PRODUCT

Specifications

  • Model Numbers: MBP20HVIEC6, MBP20HVAU3, MBP20HVDE3
  • Manufacturer: Cyber Power Systems, Inc.
  • Website : www.cyberpower.com
  • Part Number: K01-0000262-01

Product Usage Instructions

Installation:

  1. Ensure the MBP is connected to a grounded AC power outlet with a fuse or circuit breaker protection.
  2. Place the MBP near the connected equipment and ensure it is easily accessible.
  3. Install the MBP in a temperature and humidity-controlled indoor area, free of conductive contaminants.

Safety Precautions:

  • Do not unplug the unit from AC Power during operation.
  • Turn off and unplug the unit before installing the input/output power cord with a ground wire.
  • Ensure to use VDE-tested, CE-marked mains cable to connect the MBP to the AC outlet.
  • Wiring must be done by qualified personnel.

Maintenance:

  1. Ensure everything is turned off and disconnected completely before conducting any maintenance, repairs, or shipment.
  2. Connect the Protection Earth (PE) safety conductor before any other cables are connected.

Important Notes:

  • Do not use the MBP for medical or life support equipment.
  • Avoid exposure to direct sunlight or strong heat sources.
  • Avoid using near aquariums to prevent fire hazards.

IMPORTANT SAFETY INSTRUCTIONS

This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the MBP (Maintenance Bypass PDU).

CAUTION!

  • The MBP must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the MBP into an outlet that is not grounded.
  • The MBP should be placed near the connected equipment and easily accessible.
  • To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
  • (No User Serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
  • To reduce the risk of fire, connect the UPS to a branch circuit with 16 amperes maximum over-current protection in accordance to CE requirement.
  • The AC outlet where the MBP is connected should be close to the unit and easily accessible.
  • Please use only VDE-tested, CE-marked mains cable, (e.g. the mains cable of your equipment), to connect the MBP to the AC outlet.
  • Please use only VDE-tested, CE-marked power cables to connect any equipment to the MBP.
  • The MBP are only qualified maintenance personnel may carry out installations.
  • Do not unplug the unit from AC Power during operation, as this will invalidate the protective ground insulation.
  • To avoid electric shock, turn off and unplug the unit before installing the input/output power cord with a ground wire. Connect the ground wire prior to connecting the line wires!
  • Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards.
  • Wiring must be done by qualified personnel.
  • DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances this unit should be used for medical applications involving life support equipment and/or patient care.
  • DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
  • The unit has a dangerous amount of voltage. When the MBP indicators is on, the units may continue to supply power thus the unit’s outlets may have a dangerous amount of voltage even when it’s not plugged in to the wall outlet.
  • Make sure everything is turned off and disconnected completely before conducting any maintenance, repairs or shipment.
  • Connect the Protection Earth (PE) safety conductor before any other cables are connected.
  • Never install a MBP, or associated wiring or equipment, during a lightning storm.
  • Do not work alone under hazardous conditions.

DO NOT INSTALL THE MBP WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE! DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO MBP OUTPUT SOCKETS!

UNPACKING

Cyber-Power-MBP20HVIEC6-UPS-Accessory-Manueller-Bypass-FIG-
\(1\)

HARDWARE INSTALLATION

These versatile MBP can be mounted in a rackmount or vertical tower orientation. Please follow the instructions below for the respective mounting methods.

  1. Step 1: Brackets installation
    Attach the two brackets to the MBP using the provided screws M4X8L*4pcs.

  2. Step 2: MBP Installation
    Secure the MBP with the provided screws M5X12L*2pcs.

Cyber-Power-MBP20HVIEC6-UPS-Accessory-Manueller-Bypass-FIG-
\(2\)Cyber-Power-MBP20HVIEC6-UPS-
Accessory-Manueller-Bypass-FIG- \(3\)Cyber-Power-MBP20HVIEC6-UPS-Accessory-Manueller-Bypass-FIG-
\(4\)

CONNECTING THE INPUT/ OUTPUT

INPUT/ OUTPUT CONFIGURATION: Connect the input/output as shown in the following diagram.

Cyber-Power-MBP20HVIEC6-UPS-Accessory-Manueller-Bypass-FIG-
\(5\)

INSTALLING/REMOVING THE RETENTION CLIP

INSTALLING THE RETENTION CLIP

  1. Step 1: Cable Tie Installation
    Insert the Cable Tie into the hole beside the socket on the MBP. Note the flat side of the Cable Tie should face to the socket which the power cord will be inserted.

  2. Step 2: Retention Clip Installation
    Place a Retention Clip on the power cord. Insert the power cord to the MBP. Align and Insert the Cable Tie into the Retention Clip.

  3. Step 3: Fasten Retention Clip
    Push the Retention Clip until it touches the plug and fasten the Retention Clip.

Cyber-Power-MBP20HVIEC6-UPS-Accessory-Manueller-Bypass-FIG-
\(6\)

REMOVING THE RETENTION CLIP

  1. Step 1: Loosen Retention Clip
    Loosen the Retention Clip by pushing it to the right.

  2. Step 2: Remove Retention Clip
    Remove the Retention Clip by pulling the Cable Tie to the right.

BASIC OPERATION

MBP FRONT PANEL DESCRIPTION

  1. AC Output Outlets
    Provide output power to the connected equipment. The supplied power source can be selected by manual bypass switch to ensure nonstop operation during maintenance or UPS replacement.

  2. Output Circuit Breaker
    Provide output overload and fault protection.

  3. “Normal” LED Indicator
    Indicate that the connected equipment is supplied by UPS output.

  4. “Bypass” LED Indicator
    Indicate that the connected equipment is supplied directly by utility power.

  5. Manual Bypass Switch
    Provide UPS output to connected equipment when turned to “Normal”, provide utility power to connected equipment when turned to “Bypass”.

  6. “To UPS Output” Inlet
    Connect the AC Power cord to UPS Output.

  7. “To UPS Input” Outlet
    Connect the AC Power cord to UPS Input.

  8. “Utility Power” Inlet
    Connect the AC Power cord to a properly wired and grounded outlet.

Cyber-Power-MBP20HVIEC6-UPS-Accessory-Manueller-Bypass-FIG-
\(8\)

MAINTENANCE

MAINTENANCE BYPASS PDU OPERATION
This operation allows qualified personnel to remove the MBP from the UPS for routine maintenance or replacement without disrupting power to connected equipment.

The connected equipment is supplied by UPS output when the Manual Bypass Switch is turned to “Normal”.

Cyber-Power-MBP20HVIEC6-UPS-Accessory-Manueller-Bypass-FIG-
\(9\)

Cyber Power Systems, Inc.
www.cyberpower.com

Entire contents copyright© 2024 Cyber Power Systems, Inc., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® Business and PowerPanel® Personal are trademarks of Cyber Power Systems, Inc.

Copyright © 2024 CyberPower Systems, Inc.

FAQ

Q: Can I use the MBP for medical equipment?
A: No, the MBP should not be used for medical or life support equipment.

Q: Can the MBP be exposed to direct sunlight?
A: No, it is recommended not to install the MBP where it would be exposed to direct sunlight or near a strong heat source.