of the displayed messages. Intensity of LCD backlight can be set in
range from 0 to100%, in 10% intervals. Display features a function of constant
or temporary backlight mode. In temporary mode, screen will turn off if no
buttons are pressed within 5 minute.
Table 11. Description of „Control panel” screen.
Position | Description |
---|---|
Language | Available languages |
Date | Current date |
Time | Current time |
Hintergrundbeleuchtung | 5 min – backlight mode OFF if no buttons are |
pressed within 5 min
stałe **** – backlight will not be turned off
0-100% – intensity of backlight
Contrast| 0-100% – display contrast
Blinking light indicating
failure
| YES – blinking light indicating failure
OFF – constant light indicating failure
Setting display language.
One of functions of control panel menu is possibility to select language.
Display language can be set according to personal preference.
- use „<” or „>” buttons to display Language menu
- use the „<” or „>” buttons to set the delay time
- use „<” or „>” buttons to choose display language
- confirm by pressing „SET” button
Setting date.
„Date” menu in „Control panel” menu enables setting correct date, according to
which error messages and operation history will be saved. Built-in real time
clock does not take into account leap years and changes resulting from switch
between summer and winter time. These changes should be taken into account
when analyzing events recorded in history.
- use „<” or „>” buttons to display Date menu
- press the „SET” button, prompt will appear next to year digits
- use „<” or „>” buttons to set year
- press the „SET” button, prompt will appear next to month position
- use „<” or „>” buttons to set current month
- press the „SET” button, prompt will appear next to day position
- use „<” or „>” buttons to set current day
- confirm by pressing „SET” button
Setting time.
„Time” menu in „Control panel” menu enables setting correct time, according to
which error messages and operation history will be saved. Built-in real time
clock does not take into account leap year and changes resulting from switch
between summer and winter time. These changes should be taken into account
when analyzing events recorded in history.
- use „<” or „>” buttons to display Time menu
- press „SET” button, prompt will appear next to hour digits
- use „<” or „>” buttons to set hour
- press „SET” button, prompt will appear next to minute position
- use „<” or „>” buttons to set minutes
- press „SET” button, prompt will appear next to seconds’ position
- use „<” or „>” buttons to set seconds
- confirm by pressing „SET” button
Setting backlight mode.
„Backlight” menu dims display if no buttons are pressed within 5 min and sets
intensity of backlight.
- use „<” or „>” buttons to display Backlight mode menu
- press „SET” button, prompt will appear next to constant< option
- use „<” or „>” buttons to change setting to 5 min
- press „SET” button, prompt will appear at end of line
- use „<” or „>” buttons to set required brightness
- confirm by pressing „SET” button
Contrast setting.
- Contrast” menu in „Control panel” enables setting contrast of display text.
- use „<” or „>” buttons to display Contrast menu
- use the „<” or „>” buttons to set the delay time
- use „<” or „>” buttons to set contrast
- confirm by pressing „SET” button
Blinking light indicating failure
„Blinking light indicating failure” menu enables setting backlight mode during
failure indication. When on, blinking light will indicate a failure.
- use „<” or „>” buttons to display Blinking light indicating failure menu
- use the „<” or „>” buttons to set the delay time
- use „<” or „>” buttons to select
- YES – blinking light indicating failure ON
- OFF – blinking light indicating failure OFF
- confirm by pressing „SET” button
Remote monitoring (option: Ethernet, RS485).
PSU has been adjusted to operate in a system that requires a remote control of parameters in a monitoring centre. Transmitting information about the status of the PSU is possible by using an additional, external communication module realising communication in the Ethernet or RS485 standard. The various connection topologies presented in the following section constitute only a part of the possible communication schemes. More examples can be found in the manuals dedicated to the individual interfaces. When installing optional features in power supply unit, power supply current consumption, used for calculation of standby time, should be taken into account (see section. 5.6).
ETHERNET network communication.
Communication in Ethernet network is possible due to additional interfaces:
Ethernet „INTE-C” and RS485-ETH „INTRE-C”, according to IEEE802.3 standard.
Ethernet „INTE-C” interface features full galvanic isolation and protection
against surges. It should be mounted inside enclosure of PSU.
RS485-ETHERNET „INTRE-C” interface is a device used to convert signals between RS485 bus and Ethernet network. For proper operation, unit requires an external power supply in range of 10-30 V DC e.g. drawn from a PSU of HPSG3 series. Unit is mounted in a hermetic enclosure protecting against adverse environmental conditions.
„PowerSecurity” web application.
The PowerSecurity web application has been embedded in the INTE-C and INTRE-C
communication interfaces. The programme is a website uploaded from an embedded
WWW server which is loaded upon entering the IP address in the web browser
window. Upon loading the PowerSecurity application, access is gained to the
preview of the status of the PSU connected with an INTE-C interface, or to the
preview of all PSUs in the RS485 bus in case of an INTRE-C interface. From the
WWW browser level, the current status of the PSU can be checked, with preview
of such parameters as output voltages, presence of 230 V supply, or resistance
of the battery circuit. Moreover, the application has an option of interface
configuration for the function of remote alerting through email notification
including information on the status of the PSU in case of occurrence of
specific events. The drawing below shows the appearance of a tab with the
current PSU status.
The web application also has a graphic tab „Graphs” from which the PSU history of operation may be downloaded and viewed in the graphic form, as a graph. A read graph may be saved in a file on a disc.
Another tab enabling checking of the PSU history is the tab of events. The read history is displayed as a table, following a chronological order. From the table, we can read the exact time of occurrence of the event, the error code, the event type description, as well as electric parameters and the status of individual technical outputs.
The PowerSecurity programme provides functionality in the form of a remote battery test and the function of remote alerting via automatically sent email notifications. The notifications contain information on the current error codes, with the exact malfunction occurrence time. The email notifications are sent to 2 recipients. The service includes SSL encryption of the mail and authorization for the user’s verification through the outgoing mail system (SMTP) in order to ensure safety of the mail account. Time periods between alerts and types of initiating events are individually configured by user.
Specifications
- Electrical parameters (tab. 12).
- Mechanical parameters (tab. 13).
- Operation safety (tab. 14).
Table 12. Electrical parameters.
| ****
HPSG3-12V3A-C-LCD
| ****
HPSG3-12V5A-C LCD
| ****
HPSG3-12V5A-D LCD
| ****
HPSG3-12V10A-E LCD
| ****
HPSG3-24V2A-C LCD
| ****
HPSG3-24V5A-D LCD
---|---|---|---|---|---|---
PSU type EN 50131-6| A, degree of protection 1 – 3, II environmental
class
Supply voltage| ~200-240 V
Power frequency| 50/60 Hz
Current consumption| 0,52 A| 0,77 A| 1,33 A| 0,71 A| 1,32 A
Output power PSU| 48 W| 76 W| 138
W
| 69 W| 138 W
Efficiency| 81%| 82%| 85%| 83%| 86%
Output voltage at 20 ºC| ****
11 V-13,8 V DC – buffer operation
10 V-13,8 V DC – battery-assisted operation
| 22 V-27,6 V DC – buffer operation
20 V-27,6 V DC – battery- assisted operation
Total output current with charging| ****
3,5 A
| ****
5,5 A
| ****
5,5 A
| ****
10 A
| ****
2,5 A
| ****
5 A
Output current
| ****
2,7A
| ****
4,7A
| ****
3,7A
| ****
7,4A
| ****
1,7A
| ****
3,2A
Battery capacity| 17.. 20 Ah| 17.. 20 Ah| 40.. 45 Ah| 65 Ah| 17..20 Ah|
40.. 45 Ah
Battery charging current| 0,8 A| 0,8 A| 1,8 A| 2,6 A| 0,8 A| 1,8 A
Ripple voltage| 50 mV p-p| 50 mV p-p| 50 mV p-p| 80 mV p-p| 50 mV p-p|
50 mV p-p
Current consumption by PSU during battery- assisted operation| ****
45 mA
| ****
45 mA
| ****
45 mA
| ****
45 mA
| ****
55 mA
| ****
55 mA
Coefficient of temperature compensation of battery voltage| ****
-18 mV/ ºC (-5ºC-40ºC)
| ****
-36 mV/ ºC (-5ºC-40ºC)
Low battery voltage indication| ****
Ubat < 11,5 V, during battery operation
| Ubat < 23 V, during battery operation
Over voltage protection OVP| U>16 V±1 V, automatic recovery| U>32 V±2 V,
automatic recovery
Short-circuit protection SCP| Glass fuse F BAT (in case of a
failure, fuse-element replacement required)
Overload protection OLP| 105-150% PSU power, automatically recovered
Battery circuit protection SCP and reverse polarity connection| ****
Glass fuse F BAT (in case of a failure, fuse-element replacement required)
---|---
Deep discharge protection UVP| ****
10 V +/- 0,3 V
| ****
20 V +/- 0,6 V
Technical outputs:
– EPS; output indicating AC power failure
| – OC type: 50 mA max. normal status: L (0 V) level,
failure: hi-Z level, time lag: 11 s.
Technical outputs:
– APS; output indicating battery failure
– PSU; output indicating PSU failure
| ****
– OC type: 50 mA max. normal status: L (0 V) level, failure: hi-Z level.
Technical outputs:
– EXTi; input of external failure
| Closed input – no indication Open input – alarm
LCD screen battery| ****
3V, lithium, CR2032
Fuse F BAT| ****
F5A/250V
| ****
T6,3A/250V
| ****
T6,3A/250V
| ****
T10A/30V
| ****
F4A/250V
| ****
T5A/30V
Mechanical parameters
| ****
HPSG3-12V3A-C-LCD
| ****
HPSG3-12V5A-C-LCD
| ****
HPSG3-12V5A-D-LCD
| ****
HPSG3-12V10A-E-LCD
| ****
HPSG3-24V2A-C-LCD
| ****
HPSG3-24V5A-D-LCD
---|---|---|---|---|---|---
Enclosure dimensions (WxHxD) [±2mm]| 314x408x110| 314x408x110| 314x408x190|
414x407x190| 314x408x190| 414x408x190
Fixing (WxH)| 277×355| 277×355| 277×355| 377×355| 277×355| 377×355
Space for battery (WxHxD)| 304x166x94| 304x166x94| 304x172x172| 404x178x172|
304x172x172| 404x178x172
Net/gross weight [kg]| 6,4/6,7| 6,5/6,9| 8,6/9,1| 11,2/11,8| 8,6/9,1|
11,2/11,8
Terminals| ****
Battery outputs BAT: Ф6 (M6-0-2,5)
Mains supply: Ф0,41-2,59 (AWG 26-10), 0,5-4mm2 Outputs: Ф0,51-2,05 (AWG
24-12), 0,5-2,5mm2
Notes| ****
Convectional cooling
Table 14. Operating parameters.
Environmental Class EN 50131-6 | II |
---|---|
Environmental Class EN 60839-11 | I (first) |
Operating temperature | -10ºC…+40ºC |
Storage temperature | -20ºC…+60ºC |
Relative humidity | 20%…90%, without condensation |
Sinusoidal vibrations during operation: | According to PN-EN 50130-5 |
Impulse waves during operation | According to PN-EN 50130-5 |
Direct insolation | unacceptable |
Vibrations and impulse waves during transport | According to PN-83/T-42106 |
Table 15. Operation safety.
Protection class EN 62368-1 | I (first) |
---|---|
Protection grade EN 60529 | IP44 |
Electrical strength of insulation:
– between input and output circuits of PSU
– between input circuit and protection circuit
– between input circuit and output or protection circuit
| ****
4000 V DC
2500 V DC
500 V DC
Insulation resistance:
– between input circuit and output or protection circuit
| ****
100 MΩ, 500 V DC
Technical inspections and maintenance.
Technical inspections and maintenance can be performed after disconnecting the power supply from the power network. The PSU does not require performing any specific maintenance measures, however, in the case of significant dust rate, its interior is recommended to be cleaned with compressed air. In the case of a fuse replacement, use a replacement of the same parameters. Technical inspections should be carried out not less frequently than once per year. During the inspection, check batteries and run battery test. 4 weeks after installation, re-tighten all threaded connections Fig. 2 [2].
Battery replacement of LCD panel.
The estimated operating time of battery type CR2032 is about six years. After
this period, battery will need to be replaced. Battery replacement of the LCD
panel should be done during mains operation or battery-assisted operation in
order to avoid resetting the time settings.
CAUTION!
Removed batteries should be stored in a designated collection point. Do not
reverse polarity of batteries. Improper use of battery may lead to explosion.
WE MARK
According to the EU WEE Directive – It is required not to dispose of electric
or electronic waste as unsorted municipal waste and to collect such WEEE
separately.
CAUTION! The power supply module unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed of but recycled according to the applicable law.
Pulsar sp. j. Siedlec 150, 32-744 Łapczyca, Poland Tel. (+48) 14-610-19-45
- e-mail: sales@pulsar.pl
- http://www.pulsar.pl
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>