Intesis Interface integration Haier air conditioners User Manual

June 7, 2024
Intesis

Intesis Interface integration Haier air conditioners User Manual
Intesis Interface integration Haier air conditioners
KNX TP1 (EIB)

ORDER CODE

|

LEGACY ORDER CODE

---|---

INKNXHAI008C000

|

HA-AC-KNX-8

INKNXHAI016C000

| HA-AC-KNX-16
INKNXHAI064C000|

HA-AC-KNX-64

Important User Information

Disclaimer

The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.

HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.

The data, examples and illustrations found in this document are included for illustrative purposes and are onlyintended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

1 Presentation

Intesis Interface integration Haier air conditioners
INKNXHAI0–C000allows a complete and natural integration of Haier air conditioners with KNX control systems.
Compatible with all models of VRF line of Haier air conditioners.

Main features:

  • Reduced dimensions. Installation even inside the A.C. indoor unit.
  • Quick and non-visible installation.
  • External power not required.
  • Direct connection to the KNX EIB bus.
  • Direct connection to the AC indoor unit.
  • Fully KNX interoperable, configuration from ETS.
  • Multiple objects for control (of different types: bit, byte, characters…).
  • Control of the AC unit based in the ambient temperature read by the own AC unit, or in the ambient temperature read by any KNX thermostat.
  • Total Control and Monitoring of the AC unit from KNX, including monitoring of AC unit’s state of internal variables, running hours counter (for filter maintenance control), and error indication and error code.
  • AC unit can be controlled simultaneously by the IR remote control of the AC unit and by KNX.

2 Connection

Connection of the interface to the AC indoor unit:

Disconnect mains power from the AC unit. Open the front cover of the indoor unit in order to have access to the internal control board. In the control board locate the socket connector marked as ABG1.

Using a 3-wire cable, connect the ABG1 connector from the INKNXHAI0- C000to the A B G1 connector of the AC unit’s control board.

Fix the INKNXHAI0–C000inside or outside the AC indoor unit depending on your needs – remember that INKNXHAI0–C000must be also connected to the KNX bus. Close the AC indoor unit’s front cover again.

Connection of the interface to the KNX bus:

Disconnect power of the KNX bus. Connect the interface to the KNX TP-1 (EIB) bus using the KNX standard connector (red/grey) of the interface, respect polarity. Reconnect power of the KNX bus.

Connections diagram:

Connections diagram
Figure 2.1 Default parameter configuration

Each Haier Communication Adaptor connects to a single Outdoor Unit.

The INKNXHAI008C000-16-64 can be connected to more than one Haier Communication Adaptor simultaneously.

NOTE: More than one Haier Communication Adaptor can be present in the installation.
Please make sure that the address of the Haier Communication Adaptor is correctly set in the ETS. Check section 4.6 for more information.

3 Configuration and setup

This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS.

ETS project for this device can be downloaded from: https://www.intesis.com/products/ac-interfaces/haier-gateways/haier-knx-vrf- ha-ac-knx

Please consult the README.txt file, located inside the downloaded zip file, to find instructions on how to install the database.

4 ETS Parameters

When imported to the ETS software for the first time, the gateway shows the following default parameter configuration:

Figure 4.1 Default parameter configuration

With this configuration it’s possible to send On/Off (Control On/Off), change the AC Mode (Control Mode), the Fan Speed (Control Fan Speed) and also the Setpoint Temperature (Control Setpoint Temperature). The Status objects, for the mentioned Control objects, are also available to use if needed. Objects Status AC Ambient Reference Temperature and Status Error/Alarm are shown too.

Inductions
Figure 4.2 Default communication objects

4.1 General configuration

Inside this parameter’s dialog it is possible to activate or change the parameters shown in the Figure 4.1.

4.1.1 Download latest database entry for this product and its User Manual from:
The first field shows the URL where to download the database and the user manual for the product.
Inductions
Figure 4.3 Parameter detail

4.1.2 Intesis Product
This parameter is used to check, before sending the programing, the maximum number of AC units your device supports.
Inductions
Figure 4.4 Parameter detail

Select the version of the gateway that you have:

  • INKNXHAI008C000, if you only want to control up to 8 AC unit.
  • INKNXHAI016C000, if you only want to control up to 16 AC units.
  • INKNXHAI064C000, if you only want to control up to 64 AC units.

4.1.3 Number of Indoor Units in ETS
This parameter is used to hide/show communication object according to the number of AC units you need to configure. Value ranges go from 1 to 64.
Inductions
Figure 4.5 Parameter detail

In case you introduce a number higher than the maximum number of units allowed by your license, you will get a warning message. This is just for information and will not block the configuration process. Configurations with more indoor units configured than the ones allowed by the license will not be downloaded correctly.
graphical user interface, application
Figure 4.6
Parameter detail

4.1.4 First Status Updated to KNX
This parameter defines how fast the status is updated to KNX. Depending on the value selected, more or less priority will be assigned to this action. As there are so many parameters available, it is important to consider carefully how to set this parameter.

  • If set to “ASAP”, all status communication objects will send its value (if needed).
  • If set to “Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (ASAP).
  • If set to “Super Slow”, all status communication objects will send its value (if needed), but slower than in the previous option (Slow).
    Inductions
    Figure 4.7 Parameter detail

4.1.5 Enable object “Error Code [2byte]”
This parameter shows/hides the Status_ Error Code communication object which shows the indoor unit errors, if occurred, in numeric format.

Inductions
Figure 4.8 Communication object and parameter detail

  • If set to “Disabled” the object will not be shown.
  • If set to “Enabled” the Status_ Error Code [2byte signed value] object will appear.
    • This object can be read and also sends the indoor unit error, if occurred, in numeric format. If a “0” value is shown that means no error.

4.1.6 Enable object “Error Text Code [14byte]”
This parameter shows/hides the Status_ Error Text Code communication object which shows the indoor unit errors, if occurred, in text format.

Figure 4.9 Communication object and parameter detail

  • If set to “Disabled” the object will not be shown.
  • If set to “Enabled” the Status_ Error Text Code object will appear.
    • This object can be read and also sends the indoor unit error, if occurred, in text format. The errors shown have the same format as in the remote controller and in the error list from the indoor unit manufacturer. If the object’s value is empty, that means there is no error.

4.2 Global mode configuration

Global mode configuration
Figure 4.10 Default Mode Configuration dialog

All the parameters in this section are related with the different mode properties and communication objects.Inductions

The byte-type communication object for Mode works with the DTP_20.105. Auto mode will be enabled with a “0” value, Heat mode with a “1” value, Cool mode with a “3” value, Fan mode with a “9” value and Dry mode with a “14” value.

4.2.1 Enable use of “Operating Mode” objects
This parameter shows/hides the Control and Status Mode Operating Mode communication objects.

4.2.2 Enable use of Mode Heat/Cool objects

This parameter shows/hides the Control and Status Mode Cool/Heat communication objects.

  • If set to “Disabled” the objects will not be shown.
  • If set to “Enabled” the Control and Status Mode Cool/Heat objects will appear.
    • When a “1” value is sent to the Control communication object, Heat mode will be enabled in the indoor unit, and the Status object will return this value.
    • When a “0” value is sent to the Control communication object, Cool mode will be enabled in the indoor unit, and the Status object will return this value.

4.2.3 Enable use of + / – object for Mode

This parameter shows/hides the Control_ Mode +/- communication object which let’s you change the indoor unit mode by using two different datapoint types.
Inductions

  • If set to “Disabled” the object will not be shown.
  • If set to “Enabled” the Control Mode +/- object and a new parameter will appear.
    Inductions
    Figure 4.11 Parameter detail _

➢ DPT type for +/- Mode Object

This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control Mode +/-_ object.

The sequence followed when using this object is shown below:

Inductions

Keep in mind that depending on the indoor unit you have and the available features, Auto mode and Dry mode may not be present.

4.2.4 Enable use of bit-type Mode objects (for control)

This parameter shows/hides the bit-type Control _ Mode objects.

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Control_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear. To activate a mode by using these objects a “1” value has to be sent.

4.2.5 Enable use of bit-type Mode objects (for status)

This parameter shows/hides the bit-type Status_ Mode objects.

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Status_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.
    When enabled, a mode will return a “1” through its bit-type object.

4.2.6 Enable use of Text object for Mode

This parameter shows/hides the Status_ Mode Text communication object.
Inductions

  • If set to “no” the object will not be shown.
  • If set to “yes” the Status_ Mode Text object will appear. Also, in the parameters, will be shown five text fields, one for each mode, that will let modify the text string displayed by the Status Mode_ Text when changing mode.

Inductions
Figure 4.12 Parameter detail

4.3 Global Fan Speed Configuration dialog

Inductions
Figure 4.13 Default Fan Speed Configuration dialog

All the parameters in this section are related with the Fan Speed properties and communication objects.

4.3.1 DPT object type for fan speed

With this parameter is possible to change de DPT for the Control_ Fan Speed and Status Fan_ Speed byte-type communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.

  • When “Enumerated [DPT 5.010]” is selected, Control Fan Speed and Status Fan Speed communication objects for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will be different.
    Inductions
    The first fan speed will be selected if a “1” is sent to the Control object. The second
    one will be selected sending a “2”, and the last one sending a “3”.
    The Status
    object will always return the value for the fan speed selected.
      Important: If a “0” value is sent to the Control object, the minimum fan speed will be _selected. If a value bigger than “3” is sent to the Control object, then the maximum _fan speed will be selected.

  • When “Scaling [DPT 5.001]” is selected, Control_ Fan Speed and _StatusFan Speed communication objects for this DPT will appear. Also, depending on the number of fan speeds selected, these objects will be different.

When a value between 0% and 49% is sent to the Control object the first fan speed will be selected.
When a value between 50% and 83% is sent to the Control
object, the second speed will be selected.
When a value between 84% and 100% is sent to the Control object, the third speed will be selected.
The Status
object will return a 33% when the first speed is selected, a 67% for the second one and a 100% for the third one.

Inductions

4.3.2 Enable use of “Fan Speed Man/Auto” objects (for Control and Status)
This parameter shows/hides the Control Fan Speed Man/Auto and Status Fan Speed Man/Auto communication object which lets you set the Fan Speed into Manual or Auto mode.
Inductions

4.3.3 Enable use of +/- object for Fan Speed

This parameter shows/hides the Control_ Fan Speed +/- communication object which lets you increase/decrease the indoor unit fan speed by using two different datapoint types.

  • If set to “no” the object will not be shown.
  • If set to “yes” the Control_ Fan Speed +/- object and a new parameter will appear.

➢ Fan speed +/- operation
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Fan Speed +/- object.

➢ Sequence for +/- object
This parameter lets choose between the different modes available:

  • S1 >S2>….>SN
    Select this option if you don’t have Auto mode and you don’t want roll-over to be enabled.

  • S1 >S2>….>SN>S1>…
    Select this option if you don’t have Auto mode and you want roll-over to be enabled.

  • Auto >S1>S2>….>SN
    Select this option if you have Auto mode and you don’t want roll-over to be enabled.

  • Auto >S1>S2>….>SN>Auto>S1>…
    Select this option if you have Auto mode and you want roll-over to be enabled.
    Inductions

4.3.4 Enable use of bit-type Fan Speed objects (for Control)
This parameter shows/hides the bit-type Control_ Fan Speed objects.
Inductions

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Control_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 (if available) will appear. To activate a Fan Speed by using these objects a “1” value has to be sent.

4.3.5 Enable use of bit-type Fan Speed objects (for Status)

This parameter shows/hides the bit-type Status_ Fan Speed objects.
Inductions

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Status_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 (if available) will appear. When a Fan Speed is enabled, a “1” value is returned through its bittype object.

4.3.6 Enable use of Text object for Fan Speed

This parameter shows/hides the Status_ Fan Speed Text communication object.

  • If set to “no” the object will not be shown.
  • If set to “yes” the Status_ Fan Speed Text object will appear. Also, in the parameters, will be shown two (or three, depending on the number of fan speeds selected) text fields, one for each Fan Speed, that will let modify the text string displayed by the _StatusFan Speed Text when changing a fan speed.
    Inductions
    Figure 4.15 Parameter detail

4.4 Global temperature configuration

Figure 4.20 Default Temperature Configuration dialog

All the parameters in this section are related with the Temperature properties and communication objects.

4.4.1 Enable use of +/- obj for Setpoint

This parameter shows/hides the Control_ Setpoint Temp +/- communication object which lets you change the indoor unit setpoint temperature by using two different datapoint types.
Inductions

  • If set to “no” the object will not be shown.
  • If set to “yes” the Control_ Setpoint Temp +/- object and a new parameter will appear.

Inductions
Figure 4.23 Parameter detail

➢ DPT type for +/- Setp Temp object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0 -Decrease / 1-Increase [DPT_1.007] for the Control_ Setpoint Temp +/- object.
(Lower limit) 16ºC Icon 17ºC IconIcon 31ºC Icon 32ºC (Upper limit)
Up / Increase
Down / Decrease

4.4.2 Ambient Ref. Temp. is provided from KNX

This parameter shows/hides the Control_ Ambient Temperature communication object which lets you use an ambient temperature reference provided by a KNX device.
Inductions

  • If set to “no” the object will not be shown.

  • If set to “yes” the Control Ambient Temperature object will appear. Meant to be enabled when you want the temperature provided by a KNX sensor to be the reference ambient temperature for the air conditioner. Then, the following formula applies for the calculation of real Control Setpoint Temperature sent ot the AC unit:
    “AC Setp. Temp” = “Ambient ref. Temp” – (“KNX Amb. Temp.” – “KNX Setp Temp.”) Temp”)

    • AC Setp. Temp: AC indoor unit setpoint temperature
    • Ambient Ref. Temp: AC indoor unit return temperature
    • KNX Amb. Temp.: Ambient temperature provided from KNX
    • KNX Setp. Temp: Setpoint temperature provided from KNX
      As an example, consider the following situation:
      User wants: 19ºC (“KNX Setp. Temp.”)
      User sensor (a KNX sensor) reads: 21ºC (“KNX Amb Temp.”)
      Ambient temp. read by Haier system is: 24ºC (“Ambient Ref. Temp”)
      In this example, the final setpoint temperature that INKNXHAI0–C000will send out to the indoor unit (shown in “Setp. Temp.”) will become 24ºC – (21ºC – 19ºC) = 22ºC. This is the setpoint that will actually be requested to Haier unit.
      This formula will be applied as soon as the Control Setpoint Temperature and Control Ambient Temperature objects are written at least once from the KNX installation. After that, they are kept always consistent.
      Note that this formula will always drive the AC indoor unit demand in the right direction, regardless of the operation mode (Heat, Cool or Auto).

4.5 Control Mode configuration

Inductions
Figure 4.20 Control Mode Configuration dialog

All the parameters in this section are related with the Mode properties and communication objects.

4.5.1 Enable use of Control Mode objects (for Control and Status)

This parameter shows/hides the Control Control Mode and Status Control Mode communication objects which lets you change the indoor unit control: No Central, LIFO (Last Input First Output), Central Controller and Lock Central Controller.
Inductions

  • If set to “no” the objects will not be shown.
  • If set to “yes” the Control and Status Control Mode objects for No Central, LIFO (Last Input First Output), Central Controller, Lock Central Controller will appear.

4.5.1 Initial state of Control Mode

This parameter sets the initial value for the Control Mode: No Central, LIFO (Last Input First Output), Central Controller, Lock Central Controller or Do not initialize.

Figure 4.24 Parameter detail

  • If set to “Apply same initial state to all Indoor Units” , the parameter option selected will apply to all indoor units.
  • If set to “Initial state for each Indoor Unit might differ” , you will be able to set this parameter for each Indoor Unit individually.

4.6 Addressing of Indoor Units

Inductions
Figure 4.24 Parameter detail

In this section you will be able to set the AC addressing for each AC unit present in the installation.

  • Modbus GW address of ACxx refers to the addres of the Haier Communication Addapters.
  • IDU index (in Modbus GW) of ACxx refers to the AC system address of the Indoor Unit.

4.7 License

Inductions
Figure 4.24 Parameter detail

Use this section to introduce the migration code in case you need to update your box from another version different from the factory default one.

5 Technical Specifications

Enclosure

|

ABS (UL 94 V-0) de 2,5 mm / 1” thick Net dimensions (dxwxh): 71 x 71 x 27 mm / 2.8” x 2.8” x 1.1” Color: White RAL 9010

|

Operation Temperature

|

0ºC to +60ºC

---|---|---|---

Weight

|

42 g.

|

Stock Temperature

|

-20ºC to +85ºC

Power supply

|

Power is supplied by: 1 x KNX bus (29V DC, 7mA)

|

Operational Humidity

|

<90% RH, non-condensing

Terminal Wiring (for low-voltage signals)

|

For terminal: solid wires or stranded wires (twisted or with ferrule) 1 core: 0.5mm2… 2.5mm2 2 cores: 0.5mm2… 1.5mm2 3 cores: not permitted

|

Stock Humidity

|

<90% RH, non-condensing

KNX port

|

1 x KNX TP1 (EIB) port opto-isolated. Plug-in terminal block (2 poles). TNV-1

|

Isolation voltage

|

1500 VDC

AC unit port

|

1 x Specific connector Plug-in terminal block (3 poles)

|

Isolation resistance

|

1000 MΩ

Configuration

|

Configuration with ETS

|

Protection

|

IP20 (IEC60529)

LED indicators

|

1 x Onboard LED – Operational status

| |

6 AC Unit Types compatibility.

A list of Haier indoor unit model references compatible with INKNXHAI0- C000and their available features can be found in:
intesis_inxxxhaixxxc000_ac_compatibility-list [PDF]

7 Error Codes

Error Code in

KNX Object

|

Error in Remote Controller

| ****

Category

| ****

Error Name

---|---|---|---

1

|

1

|

Indoor Unit

| Indoor ambient temp.sensor TA (Tas) failure

2

|

2

| Indoor gas pipe temp. sensor TC1 failure

3

|

3

| Indoor liquid pipe temp. sensor TC2 failure

4

|

4

| Dual heat source sensor TW failure

5

|

5

| Indoor EEPROM failure

6

|

6

| Communication between indoor and outdoor failure

7

|

7

| Communication between indoor and wired controller failure

8

| 8|

Indoor float switch failure

9

|

9

| Indoor address repeated failure

10

|

10

| Reserved

11

|

11

|

Reserved

12

|

12

| No 50 Hz zero passage signal

13

|

13

| Coil sensor TC3 failure

14

|

14

| DC motor failure

15

|

15

| Indoor ambient temp.sensor TA (Taf) failure

16

|

16

| –

17

|

17

| ****
























Outdoor Unit

| –

18

|

18

| –

19

|

19

| –

20

|

20

| Defrosting temp. sensor Tdef1 failure Defrosting temp. sensor Tdef2 failure

21

|

21

| Ambient temp. sensor Ta failure

**** 22

|

**** 22

| Suction temp. sensor Ts1 failure Suction temp. sensor Ts2 failure Suction temp. sensor Tsacc failure Suction temp. sensor Tsuc failure


23

| ****

23

| Discharging temp. sensor Tdi failure Discharging temp. sensor Td1 failure Discharging temp. sensor Td2 failure

24

|

24

| Oil temp. sensor Toilp failure Oil temp. sensor Toil failure

25

|

25

| Inlet temp. of heat exchanger Toci1 failure Inlet temp. of heat exchanger Toci2 failure

**** 26

|

**** 26

| indoor communication failure

Reduce the number of indoor units failure Increase the number of indoor units failure

27

|

27

| Oil temp. too high protection (Toil) Oil temp. too high protection (Toi2)

28

|

28

| High pressure sensor Pd1 failure High pressure sensor Pd2 failure

29

|

29

| Low pressure sensor Ps failure

**** 30

|

**** 30

| High pressure switch HPSi failure High pressure switch HPS1 failure High pressure switch HPS2 failure

31

|

31

| Liquid pipe pressure Pl failure

32

|

32

| Outlet temp. of subcooler Tsco failure

Liquid pipe SC temp. of subcooler Tliqsc failure

33

|

33

| EEPROM (AT24C04) failure


34

| ****

34

| Discharging temp. too high protection (Tdi) Discharging temp. too high protection (Td1) Discharging temp. too high protection (Td2)

35

|

35

| 4-way valve reversing failure 4-way valve reversing failure

36

|

36

| Oil temp. too low protection (Toil) Oil temp. too low protection (Toi2)

37

|

37

| Lack of phase of 3N power supply or wrong phase sequence

38

|

38

| High pressure sensor Pd too low protection

**** 39

|

**** 39

| Low pressure sensor Ps too low protection Compression ratio too high protection

Compression 1 ratio too low protection Compression 2 ratio too low protection

40

|

40

| High pressure sensor Pd1 too high protection High pressure sensor Pd2 too high protection

41

| 41| Water temp. Twi too low protection Water temp. Twi too high protection

**** 42

|

**** 42

| Frost protection of water system

Water system out of water freeze protection Water flow of Water system is too small to protect

**** 43

|

**** 43

| Discharging temp. sensor Tdi too low protection Discharging temp. sensor Td1 too low protection Discharging temp. sensor Td2 too low protection

44

|

44

| | Low pressure sensor PS too high protection
---|---|---|---

45

|

45

| Communication among outdoors failure

46

|

46

| Communication with inverter board 1 failure Communication with inverter board 2failure

47

|

47

| –

48

|

48

| Unloading valve SV1 failure

49

|

49

| –

50

|

50

|

51

|

51

| –

52

|

52

| –

53

|

53

| Current detector CT1 failure

54

|

54

| Communication with Thermal storage module failure

55

|

55

| Thermal storage module LEV failure

56

|

56

| Thermal storage module too hot failure

57

|

57

| Communication between Thermal storage module and host computer

58

|

58

| Thermal storage module Tc1 temp. sensor failure

59

|

59

| Thermal storage module Tc2 temp. sensor failure

60

|

60

| Reserved

61

|

61

| Reserved

62

|

62

| Reserved

63

|

63

| Thermal storage module DIP setting failure

64

|

64

| CT1 over current CT2 over current

65

|

65

| –

66

|

66

| –

67

|

67

| Communication with motor driving board failure

68

|

68

| –

69

|

69

| –

70

|

70

| –

71

|

71

| Left DC motor blocked Right DC motor blocked

72

|

72

| Left DC motor reversed Right DC motor reversed

73

|

73

| Left DC motor current too high Right DC motor current too high

74

|

74

| –

75

|

75

| No pressure drop between high pressure and low one Pressure too low between high pressure and low one

76

|

76

| Incorrect outdoor address or capacity setting

77

|

77

| Oil equalization protection among outdoors

78

|

78

| Lack of refrigerant in cooling Lack of refrigerant in heating

79

|

79

| Incorrect wiring

80

|

80

| Indoor and outdoor do not match

81

|

81

| Model temp. too high protection

82

|

82

| Compressor current protection

83

|

83

| Wrong model selection

84

|

84

| –

85

|

85

| –

86

|

86

| –

87

|

87

| –

88

|

88

| –

89

|

89

| –

90

|

90

| –

91

|

91

| –

92

|

92

| –

93

|

93

| –

94

|

94

| –

95

|

95

| –

96

|

96

| –

97

|

97

| –

98

|

98

| –

99

|

99

| Program self-test failure

100

|

100

| DC motor driving board IPM alarm

101

|

101

| DC motor driving board detecting out of control

102

|

102

| DC motor driving board EEPROM faulty

103

|

103

| DC motor driving board over current or current detector damaged

104

|

104

| Voltage too low protection of DC motor driving board

105

|

105

| Voltage too high protection of DC motor driving board

106

|

106

| DC motor driving board blocked

107

|

107

| Protection of motor rate over Limitation

108

|

108

| –

109

|

109

| –

110

|

110

| model 1 Over current model 2 Over current

111

|

111

| | Compressor 1 out of control Compressor 2 out of control
---|---|---|---

112

|

112

| Radiator of model 1 temp. too high Radiator of model 2 temp. too high

113

|

113

| model 1 overload

model 2 overload

114

| 114|

Voltage too low of model 1 Voltage too low of model 2

115

|

115

| Voltage too high of model 1 Voltage too high of model 2

116

|

116

| Communication abnormal with model 1 Communication abnormal with model 2

117

|

117

| Model 1 Over current (software) Model 1 Over current (software)

118

|

118

| Model 1 startup failure Model 2 startup failure

119

|

119

| Current Detecting Circuit Abnormal of transducer 1 Current Detecting Circuit Abnormal of transducer 2

120

|

120

| Power supply of transducer 1 abnormal Power supply of transducer 2 abnormal

121

|

121

| Power supply of inverter board 1 is abnormal Power supply of inverter board 2 is abnormal

122

|

122

| Radiator temp. sensor of transducer 1 abnormal Radiator temp. sensor of transducer 2 abnormal

123

|

123

| –

124

|

124

| –

125

|

125

| Compressor 1 frequency not match Compressor 2 frequency not match

126

|

126

| –

127

|

127

| MCU reset abnormal

128

|

128

| MCU Program needs to be upgraded

0

|

N/A

| KNX interface| No error

65535 (-1)

|

N/A

| KNX interface| Indoor Units not ready for communication

65436 (-100)

|

N/A

| KNX interface| License Error / indoor unit not supported by current license

65336 (-200)

|

N/A

| KNX interface| Overconsumption error in EXY bus

In case you detect an error code not listed, contact your nearest Haier technical support service for more information on the error meaning.

Appendix A – Communication Objects Table


SECTION

| OBJECT NUMBER| ****

NAME

| ****

LENGTH

| DATAPOINT TYPE| FLAGS| ****

FUNCTION

---|---|---|---|---|---|---
DPT_NAME| DPT_ID| R| W| T| U
On/Off| 1| Control_ On/Off| 1 bit| DPT_Switch| 1.001| | W| T| | 0 – Off; 1-On









Mode

| 2| Control_ Operating Mode| 1 byte| DPTHVACMode| 20.102| | W| T| | 0 – Auto; 1 – Com; 2 – Stan; 3 – Eco; 4 – Pro
3| Control
Mode| 1 byte| DPTHVACControl| 20.105| | W| T| | 0 – Auto; 1 – Heat; 3 – Cool; 9 – Fan; 14 – Dry
4| Control
Mode Cool/Heat| 1 bit| DPTCool/Heat| 1.100| | W| T| | 0 – Cool; 1 – Heat
5| Control
Mode Auto| 1 byte| DPTScaling| 5.001| | W| T| | 1 – Auto
6| Control
Mode Heat| 1 byte| DPTScaling| 5.001| | W| T| | 1 – Heat
7| Control
Mode Cool| 1 bit| DPTBool| 1.002| | W| T| | 1 – Cool
8| Control
Mode Fan| 1 bit| DPTBool| 1.002| | W| T| | 1 – Dry
9| Control
Mode Dry| 1 bit| DPT_Bool| 1.002| | W| T| | 1 – Fan


10

| Control_ Mode +/-| 1 bit| DPTStep| 1.007| | W| | | 0 – Decrease; 1 – Increase
Control
Mode +/-| 1 bit| DPT_UpDown| 1.008| | W| | | 0 – Up; 1 – Down







Fan Speed

| ****

11

| ****

Control_ Fan Speed / 3 Speeds

| ****

1 byte

| ****

DPT_Scaling

| ****

5.001

| | ****

W

| ****

T

| | 0%-49% – Speed 1; 50%-83% – Speed 2;

84%-100% Speed 3

Control_ Fan Speed / 3 Speeds| 1 byte| DPTEnumerated| 5.010| | W| T| | 1 – Speed 1; 2 – Speed 2; 3 Speed 3
12| Control
Fan Speed Man/Auto| 1 bit| DPTBool| 1.002| | W| T| | 0 – Manual; 1 – Auto
13| Control
Fan Speed 1| 1 bit| DPTBool| 1.002| | W| T| | 1 – Fan Speed 1
14| Control
Fan Speed 2| 1 bit| DPTBool| 1.002| | W| T| | 1 – Fan Speed 2
15| Control
Fan Speed 3| 1 bit| DPT_Bool| 1.002| | W| T| | 1 – Fan Speed 3


16

| Control_ Fan Speed +/-| 1 bit| DPTStep| 1.007| | W| T| | 0 – Decrease; 1 – Increase
Control
Fan Speed +/-| 1 bit| DPT_UpDown| 1.008| | W| T| | 0 – Up; 1 – Down




Temperature

| 17| Control_ Setpoint Temperature| 2 byte| DPT_Value_Temp| 9.001| | W| T| | 17ºC to 30ºC
---|---|---|---|---|---|---|---|---|---|---


18

| Control_ Setpoint Temp +/-| 1 bit| DPTStep| 1.007| | W| | | 0 – Decrease; 1 – Increase
Control
Setpoint Temp +/-| 1 bit| DPTUpDown| 1.008| | W| | | 0 – Up; 1 – Down
19| Control
Ambient Temperature| 2 byte| DPT_Value_Temp| 9.001| | W| T| | ºC value in EIS5 format




Control Mode

| 20| Control_ Control Mode No Central| 1 bit| DPTBool| 1.002| | W| T| | 1 – No Central Controller
21| Control
Control Mode LIFO| 1 bit| DPTBool| 1.002| | W| T| | 1 – Last Input First Output (LIFO)
22| Control
Control Mode Central| 1 bit| DPTBool| 1.002| | W| T| | 1 – Central Controller
23| Control
Control Mode Lock| 1 bit| DPTBool| 1.002| | W| T| | 1 – Lock Central Controller
On/Off| 24| Status
On/Off| 1 bit| DPT_Switch| 1.001| R| | T| | 0 – Off; 1-On
---|---|---|---|---|---|---|---|---|---|---








Mode

| 25| Status_ Operating Mode| 1 byte| DPTHVACMode| 20.102| R| | T| | 0 – Auto; 1 – Com; 2 – Stan; 3 – Eco; 4 – Pro
26| Status
Mode| 1 byte| DPTHVACContrMode| 20.105| R| | T| | 0 – Auto; 1 – Heat; 3 – Cool; 9 – Fan; 14 – Dry
27| Status
Mode Cool/Heat| 1 bit| DPTHeat/Cool| 1.100| R| | T| | 0 – Cool; 1 – Heat
28| Status
Mode Auto| 1 bit| DPTBool| 1.002| R| | T| | 1 – Auto
29| Status
Mode Heat| 1 bit| DPTBool| 1.002| R| | T| | 1 – Heat
30| Status
Mode Cool| 1 bit| DPTBool| 1.002| R| | T| | 1 – Cool
31| Status
Mode Fan| 1 bit| DPTBool| 1.002| R| | T| | 1 – Fan
32| Status
Mode Dry| 1 bit| DPTBool| 1.002| R| | T| | 1 – Dry
33| Status
Mode Text| 14 byte| DPT_String_8859_1| 16.001| R| | T| | ASCII String



Fan Speed

| ****

34

| Status_ Fan Speed / 3 Speeds| 1 byte| DPTScaling| 5.001| R| | T| | 33% – Speed 1; 67% – Speed 2; 100% – Speed 3
Status
Fan Speed / 3 Speeds| 1 byte| DPTEnumerated| 5.010| R| | T| | 1 – Speed 1; 2 – Speed 2; 3 – Speed 3
35| Status
Fan Speed Man/Auto| 1 bit| DPTBool| 1.002| R| | T| | 0 – Manual; 1 – Auto
| 36| Status
Fan Speed 1| 1 bit| DPTBool| 1.002| R| | T| | 1 – Speed 1
---|---|---|---|---|---|---|---|---|---|---
37| Status
Fan Speed 2| 1 bit| DPTBool| 1.002| R| | T| | 1 – Speed 2
38| Status
Fan Speed 3| 1 bit| DPTBool| 1.002| R| | T| | 1 – Speed 3
39| Status
Fan Speed Text| 14 byte| DPT_String_8859_1| 16.001| R| | T| | ASCII String


Temperature

| 40| Status_ AC Setpoint Temp| 2 byte| DPT_ValueTemp| 9.001| R| | T| | 16ºC to 32ºC
41| Status
AC Ambient Ref Temp| 2 byte| DPT_Value_Temp| 9.001| R| | T| | ºC value in EIS5 format



Error

| 42| Status_ Error/Alarm| 1 bit| DTPAlarm| 1.005| R| | T| | 0 – No Alarm; 1 – Alarm
43| Status
Error Code| 2 byte| Enumerated| R| | T| | 0 – No Error; Any other see user’s manual
44| Status_ Error Text code| 14 byte| DPT_String_8859_1| 16.001| R| | T| | 2 char Haier Error; Empty – none




Control Mode

| 45| Control_ Control Mode No Central| 1 bit| DPTBool| 1.002| | W| T| | 1 – No Central Controller
46| Control
Control Mode LIFO| 1 bit| DPTBool| 1.002| | W| T| | 1 – Last Input First Output (LIFO)
47| Control
Control Mode Central| 1 bit| DPTBool| 1.002| | W| T| | 1 – Central Controller
48| Control
Control Mode Lock| 1 bit| DPT_Bool| 1.002| | W| T| | 1 – Lock Central Controller

NOTE: This addressing corresponds to the first AC indoor unit of the configuration. Communication objects for the rest of AC units are consecutively listed.

Icon

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Intesis User Manuals

Related Manuals