Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol

June 5, 2024
Intesis

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol

Important User Information

Disclaimer

  • The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.
  • HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.
  • The data, examples and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

Description

Introduction

  • This document describes how to integrate OCPP devices (EV Chargers) into Modbus TCP and RTU compatible devices and systems, or into an external OCPP Central System (CS), through Intesis Modbus – OCPP gateway. An assumption is made that the user is familiar with Modbus and OCPP technologies and their technical terms.
  • When working as an OCPP Central System, the gateway enables OCPP signals and operations to be managed by a Modbus controller acting as a closed OCPP system. Alternatively, the gateway can be configured to connect to an External OCPP Central system, providing transparent OCPP communication between EV chargers and the external OCPP CS while reading out valuable information for Modbus supervisory applications.
  • The gateway acts as a Modbus TCP Server or a Modbus RTU slave in its Modbus interface, allowing a Modbus client/master device to read/write to its internal points. From OCPP standpoint, Intesis gateway parses data from OCPP messages to their corresponding Modbus registers or directly transmits to an External OCPP system. In every OCPP installation, one and only one Central System must be present. Options are:
    • Central System implemented in a Modbus enabled control system
    • External OCPP Central System, and Modbus supervisory applications.

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig2
Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig3

Functionality

  • The configuration tool for this gateway is Intesis® MAPS software. For a detailed information about the necessary steps to integrate the gateway in a Modbus BMS, please review the Intesis Configuration Guide for more information. Available in www.intesis.com
  • From the OCPP system standpoint, after the start up process, all EV Chargers will try to connect with Intesis gateway (Intesis gateway must be configured as a Central System in the EV Chargers configuration). Only if the gateway has EV Chargers configured will accept the connections. Then EV Chargers will notify any event or update to the gateway.
  • When working as a Central System, after the start up process, the gateway presents its points as Modbus Registers, to be read or written by a Modbus client/master device using standard Modbus functions. The values received from Modbus are immediately written in an OCPP message and sent to the EV Charger.
  • When working with an External Central System, the gateway must be configured to connect to the IP of the External Central system to, after the start up process, enable transparent OCPP communication between the EV chargers and the Central System. At the same time, the gateway presents its points as Modbus Registers, to be read by a Modbus client/master device using standard Modbus functions.

Gateway’s capacity

Intesis gateway capacity is detailed below:

Element Capacity Notes

Number of OCPP devices

| Model INMBSOCP0010100: 1 device| Maximum number of different OCPP devices/chargers the Intesis gateway can communicate to
Model INMBSOCP0200100: Up to 20 devices
Connectors per device supported| 7| Maximum number of connectors integrable from an OCPP device
OCPP protocol version supported| OCPP 1.6| JSON version implemented
Modbus link layers supported| Modbus RTU (EIA485)

Modbus TCP

| Those supporting Modbus protocol. Communication over TCP/IP and RTU
Number of Modbus Master devices| Up to 6 TCP connections| Number of Modbus Client devices supported by the device

Modbus interface

  • Description
    Intesis acts as a server device in its Modbus TCP or RTU interface, connecting to the Ethernet port of the gateway or the RS485 port. To access the points and resources of the Intesis from a Modbus client/master device, see details below in this document.

  • Functions supported

    • Modbus functions 01 and 02 (coils and digital input registers) can be used to read Modbus registers.
    • Modbus functions 03 and 04 (read holding registers and read input registers) can be used to read Modbus registers.
    • Modbus functions 05 and 15 (Single digital Holding Registers and Write Multiple Holding Registers) can be used to write Modbus registers.
    • Modbus functions 06 and 16 (Single Multiple Holding Registers and Write Multiple Holding Registers) can be used to write Modbus registers.
    • If poll records are used to read or write more than one register, it is necessary that the range of addresses requested contains valid addresses, if not the corresponding Modbus error code will be returned.
    • All the registers are of 2 bytes, even if they are associated to signals of type bit in the external system, and its content is expressed in MSB..LSB.
    • Modbus error codes are fully supported; they will be sent whenever a non-valid Modbus action or address is required.
  • Modbus TCP

    • The TCP port to use can be configured (by default 502 is used).
    • The IP address, subnet mask and default router address to use by Intesis gateway can be also configured.
  • Modbus RTU

    • Connect the communication cable coming from the Modbus network to the port marked as Modbus of Intesis.
    • Connect the EIA485 bus to connectors A3 (B+), A2 (A-) and A1 (SGND). Respect the polarity.
    • Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices connected to the bus, and in each end of the bus it must be a termination resistor of 120 Ω.
  • Address Map

    • The Modbus address map is predefined and it’s not configurable. Check the Configuration Guide to find a list with all the available registers implemented in the gateway.
  • Points definition

    • Every point defined in the gateway has the Modbus Format, Point and R/W features associated to it.
    • Each point defined in Intesis has the following Modbus features associated to it:
      Feature| Description
      ---|---
      #Bits| One of the following bit lengths can be used:

·         1 bit

·         16 bits

·         32 bits

Data Coding Format| One of the following Modbus data coding formats can be used:

·         16/32 unsigned.

·         16/32 bits signed (one’s complement – C1).

·         16/32 bits signed (two’s complement – C2).

·         16/32 bits Float.

·         16/ bits Bitfields.

·         Error comm

Function code| One of the following Modbus function codes can be used:

·         1- Read Coils.

·         2- Read Discrete Inputs.

·         3- Read Holding Registers.

·         4- Read Input Registers.

·         5- Write Single Coil.

·         6- Write Single Register.

·         15- Write Multiple Coils.

·         16- Write Multiple Registers.

Byte Order| ·         Big Endian

·         Little Endian

·         Word Inverted Big Endian

·         Word Inverted Little Endian

Register Address| The Modbus register address inside the slave device for the point.
Bit inside the register| Bit inside the Modbus register (optional). The gateway allows bit decoding from generic 16 bits input/holding Modbus registers.

Bit coding into 16 bits input/holding Modbus registers is used for some devices to encode digital values into this type of registers, being these registers normally accessible using Modbus function codes 3 and 4 (read holding/input registers).

Read/Write| 0: Read

1: Write

2: Read / Write

Connections

Find below information regarding the Intesis connections available.

  • Power Supply
    Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply. Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table below). The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.

  • Ethernet / Modbus TCP / OCPP
    Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual for more information). With factory settings, after powering up the gateway, DHCP will be enabled for 30 seconds. After that time, if no IP is provided by a DHCP server, the default IP 192.168.100.246 will be set

  • Port Modbus RTU
    Connect the EIA485 bus to connectors A3 (B+), A2 (A-) and A1 (SNGD) of Intesis gateway’s Port. Respect the polarity.

  • Note for EIA485 port; Remember the characteristics of the standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices connected to the bus, and in each end of the bus it must be a termination resistor of 120 ΩNot used.

Ensure proper clearance for cables (see section 6).

Terminal Wiring

(for power supply and low-voltage signals)

| Per terminal: solid wires or stranded wires (twisted or with ferrule)

1 core: 0.5mm2… 2.5mm2 2 cores: 0.5mm2… 1.5mm2 3 cores: not permitted

---|---

Power

| 1 x Plug-in screw terminal block (3 poles) Positive, Negative, Earth

9-36 VDC / 24 VAC / 50-60 Hz / 0.140 A / 1.7 W

Ethernet

| 1 x Ethernet 10/100 Mbps RJ45

2 x Ethernet LED: port link and activity

Port

| 1 x Serial EIA485 (Plug-in screw terminal block 3 poles) A1, A2, A3 (Reference ground or shield)

1500VDC isolation from other ports

  • Powering the device

    • A power supply working with any of the voltage range allowed is needed (check section 5).
    • WARNING! To avoid earth loops that can damage the gateway and/or any other equipment connected to it, we strongly recommend:
    • The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a DC power supply with the positive terminal connected to earth.
  • Connection to Modbus

    • Modbus TCP
      Connect the communication cable coming from the network HUB or switch to the ETH port of Intesis. The cable to be used shall be a straight Ethernet UTP/FTP CAT5 cable.

    • Modbus RTU
      Connect the communication cable coming from the Modbus network to the port marked as Modbus of Intesis. Connect the EIA485 bus to connectors A3 (B+), A2 (A-) and A1 (SGND). Respect the polarity.
      Observe standard EIA485 bus specifications: maximum distance of 1200 meters, maximum of 32 devices connected to the bus, and in each end of the bus it must be a termination 120 Ω resistor.

  • Connection to the configuration tool
    This action allows the user to have access to configuration and monitoring of the device (more information can be found in the configuration tool User Manual). One method to connect to the PC can be used:

    • Ethernet: Using gateway´s Ethernet port.

Set-up process and troubleshooting

Pre-requisites

  • It is necessary to have a Modbus TCP client or RTU master device operative and properly connected to the corresponding Modbus port of Intesis and OCPP devices connected to its corresponding ports as well.
  • An External OCPP system is required in the system if the External OCPP Central System functionality is enabled.
  • Connectors, connection cables, PC to use the configuration tool and other auxiliary material, if needed, are not supplied by HMS Industrial Networks S.L.U for this standard integration.
  • Items supplied by HMS Networks for this integration are:
    • Intesis gateway.
    • Link to download the configuration tool.
    • Product documentation.
Intesis MAPS. Configuration & monitoring tool for Intesis Modbus series

Introduction
Intesis MAPS is a Windows® compatible software developed specifically to monitor and configure Intesis Modbus series. In this document, only the specific case of Modbus OCPP gateway will be covered. The installation procedure and main functions are explained in the Intesis MAPS User Manual. This document can be downloaded from Intesis product website at https://www.intesis.com/ Please check the Intesis MAPS User manual and Configuration guide for specific information about the different parameters and how to configure them.

Connection
To configure the Intesis connection parameters press on the Connection button in the menu bar.

Configuration tab
Select the Configuration tab to configure the connection parameters. Three subsets of information are shown in this window: General (Gateway general parameters), Modbus slave (Modbus TCP and RTU interface configuration) and OCPP (OCPP configuration and devices parameters).

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig7

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig8

The OCPP Configuration window allows for the following settings:

  • OCPP type: select the OCPP mode for the gateway
    • BMS Central System: Gateway and BMS act as an OCPP Central System
    •  External Central System: Gateway acts as a bridge between an external OCPP CS and OCPP chargers
    • IP: The IP of the external OCPP CS
    • Port: The port of the external OCPP CS
    • Check connection. Press this button to stablish a test connection between the gateway and the External Central System.
  • OCPP Scan. Press this button to search for OCPP Chargers in your network. Scan function will generate a list of all chargers that are trying to connect with the gateway. – Note that chargers must be configured first to connect to the gateway before they can be discovered with the Scan tool. For more information, please review the Intesis Configuration Guide.

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig9

  • Chargers Configuration: A list of all available chargers with its corresponding Charger Id and number of connectors. Activating each Charger will change the Signals available in Signals tab. Keep in mind the different capacities for each gateway model.
    • Heartbeat interval: Changes the Heartbeat interval time for OCPP messages
  • TCP Configuration port: Sets the TCP port for the OCPP communication with the OCPP Chargers
  • TCP Keep Alive: Sets the time of inactivity to send a Keep Alive message (0-disabled)
  • Enable Smart Charging Operations: Enables the registers necessary to set the charging profile, only available under BMS central system OCPP Type.

Signals
All available OCPP signals, its corresponding Modbus register and other main parameters are listed in the signals tab. More information on each parameter and how to configure it can be found in the Intesis MAPS user manual.

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig10

NOTE: Depending on the OCPP mode selected in Configuration, signals list and displayed properties will vary.

Sending the configuration to Intesis
When the configuration is finished, follow the next steps.

  1. Click on Save button to save the project to the project folder on your hard disk (more information in Intesis MAPS User Manual).
  2. You will be prompted to generate the configuration file to be sent to the gateway.
    • If Yes is selected, the file containing the configuration for the gateway will be generated and saved also into the project folder.
    • If NO is selected, remember that the binary file with the project needs to be generated before the Intesis starts to work as expected.
  3. Press the Send File button to send the binary file to the Intesis device. The process of file transmission can be monitored in the Intesis Communication Console window. Intesis will reboot automatically once the new configuration is loaded.

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig11
IMPORTANT! After any configuration change, send the configuration file to the Intesis using button Send File.

Diagnostic
To help integrators in the commissioning tasks and troubleshooting, the Configuration Tool offers some specific tools and viewers.

  • To start using the diagnostic tools, connection with the Gateway is required.

  • The Diagnostic section is composed by two main parts: Tools and Viewers.

    • Tools
      Use the tools section to check the current hardware status of the box, log communications into compressed files to be sent to the support, change the Diagnostic panels’ view or send commands to the gateway.

    • Viewers
      To check the current status, viewer for the Internal and External protocols signals are available. It is also available a generic Console viewer for general information about communications and the gateway status and finally a Signals Viewer to simulate the BMS behaviour or to check the current values in the system.

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig12
NOTE: Depending on the OCPP mode selected in Configuration, signals list and displayed properties will vary. Refer to the Configuration Tool manual for more information.

Set-up procedure

  1. Install Intesis MAPS on your laptop, use the setup program supplied for this and follow the instructions given by the Installation wizard.

  2. Install Intesis in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface (DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).

  3. If using, Modbus RTU, connect the communication cable coming from the EIA485 port of the Modbus RTU installation to the port marked as Port A of Intesis (More details in section 3).

  4. Connect the communication cable coming from the Modbus TCP and/or OCPP installations to the port marked as ETH of Intesis gateway (More details in section 3).

  5. Power up Intesis. The supply voltage can be 9 to 24 Vdc. Take care of the polarity of the supply voltage applied.
    WARNING! To avoid earth loops that can damage Intesis and/or any other equipment connected to it, we strongly recommend:
    The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a DC power supply with the positive terminal connected to earth.

  6. If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as ETH of Intesis (More details in section 3).

  7. Open Intesis MAPS and create a new project by selecting a copy of the one named INMBSOCPxxx0100.

  8. Modify the configuration as desired (refer to Configuration Guide for more details) save it and download the configuration file to Intesis as explained in the Intesis MAPS user manual.

  9. Visit the Diagnostic section and check that there is communication activity, some TX frames and some other RX frames. This means that the communication with the Modbus TCP Client device/s and OCPP devices is OK. In case there is no communication activity between Intesis and the OCPP or Modbus devices, check that those are operative: check the baud rate, the communication cable used to connect all devices and any other communication parameter.

Electrical & Mechanical Features


Enclosure

| Plastic, type PC (UL 94 V-0)

Net dimensions (dxwxh): 93x53x58 mm

Recommended space for installation (dxwxh): 100x60x70mm Color: Light Grey. RAL 7035

---|---


Mounting

| Wall.

DIN rail EN60715 TH35.


Terminal Wiring

(for power supply and low-voltage signals)

| Per terminal: solid wires or stranded wires (twisted or with ferrule)

1 core: 0.5mm2… 2.5mm2

2 cores: 0.5mm2… 1.5mm2 3 cores: not permitted


Power

| 1 x Plug-in screw terminal block (3 poles) Positive, Negative, Earth

9-36 VDC / 24 VAC / 50-60 Hz / 0.140 A / 1.7 W


Ethernet

| 1 x Ethernet 10/100 Mbps RJ45

2 x Ethernet LED: port link and activity


Port

| 1 x Serial EIA485 (Plug-in screw terminal block 3 poles) A, B, SGND (Reference ground or shield) 1500VDC isolation from other ports


Operation Temperature

| ****

0°C to +60°C

Operational Humidity| ****

5 to 95%, no condensation


Protection

| ****

IP20 (IEC60529)

Dimensions

Recommended available space for its installation into a cabinet (wall or DIN rail mounting), with space enough for external connections

Intesis INMBSRTR0320000 Modbus Server Open Charge Point Protocol-
fig16

https://www.intesis.com