GIANNI INDUSTRIES GK1900 Series Electric Strike Installation Guide
- June 8, 2024
- GIANNI INDUSTRIES
Table of Contents
INDUSTRIES GK1900 Series Electric Strike
Installation Guide
Electric Strike Installation Instructions GK1900 Series
Specifications
Operating Voltage | 12/24VDC |
---|---|
Voltage Tolerance | ±15% |
Current Draw | 700mA/12VDC, 350mA/24VDC |
Operating Temperature | -10~49˚C |
Humidity | 0% to 85% Non-condensing |
Application | Sliding doors |
Lock Mode | Fail-secure |
Cavity Depth | 5/8” (15.5mm) |
Keeper Width | 3/4” (19mm) |
Endurance | 250,000 cycles |
Static Strength | 700 lbs |
Preload | 100 lbs |
Connecting Diagram
Voltage Selection
Voltage Selection Jumpers Check jumper settings before connecting the lock to 24VDC inpput power. Damage to the lock may result from incorrect jumper settings.
Hollow Metal Frame Installation
Installation Steps
Measure the centerline of the latchbolt Align to the latchbolt’s center position and mark on the frameAttach the template to the marked positionCut hole using templateInstall the mounting tabs
Connect the wires, and install the strike